ACDC
Specification
3060 Watts
Energy Efficiency Level V
CEC2008 & EISA2007 Compliant
IT & Medical Approvals
China Compulsory Certification (CCC) Qualified
Optional Class II Versions
Optional White Case Versions
3 Year Warranty
AFM Series
Input
Input Voltage 80-264 VAC, derate output power 25%
<90 VAC
Input Frequency 47-63 Hz
Input Current AFM30: 0.8 A rms at 115VAC,
AFM45: 1.2 A rms at 115VAC,
AFM60: 1.5 A rms at 115 VAC
Power Factor EN61000-3-2, class A
Earth Leakage Current 150 µA max at 264 VAC/60 Hz
No Load Input Power AFM30/45: <0.3 W, AFM60: <0.5 W
Output
Output Voltage See table
Output Voltage Trim Not user-adjustable
Initial Set Accuracy ±2%
Minimum Load No minimum load required
Start Up Delay 3 s max at 115 VAC
Hold Up Time 8 ms minimum at 115 VAC
Line Regulation ±1.0% maximum
Load Regulation 2.5% maximum
Transient Response 4% max. deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise 1% max pk-pk (1)
Overvoltage Protection 110-170% Vnom, recycle input to reset
Overload Protection AFM45/60: 110-170%,
AFM30: 110-220%, auto recovery
Short Circuit Protection Trip and restart (hiccup mode)
Temperature 0.04%/°C
Coefficient
xppower.com
General
Efficiency See table
Energy Efficiency Level V
Isolation 4000 VAC Input to Output, 2 x MOPP
1500 VAC Input to Ground, 1 x MOPP*
Output 0 V is electrically connected to
Input Ground*. *Not C8 version.
Switching Frequency 30/45 W: 58 kHz typ., 60 W: 52 kHz typ.
Power Density AFM30: 2.8 W/In3, AFM45: 4.2 W/In3,
AFM60: 3.76 W/In3
MTBF >250 kHrs to MIL-HDBK-217F at 25 °C,
GB, full load
Environmental
Operating Temperature 0 °C to +60 °C, derate from 100% power
at +40 °C to 60% power at +60 °C
Operating Humidity 10-95% RH, non-condensing
Storage Temperature -40 °C to +80 °C
Operating Altitude 2000 m
Shock 30 g, 10 ms on 3 axes
Vibration 5-100 Hz, 2.31 m/s2, 20 mins, 3 axes
EMC & Safety
Emissions EN55011/22/FCC Class B conducted,
EN55011/22/FCC Class B radiated
Harmonic Currents EN61000-3-2, Class A
Voltage Flicker EN61000-3-3
ESD Immunity EN61000-4-2, 6 kV contact and
8 kV air discharge
Radiated Immunity EN61000-4-3, 3 V/m Perf Criteria A
EFT/Burst EN61000-4-4, level 3 Perf Criteria A (7)
Surge EN61000-4-5, installation class 3
Perf Criteria A
Conducted Immunity EN61000-4-6, 3 Vrms Perf Criteria A
Magnetic Field EN61000-4-8, 3 A/m, Perf Criteria A
Dips & Interruptions EN61000-4-11, 30% for 10 ms,
60% 100 ms, 100% 5000 ms,
Perf Criteria A, B, B
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms,
Perf A, A, A, B (8)
Safety Approvals EN60950-1, UL60950-1, IEC60950-1
EN60601-1 (3rd Ed.), UL60601-1 (2nd Ed.),
IEC60601-1 (3rd Ed.) China Compulsory
Certification (CCC) Qualified.
04-Aug-14
ACDC
AFM3060
Mechanical Details
Models and Ratings
Notes
1. Ripple and noise measured at 20 MHz bandwidth with a 10 µF tantalum and
0.1 µF ceramic cap connected at the measurement point.
2. Total regulation includes initial set accuracy, line and load regulation.
3. For optional Class II versions with a polarised IEC320-C8 inlet, add suffix ‘C2’
to the model number, e.g. AFM60US24C2.
4. For alternative IEC320-C6 inlet, add suffix ‘C6’ to the model number
eg. AFM60US24C6.
5. For white case version add suffix -W. MOQ applies, contact sales for details.
6. Other output voltages are available, contact sales for details.
7. Minimum average of efficiencies measured at 25%, 50%, 75% & 100% load.
8. A minimum load of 1% is required to meet performance criteria A.
9. Performance criteria given for high line input.
0.17
(4.4)
0.68
(17.3)
0.07
(1.8)
0.66
(16.8)
B
0.53
(13.7)
80º
1.41
(36.0)
C
A
37.4 ±2 (950 ±50)
Output Plug: ø 5.5 x ø 2.5 x 11.0 mm
inner positive
Optional AC Cable Restraint (see note 8 below)
1.31
(33.4)
Standard AC INLET
IEC-320-C14
Optional C8P AC INLET
IEC-320-C8P
Optional C6 AC INLET
IEC-320-C6
1. All dimensions shown in inches (mm). Tolerance is 0.02 (0.5) maximum, except
output cable length.
2. Weight: AFM45: 0.56 lbs (256 g), AFM60: 0.78 lbs (360 g) approx.
3. Case material is PC Class 94 V-0.
4. Output Lead: UL1185, 16 AWG
5. For European mains lead order part EU-MAINS-IEC for C14 versions,
EU-MAINS-5 for C6 versions or EU-MAINS-8 for C8 versions.
6. For UK mains lead order part UK-MAINS-IEC for C14 versions,
UK-MAINS-5 for C6 versions or UK-MAINS-8 for C8 versions.
7. For US mains lead order part US-MAINS-IEC for C14 versions,
US-MAINS-5 for C6 versions or US-MAINS-8 for C8 versions.
8. For optional AC Cable Restraint on the standard input version add suffix ‘‘A’ to
the model number e.g. AFM60US24A. AC Mains Lead must be Interpower
Corporation, part number 70006020300. Option AC Cable Restraint is not
available on IEC320-C6 inlet or Class II versions.
9. The standard C7 cable fits the C8P connector.
Output Power Output Voltage(6) Output Current Efficiency(7) Model Number(3,4,5)
30 W 12 V 2.50 A 87.9% AFM30US12
30 W 15 V 2.00 A 88.4% AFM30US15
30 W 18 V 1.67 A 87.6% AFM30US18
30 W 24 V 1.25 A 88.0% AFM30US24
48 W 12 V 4.00 A 87.7% AFM45US12
48 W 15 V 3.20 A 88.0% AFM45US15
48 W 18 V 2.67 A 87.2% AFM45US18
48 W 24 V 2.00 A 87.7% AFM45US24
60 W 12 V 5.00 A 87.3% AFM60US12
60 W 15 V 4.00 A 88.2% AFM60US15
60 W 18 V 3.34 A 88.3% AFM60US18
60 W 24 V 2.50 A 87.8% AFM60US24
Notes
AFM30 & 45 AFM60
A 4.76 (121.0) 4.92 (125.0)
B 1.97 (50.0) 2.44 (62.0)
C 1.21 (30.8) 1.33 (34.0)