Quartz Timer Off ers Eight Time
Ranges, Seven Output Operations
Field-selectable time ranges from 0.01
second to 9999 hours
Selectable elapsed time (UP) and
time remaining (DOWN) display
Contact and solid-state outputs available
simultaneously
ON-delay with sustained and adjustable
one-shot outputs, with and without
continued timing
Built-in DC power supply for input devices
Easy-to-read 8 mm-high LED display
10-year battery memory back-up available
Draw-out construction allows setting,
servicing without disconnecting wiring
Panel mounting hardware included
Add the supply voltage to the part number when you order. For example, H5AN-4DM-AC100-240.
TIMERS
Timing functions ON-delay and ON-delay with one-shot
Contact type SPDT relay and open collector transistor outputs, both available simultaneously
Terminal form 14 terminal screws on rear of case
DC power supply for Provided Provided
external components
Memory back-up Not provided Provided, 10-year built-in battery
Part number H5AN-4D H5AN-4DM
AC 24 V or 100 to 240 V; 50/60 Hz 24 V or 100 to 240 V; 50/60 Hz
DC 12 to 24 V, 48 V or 100 V 12 to 24 V
Description Part number
Plastic front cover H5AN COVER 0377762-0
Mounting bracket (one pair supplied with each timer); order two Y92H-5
REPLACEMENT PARTS
Supply
voltage
Multifunction Digital Timer H5AN
Ordering Information
1
H5AN H5AN
2
Part number H5AN-4D H5AN-4DM
AC 24 V or 100 to 240 V; 50/60 Hz 24 V or 100 to 240 V; 50/60 Hz
DC
Operating voltage 85 to 100% of rated voltage
AC 10 VA at 240 VAC, 50 Hz
DC 5 W at 24 VDC
Internal power supply 12 VDC ±10%, 80 mA
for external components (permissible ripple factor: 5% max.)
Timing functions ON-delay and ON-delay with one-slot
Reset and Gate inputs No-voltage
Type Time limit SPDT relay and open collector solid-state output
Instantaneous
Max. load 3 A, 250 VAC (p.f. = 1) for relay; 100 mA max., 30 VDC for open collector output
Min. load 10 mA, 5 VDC
Repeat accuracy ±0.01% ±0.05 sec max. (power-OFF start); ±0.005% ±0.03 sec max. (reset start)
Setting error See "Repeat Accuracy"
Resetting system Power-OFF, manual or external Manual or external
Resetting time Power-OFF: 0.5 sec min.; External: 0.02 sec signal minimum
Indicators Time Up (red LED), Reset Input (red LED); 8 mm LED numeric display
Materials Plastic
Mounting Panel; two mounting brackets included
Connections Back-mounted screw terminals
Weight 360 g (12.7 oz.)
Approvals UL/CSA/SEV
Operating ambient temperature -10° to 55°C (14° to 131°F)
Humidity 35 to 85% RH
Vibration Mechanical durability 10 to 55 Hz; 0.75 mm (0.03 in) double amplitude
Malfunction durability 10 to 55 Hz; 0.5 mm (0.02 in) double amplitude
Shock Mechanical durability 30 G
Malfunction durability 10 G
Variation due to voltage change See "Repeat Accuracy"
Variation due to temperature change See "Repeat Accuracy"
Insulation resistance 100 M min. at 500 VDC
Dielectric strength 2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals and non-current-
carrying metal parts
750 VAC, 50/60 Hz for 1 minute between non-continuous contacts
Service life Mechanical 10 million operations minimum
Electrical 100,000 operations minimum at maximum rating
Supply
voltage
Power
consumption
Control
output
12 to 24 V
(permissible ripple factor: 20% max.)
12 to 24 V, 48 V or 100 V
(permissible ripple factor: 20% max.)
