3
70
Interface Modules
JUMPFLEX® Transducers
Universal Isolation Amplifier
OUT
U; I
IN
U; I
POWER
5
6
1
2
3
4
7
8
OUT+
OUT-
Us+
GND 3
U+
I+
I+
I-/U-
<_________ 94 mm/3.68 in _________> 6 mm/0.23 in
<_________ 96 mm/3.76 in _________>
____________
_>
_>
Short description:
The 857-402 Universal Isolation Amplifier converts, amplifies and electrically
isolates analog standard signals. The device has a 3-way isolation with a 2.5kV
test voltage. In addition to standard signals, both unipolar and bipolar signals
(± 10V, ± 20mA) up to 200V and 100mA can be set on the input side via DIP
switches, which are accessible from the side of the housing. The analog output
also supports standard unipolar and bipolar signals. Measurement range swit-
ching is calibrated. The device is supplied with 24VDC, which can be efficiently
commoned using lateral push-in type jumper bars. A green LED on the front pa-
nel indicates normal operation.
The isolation amplifier provides safe isolation of input, output and supply circuits
with 2.5kV test voltage according to EN 61140.
A self-resetting fuse effectively protects the current input against overload.
The fuse automatically resets when the overload is removed.
Description Item No. Pack.
Unit
Universal isolation amplifier 857-402 1
Accessories
General accessories see Full Line Catalog 2010/2011
Interface Modules
Approvals
Shipbuilding g (pending)
4 r ANSI/ISA 12.12.01 (pending)
Conformity marking 1
General Specifications
Dimensions (mm) W x H x L 6 x 96 x 94
Height from upper-edge of DIN 35 rail
Wire connection CAGE CLAMP®S
Cross sections solid: 0.08 mm² ... 2.5 mm² /
AWG 28 ... 12
fine-stranded: 0.34 mm² ... 2.5 mm² /
AWG 22 ... 12
Stripped lengths 9 ... 10 mm / 0.37 in
Ambient operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Technical Data
Configuration DIP switch
Input signal Voltage:
± 60 mV, 0 … 60 mV, ± 100 mV,
0 … 100 mV ± 150 mV, 0 … 150 mV,
± 300 mV, 0 … 300 mV , ± 500 mV,
0 … 500 mV, ± 1 V, 0 … 1 V ,± 5 V,
0 ... 5 V, 1 ... 5 V, ± 10 V, 0 ... 10 V,
2 ... 10 V ± 100 V, 0 … 100 V, ± 200 V,
0 … 200 V
Current:
± 0.3 mA, 0 ... 0.3 mA, ± 1 mA,
0 ... 1 mA ,± 5 mA ,0 ... 5 mA ,± 10 mA ,
0 ... 10 mA ,2 ... 10 mA ,± 20 mA ,
0 ... 20 mA ,4 ... 20 mA ,± 50 mA ,
0 ... 50 mA ,± 100 mA ,0 ... 100 mA
Output signal Voltage:
± 10 V, 0 ... 10 V, 2 ... 10 V,
± 5 V, 0 ... 5 V, 1 ... 5 V
Current:
± 20 mA, 0 ... 20 mA, 4 ... 20 mA,
± 10 mA, 0 ... 10 mA, 2 ... 10 mA
Load impedance ≤ 600 Ω (I output)
≥ 1 kΩ (U output)
Max. operating frequency 100 Hz / > 5 kHz
(switchable via DIP switch)
Voltage supply VN DC 24 V
Supply voltage range 16.8 V ... 31.2 V
Transmission error < 0.08 % of upper range value
Test voltage
(input/output/supply) 2.5 kV AC, 50 Hz, 1 min.
857-402
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 17.11.2010
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com