1211
Dimensions are shown for
reference purposes only. Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change. www.tycoelectronics.com
Technical support:
Refer to inside back cover.
P&B
Catalog 1308242
Issued 3-03
O
NC N
A 1 1 1 H
1.88
(47.8)
1.88
(47.8) 2.83
(71.9)
.32
(8.1)
1.76
(44.7)
.64
(16.3)
3.15
(80.0)
CNT series
Multifunction, Digital
Time Delay Relay/Counter
10 programmable timing modes + 2 counting modes
0.1 sec. to 9,990 hr. programmable timing range
1 to 99,900 counting range
LCD digital display
Universal (24-240VAC/VDC) and fixed input types
10A output relay with DPDT contacts
Thumbwheel switches for programming
File E22575
File LR15734
Timing and Counting Modes
See the following page for a complete description of all program-
mable timing and counting modes.
Timing Specifications
Timing Ranges: 0.1 to 99.9 / 1 to 999 sec.; 0.1 to 99.9 / 1 to 999 min.;
0.1 to 99.9 / 1 to 999 / 10 to 9,990 hr.
Timing Adjustment: Digital adjustment via thumbwheel switches.
Tolerance: ±0.5% ±0.05 sec.
Delta Time (for AC units add ±1 cycle 60 Hz.): ±0.1% ±0.05 sec.
Repeatability (Including first cycle of operation.): ±0.1% ±0.05 sec.
Reset Time (power interruption): 45 ms, typ.; 60 ms, max.
Minimum Pulse Width, Control: 50 ms.
Recycle Time: 45 ms, typ.; 60 ms, max.
Counting Specifications
Maximum Count: 1 to 999; 10 to 9,990 (÷10); 100 to 99,900 (÷100).
Maximum Count Rate: 100 counts per second.
Mimumum Pulse Width:Count (Control): 3 ms.; Reset: 3 ms.
Available Counting Functions: Operate at preset count and release at
preset count.
Contact Data @ 25°C
Arrangements: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @
120VAC.
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
Initial Dielectric Strength
Between Open Contacts: 1,000V rms, 60 Hz.
Between All Other Conductors: 1,500V rms, 60Hz.
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Input Data @ 25°C
Voltage: Universal Input Type: 24 - 240V ±15%, 50/60 Hz. AC or DC.
Fixed Input Types: 120VAC ±15%, 50/60 Hz and 12VDC.
Power Requirement:
Universal Input Type:10VA @ 240VAC; 5VA @ 120VAC; 1VA @ 24VAC.
10W @ 240VDC; 5W @ 120VDC; 1W @ 24VDC.
Fixed Input Types: 3VA @ 120VAC; 3W @ 12VDC.
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Outline Dimensions Wiring Diagrams (Bottom Views)
(pins numbered clockwise from keyway)
* Note: Input polarity for DC operation. For most reliable operation on AC, connect high side
to “+” and low side to “–”.
** Important: A dry circuit switch is recommended. A “dry circuit” switch is one rated to
reliably switch currents of less than 50mA. Use of a switch rated for other
than dry circuit may result in failure of the time delay relay to function properly.
Fits 1.77 x 1.77 (45 x 45)
Panel cutout
Universal Input Model
Input Voltage Part Number
24-240VAC/VDC CNT-35-96
Fixed Input Models
Input Voltage Part Number
12VDC CNT-35-26
120VAC CNT-35-76
INPUT*
111
+_
RETURN
CONTROL
RESET
USE SAME
FOR RESET
Accessories
Part Number Name Description
SSA-24C667 Mounting Clip Ratchet-fit clip slides onto CNT from behind
to secure CNT in panel mount applications.
SSA-24C668 Protective Cover Clear, flexible cover slips snugly over bezel of
CNT to help protect against dust and moisture.
Durable cover also helps prevent inadvertant
changes of programming switch settings.
Mechanical Data
Termination: 11-pin octal style plug.
Enclosure: Beige plastic 1/16 DIN case.
Sockets: Fits either 27E123 or 27E892 (snap-on) screw terminal sockets.
Weight: 4.3 oz. (122g) approximately.
External Control: CONTROL, RESET: Active on contact closure or solid
state switch closure to RETURN, 0-1.0VDC maximum
voltage level (see wiring diagrams for interface circuits.
Environmental Data
Temperature Range: Storage: -20°C to +70°C.
Operating: -10°C to +55°C.
Humidity: 85% relative humidity, non-condensing.
Input Voltages & Limits @ 25°C
Input Nominal Minimum Maximum
Type Voltage Voltage Voltage
Universal 24-240VAC/VDC 20.4VAC/VDC 276VAC/VDC
Fixed 120VAC 102VAC 138VAC
12VDC 10.2VDC 13.8VDC
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
AC models will operate on 50 or 60 Hz.
