Tmax
MCCBs
Low Voltage Products & Systems 16.1
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Introduction
ABB is once again demonstrating its
commitment to new product development
and its superiority in product technology.
Never before has the industry seen such high
performance, versatility and standardization
in a range of molded case circuit breakers.
The ABB Tmax line of circuit breakers, with a
range up to 3000A, has several key features
that go along with its very small size:
Double insulation – this construction
characteristic allows for the UL Listed
eld installation of internal accessories
without exposure to energized parts.
Complete range of electrical and
mechanical accessories
Positive operation – breakers from ABB
ensure that the toggle indicates the
precise position of the moving contacts.
This guarantees safe and reliable
signaling by the device.
Installation – Tmax molded case circuit
breakers can be installed in panels and
switchboards in either the horizontal
or vertical planes while being fed from
either end without any derating of their
performance characteristics.
Interrupting ratings at 480VAC up to
150kAIC.
Compact size
All Tmax molded case circuit breakers
are UL Listed and IEC rated for global
application and acceptance.
All versions of the Tmax family are
suitable for reverse feed applications.
The ABB Tmax product line has the
performance and accessories to satisfy all
industry requirements in the 600VAC to 600VDC
ranges.
Frame sizes — Nine basic sizes
The ABB Tmax series includes nine basic frame
sizes as well as the T1 single pole with the
range rated from 15A to 3000A at 480VAC. The
various versions carry the following interrupting
capacities:
B Basic breaking capacity
N Normal breaking capacity
S Standard breaking capacity
H High breaking capacity
L Extra high breaking capacity
V Very high breaking capacity
Derived versions
Thermal magnetic
Electronic
Molded case switches
Motor circuit protectors (MCPs)
Direct current (DC) rated
ABB Tmax versions
Fixed: all models
Drawout or plug-in: T2, T3, Ts3, T4, T5, T6,
T7 & T7M
UL File #E93565 (breakers and MCPs)
#E116596 (Accessories)
#E116595 (Molded case switches)
Tmax
Molded case circuit breakers
Tmax
Molded case circuit breakers
Tmax
MCCBs
16.2 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Selection Guide
Circuit breakers for power distribution
T1 – Ts3
1 In15A = 10kA@277VAC 10kA@347VAC
2 In15A = 35kA@240VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version
4 2p breakers: available only in N interrupting rating
5 In from 15A up to 30A=65kA@480V AC
T1 1P T1 T2 T3 Ts3
Type Tmax T1 1p Tmax T1 Tmax T2 Tmax T3 Tmax Ts3 Tmax Ts3
Frame size [A] 100 100 100 225 150 225
Number of poles [Nr] 1 3-4 3-4 3-4 2-3-4 2-3-4
Rated voltage AC (50-60Hz) [V] 347 600Y/347 480 600Y/347 600 480
DC [V] 500 500 600 500
Interrupting ratings B N S H N S N H L N H L
240V AC [kA rms] 50 265 150 50 65 65 100 150 65 100 150
277V AC [kA rms] 18 1
347V AC [kA rms] 14 1
480V AC [kA rms] 22 235 65 25 35 25 50 85 525 50 65
600Y/347V AC [kA rms] 10 10 10
600V AC [kA rms] 14 14 25
250V DC (2 poles in series) [kA rms] 25 25 35
500V DC (3 poles in series) [kA rms] 25 25 35
500V DC (2 poles in series) [kA rms] 35 50 65 20 35 50
600V DC (3 poles in series) [kA rms] 20 35 50
Trip units TMF
TMD/TMA
ELT
MA
Electronic
Dimensions H[in/mm] 5.12/130 5.12/130 5.12/130 5.9/150 6.7/170 6.7/170
W 3p [in/mm] 1/25.4 3/76 3.54/90 4.13/105 4.13/105 4.13/105
D [in/mm] 2.76/70 2.76/70 2.76/70 2.76/70 4.07/103.5 4.07/103.5
Mechanical life [No. operations] 25000 25000 25000 25000 25000 25000
Tmax
MCCBs
Low Voltage Products & Systems 16.3
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Selection Guide
Circuit breakers for power distribution
T4 – T8
Type Tmax T4 Tmax T5 Tmax T6 Tmax T7/T7M Tmax T8
Frame size [A] 250 400-600 3800 1000-1200 1600, 2000,
2500 & 3000
Number of poles [Nr] 2-3-4 42-3-4 43-4 3-4 3-4
Rated voltage AC (50-60Hz) [V] 600 600 600 600 600
DC [V] 600 600 600
Interrupting ratings N S H L V N S H L V N S H L S H L V
240V AC [kA rms] 65 100 150 200 200 65 100 150 200 200 65 100 200 200 65 100 150 125
277V AC [kA rms]
347V AC [kA rms]
480V AC [kA rms] 25 35 65 100 150 25 35 65 100 150 35 50 65 100 50 65 100 125
600Y/347V AC [kA rms]
600V AC [kA rms] 18 25 35 65 100 18 25 35 65 100 20 25 35 42 25 50 65 100
250V DC (2 poles in series) [kA rms]
500V DC (3 poles in series) [kA rms]
500V DC (2 poles in series) [kA rms] 25 35 50 65 100 25 35 50 65 100 35 35 50 65
600V DC (3 poles in series) [kA rms] 16 25 35 50 65 16 25 35 50 65 20 20 35 50
Trip units TMF
TMD/TMA
ELT
MA
Electronic
Dimensions H[in/mm] 8.07/205 8.07/205 10.55/268 10.55/268 15 / 382
W 3p [in/mm] 4.13/105 5.51/140 8.26/210 8.26/210 16.8 / 427
D [in/mm] 4.07/103.5 4.07/103.5 4.07/103.5 6.06/154 (toggle)
7/178 (motor) 11.2 / 282
Mechanical life [No. operations] 20,000 20,000 20,000 10,000 15,000
1 In15A = 10kA@277 VAC 10kA@347 VAC
2 In15A = 35kA@240 VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version-
4 2p T4N250 and T5N400 available only in N interrupting capacity.
