Security information 1 Product overview 2 SIMATIC Wiring 3 ET 200SP HA Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Parameters 4 Displays and interrupts 5 HART function 6 Technical specifications 7 Manual Drivers, parameters, diagnostics messages and address space 11/2017 A5E39408968-AB A HART operating data records B Analog value display C Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NURNBERG GERMANY A5E39408968-AB 01/2018 Subject to change Copyright (c) Siemens AG 2017. All rights reserved Table of contents 1 Security information......................................................................................................................................5 2 Product overview..........................................................................................................................................7 2.1 3 4 5 6 Properties of the AI 16xI 2-wire HART HA I/O module............................................................7 Wiring...........................................................................................................................................................9 3.1 Pin assignment of the AI 16xI 2-wire HART HA I/O module....................................................9 3.2 Schematic circuit diagram......................................................................................................12 Parameters.................................................................................................................................................13 4.1 Configurations of the AI 16xI 2-wire HART HA I/O module....................................................13 4.2 Module/channel parameters...................................................................................................14 4.3 Explanation of the module/channel parameters.....................................................................16 4.4 HART mapping parameters...................................................................................................20 Displays and interrupts...............................................................................................................................21 5.1 Status and error displays of the AI 16xI 2-wire HART HA I/O module...................................21 5.2 Interrupts................................................................................................................................24 HART function............................................................................................................................................25 6.1 How HART works...................................................................................................................26 6.2 HART applications.................................................................................................................30 6.3 HART variables......................................................................................................................32 7 Technical specifications..............................................................................................................................35 A Drivers, parameters, diagnostics messages and address space...............................................................41 B A.1 Concept of the driver and diagnostics blocks.........................................................................41 A.2 Parameter assignment...........................................................................................................43 A.3 Parameter assignment and structure of the module/channel parameters.............................45 A.4 Parameter assignment and structure of the HART mapping parameters..............................49 A.5 Diagnostics messages and maintenance events...................................................................51 A.6 Hardware interrupts................................................................................................................56 A.7 Address space.......................................................................................................................57 HART operating data records.....................................................................................................................61 B.1 HART command interface......................................................................................................61 B.2 HART job and response data records....................................................................................63 B.3 HART directory.......................................................................................................................69 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 3 Table of contents C B.4 HART feature data.................................................................................................................70 B.5 HART variable data record.....................................................................................................71 B.6 HART-specific settings...........................................................................................................72 Analog value display...................................................................................................................................75 C.1 Representation of analog values in the current measuring ranges........................................75 Index...........................................................................................................................................................77 4 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Security information 1 Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines, and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial security concept. Siemens' products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial security measures that may be implemented, please visit: https://www.siemens.com/industrialsecurity Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer's exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under https://www.siemens.com/industrialsecurity. Validity of the documentation This manual describes the AI 16xI 2-wire HART HA I/O module with article number 6DL1134-6TH00-0PH1. It supplements the "ET 200SP HA Distributed I/O System" system manual, Functions that generally relate to the system are described in this manual. The information in this manual and in the system and function manuals enables you to commission the ET 200SP HA. Appendices The appendices provide information that is relevant for using the ET 200SP HA outside the PCS 7 environment. If you do not plan to use the ET 200SP HA outside the PCS 7 environment, you will not need the information in the appendices. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 5 Security information Conventions Please also observe notes marked as follows: Note A note contains important information on the product described in the documentation, on the handling of the product and on the section of the documentation to which particular attention should be paid. 6 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 2 Product overview 2.1 Properties of the AI 16xI 2-wire HART HA I/O module View of the module AI 16x I 2-w ire HA HA RT DIA G MT AI 2-w ire 1 3 5 7 9 11 13 15 I0+ I2+ I4+ I6+ I8+ I10+ I12+ I14+ I1+ I3+ I5+ I7+ I9+ I11+ I13+ I15+ 2 4 6 8 10 12 14 16 17 19 21 23 25 27 29 31 AI 2-w ire UV0 UV1 UV2 UV3 UV4 UV5 UV6 UV7 UV8 UV9 UV1 0 UV11 UV12 UV1 3 UV1 4 UV15 18 20 22 24 26 28 30 32 1P1 L+ 24V 2P1 L+ 24V DC M 1P2 DC MA X. 10 A M 2P2 AI0 F0 AI2 F2 AI4 F4 AI6 F6 AI8 F8 AI10 F10 AI12 F12 AI14 F14 AI1 F1 AI3 F3 AI5 F5 AI7 F7 AI9 F9 AI11 F11 AI13 F13 AI15 F15 X 2 3 4 CC0 1 PW R V 1.0.0 6DL1134- 6TH 00- 0PH1 Module type and designation LED for diagnostics LED for maintenance 2D matrix code Wiring diagram LEDs for channel status/channel fault Module type color coding Product version Function status and firmware version Color code for selection of the color-coded labels Serial number Article number LED for supply voltage Figure 2-1 View of AI 16xI 2-wire HART HA Properties The I/O module has the following technical properties: 16 analog inputs 16 outputs as encoder supply for 2-wire transmitters Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 7 Product overview 2.1 Properties of the AI 16xI 2-wire HART HA I/O module The analog inputs have the following channel-specific parameterizable properties: - Current measurement type for 2-wire HART transmitter - Measuring range 0 to 20 mA, 0 to 10 mA, 4 to 20 mA and 4 to 20 mA with HART - Resolution dependent on measuring range and interference frequency suppression, minimum 15 bits including sign, maximum 16 bits including sign - Smoothing - Interference frequency suppression 10 Hz, 50 Hz and 60 Hz Channel-specific configurable diagnostics Module-specific configurable diagnostics for missing supply voltage L+ Hardware interrupt at limit violation, per channel (two high and two low limits each) The module supports the following functions: Firmware update I&M identification data Parameter reassignment in RUN Value status QI IO redundancy HART communication (Rev. 5 to Rev. 7) Up to 8 HART variables directly in the input address area A multiHART area in the input/output area You can configure the I/O module with HW Config and integrate it into your system. Accessories The following accessories must be ordered separately: Labeling strips Color-coded labels Reference identification label Shield connector 8 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 3 Wiring 3.1 Pin assignment of the AI 16xI 2-wire HART HA I/O module Terminal blocks You can operate the I/O module with the following terminal blocks: 6DL1193-6TP00-0DH1 light 6DL1193-6TP00-0BH1 dark 6DL1193-6TP00-0DM1 light, for redundant design 6DL1193-6TP00-0BM1 dark, for redundant design The terminal block is not included in the scope of delivery of the I/O module and must be ordered separately. Note You can find additional information on the configuration in the system manual. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 9 Wiring 3.1 Pin assignment of the AI 16xI 2-wire HART HA I/O module General pin assignment Table 3-1 Terminal assignment of AI 16xI 2-wire HART HA Terminal Assignment Terminal Assignment Explanations 1 I0+ 2 I1+ Terminal 1 to 16: 3 I2+ 4 I3+ In+: Input signal "+", channel n 5 I4+ 6 I5+ Terminal 17 to 32: 7 I6+ 8 I7+ UVn: Sensor supply channel n M: Reference point, ground 9 I8+ 10 I9+ 11 I10+ 12 I11+ 13 I12+ 14 I13+ 15 I14+ 16 I15+ 17 UV0 18 UV1 19 UV2 20 UV3 21 UV4 22 UV5 23 UV6 24 UV7 25 UV8 26 UV9 27 UV10 28 UV11 29 UV12 30 UV13 31 UV14 32 UV15 1P1 L+ 1P2 M 2P11 L+ 2P2 M 1P1: Supply voltage L+ of the voltage bus 1P 2P1: Supply voltage L+ of the voltage bus 2P 1P2: Ground reference of the voltage bus 1P 2P2: Ground reference of the voltage bus 2P 1 3 5 7 9 11 13 15 AI 2-wire I1+ I0+ I2+ I3+ I5+ I4+ I7+ I6+ I8+ I9+ I10+ I11+ I12+ I13+ I14+ I15+ 2 4 6 8 10 12 14 16 17 19 21 23 25 27 29 31 AI 2-wire UV0 UV1 UV3 UV2 UV5 UV4 UV6 UV7 UV8 UV9 UV10 UV11 UV12 UV13 UV14 UV15 18 20 22 24 26 28 30 32 1P1 L+ 24VDC M 1P2 2P1 L+ 24VDC M 2P2 MAX. 10 A 1 10 If the module is plugged into a TB45R-P32 terminal block suitable for IO redundancy, the potential at this terminal is 1P3. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Wiring 3.1 Pin assignment of the AI 16xI 2-wire HART HA I/O module Example of 2-wire connection of a transmitter using channel 0: L+ U V0 Sensor supply + + HART XDCR - I 0+ A Backplane bus 250 M D Example of non-isolated connection of a 4-wire transmitter using channel 0: L+ UV0 Sensor supply UV+ HART + + I 0+ A XDCR Backplane bus 250 UV- M D You can also supply the 4-wire transmitter via the encoder supply terminal UV0. Reference potential of the supply is M. In this case, monitoring of the sensor supply is available for analog input I0. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 11 Wiring 3.2 Schematic circuit diagram 3.2 Schematic circuit diagram The following figure shows the schematic circuit diagram of the I/O module. Redundancy coupling DIAG MT UV0 HART D 3 k 200 A AI0+ Channel 0 Status Error Process handling Backplane bus ET 200SP HA backplane bus interconnection Encoder supply . . . . . Encoder supply UV15 HART D 3 k AI15+ 200 A Status Error Channel 15 24 V DC L+ M DC Reverse polarity protection DC PWR Figure 3-1 Block diagram of AI 16xI 2-wire HART HA Supply voltage L+/M Connect the supply voltage L+ to the L+ and M terminals. An internal protective circuit protects the I/O module from reverse polarity. The I/O module monitors whether the supply voltage is connected and present. Firmware update The supply voltage L+ must be available on the I/O module at the start of firmware updates and during the update. 12 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Parameters 4.1 4 Configurations of the AI 16xI 2-wire HART HA I/O module Configuring You configure the I/O module with PCS 7 V9.0 or higher. Configuration options The following configurations, each with value status, are possible: Without HART variables in the input area With 8 HART variables in the input area With a multiHART range in the input/output range When configuring is done in HW Config, the configuration is carried out indirectly in the parameter assignment dialog of the module. Note Only the listed configurations can be directly configured for the I/O module while the CPU is in RUN mode. To set another configuration, first remove the I/O module in CPU RUN. You then add the I/O module with the new configuration while the CPU is in RUN mode. Please note that this might change the I/O address area. Parameters You define the functioning of the I/O module via parameters. The parameters are subdivided into: Module/channel parameters (data record 128) Parameters that determine the display of HART variables in the address space of the module; HART mapping parameters (data record 130) System parameters (potential group, IO redundancy) See also Parameter assignment and structure of the module/channel parameters (Page 45) Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 13 Parameters 4.2 Module/channel parameters 4.2 Module/channel parameters Parameters of AI 16xI 2-wire HART HA You have the following setting options: Table 4-1 Parameters and their default settings Parameter Value range Default Parame ter reas signment in RUN Efficiency range Diagnostics, Missing supply voltage L+ Enabled Enabled Yes Module IO redundancy None None Yes Module Use potential group of the left module No Module Yes Channel Current (2-wire transducer) Current (2-wire transducer) 0 to 10 mA 4 to 20 mA HART Yes Channel Enabled Yes Channel Enabled Yes Channel Enabled Yes Channel Enabled Yes Channel Enabled Yes Channel Enabled Yes Channel Disabled 2 modules Potential group Use potential group of the left module Allow new potential group Measurement type Measuring range Disabled 0 to 20 mA 4 to 20 mA 4 to 20 mA HART There is no underrange in the ranges 0 to 10 mA or 0 to 20 mA That is, the smallest analog value is zero. Diagnostics encoder supply Enabled Disabled Diagnostic short-circuit to L+ Enabled Disabled Diagnostics overflow Enabled Disabled Diagnostics underflow Enabled Disabled Diagnostics, Wire break Enabled Disabled Diagnostics HART Enabled Disabled 14 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Parameters 4.2 Module/channel parameters Parameter Value range Default Parame ter reas signment in RUN Efficiency range Smoothing None None Yes Channel 10 Hz Yes Channel 1.185 mA Yes Channel Number of HART frame rep 0 to 10 etitions 5 Yes Channel Hardware interrupt high limit Enabled 1/2 Disabled Disabled Yes Channel Hardware interrupt low limit 1/2 Enabled Disabled Yes Channel High limit 1/2 Value 20 mA Yes Channel Low limit 1/2 Value 4 mA at 4 to 20 mA Yes Channel Weak Medium Strong Interference frequency sup pression 60 Hz (integration time 16.6 ms) 50 Hz (integration time 20 ms) 10 Hz (integration time 100 ms) When 50 Hz is set, the interfer ence signals of 400 Hz are also filtered automatically. Wire break limit 1.185 mA 3.6 mA Disabled 1 uA for 0 to 10 mA and 0 to 20 mA Note Unused channels "Disable" unused channels in the parameter assignment to improve the cycle time of the module. A disabled channel always supplies the analog value 7FFFH. See also Parameter assignment and structure of the module/channel parameters (Page 45) Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 15 Parameters 4.3 Explanation of the module/channel parameters 4.3 Explanation of the module/channel parameters Diagnostics, Missing supply voltage L+ Enabling of the diagnostics for missing or insufficient supply voltage L+. IO redundancy You can configure two identical modules redundantly. To do so, plug both modules into a redundant terminal block side by side. You can find additional information on mounting modules in an IO redundancy configuration in the ET 200SP HA System Manual, section "Installing", "Installing terminal block". In IO redundancy mode, the left module is the master and the right module is the slave. Both redundant modules measure simultaneously and independently in the process. Both redundant modules generate diagnostics, alarms and process values. The process values are based on the measured values of the respective leading channel that measures with low resistance in the process. By default, the channels of the master are the leading channels. When a module fails or when the failure of a channel is detected, the respective leading channels are switched over to the partner module. Once an error has been corrected, there is no changeover of the leading channels involved. HART communication can only take place over the leading channel. Measurement type/measuring ranges The I/O module supports the following measuring ranges: Measurement type Measuring range Resolution for interference frequency suppression 10 Hz Disabled Current (2-wire transducer) 50 Hz 60 Hz -- -- -- -- 0 to 10 mA 15 bits plus sign 15 bits plus sign 14 bits plus sign 0 to 20 mA 15 bits plus sign 15 bits plus sign 15 bits plus sign 4 to 20 mA 4 to 20 mA HART The resolution of the analog values is dependent on the interference frequency suppression setting. HART mode is only possible with a measuring range of 4 to 20 mA. HART communication is not interrupted even at currents below 4 mA. An overview of the measuring range and the overflow, overrange, etc. can be found in section Configurations of the AI 16xI 2-wire HART HA I/O module (Page 13). Diagnostics encoder supply The sensor supply of the analog input is monitored for overload and short-circuit to M. 16 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Parameters 4.3 Explanation of the module/channel parameters Diagnostic short-circuit to L+ Enabling of the monitoring for a short-circuit of the analog input to sensor supply or L+. The short-circuit and overflow diagnostics can be activated at the same time. If both diagnostics occur simultaneously, the short-circuit diagnostics is output. Diagnostics, Wire break You can enable a wire break diagnostics for measuring range 4 to 20 mA or 4 to 20 mA HART. The diagnostics are output when the current flow falls below the assigned wire break limit. The wire break and underflow diagnostics can be activated at the same time. If both diagnostics occur