Specifications
H5AN H5AN
3
Engineering Data
ELECTRICAL SERVICE LIFE
Timing Charts
ELAPSED TIME (UP) DISPLAY
ON
OFF
Reset 8 - 9
input
Gate 8 - 10
input ON
OFF
Time setting
Digital display
ON
OFF
Control Relay 4 - 5, 4 - 6
output Solid-state 12-13-14
Time up indicator ON
OFF
Reset input indicator ON
OFF
Interruption
(See note)
(See note)
NOTE: After the set time has elapsed, operation continues according to the mode selected.
TIME REMAINING (DOWN) DISPLAY
Power 1 - 2 ON
OFF
ON
OFF
Reset 8 - 9
input
Gate 8 - 10
input ON
OFF
Time setting
Digital display
ON
OFF
Control Relay 4 - 5, 4 - 6
output Solid-state 12-13-14
Time up indicator ON
OFF
Reset input indicator ON
OFF
NOTE: After the set time has elapsed, operation continues according to the mode selected.
Interruption
(See note)
(See note)
Power 1 - 2 ON
OFF
H5AN H5AN
4
OPERATION MODES
Set value
Digital display
Reset
Control output
Set value
Digital display
Reset
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized. The
preset is display until the timer is reset.
F
Sustained
Output Set value
Digital display
Reset
Control output
Set value
Digital display
Reset
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized. The
display will continue to increment until the timer is reset.
The display decrements from the preset to zero. When
zero is reached, the output is energized. The display
will continue to decrement until the timer is reset.
C
One-shot
Output Set value
Digital display
Reset
Control output
Set value
Digital display
Reset
Control output
The display increments from zero to the preset. When
the preset is reached, the timer restarts its timing from
zero and energizes a one-shot output. The cycle is
repeated until the timer is reset.
Set value
Digital display
Reset
Control output
R
One-shot
Output Set value
Digital display
Reset
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. Timing from zero is restarted at the
trailing edge of the output. The cycle is repeated until
the timer is reset.
K
One-shot
Output Set value
Digital display
Reset
Control output
Set value
Digital display
Reset
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. The display continues to increment until
the timer is reset.
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. The display continues to decrement until the timer
is reset.
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. Timing from the preset is restarted at the trailing
edge of the output. The cycle is repeated until the timer
is reset.
The display decrements from the preset to zero. When
zero is reached, the timer restarts its timing from the
preset and energizes a one-shot output. The cycle is
repeated until the timer is reset.
The display decrements from the preset to zero. When
zero is reached, the output is energized. Zeros are
displayed until the timer is reset.
NOTE: In modes F and K, when the 99 min 59 s or 99 h 59 min ranges are selected in DOWN display, the overflow values will be
shown as 9959, 9958, 9957, etc.
In C mode, the set time should be longer than the one-shot time.
Mode Elapsed time (UP) display Time remaining (DOWN) display
N
Sustained
output
H5AN H5AN
5
Mode Elapsed time (UP) display Time remaining (DOWN) display
P
One-shot
output
OPERATION MODES (continued)
Set value
Digital display
Reset
Control output
Reset
Control output
Set value
Digital display
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. The timer restarts its timing, but the
display is not updated until the one-shot time is up.
The cycle is repeated.
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. The timer restarts its timing, but the display is not
updated until the one-shot time is up. The cycle is
repeated.
Q
One-shot
Output Set value
Digital display
Reset
Control output
The display increments from zero to the preset. When
the preset is reached, the output is energized for the
one-shot time. The display continues incrementing
during the one-shot, but restarts from zero when the
one-shot time is up. The cycle is repeated.
The display decrements from the preset to zero. When
zero is reached, the output is energized for the one-shot
time. The display continues decrementing during the
one-shot, but restarts from the preset when the one-shot
time is up. The cycle is repeated.
NOTE: In mode Q, when the 99 min 59 s or 99 h 59 min ranges are selected in DOWN display, the overflow values will be shown as
9959, 9958, 9957, etc.
In P mode, the set time should be longer than the one-shot time.
