ADTECH
Analog-Digital Technology, Inc.
Typical Applications
Loop-Powered Trip
Alarm/
Current Loop Alarm
• General limit detector of
DC current signal inputs
On/off controller
Alarm or shutdown of
process variables
Machine and process
protection
Contact inputs to annuncia-
tors, lights, and horns
Tank-filling applications
with dead band option
The Adtech CLA 114 Loop-Powered Trip Alarm accepts 4-20 mA DC input
and provides a relay contact output. The CLA loop-powered alarm does not
require a separate DC or AC power supply source as conventional alarms
do.
It accepts the standard process current signal of 4-20 mA DC and provides a
SPDT contact output, or optionally, a DPDT contact output. Both are rated
4 amps, 30 VDC or 250 VAC resistive for either high- or low-alarm configu-
ration.
The CLA 114 has 0-100% adjustable set point and a 0.5% fixed dead band.
Option O 46S provides a 1-100% adjustable dead band.
It has an input voltage drop of 7 VDC, which represents a 350 ohm input
impedance to a 4-20 mA signal at full scale.
Two indicating LEDs are standard to the CLA. When the input signal
exceeds the set point, a red pulsing LED comes on.
A pulsing green LED indicates the magnitude of the input signal. The pulse
rate increases with an increasing input signal. This unique feature provides a
visual indication of the relative signal level at a glance. When the input
exceeds the set point, the green LED turns off, and the red LED turns on.
DIN mounting is supplied as standard. Surface mount (Option H 26) and
snap track (Option H 25) are available at no extra cost, specify.
FEATURES
No External Power Source: Loop powered, 28 mW at 4 mA
from input loop
DC Current Inputs: 4-20 mA
Repeatability: 0.1% of span
Relay Action: High- or low-trip
Output Contacts: 4 amp, SPDT—standard;
4 amp, DPDT—optional
Input Signal Status: Green LED
Alarm Status: Red LED
Adjustable Dead Band: 1-100%—optional
Isolation: 1,500 VAC input to output contacts
Model No. CLA 114
ALARM STATUS
Red LED
ALARM STATUS
Green LED
4-20 mA DC
INPUT
SET POINT DEAD BAND
OPTION O 46S
INPUT CONDITIONING
AND
COMPARATOR
RELAY
DRIVER
DPDT
option
O 49
Connections/Dimensions
Represented by:
Printed in U.S.A. #A097A
Information subject to change without notice.
Ordering Information
Model number
High or low alarm
Electrical options
Housing and miscellaneous
options
Please refer to the Housing and/or
Option Section for more specific
and detailed information.
Input/Output Input Signals: 4-20 mA DC
Output Signals:
Standard: SPDT output contact, rated 4 amps at 30 VDC or 250 VAC rseistive
Optional: DPDT output contact, rated 4 amps at 30 VDC or 250 VAC resistive: (Option O 49)
Option Number Description
O 46S Adjustable blind set dead band
O 49 DPDT contacts
H 15D Explosion Proof: Class 1, Group B, C & D
H 25 Snap-track Mount (Specify)
H 26 Surface Mounting (Specify)
H 27 NEMA 4 Enclosure
H 29 T 35 DIN "T" rail—2 ft. long
H 30 T 32 DIN "G" rail—2 ft. long
Options
Repeatability: ±0.1% of span
Trip Point Stability: Zero and span ±0.005%/˚F typical,
±0.01%/˚F maximum for a 50˚F change from ambient
Trip Adjustmant: 0-100% of span continuously adjustable; blind set: infinite resolution
Fixed Dead Band: Factory set at 0.5% of span or setting (specify)
Adjustable Dead Band: 1% to 100% of span (specify), continuously adjustable; blind set
Response Time: Less than 200 milliseconds
Temperature Range: 0˚ to 140˚F (-18˚ to 60˚C) operating; -40˚ to 185˚F (-40˚ to 85˚C) storage
Input Voltage Drop: 7 volts nominal
Note: All accuracies are given as a percentage of span.
Electrical Classification: General purpose Mounting: DIN:Optional surface, snap track or
Connection: Screw compression type Nema 4 & 7.
accepts up to 14 AWG Weight: Net unit: 4 oz (115 grams)
Controls: Multiturn setpoint, (optional) Shipping: 7 oz (200 grams)
deadband and jumpers for
relay action
Performance
Power
Mechanical
External Power: None
ADTECH
Analog-Digital Technology, Inc.
3750 Monroe Avenue
Pittsford, New York 14534-1302
Phone: (716) 383-8280
Fax: (716) 383-8386
Internet: ainc847401@aol.com
AOL: AInc847401
CLA 114
LOOP PWR
ALARM
ADTECH
+
INPUT
OUTPUT
KA
4-20 mA Input
(+)
()
N.C.
Comm.
N.O.
SP
DB
ALRM
NORM
OUTPUT
KB
Option O 49
WIRE INSERTION
G RAIL MOUNTING
DIN EN 50 035 (32mm, 15mm) T RAIL MOUNTING
DIN EN 50 022 (35mm, 7.5mm)
DIN EN 50 022 (35mm, 15mm)
1.56 (39.7)
C
LC
L
.98 (25.0)
3.11 (79.0)
T RAIL MOUNTING
DIN EN 50 022 (35mm, 7.5mm)
G RAIL MOUNTING
DIN EN 50 035 (32mm, 15mm)
T RAIL MOUNTING
DIN EN 50 022 (35mm, 15mm)
SLOT FOR T RAIL
RELEASE
ADTECH
1.56 (39.7)
3.36 (85.0)
3.55 (89.7)
3.65 (92.5)
0.47 (11.9)
Term block
with option O-49 only
0.58 (14.9)
(with option O-49 only)
3.68 (93.4)
(with option O-49 only)
1.54 (39.0)
0.63 (16.0)