simultaneously, the wire break diagnostics is output. Diagnostics overflow Enabling of the diagnostics when the measured value exceeds the overrange. Diagnostics underflow You can enable a underflow diagnostics for measuring range 4 to 20 mA or 4 to 20 mA HART. The diagnostics are output when the measured value falls below the underrange. There is no underrange in measuring ranges 0 to 20 mA and 0 to 10 mA. Diagnostics HART Enabling of the diagnostics of the HART frame-specific monitoring and the status information supplied by the connected field device in the HART frame (HART device status). The HART diagnostics are signaled as maintenance events. Wire break limit You use this to specify the current limit for detecting wire breaks. If the current falls below the configured wire break limit, the measured value is declared invalid and, if wire break diagnostics is enabled, corresponding diagnostics information is generated. The value status of the analog input is set to "bad". With a wire break limit of 3.6 mA, the measured value becomes invalid when the current falls below 3.6 mA and is marked as valid again when it rises above 3.8 mA. There is no hysteresis for a wire break limit of 1.185 mA. Smoothing The individual measured values are smoothed by filtering. Smoothing can be set in 4 levels. Smoothing time = number of module cycles (k) x cycle time of the module. The following figure shows the number of module cycles after which the smoothed analog value approaches 100%, depending of the smoothing setting. This applies to every signal change at the analog input. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 17 Parameters 4.3 Explanation of the module/channel parameters [ [ [ [ 0RGXOHF\FOHV N No smoothing (k = 1) Weak (k = 4) Medium (k = 8) Strong (k = 16) Figure 4-1 Smoothing of the analog value Interference frequency suppression Suppresses the interference that is caused by the frequency of the alternating voltage network used. When HART operation is activated, an interference frequency suppression of 10 Hz is recommended so that the HART signal does not influence the analog value. Number of HART frame repetitions Specifies the number of HART frame repetitions. If AI 16xI 2-wire HART HA does not receive a response or receives a faulty response to a HART frame sent to the field device, the frame is repeated, i.e. resent to the field device, according to this setting. Hardware interrupt 1 / 2 Enabling of a hardware interrupt when the high limit 1 /2 is exceeded or the low limit 1 / 2 is fallen below. Low limit 1 / 2 Specify a threshold which triggers a hardware interrupt when violated. High limit 1/2 Specify a threshold which triggers a hardware interrupt when violated. 18 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Parameters 4.3 Explanation of the module/channel parameters Potential group A potential group consists of a group of adjacently placed I/O modules within an ET 200SP HA station that are supplied using a common supply voltage. A potential group begins with a light terminal block via which the needed supply voltage for all I/O modules of the potential group is fed. The light-colored terminal block interrupts the selfassembling voltage buses to the left neighbor All other I/O modules of this potential group are plugged into dark terminal blocks. I/O modules on dark terminal blocks take the potentials of self-assembling voltage rails from the left neighbor. A potential group ends with the dark terminal block that is followed by a light terminal block or a server module in the station configuration. You can find additional information on the configuration of the potential group in the system manual SIMATIC; Distributed I/O System; ET 200SP HA. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 19 Parameters 4.4 HART mapping parameters 4.4 HART mapping parameters A maximum of 8 HART variables can be configured (mapped) to the address space of the I/O module with the HART mapping parameters. If you want to use a maximum of 8 HART variables in the input area of the I/O module, configure these parameters in the properties dialog of the I/O module. Parameters Table 4-2 HART mapping parameters of the I/O module Parameter Variable 0 Value range Default Parameter reassign ment in RUN Chan nel 0...15 0 Yes Type Non / CiR Non / CiR Yes Primary Secondary Tertiary Quaternary : : Variable 7 Chan nel 0...15 0 Yes Type Non / CiR Non / CiR Yes Primary Secondary Tertiary Quaternary See also Parameter assignment and structure of the HART mapping parameters (Page 49) 20 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Displays and interrupts 5.1 5 Status and error displays of the AI 16xI 2-wire HART HA I/O module LED displays The figure below shows the status and error displays of I/O module. HA AI 16xI 2-wire HART DIAG MT AI 2-wire 1 3 5 7 9 11 13 15 I0+ I2+ I4+ I6+ I8+ I10+ I12+ I14+ I1+ I3+ I5+ I7+ I9+ I11+ I13+ I15+ 2 4 6 8 10 12 14 16 17 19 21 23 25 27 29 31 AI 2-wire UV0 UV1 UV3 UV2 UV5 UV4 UV6 UV7 UV9 UV8 UV11 UV10 UV13 UV12 UV15 UV14 18 20 22 24 26 28 30 32 1P1 L+ 24VDC M 1P2 2P1 L+ 24VDC M 2P2 MAX. 10 A AI0 F0 AI2 F2 AI4 F4 AI6 F6 AI8 F8 AI10 F10 AI12 F12 AI14 F14 AI1 F1 AI3 F3 AI5 F5 AI7 F7 AI9 F9 AI11 F11 AI13 F13 AI15 F15 PWR X 2 3 4 CC01 V 1.0.0 6DL1134-6TH00-0PH1 DIAG LED (green/red) MT LED (yellow) Channel status LED (green) Channel fault LED (red) PWR LED (green) Figure 5-1 LED displays Meaning of the LED displays The following tables show the meaning of the status and fault displays. Corrective measures for diagnostics interrupts can be found in the section Diagnostics messages and maintenance events (Page 51). Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 21 Displays and interrupts 5.1 Status and error displays of the AI 16xI 2-wire HART HA I/O module DIAG LED Table 5-1 Diagnostics display of the DIAG LED DIAG LED Meaning The supply voltage of the ET 200SP HA is disrupted or switched off. Off Module is not configured. Flashes Module is configured, a diagnostics message is not pending. On Module is configured, at least one diagnostic message is pending. Flashes MT LED Table 5-2 MT LED Maintenance display of the MT LED Meaning No maintenance required. Off On At least one maintenance requirement, i.e. at least one maintenance event has oc curred. Channel status/channel error LED The green channel status LED indicates whether a channel is enabled. The LED is off when channel or module diagnostics for an enabled channel are pending. The red channel fault LED lights up when a channel diagnostics are pending with enabled channel. Table 5-3 Status and error displays of the channel status/channel fault LEDs Channel status LED Channel fault LED Off Off Meaning Channel disabled or module switched off Module diagnostics pending Channel enabled and no channel/module diagnostics pending On Off Channel enabled and channel diagnostics pending Off 22 On Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Displays and interrupts 5.1 Status and error displays of the AI 16xI 2-wire HART HA I/O module PWR LED Table 5-4 Status display of the PWR LED PWR LED Meaning Supply voltage L+ missing Off Supply voltage L+ present On Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 23 Displays and interrupts 5.2 Interrupts 5.2 Interrupts The I/O module supports diagnostics interrupts and hardware interrupts. You can find additional information about hardware interrupts in appendix "Hardware interrupts (Page 56)". Diagnostics interrupts Diagnostics interrupts are used by the I/O module to signal diagnostics messages as well as maintenance events, see also appendix Diagnostics messages and maintenance events (Page 51). The I/O module generates a diagnostics interrupt at the following events: Overtemperature Channel/component temporarily unavailable Short-circuit / overload of sensor supply Wire break Low limit violated (underflow) High limit violated (overflow) Supply voltage missing Hardware interrupt lost Module is faulty Short-circuit of an analog input to sensor supply or L+ Retentive memory in carrier module defective Retentive memory in the terminal block defective Redundancy partner has different hardware/firmware IO redundancy warning Redundancy parameter assignment inconsistent HART communication error HART field device error Note The diagnostics "Module is defective" and "Excess temperature" are not cleared again by the module without a restart. 24 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB HART function 6 Definition "HART" stands for "Highway Addressable Remote Transducer". Using the HART functionality, you can exchange data between the I/O module and the connected field devices. The HART protocol is generally accepted as a standard protocol for communication with intelligent field devices: HART is a registered trademark of the HART Communication Foundation (HCF), which owns all the rights to the HART protocol. You can find detailed information about HART in the HART specification. Advantages of HART Use of the AI 16xI 2-wire HART HA gives you the following advantages: Connection compatibility with standard analog modules: Current loop 4 - 20 mA Additional digital communication via the HART protocol, HART communication (Rev. 5 to Rev. 7) Numerous field devices with HART functions are in use I/O module enables application of HART devices on an IO device based on ET 200SP HA Use in the system The I/O module is used in an IO device based on the ET 200SP HA. You can connect a HART field device to each channel (monodrop mode). The I/O module serves as HART master, the field devices as HART slaves. The maximum 16 channels communicate in parallel. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 25 HART function 6.1 How HART works 6.1 How HART works Introduction The HART protocol describes the physical form of the transfer: transfer procedures, message structure, data formats and commands. HART signal The figure below shows the analog signal with the modulated HART signal (FSK method), which consists of sine waves of 1200 Hz and 2200 Hz and has a mean value of 0. It can be filtered out using an input filter so that the original analog signal is available again. +0,5 mA 0 -0,5 mA 1200 Hz 2200 Hz "1" "0" 20 mA 1 K A K A K A A K 4 mA 0 2 Figure 6-1 The HART signal Time (seconds) K Command A Response Analog signal HART communication The I/O module processes the HART communication in parallel operation, that is, all channels simultaneously. With enabled HART operation, the I/O module automatically sends HART commands to the connected field devices. These commands always alternate with any pending external HART 26 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB HART function 6.1 How HART works commands for the specific channel that arrive via the command interface of the module, see section HART command interface (Page 61). Commissioning a HART field device Only HART field devices that have been set to short frame address 0 can be operated. If a HART field device with a different short frame address is connected or a connected field device is reconfigured to a short frame address other than 0 during operation, the module starts a scan of all possible short frame addresses at the next re-establishment of HART communication (command 0 with short frame addresses 1...63). As soon as the connected field device responds, it is converted to the short frame address 0 (HART command 6) by the module. The I/O module signals a HART communication error during the scan. HART commands The configurable properties of the HART field devices (HART parameters) can be set with HART commands and read out using HART responses. The HART commands and their parameters are divided into three groups with the following properties: Universal Common practice Device-specific Universal commands must be supported by all manufacturers of HART field devices and common practice commands should be supported. There are also device-specific commands that apply only to the particular field device. Examples of HART commands The following two tables show examples of HART commands: Table 6-1 Examples of universal commands Command Function 0 Reads manufacturer and device type - only with this command 0 can field devices be addressed by means of a short frame address 11 Reads manufacturer and device type 1 Reads primary variable and unit 2 Reads current and percentage of range, digitally as floating-point number (IEEE 754) 3 Reads up to four pre-defined dynamic variables (primary variables, secondary variables, etc.) 13, 18 Reads or writes process tag name ("tag"), description and date (dates are also sent) Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 27 HART function 6.1 How HART works Table 6-2 Examples of common practice commands Command Function 36 Sets high range limit 37 Sets low range limit 41 Perform self-test 43 Sets the primary variable to zero Structure of the HART protocol Each HART frame sent from the I/O module to the connected field device (request frame) and each HART frame received by the field device (response frame) has the following basic structure. PREAMBLE PREAMBLE: STRT: ADDR: COM: BCNT: STATUS: DATA: CHK: STRT ADDR COM BCNT STATUS DATA CHK Bytes (0xFF) for synchronizing, default: 5 bytes (can be changed using DS131 - DS138) Start character (start delimiter) Address of the field device (1 byte; short address or 5 bytes; long address) HART command number Byte count, number of bytes to follow without checksum HART device status (1st and 2nd status byte). Only present for a response frame. For structure of HART device status, see below. Transferred user data / parameters, quantity depending on command (0...230 bytes) Checksum With the exception of the preamble bytes, this structure is contained in the communication data of the HART command interface. See section HART job and response data records (Page 63). HART responses always contain data. Status information (HART device status; 1st and 2nd status bytes) is always sent together with a HART response. status bytes) is always sent together with a HART response. You should evaluate these to make sure the response is correct. 28 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB HART function 6.1 How HART works Structure of HART device status (1st and 2nd status bytes) Table 6-3 1st status byte Bit 7 = 1: "Communication error" Bit 6 = 1 Bit 5 = 1 Bit 4 = 1 Bit 3 = 1 Bit 2 = 0 Bit 1 = 1 Bit 0 = 0 Parity error Overflow Framing error Checksum error Reserved Overflow in the receive buffer Reserved Bit 7 = 0: "No communication error" Bit 0...6: "Specific according to the response frame" Table 6-4 Bit 7 = 1 Bit 6 = 1 Bit 5 = 1 Bit 4 = 1 Bit 3 = 1 Bit 2 = 1 Bit 1 = 1 Bit 0 = 1 2nd status byte Device fault Configuration changed Startup (cold start) Additional status information available Fixed analog output current setting Analog output current saturated Secondary variable outside the limits Primary variable outside the range HART fast mode The I/O module supports the processing of HART commands as an SHC string ("Successive HART Command"). If a HART command with set SHC bit is detected by the I/O module for a channel, this channel is reserved for external HART commands for approximately 2 s. Internal HART commands are not issued, see section HART command interface (Page 61) Burst mode The I/O module does not support burst mode. HART commands with set burst bit are ignored and are not forwarded to the connected field device. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 29 HART function 6.2 HART applications 6.2 HART applications System environment for the use of HART To use an intelligent field device with HART functionality, you require the following system environment: 4 to 20 mA current loop Connecting measuring transmitters to the I/O module HART parameter assignment tool "Client": You can assign the HART parameters using an external handheld operating device (HART Handheld) or a HART configuration tool (PDM). Both assume the function of a "client": The parameter assignment tool affects the entire I/O module; the HART handheld is connected in parallel to the field device. PDM (Process Device Manager) is available standalone or integrated in STEP 7 HW Config. In the latter case, PDM is opened from HW Config. HART system integration: The I/O module takes on the function of a "master" by receiving commands from the HART parameter assignment tool, for example, forwarding them to the smart field device and sending back the responses. The interface of the I/O module is made up of data records that are transmitted internally via the ET 200SP HA IO device between IM and I/O module. The data records must be created and interpreted by the client. )LHOGGHYLFHZLWK+$57IXQFWLRQDOLW\ +$57DQDORJPRGXOH ,QWHUIDFHWR 352),1(7,2 P$ /9 0RGHP +$57+DQGKHOG $'8 6HQGUHFHLYH RI+$57VLJQDO $QDORJGLJLWDOFRQYHUVLRQ RIF\FOLFPHDVXUHGYDOXH 6,0$7,& 3'0 +$57SDUDPHWHU DVVLJQPHQWWRRO 0*URXQG Figure 6-2 30 System environment for the use of HART Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB HART function 6.2 HART applications Error management The two HART status bytes (HART device status) that are transferred with every response of the field device contain error indications regarding the HART communication, HART command and device status. These are evaluated by the I/O module and made available in the system using S7 maintenance messages. Configuration/commissioning How to configure the I/O module with HW Config You assign parameters for the individual channels with regard to the actual analog value acquisition and the use of HART variables in the input address space of the module. You can configure one field device per channel. The configuration/parameter assignment of the connected field device is then carried out from this configured field device using PDM or the EDD for the ET 200SP HA. Parameter reassignment of the field devices The I/O module generally accepts triggered parameter reassignments for field devices. The awarding of access rights can only be made in the parameter assignment tool. To reassign parameters of the field devices connected to the I/O module, proceed as follows: 1. You initiate parameter reassignment of a field device with a HART command that you enter with the SIMATIC PDM parameter assignment tool. 2. After you complete parameter reassignment of a HART field device, the corresponding bit is set in the HART device status of the connected field device (in the 2nd status byte). 