Dimensions
Set value
Digital display
Reset
Control output
Unit: mm (inch)
Panel cutout Panel cutout for side-by-side
mounting for two units
NOTE: Recommended panel thickness is 1 to 5 mm.
Panel cutout conforms to DIN 43700.
72
(2.83)
72
(2.83) 115 (4.53)
130 (5.12)
67.6
(2.66)
Two mounting
brackets M3.5 terminal
screws
H5AN H5AN
6
Connections
Input terminal number (no-voltage only)
COM Reset Gate
8 9 10
Power supply terminal numbers
AC (common), DC- AC (hot), DC+ Ground
1 2 3
Output terminal numbers
Contact
COM NO NC
4 5 6
Solid-state
COM Load Surge absorber
12 13 14
POWER SUPPLY CONNECTION
Connect the required supply voltage to terminals
1 and 2. In environments with external noise,
connect ground terminal 3 at a resistance of less
than 100.
0 VDC
+
LOAD CONNECTION
Terminals 4, 5 and 6 are for contact output.
Terminals 12 and 13 are for solid-state output.
Terminal 14 is a surge absorber for use when
an inductive load is connected.
Load Operation
Contact output Solid-state output
High and low output levels
are selected by internal switch.
See "Operations" section for
setting information.
AC power supply DC power supply
24 VAC or
100 to 240 VAC, 50/60 Hz
12 to 24 VAC,
(48 VDC or 100 VDC
for H5AN-4DM only)
+
Power supply for externally connected equipment
Voltage supply DC- DC+
12 VDC, 80 mA 8 11
Timing operation
Load 1
Load 2
HL
setting
LH
setting
Load 3
Start Time up
H5AN H5AN
7
RESET AND GATE INPUTS
Reset input Gate input
Use a no-voltage contact or open
collector type transistor between
terminals 8 and 9. The timer resets
when contact is made or when the
transistor is ON.
Use a no-voltage contact or open
collector type transistor between
terminals 8 and 10. The timer stops
when the contact makes or when
the transistor is ON. When the gate
signal opens, timing resumes at the
point of interruption. Use a contact
with minimum contact bounce (chatter),
otherwise the bounce time will cause
an error in the timer's operating time.
Input signal requirements
Contact input
Solid-state input
Input type Open collector transistor
Voltage when collector is OFF 20 V min.
Saturated voltage when transistor is ON 3 V max.
Collector current 50 mA min.
Input current between collector and base 0.5 µA max.
Solid-state inputs (NPN)
When connecting a solid-state circuit not of
the open collector type to the gate or reset
inputs as shown in the figure below, the
voltage of the solid-state circuit (+ V)
should be 13 to 30 V, and the VCE(S) of the
transistor should be less than 3 V (the
current that flows from either terminal 9 or
10 is approximately 10 mA). Moreover, it is
essential that the circuit be ON for gate or
reset input, and OFF when there is no input.
POWER SUPPLY FOR EXTERNALLY-CONNECTED COMPONENTS
Resistance 1 k max.
Residual voltage 1 V max. when the contact makes
Contact material Gold-plated contacts recommended
The H5AN has a built-in power supply for
externally connected components such as
sensors for gate or reset input, or loads
connected to the solid-state control output
(12 VDC, 80 mA).
Power can be applied to the sensors and
loads simultaneously.
Gate or Reset input Solid-state output load
H5AN H5AN
8
A single contact or open collector type transistor
can be used to apply the gate or reset input to
two or more H5AN timers. Caution is required
because a large current flows into the transistor.
The current that flows from H5AN is approximately
10 mA per unit.
Operation
NOMENCLATURE
Front cover
Time-up indicator
Reset input indicator
Pushbutton switch for manual reset
Maintenance access screw
One-Shot time adjustment screw
(0.1 to 1 sec range)
Time range decal
7-segment LED display
SIMULTANEOUS INPUT TO SEVERAL H5AN TIMERS
ACCESS TO SELECTOR SWITCHES
Open the front cover.
