2761-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
RSAN Series
Features
High Voltage Pulse Attenuation
DIN Rail Mount Option (Up 30A)
Low Earth Leakage Current Option (Up to 30A)
Conforms to UL, CSA and EN Safety Agency Certifi cations
3A to 60A, 250VAC EMI Filters
RSAN-2003 RSAN-2006 RSAN-2010 RSAN-2016 RSAN-2020
RSAN-2003D RSAN-2006D RSAN-2010D RSAN-2016D RSAN-2020D
Model RSAN-2003L RSAN-2006L RSAN-2010L RSAN-2016L RSAN-2020L
Rated Voltage (AC, DC) V 250V
Rated Current A 3A 6A 10A 16A 20A
Withstand Voltage V Terminals to Case: 2500VAC (1 Minute)
Isolation Resistance 100MΩ minimum (500VDC, 1 Minute)
Leakage Current (max) A RSAN-20xx 1mA; RSAN20xxL 10uA (250VAC, 60Hz)
DC Resistance (total) 250 110 40 20 10
RSAN-2030
RSAN-2030D RSAN-2040 RSAN-2050 RSAN-2060
Model RSAN-2030L
Rated Voltage (AC, DC) V 250V
Rated Current A 30A 40A 50A 60A
Withstand Voltage V Terminals to Case: 2500VAC (1 Minute)
Isolation Resistance 100MΩ minimum (500VDC, 1 Minute)
Leakage Current (max) A RSAN-20xx 1mA; RSAN20xxL 10uA (250VAC, 60Hz)
DC Resistance (total) 6 6 4 3
Operating Temperature °C -25 to +85°C (Derate above 55°C, see derating curve)
Storage Temperature °C -25 to +85°C
Safety Agency Certifi cations - UL1283, CSA C22.2 No.8, EN60939
Weight g 170g to 870g model dependant (See weights chart on website)
Warranty yr 5 Year
Specifi cations
Chassis Mount & Standard Leakage Current RSAN-20xx
DIN Rail Mount & Standard Leakage Current RSAN-20xxD
Chassis Mount & Low Leakage Current RSAN-20xxL
Options Circuit
Derating
2771-800-526-2324 • www.us.tdk-lambda.com/lp/ Revision A6: Jun 2018
RSAN Series
For Additional Information, please visit
us.tdk-lambda.com/lp/products/r-series.htm
Outline Drawing