3. As a result of field device reconfiguration, the I/O module triggers a "Configuration changed" maintenance message if such a message is enabled. This maintenance message should be regarded as a notice and not an error. It is automatically deleted again by the I/O module after approximately 1 minute. If enabled, a maintenance message can also be triggered by a new parameter assignment with the handheld device. See also Pin assignment of the AI 16xI 2-wire HART HA I/O module (Page 9) Diagnostics messages and maintenance events (Page 51) Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 31 HART function 6.3 HART variables 6.3 HART variables Introduction Numerous HART field devices make available additional measured quantities (e.g. sensor temperature). A maximum of four HART variables supported by the connected field device are read cyclically for each channel with enabled HART functionality. The HART variables are read automatically via the HART command 3 (for field devices with HART Rev. 5 and 6) or via command 9 (for field devices with HART Rev. 7 or later). These four HART variables per channel are always stored in HART variable data record 121 and can be read at any time. In addition, you can optionally configure the following: You can map a maximum of 8 HART variables to the input address space of the I/O module. The HART variables are assigned to a channel in the properties dialog of the I/O module. This allows you to easily process measured values directly from the field device as input data in the automation device. You can configure a multiHART area in the input/output address space of the I/O module. You can read all HART variables available in the I/O module with each of these multiHART areas. You specify the multiHART area in the properties dialog for the I/O module. Address assignment Each HART variable occupies 5 bytes of input data. As soon as you configure (map) at least one HART variable in the input address space, the addresses for all 8 tags are assigned (40 bytes). When the multiHART area is used, an additional 6 bytes of input address space and 1 byte of output address space are assigned. Configuration of HART variables You can configure up to 8 HART variables in the properties dialog of the I/O module. You select these from the four HART variables provided by each channel: PV (Primary Variable) SV (Secondary Variable) TV (Tertiary Variable) QV (Quaternary Variable) When HART mode is enabled, the I/O module cyclically reads the variables provided by the connected field devices itself and makes them available in the configured input address space. Configuring of a multiHART area You can use a multiHART area for the AI 16xI 2-wire HART HA I/O module. You select whether or not to use a multiHART area in the properties dialog of the I/O module. 32 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB HART function 6.3 HART variables When HART mode is enabled, the I/O module cyclically reads the variables provided by the connected field devices itself. You can request and read one of these HART variables via the multiHART range. Quality code The quality code describes the process status of the corresponding HART variable. Basic structure of the quality code Bit 7....6 5....2 1...0 Quality Sub-status Limits 0 0 1 1 Coded according to "PROFIBUS PA Profile for Process Control Devices" 0 0 1 1 0: Bad 1: Uncertain 0: Good 1: Good 0: OK 1: Low limit 0: High limit 1: Constant The quality codes generated by the I/O module conform to the HART revision of the field device used. For field devices with HART Revision 5 and 6 The quality code is formed exclusively from the 1st and 2nd status byte (HART device status) of the response frames (HART command 3). Quality code Meaning (process status) 80H Value is okay Also applies when the following bits are set in the 2nd status byte of the HART response frame: Configuration changed Startup (cold start) Fixed analog output current setting 78H Value is uncertain Also applies when the following bits are set in the 2nd status byte of the HART response frame: Additional status information available Analog output current saturated Secondary variable outside the limits Primary variable outside the range 84H Response code RC8: Update error 24H Response code RC16: Access restricted 23H Communication error or HART variable not present in the field device Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Request from field device refused 33 HART function 6.3 HART variables 1 Quality code Meaning (process status) 37H Initialization value from analog module 00H Initialization value from S7 system After module start-up, after incorrect operation of the multiHART interface or after redundancy failover to the standby channel1 A channel is in standby mode when a redundancy failover occurred due to an error in an IO-redundant module. For field devices as of HART revision 7 The quality code is formed from the 1st status byte (HART device status) and the "Device variable status" (DVS) of the response frames (HART command 9). 1 Quality code Meaning (process status) 80H Value is okay 89H "Good" with "low limit" 8AH "Good" with "high limit" 28H...2BH "Bad" 68H...6BH "Poor accuracy" 78H...7BH "Manual" or "Fixed" (manually controlled or fixed value) 88H...8BH "More device variable state available" (additional status information available) 84H Response code RC8: Update error 24H Response code RC16: Access restricted 23H Communication error or HART variable not present in the field device 37H Initialization value from analog module 40H Read alternatively via command 3 00H Initialization value from S7 system Process status, formed from the "De vice variable status" (DVS) of the re sponse frames with corresponding lim its (see above). Request from field device refused After module start-up, after incorrect operation of the multiHART interface or after redundancy failover to the standby channel1 A channel is in standby mode when a redundancy failover occurred due to an error in an IO-redundant module. See also HART variable data record (Page 71) Parameter assignment and structure of the HART mapping parameters (Page 49) 34 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 7 Technical specifications Technical data of AI 16xI 2-wire HART HA Article number 6DL1134-6TH00-0PH1 General information Product type designation AI 16 x I 2-wire mA HART HW functional status FS01 Firmware version V1.0 FW update possible Yes Usable terminal block TB type H1 and M1 Color code for module-specific color identifica tion plate CC01 Product function I&M data Yes; I&M0 to I&M3 Engineering with PCS 7 configurable/integrated as of version V9.0 Redundancy Redundancy capability Yes; With TB type M1 CiR - Configuration in RUN Reparameterization possible in RUN Yes Supply voltage Rated value (DC) 24 V permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Yes Input current Current consumption (rated value) 80 mA; without sensor supply Current consumption, max. 90 mA; without sensor supply Encoder supply 24 V encoder supply 24 V Yes Short-circuit protection Yes; Electronic (response threshold 0.7 A to 1.5 A) Power loss Power loss, typ. 4.5 W; without sensor supply Address area Address space per module Address space per module, max. 34 byte; 32-byte inputs and 2 bytes for QI informa tion Address space per module with HART, max. 74 byte; 32-byte inputs and 2 bytes for QI informa tion, 40-byte inputs for HART Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 35 Technical specifications Article number 6DL1134-6TH00-0PH1 Address space per module with MultiHART, max. 41 byte; 32-byte inputs for HART and 2 bytes for QI information, 6-byte inputs for HART, and 1-byte output for MultiHART command Analog inputs Number of analog inputs 16 permissible input current for current input (de struction limit), max. 30 mA Input ranges (rated values), currents 0 to 20 mA Yes; 16 bit incl. sign Input resistance (0 to 20 mA) 250 4 mA to 20 mA Yes; 16 bit incl. sign Input resistance (4 mA to 20 mA) 250 Cable length 800 m; Shielded shielded, max. Analog value generation for the inputs Measurement principle integrating (Sigma-Delta) Integration and conversion time/resolution per channel Resolution with overrange (bit including sign), max. 16 bit; 14 bit at 60 Hz (0 ... 10 mA), 16 bit at 10 Hz, 15 bit at 50 Hz and 15 bit at 60 Hz interference suppression Integration time, parameterizable Yes; channel by channel Smoothing of measured values Yes; none, weak, medium, strong, channel-bychannel parameterizable Encoder Connection of signal encoders for current measurement as 2-wire transducer Yes Errors/accuracies Linearity error (relative to input range), (+/-) 0.01 % Temperature error (relative to input range), (+/-) 0.005 %/K Crosstalk between the inputs, min. 60 dB Repeat accuracy in steady state at 25 C (rela tive to input range), (+/-) 0.05 % Operational error limit in overall temperature range Current, relative to input range, (+/-) 0.5 % Basic error limit (operational limit at 25 C) Current, relative to input range, (+/-) 0.1 % Interrupts/diagnostics/status information Diagnostics function Yes Alarms 36 Diagnostic alarm Yes Limit value alarm Yes; two upper and two lower limit values in each case Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Technical specifications Article number 6DL1134-6TH00-0PH1 Diagnostic messages Monitoring the supply voltage Yes Wire-break Yes; channel by channel Short-circuit Yes; Channel-by-channel, short-circuit of the en coder supply to ground or of an input to the encod er supply Overflow/underflow Yes; channel by channel Diagnostics indication LED MAINT LED Yes; yellow LED Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED Channel status display Yes; Green LED for channel diagnostics Yes; Red LED for module diagnostics Yes; green/red DIAG LED Potential separation Potential separation channels between the channels No between the channels and backplane bus Yes Between the channels and load voltage L+ No Isolation Isolation tested with 1 500 V DC/1 min, type test Ambient conditions Ambient temperature during operation horizontal installation, min. -40 C horizontal installation, max. 70 C; Observe derating vertical installation, min. -40 C vertical installation, max. 60 C; Observe derating Dimensions Width 22.5 mm Height 115 mm Depth 138 mm Weights Weight, approx. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 148 g 37 Technical specifications Note With use of sensor supply UVn (terminal 17...32), the following derating must be observed: Horizontal mounting position: Up to 70C, up to 12 channels when using the encoder supplies (total current of outputs 300 mA) Up to 70C, up to 16 channels when using the encoder supplies Up to 65C, up to 16 channels when using the encoder supplies (total current of outputs 400 mA) Up to 60C, up to 16 channels when using the encoder supplies (total current of outputs 2 A) Vertical mounting position: Up to 60C, up to 12 channels when using the encoder supplies (total current of outputs 300 mA) Up to 60C, up to 16 channels without using the encoder supplies Up to 55C, up to 16 channels when using the encoder supplies (total current of outputs 400 mA) Up to 50C, up to 16 channels when using the encoder supplies (total current of outputs 2 A) Maximum supply voltage ripple during HART operation 390 mVpp at 50 Hz 8.3 mVpp at 300 Hz Cycle time The cycle time describes the time slice in which signals from the inputs are acquired and processed. The cycle time depends on the parameter assignment and can be different for each channel. 38 Operating mode Cycle time Analog inputs for 60 Hz interference frequency suppression 16.6 ms Analog inputs for 50 Hz interference frequency suppression 20 ms Analog inputs for 10 Hz interference frequency suppression 100 ms Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Technical specifications Redundancy failover time At an IO redundancy failover, the update time of process values is delayed once by a time less than or equal to this time. The maximum redundancy failover time of the I/O module is 20 ms + cycle time. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 39 Technical specifications 40 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.1 A Concept of the driver and diagnostics blocks Use outside of the PCS 7 environment The following information of the appendix is relevant for use of the ET 200SP HA outside the PCS 7 environment. If you do not plan to operate outside the PCS 7 environment, you do not need the information in the appendix. Tasks of the driver and diagnostics blocks (driver blocks) In process control systems, certain demands are placed on the diagnostics/signal processing. This includes the monitoring of modules, DP/PA slaves and DP master systems for malfunctions and failures. To enable this, blocks are available in the PCS 7 library that implement the interface to the hardware including test functions. These blocks perform two basic tasks: They provide signals from the process to the AS for further processing. They monitor modules, DP/PA slaves, and DP master systems for failure. When the process signals are read in, these blocks access the process image input (or process image partition) (PII) and when the process signals are output, they access the process image output (or process image partition) (PIQ). Concept The concept of the driver and diagnostics blocks for PCS 7 can be characterized as follows: The separation between user data processing (CHANNEL blocks) and diagnostics data processing (MODULE blocks) The symbolic addressing of the I/O signals The automatic generation of the MODULE blocks by CFC Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 41 Drivers, parameters, diagnostics messages and address space A.1 Concept of the driver and diagnostics blocks This block concept supports all modules from the list of approved modules. When new Siemens or non-Siemens module types are integrated, the meta-knowledge for the driver generator can be extended by additional XML files (object and action lists). Note Note the following: The library with the driver blocks has to installed using the Setup program on the PC. This is the only method of ensuring that the meta-knowledge required for the driver generator is available. You must not copy the library from another computer. You can also use driver blocks from another library (for example, your own blocks from your own library). You can specify this additional library in the "Generate module drivers" dialog box. The driver generator then searches for the block to be imported in the library specified here. If the block is not found here, it is searched for in the library specified in the control file (XML file). If the S7 program contains a signal-processing block but not from one of the PCS 7 libraries, you have to specify the version of the driver library from which the driver blocks are to be imported in the "Generate module drivers" dialog box. Time-optimized processing To enable time-optimized processing during runtime, the organization blocks for error handling (for example, OB85, OB86) are automatically divided into runtime groups and the driver blocks are integrated in the corresponding runtime groups. If an error occurs, the SUBNET block, for example, activates the relevant runtime group, the RACK block or MODULE block contained in the runtime group detects the error, evaluates it and outputs a process control message to the OS. The diagnostics information of the module block (OMODE_xx output) is also transferred to the corresponding CHANNEL block (MODE input). If necessary, this information can be displayed by means of a PCS 7 block that can be operated and monitored on the OS or by means of a user block in a process picture (color change of the measured value or flashing display, etc.). 42 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment A.2 Parameter assignment Parameter assignment in the user program You can reconfigure individual channels of the I/O module and HART variable mapping in RUN without this affecting the other channels. Changing parameters in RUN The parameters are transferred to the I/O module with the instruction "WRREC". Module/channel parameters using data record 128 HART mapping using data record 130 The parameters assigned with STEP 7 are not changed permanently in the CPU, which means the parameters assigned with STEP 7 are valid again after a restart. Output parameter STATUS If errors occur when transferring parameters with the "WRREC" instruction, the module continues operation with the previous parameter assignment. The STATUS output parameter contains a corresponding error code. The STATUS output parameter is 4 bytes long and is configured as followed: Byte 1: Function_Num, general error code Byte 2: Error_Decode, location of the error code Byte 3: Error_Code_1, error code Byte 4: Error_Code_2, manufacturer-specific extension of the error code Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2. Error_ Code_ 1 Error_ Code_ 2 Cause Remedy 0xB0 0x00 Number of the data record unknown Enter valid number for data record. 0xB1 0x01 Length of the data record is incorrect Enter valid value for data record length. 0xB2 Varia ble Module cannot be reached Check station - is the module plugged in correctly? Check the parameters of the WRREC instruction. 0xE0 0x01 Incorrect version in the header Correct the version number of the parameter block. 0xE0 0x02 Header error (number or length of parameter block) Correct the length and number of the parameter blocks. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 43 Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment Error_ Code_ 1 Error_ Code_ 2 Cause Remedy 0xE1 0x01 Reserved bit set Check and correct the parameters 0xE1 0x02 Invalid diagnostics enable bit set for operating mode 0xE1 0x04 Invalid value for hardware interrupt limit 0xE1 0x08 Invalid coding for interference frequency suppres sion / integration time 0xE1 0x09 Invalid coding for smoothing 0xE1 0x0E Invalid redundancy parameter assignment 0xE1 0x10 Invalid measurement type 0xE1 0x11 Invalid measuring range 0xE1 0x21 Incorrect number of HART repetitions Valid parameters Only the values specified in the following are permitted. Values that are not listed are rejected by the I/O module. Each parameter data record is checked by the I/O module. If a parameter with errors is detected, the complete data record is rejected and the parameters of the I/O module remain unchanged. 44 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters A.3 Parameter assignment and structure of the module/channel parameters Structure of data record 128 Data record 128 has a length of 236 bytes. It contains module parameters and all channel or technology parameters of the 16 channels. The channel and technology parameters are divided into parameters that influence the actual analog value acquisition, diagnostics enables and basic parameters of the HART communication. You can specify and change other parameters and HART-specific settings with data records 131 to 146. See section HART-specific settings (Page 72). %\WH +HDGHULQIRUPDWLRQ PRGXOH %\WH 0RGXOHSDUDPHWHUV %\WH +HDGHULQIRUPDWLRQ FKDQQHO %\WH 3DUDPHWHUV&KDQQHO %\WH 3DUDPHWHUV&KDQQHO %\WH 3DUDPHWHUV&KDQQHO Figure A-1 Structure of data record 128 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 45 Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters Header information and module parameters The following figure shows the structure of the header information and module parameters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igure A-2 46 'LDJQRVWLFVIRUPLVVLQJVXSSO\YROWDJH/ 5HGXQGDQF\UROH RII 0DVWHU VWDWLRQLQWHUQDO 6ODYH VWDWLRQLQWHUQDO Header information and module parameters of data record 128 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters Channel parameters Each channel parameter block contains the channel parameters for the analog output including HART (14 bytes). The following figure shows the structure of the channel parameters for channel 0 to 15. x = 12 + (channel number * 14); with channel number 0...15 All unused bits and the bits or bytes marked as "reserved" must be set to zero. You activate a channel parameter by setting the corresponding bit to "1" or the corresponding value. %\WH[ %\WH[ %\WH[ 0HDVXUHPHQWW\SH $QDORJLQSXWGLVDEOHG &XUUHQW ZLUHWUDQVPLWWHU 0HDVXULQJUDQJH bP$ bP$ bP$+$57 bP$ 6PRRWKLQJ QRQH ZHDN PHGLXP VWURQJ ,QWHUIHUHQFHIUHTXHQF\VXSSUHVVLRQ b+] b+] b+] %\WH[ 'LDJQRVWLFV+$57HQDEOH :LUHEUHDNOLPLW bP$ bP$ ZLWKK\VWHUHVLV +DUGZDUHLQWHUUXSWV %LW ZKHQKLJKOLPLWLVH[FHHGHG %LW ZKHQORZOLPLWLVYLRODWHG %LW ZKHQKLJKOLPLWLVH[FHHGHG %LW ZKHQORZOLPLWLVYLRODWHG Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 47 Drivers, parameters, diagnostics messages and address space A.3 Parameter assignment and structure of the module/channel parameters %\WH[ (QDEOHGLDJQRVWLF 6HQVRUVXSSO\ 6KRUWFLUFXLWWR/ :LUHEUHDN 8QGHUIORZ 2YHUIORZ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ Figure A-3 48 1XPEHURI+$57IUDPHUHSHWLWLRQV GHIDXOW +DUGZDUHLQWHUUXSWKLJKOLPLW +DUGZDUHLQWHUUXSWORZOLPLW +DUGZDUHLQWHUUXSWKLJKOLPLW +DUGZDUHLQWHUUXSWORZOLPLW Structure of byte x to x+n for channels 0 to 15 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.4 Parameter assignment and structure of the HART mapping parameters A.4 Parameter assignment and structure of the HART mapping parameters Structure of data record 130 Data record 130 has a total length of 20 bytes. You can use the parameters of data record 130 to configure/map up to 8 HART variables of the individual channels in the input address space of the I/O module, provided you have selected configuration with HART variables in the input area, see section Configurations of the AI 16xI 2-wire HART HA I/O module (Page 13). Header information The figure below shows the structure of the header information. %\WH %\WH %\WH %\WH Figure A-4 9HUVLRQ %ORFNOHQJWK %ORFNW\SH 5HVHUYHG Header information of data record 130 Parameters The figure below shows the parameter assignment of the 8 HART variables. x = 4, 6, 8, 10, ..., 18 %\WH[ %\WH[ Figure A-5 &KDQQHOQXPEHU 9DULDEOHLGHQWLILHU 3ULPDU\ 6HFRQGDU\ 7HUWLDU\ 4XDWHUQDU\ QRQ&L5 Parameters of data record 130 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 49 Drivers, parameters, diagnostics messages and address space A.4 Parameter assignment and structure of the HART mapping parameters The variable ID 15 = non/CiR prevents the I/O module from configuring/mappping a HART variable; that is, the corresponding memory area in the input address area remains unallocated. 50 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.5 Diagnostics messages and maintenance events A.5 Diagnostics messages and maintenance events Diagnostics messages A diagnostics message is generated for each detected diagnostics event. The DIAG LED on the module flashes. There is additionally a channel-specific display of the diagnostics through the corresponding channel fault/channel status LEDs. The diagnostics messages can, for example, be read out in the diagnostics buffer of the CPU. Diagnostic messages are assigned either to one input on a channel-specific basis or to all inputs as a module message. In the event of diagnostics messages that affect the entire module, all channels are switched off. For diagnostics messages that relate to individual channels, only the corresponding analog input is affected. Table A-1 Diagnostic messages, their meaning and possible remedies Diagnostics mes sage Error code Assignment Meaning Channel/compo nent temporarily unavailable 1FH Module Update of the firmware is being performed Restart firmware update or has been canceled. The module does not Wait for firmware update perform any measurements during this time. Overtemperature 5H Module Ambient temperature is too high Check wiring Short-circuit or overload of one or more digital outputs/sensor supplies Eliminate the cause of the excess temperature and restart the module Impedance of encoder circuitry is too high Use a different encoder type or modify the wiring, for example, using cables with a larger cross-section Wire break 6H Analog input Wire break between the module and sensor Channel not connected (open) Remedy Connect the cable Disable diagnostics Connect the encoder contacts High limit violated 7H Analog input The analog value is above the overrange. Correct the module/encoder tuning Short-circuit of input to L+ Low limit violated 8H Analog input The analog value is below the underrange. Correct the module/encoder tuning Parameter as signment error 10H Module Parameter assignment does not match the terminal block used Correct the parameter assignment Incorrect parameter assignment Check terminal block1 Missing or insufficient supply voltage L+ Check wiring of the supply voltage L+ on the terminal block Supply voltage missing 11H Module Check the terminal block type Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 51 Drivers, parameters, diagnostics messages and address space A.5 Diagnostics messages and maintenance events Diagnostics mes sage Error code Assignment Meaning Hardware inter rupt lost 16H Module Error is reported because the events occur faster than they can be processed in the system Module is faulty 100H Module Internal module error has occurred Replace module Short-circuit to L+ 105H Analog input Short-circuit of the analog input to sensor supply or L+ Correct the process wiring Short-circuit/over 10EH load at external encoder supply Analog input Short-circuit of the encoder supply to ground Correct the module/ encoder tuning Encoder supply overload Check the wiring Inconsistent pa rameter assign ment 123H Module Error in the redundancy parameters trans ferred to the module Check the parameter assignment Retentive memo ry in carrier mod ule defective 154H Module A memory block error was detected on the support module Replace carrier module Retentive memo ry in the terminal block defective 155H Module A memory block error was detected on the terminal block Replace terminal block 1 Remedy Check the slot and terminal block Only the terminal blocks (TB 45 ...) are suitable for operating the I/O modules in IO redundancy. Maintenance events A maintenance event is generated each time a maintenance requirement is identified. The MT LED lights up on the module. Maintenance messages are assigned either to one input on a channel-specific basis (HART error) or to inputs as a module message affecting all inputs. 52 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.5 Diagnostics messages and maintenance events Maintenance messages have no direct effect on the function of the module or the analog value acquisition. Maintenance events of the HART communication do not affect the analog value acquisition of the module. Table A-2 Maintenance messages, their meaning and possible remedies Maintenance message Error code Assignment Meaning / Cause Remedy Redundancy part 120H ner has different hardware/firm ware version Module The redundantly configured and intercon nected I/O modules are not compatible Check and replace modules IO redundancy warning Module Unable to correctly communicate with the partner module Check/replace right module 121H Check/replace left module Check/replace terminal block See also system manual Dis tributed I/O System; ET 200SP HA", section "Replacing an I/O module for I/O redundancy" HART communi cation error 141H Analog input HART field device is not responding Check the process wiring Timing error Correct the parameter assignment HART field device did not understand the command that was sent (1st status byte) Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Set current 4 mA Increase number of configured repetitions 53 Drivers, parameters, diagnostics messages and address space A.5 Diagnostics messages and maintenance events Maintenance message Error code Assignment Meaning / Cause Remedy HART primary variable outside of limits 142H Analog input Incorrect parameters in the HART field device Check the parameter assignment of the HART device HART field device is set to "Primary variable outside of limits" in simulation mode Incorrect measuring point Parameter assignment of primary variable outside of limits HART analog out 143H put current of the field device is sa turated Analog input Correct the simulation Check whether the correct measuring transducer is connected The output current of the HART field device is saturated: Incorrect parameters in the HART field device HART field device is set to a measured value that is too high in simulation mode Incorrect measuring point HART output cur 144H rent of the field de vice specified Analog input The output current of the HART field device is fixed: Incorrect parameters in the HART field device HART field device is set to a measured value that is too high in simulation mode Incorrect measuring point HART additional status information available 145H Analog input In the HART device status (in the 2nd status byte), the HART field device identifier for "further status information available" has been set Read out status with HART command 48 and clear error/ cause if necessary HART configura tion changed1 146H Analog input In the HART device status (in the 2nd status If no diagnostics interrupt is to byte), the identifier for "parameter reassign be triggered by reconfigura ment" of the HART field device has been set tion, the HART diagnostics must be disabled. HART malfunc 147H tion in the field de vice Analog input In the HART device status (in the 2nd status byte) the field device reports a malfunction Read out status with HART command 48 and clear error/cause if necessary Replace the field device HART secondary variable outside the limits 149H Analog input Incorrect parameters in the HART field device HART field device is set to "Non-primary variable outside limits" in simulation mode Incorrect measuring point Parameter assignment of non-primary variable is outside the limits 54 Check the parameter assignment of the HART device Correct the simulation Check whether the correct measuring transducer is connected Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.5 Diagnostics messages and maintenance events Maintenance message Error code Assignment Meaning / Cause Retentive memo ry in carrier mod ule defective 154H Module Fault detected in the data block on the carri Replace carrier module er module during operation Retentive memo ry in the terminal block defective 155H Module A memory block error was detected on the terminal block during operation 1 Remedy Replace terminal block Response of the HART configuration changed maintenance message If the HART field device signals "parameter reassignment" (configuration changed) in the 2nd status byte, the module generates the maintenance message "HART configuration changed". If the field device withdraws the message in the 2nd status byte within a minute, the maintenance message is also deleted again by the module. If the message in the 2nd status byte is still set after a minute, the module then independently sends HART command 38 for resetting the message in the field device. Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB 55 Drivers, parameters, diagnostics messages and address space A.6 Hardware interrupts A.6 Hardware interrupts Hardware interrupts The I/O module can initiate hardware interrupts when limit violations of analog input signals occur. Interrupt OBs are called automatically if an interrupt occurs. You can find detailed information on the event in the hardware interrupt organization block with the "RALRM" instruction (read additional interrupt information). The module generates a hardware interrupt at the following events: Violation of the low limit 1 Violation of the high limit 1 Violation of the low limit 2 Violation of the high limit 2 The module analog input (channel) that has triggered the hardware interrupt is entered in variable OB40_POINT_ADDR in the start information of OB40. The figure below shows the assignment to the bits of local data double word 8. /% /% /% /% : 8VHU6WUXFWXUH,GHQWLILHU 86, ; ; ; ; ; ; ; %LWQR /' )DXOWWKDWWULJJHUHGWKHKDUGZDUHLQWHUUXSW +9LRODWLRQRIORZOLPLW +9LRODWLRQRIKLJKOLPLW +9LRODWLRQRIORZOLPLW +9LRODWLRQRIKLJKOLPLW &KDQQHOWKDWWULJJHUHGWKHKDUGZDUHLQWHUUXSW +&KDQQHORIWKH,2PRGXOH +&KDQQHORIWKH,2PRGXOH )+&KDQQHORIWKH,2PRGXOH 56 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.7 Address space A.7 Address space Abbreviations "IB" stands for input byte, that is, the module start address in the input area "QB" stands for output byte, that is the module start address in the output area "QAIn" stands for value status (QI) of analog input n "QC"stands for Quality Code Evaluating the value status The input address space contains one value status (QI) bit for each analog input. Irrespective of the diagnostics enables, each value status (each QI bit) provides information on the validity of the corresponding process value. Value status = 1: Process value okay, "good" Value status = 0: Process value not okay, "bad" Basically, the value status is set to "good" when the analog value can be acquired without error. The value status is set to "bad" in the following cases: The analog value cannot be acquired due to an error. The analog input is disabled. Address space The following tables show the allocation of the address space of the I/O module. Addresses for the HART area are only available if HART variables or a multiHART area were configured in the properties dialog of the module. Input area IB x + 7 6 5 4 3 2 1 0 0...1 Analog value, analog input 0 : : : : 30...31 Analog value analog input 15 32 QAI7 QAI6 33 QAI15 QAI14 QAI5 QAI4 QAI3 QAI2 QAI1 QAI0 QAI13 QAI12 QAI11 QAI10 QAI9 QAI8 34 : : Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB HART range 57 Drivers, parameters, diagnostics messages and address space A.7 Address space HART range When HART variables or the multiHART area is used, the HART area is arranged directly flush against the QI bits of the analog inputs. The structure of the HART area is dependent on the configuration: In the configuration with 8 HART variables in the input area, the area has a length of 40 bytes and always contains 8 HART variables, each with a 4-byte value and a 1-byte quality code (QC). IB x + HART range 34 : 37 Value 38 QC 39 : Value Configured HART variable 0 Configured HART variable 1 42 43 QC : : : 69 : 72 Value 73 QC Configured HART variable 7 In the configuration with 1 multiHART area in the input/output area, the area has a length of 6 bytes: IB x + HART range 34 Acknowledgment 35 : 38 Value 39 QC multiHART range HART variable Output range In the configuration with a multiHART area, there is one byte in the output area. QB x Command multiHART range Evaluating HART variables If you have configured (mapped) HART variables for the I/O module, then 8 HART variables with 5 bytes each are stored in the input address space. Each HART variable consists of a 4-byte real value and a 1-byte quality code. The quality code describes the validity of the value, see section HART variables (Page 32). 58 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Drivers, parameters, diagnostics messages and address space A.7 Address space The assigned HART variables are automatically updated by the module and can be used directly in the user program. Evaluating the multiHART area You can select the multiHART area in the parameter assignment dialog. The multiHART range occupies 1 byte in the output range (command) and 6 bytes in the input range (1 byte acknowledgment + 5 bytes HART variable). You can read all HART variables available in the module using the multiHART area. To do so, you must use the command byte in the output area to request a HART variable from the module. The command byte identifies the requested HART variable (HART variable reference): HART variable reference Bit 0...3: Bit 4...7: Variable identifier Channel number 0...15 1 = Primary 2 = Secondary 3 = Tertiary 4 = Quaternary The command is acknowledged via the acknowledgment byte in the input range. As soon as the HART variable reference requested using the command can be read, the requested HART variable can be evaluated. If you leave the command byte of the multiHART range unchanged, the module will continuously update the corresponding HART variable. If an invalid HART variable reference is requested, this is also acknowledged accordingly. The value of the corresponding HART variable is then zero and the quality code is signaled with 0x37H (initialization value of the analog module). Example: The primary variable is to be read from channel 6. Command = 61 H Acknowledgment == 61 H ? 11.76 mA Overflow 11.76 mA Overrange 10 mA Nominal range Current measuring range 0 to 20 mA Values Dec. Table C-3 Range Current measuring range Hex. Range 0 to 20 mA 32767 7FFF >23.52 mA Overflow 32511 7EFF 27649 6C01 27648 6C00 20 mA Nominal range 20736 5100 15 mA 1 1 723.4 nA 0 0 0 mA 23.52 mA Overrange Current measuring ranges 4 to 20 mA and 4 to 20 mA HART Values Dec. Current measuring range Hex. Range 4 to 20 mA 32767 7FFF 32511 7EFF 27649 6C01 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB >22.81 mA Overflow 22.81 mA Overrange 75 Analog value display C.1 Representation of analog values in the current measuring ranges Values 76 Current measuring range Range 27648 6C00 20 mA Nominal range 20736 5100 16 mA 1 1 4 mA + 578.7 nA 0 0 4 mA -1 FFFF -4864 ED00 -32768 8000 Underrange 1.185 mA < 1.185 mA Underflow Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Index A Address assignment, 32 AI 16xI 2-wire HART HA Accessories, 8 Channel parameters, 14 Commissioning, 31 Configuration, 31 Diagnostics interrupt, 24 Diagnostics message, 51 Functions, 8 Module parameters, 14 Parameters, 13, 14 Pin assignment, 10 Properties, 7 Schematic circuit diagram, 12 Technical specifications, 35 B Burst mode, 29 C Channel fault LED, 21 Channel parameters, 14, 45 Channel status LED, 21 Command interface, 61, 63 Commissioning, 31 Communication, 72 Configuration, 31 HART variable, 32 Conventions, 6 D Data record 128, 45 Header information, 46 Parameters, 47 Data record 130, 49 Header information, 49 Parameters, 49 Data records, 61 Device status, 29 DIAG LED, 22 Diagnostics interrupt, 24 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB Diagnostics message, 51 Documentation Range of validity, 5 E Error management, 31 F Fast mode, 29 Fault displays, 21 Feature data, 70 Field devices Parameter reassignment, 31 H HART Command, 63 Command interface, 61, 66 Commands, 27 Communication, 26, 72 Definition, 25 Device status, 29 Directory, 69 Error management, 31 Evaluating variables, 58 Fast mode, 29 Feature data, 70 Mapping parameters, 20 Operating data records, 62 Operating principle, 26 Parameter assignment tool, 30 Programming, 66 Protocol, 25, 28 Settings, 73 Signal, 26 System environment, 30 Variable data record, 71 Variables, 32 HART variables Configuring, 32 HCF, 25 77 Index I T Interference frequency suppression, 18 Technology parameters, 45 Terminal block, 9 L LED displays, 21 M V Value status Evaluating, 57 Variable data record, 71 Mapping parameters, 20, 49 Module parameters, 14 MT LED, 22 O Operating data records, 62 P Parameter reassignment, 31 Parameters, 13, 14 Pin assignment, 10 PWR LED, 23 Q Quality code, 33 as of revision 7, 34 Revisions 5 and 6, 33 R Request data record, 63 Response data record, 64 Reverse polarity, 12 S Schematic circuit diagram, 12 SHC sequence, 61 SIMATIC PDM configuration tool, 30 Smoothing, 17 Status displays, 21 Supply voltage, 12 System environment, 30 78 Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1) Manual, 11/2017, A5E39408968-AB