Use a Phillips screwdriver
to gain access to internal
parts. As the maintenance
access screw is turned, the
internal mechanism draws
out. Pull out the timer from
its case to set internal
switches to desired settings.
H5AN H5AN
9
PROGRAMMING H5AN SPECIFICATIONS
Internal selector switches are used for programming
elapsed time (UP) or time remaining (DOWN) display,
time range, operation mode and solid-state output level.
Manual reset (front panel)
enable switch
Time range
selection switch Operation mode
selector switch
Changed "high" to "low" when time is up
Changed "low" to "high" when time is up
Solid-state output
level selector switch
Switch
position Time range
Time range selector settings
0 0.01 to 99.99 s
1 0.1 to 999.9 s
2 1 to 9999 s
3 1 s to 99 min 59 s
4 0.1 to 999.9 min
5 1 min to 99 h 59 min
6 0.1 to 999.9 h
7 1 to 9999 h
8 same as "0"
9 same as "1"
Switch Operation
position Mode Display mode
0N
1F
2 C Time remaining
3 R (DOWN) display
4K
5P
6Q
7 (same as 0)
8N
9F
A C Elapsed time
B R (UP) display
CK
DP
EQ
F (same as 8)
Operation mode selector
Use the four pushwheel switches on the front
panel to set the desired time. The H5AN timer
does not display the decimal point in ranges for
99.99 sec, 999.9 sec, 999.9 min or 999.9 hr.
Firmly push the switches to avoid having two
numbers appear in the display window. This
causes the operating time to drift widely.
In the 99 hr 59 min and 99 min 59 sec
ranges, the second digit from the right
cannot be more than 5. Even if the digit
is set to 6, 7, 8 or 9, the setting will be
interpreted as 5.
SETTING TIME PRESET
Undesirable setting
5 min
30 second
59 second
99 min
Warning
Do not set all four digits to
zero. This causes a momentary
output to occur that may lead to
accidental injury or damage.
00 h 00 min
(Momentary
output)
59 min
99 h
9 9 7 9
SETTING ONE-SHOT TIME
Output modes C, R, K, P and Q provide a one-
shot output. Be sure to set the one-shot value,
between 0.1 and 1 second, using the poten-
tiometer in the lower right corner of the front
panel.
Any digit higher
than 5 will be
interpreted as 5.
H5AN H5AN
10
PROGRAMMING CONSIDERATIONS FOR TIMERS WITH MEMORY PROTECTION
H5AN-4D
RECOVERY FROM A POWER FAILURE
H5AN-4DM
This timer has a battery backed memory to
protect settings against power failure.
When a power failure occurs, the timing
operation is interrupted. When power
returns, the timer continues from the point
of interruption.
The back-up battery will retain data for up
to 10 years. However, the battery may not
be replaced.
The duration of the power failure determines how the
timer acts when power is restored.
With a power failure of less than 0.01 second duration,
the timer resumes timing from the point of interruption
upon recovering power.
Length of power failure Action when power is restored
0.01 sec or less Timer resumes timing and does not reset
0.01 sec to 0.5 sec Timer either resets or resumes timing
0.5 sec or more Timer resets
NOTE: ALL DIMENSIONS ARE IN MILLIMETERS. To convert millimeters into inches divide by 25.4.
For units with memory protection, it is
necessary to reset (either externally or
manually) the timer at the time the power is
applied. If the timer is not reset, it operates
in accordance with the previous data. Also
reset the timer after any changes are made
to the internal switches.
OMRON ELECTRONICS, INC. OMRON CANADA, INC.
One East Commerce Drive 885 Milner Avenue
Schaumburg, IL 60173 Scarborough, Ontario M1B 5V8
1-800-55-OMRON 416-286-6465
Cat. No. GC TI8 11/97 Specifications subject to change without notice. Printed in the U.S.A.