SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED PO WER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.4
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPU T
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP. Note.5
CURRENT SHARING
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
DC OK REALY CONTACT RATINGS (max.)
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1000ms, 100ms/400VAC 800ms, 100ms/500VAC at full load
12ms / 400VAC at full load14ms / 500VAC
Three-Phase 340 ~ 550VAC (Dual phase operation possible) 480 ~ 780VDC
47 ~ 63Hz
94%
2A/400VAC 1.4A/500VAC
56 ~ 65V
85 5 (TSW) detect on heatsink of power switch℃± ℃
94.5%
COLD START 60A
<3.5mA / 530VAC
29 ~ 33V
Pro tection type : Constant current limiting, unit will shut down after 3 sec. ,re-p ower on to recover
Protection type : Shut down o/p voltage, re-power on to recover
90 5 (TSW) detect on heatsink of power switch℃ ± ℃
Pro tection typ e : Shut down o/p voltage, recovers automatically after temperature goes down
UL508 approved, IEC60950-1 CB approved by SIQ
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
-30 ~ +70℃(Refer to "Derating Curve")
Please refer to function manual
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
± ℃ ℃)0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
59.4K hrs min. MIL-HDBK-217F (25 )℃
110*125.2*150mm (W*H*D)
2.47Kg ; 6pcs/15.8Kg/1.47CUFT
TDR-960-48
48V
20A
0 ~ 20A
960W
250mVp-p
48 ~ 5 5V
±1.0%
±0.5%
±1.0%
TDR-960-24
24V
40A
0 ~ 40A
960W
180mVp-p
24 ~ 28V
±1.0%
±0.5%
±1.0%
■
TDR-960 series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
℃
960W Three Phase Industrial DIN RAIL with PFC Function
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
105 ~ 130% rated output power
POWER FACTOR (Typ.) PF 0.88/400VAC PF 0.86/500VAC at full load≧ ≧
EMC IMMUNITY
EMC EMISSION
File Na me:T DR-960-SPEC 2013-04-26