EC centrifugal fan
backward curved, single inlet
R1G310-AD17-11
Charts: Air flow
Druck psf [Pa]f ür Rho=1,2kg/m^3
qv[m^3/h]
2.4002.2002.0001.8001.6001.4001.2001.0008006004002000
qv[cfm]
1.4001.2001.0008006004002000
psf [Pa]
580
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
180
160
140
120
100
80
60
40
20
0
psf _E[IN H2O]
2,3
2,2
2,1
2
1,9
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
psf [Pa]
psf [Pa]
psf [Pa]
1
2
3
4
5
6
7
8
9
10
11
12
Measurement: LU-53929
Measurement: LU-53928
Measurement: LU-52983
Air performance measured as per ISO
5801 Installation Category A. For detailed
information on the measuring set-up,
please contact ebm-papst. Suction-side
noise levels: LwA measured as per ISO
13347 / LpA measured with 1m distance to
fan axis. The values given are valid under
the measuring conditions mentioned above
and may vary according to the actual
installation situation. With any deviation
from the standard set-up, the specific
values have to be checked and reviewed
with the unit installed.
Measured values
1
2
3
4
5
6
7
8
9
10
11
12
U
V
53
53
53
53
48
48
48
48
36
36
36
36
n
min-1
1860
1680
1580
1640
1800
1615
1525
1580
1570
1435
1355
1395
P1
W
135
144
150
147
120
126
131
128
74
80
83
81
I
A
3.07
3.36
3.55
3.42
3.00
3.17
3.32
3.22
2.34
2.54
2.65
2.59
qv
m3/h
2195
1710
1210
635
2110
1645
1160
610
1805
1435
1005
530
psf
Pa
0
107
218
327
0
100
200
300
0
76
150
228
Item no.: 51178-5-9980 · Revision status: KM73287 · Print-out on 05/04/2011 · Y. Uhlmann (VM-TDO) · Page 5 of 5