INPUT*
111
+_
RETURN RESET
CONTROL
(COUNT)
EXTERNAL CONTROL SWITCHES**
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
1212 Dimensions are shown for
reference purposes only. Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
P&B
Catalog 1308242
Issued 3-03
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Protective Cover & Mounting Clip Dimensions
SSA-24C668
Protective Cover SSA-24C667
Mounting Clip
A . Delay On Operate
Output relay turned on at end of programmed time interval which is started
by CONTROL input or power-on with CONTROL on. Relay turned off by
RESET input until next cycle is started. With CONTROL on, turning RESET
off restarts timing
B. Delay On Release
Output relay turned on with CONTROL input and remains on for programmed
time interval following removal of CONTROL. During time interval after
release of CONTROL, RESET turns relay off until cycle restarted with
reapplication of CONTROL. With CONTROL on, relay is held off while
RESET is activated.
C. Interval On
Output relay turned on for programmed time interval by CONTROL or power-
on with CONTROL on. RESET turns relay off until next cycle is started, and
does not restart timing when RESET is removed.
D. Control-Off Interval On
Output relay turned on for programmed time interval by turn-off of CON-
TROL. RESET turns relay off until next cycle is started, and does not restart
timing when RESET is removed.
E. Recycle
Output relay turned on at end of programmed time interval which is started
by momentary CONTROL input or power-on with CONTROL on. Relay stays
on for equal time interval, then turns off and cycle is repeated on a free-
running basis until terminated by momentary RESET, turning relay off. With
CONTROL on, turning RESET off restarts cycle.
F. Single Cycle
Output relay turned on at end of programmed time interval which is
started by momentary CONTROL input or power-on with CONTROL
on. Relay stays on for equal time interval, then turns off. RESET
terminates timing and turns relay off. Turning RESET off does not restart
timing.
G. Control On-Off Interval On (Watch Dog Timer)
Output relay turned on and programmed time interval started or restarted
by change of CONTROL input. RESET turns relay off and stops timing.
Turning RESET off does not restart timing.
H. Control On-Off Delay
Output relay turned on at end of programmed timing interval which is
started or restarted by change of CONTROL input. If relay is on, turn-off
of relay occurs at end of programmed time interval which is started or
restarted by change of CONTROL input. RESET turns relay off and stops
timing. Turning RESET off does not restart timing.
I. Pulse
Output relay turned on at end of programmed time interval, which is
started by CONTROL input, for 0.5 second duration, and continues in
pulsed mode at programmed time interval with fixed 0.5 second on-time.
Turning CONTROL off turns relay off and stops timing. RESET turns relay
off and inhibits operation. With CONTROL on, removal of RESET restarts
timing.
J. Cumulative Delay On Operate
Output relay turned on at completion of total accumulate CONTROL input
duration equal to programmed time. Turning CONTROL off before
accumulation of programmed time results in measured time total being
held until CONTROL is again turned on and total programmed time value
is reached. RESET input resets time value to zero and turns relay off if
energized. Turning RESET off restarts timing if CONTROL is on.
Timer Function Descriptions
1.99
(50.5)
.40
(10.2)
1.99
(50.5)
“A
“A
Section "A-A"
.591
(15.0)
1.654
(42.0)
1.890
(48.0)
1.970
(50.0)
2.047
(52.0)
2.283
(58.0)
CO – Operate at Preset Count – Normal Mode
After initializing by momentary activation of RESET input, each on/off signal
at COUNT (CONTROL) input increments displayed count in upcounting
manner from initial 000 value until preset count, set by thumbwheel
switches, is reached and output relay turns on. Additional inputs continue to
increment displayed count. Continued counting past maximum count (999)
results in a “wrap-around” effect to 000, followed by contrinued up-counting.
Activation of RESET input turns relay off and resets count to zero.
Counter Function Descriptions CR – Release at Preset Count – Normal Mode
Initializing by momentary activation of RESET input turns relay on. Operation
is similar to CO (Operate at Preset Count) except relay turns off at a preset
count.
CO or CR – Divide-by-10 Mode
Operation is as described previously, except count is incremented for every
10 on/off input signals for a maximum presettable count of 9,990.
CO or CR – Divide-by-100 Mode
Operation is as described previously, except count is incremented for every
100 on/off input signals for a maximum presettable count of 99,900.
Programming Switch Diagram
With this setting, the relay would operate after a delay period of 214 seconds.
A214S
Function Select:
Timer Mode: A = Delay On Operate E = Recycle I =Pulse
B = Delay On Release F =Single Cycle J =Cumulative Delay On Operate
C = Interval On G = Control On-Off Interval On
D = Control-Off Interval On H = Control On-Off Delay
Counter Mode: B = Divide by 10 C = Divide by 100 A & D-J = Normal Count
Time/Counter Setting: 001 to 999
Time Base/Counter Mode Select:
Time Base: .1S = 0.1 to 99.9 Sec. .1M = 0.1 to 99.9 Min. .1H = 0.1 to 99.9 Hrs. 10H =10 to 9990 Hrs.
S = 1 to 999 Sec. M = 1 to 999 Min. H = 1 to 999 Hrs.
Counter Mode: CO =Operate at Preset Count CR = Release at Preset Count