5 In from 15A up to 30A=65kA@480 VAC
6 Applies to MCS only.
T4 T5 T6 T7 T8
Tmax
MCCBs
16.4 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
T3 S 080 T W - 4 xxx
Interrupting rating class
B = Basic
N = Normal
S = Standard
H = High
L = Extra High
V = Very high
Current rating
015 = 15A
080 = 80A
100 = 100A
225 = 225A
250 = 250A
400 = 400A
600 = 600A
800 = 800A
1200 = 1200A
Trip unit function
B = LS/I (AC only)
D = Molded Case Switch (MCS)
T = Thermal-magnetic
M = Magnetic only (MCP)
E5 = Electronic MCP (AC only)
C = LSI (AC only)
E = LSIG (AC only)
Type connectors
W = None
L = Lugs included
Number of poles
-1 =1 pole (T1 only)
-2 = 2 pole
-4 = 4 pole
None = 3 pole
Accessories (added in alpha-numeric order) 1
A = Auxiliary Switch
S_ = Shunt trip with voltage code
U_ = Undervoltage release with voltage code
Frame size
T1 = 100A
T2 = 100A
T3 = 225A
Ts3 = 225A
T4 = 250A
T5 = 400A, 600A
T6 = 600A, 800A
T7 = 1000A, 1200A (toggle)
1 Consult ABB for factory installed accessories.
General information
Catalog number explanation
Tmax
MCCBs
Low Voltage Products & Systems 16.5
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage Continuous rating B (1 pole) N
240VAC 15 – 100A 50 1
347VAC 15A
20 – 100A
10
14
480VAC ∆ 15A 2
20 – 100A
14
22
600Y/347VAC 15 – 100A 10
250VDC 2 pole series 15 – 100A 25
500VDC 3 pole series 15 – 100A 25
T1
General
The T1 breaker family ranges from 15 through 100 amperes. The T1 trip units
are non-interchangeable and use the very latest technology in electromagnetic
relays for overcurrent trip protection. Thermal overload protection is provided by
heat sensitive bimetals. Short circuit protection for the breaker is accomplished
using a precise magnetic coil. State of the art construction in contacts and arcing
chambers aid in limiting damaging fault currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T1 also carries an IEC-60947-2 rating.
Versions
The T1 frame is available in two versions:
T = Thermal-magnetic, xed
D = Molded case switch
Performance levels
The T1 breaker has two performance levels available:
B = Basic single pole
N = Normal three pole
Number of poles
The T1 molded case circuit breaker is available in single, three and four pole
versions. Estimate 4 pole pricing by adding 35% to the 3 pole price and contact
your ABB sales person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
1 In 15A 35kA @ 240VAC.
2 15A available in 480Y/277 VAC only.
3 Interrupting capacity for 16-20A is 16kA
Dimensions 3P Fixed Version 5.12H x 3.00W x 2.76D
Weight 2.34 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage Continuous rating B (1 pole) N
230VAC 15 – 100A 25 350
415VAC 15 – 100A 36
690VAC 15 – 100A 6
500VDC 2 pole series 15 – 100A 36
Tmax
MCCBs
16.6 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Discount schedule S1T [T1]
T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic/Molded Case Switch
T1N TMF — 3 pole thermal magnetic xed
T1B TMF — Single pole thermal magnetic xed 1
T1N-D — Molded case switch
1 Electrical/mechanical accessories cannot be installed on single pole breakers.
2 Rated 480Y/277 VAC for 15A.
3 When protected by a OCPD with appropriate ratings.
T1N TMF — 100% Rated thermal-magnetic
Breaker IC at
480VAC Rating Magnetic
trip
3 pole 600Y/347 500VDC
catalog number
List
price
14kA 15 11000A T1NQ015TL
$ 442
T1N 22kA
20 1000A T1NQ020TL
25 1000A T1NQ025TL
30 1000A T1NQ030TL
40 1000A T1NQ040TL
50 1500A T1NQ050TL
60 1500A T1NQ060TL
70 1500A T1NQ070TL
527
80 1500A T1NQ080TL
90 1500A T1NQ090TL
100 1500A T1NQ100TL
Breaker IC at Rating Magnetic 3 pole, 600Y/347VAC/500VDC List
480VAC trip catalog number price
14kA 15A 1000A T1N015TL 2
20A 1000A T1N020TL
25A 1000A T1N025TL
30A 1000A T1N030TL
40A 1000A T1N040TL $ 402
T1N 22kA 50A 1500A T1N050TL
60A 1500A T1N060TL
70A 1500A T1N070TL
80A 1500A T1N080TL 479
90A 1500A T1N090TL
100A 1500A T1N100TL
Breaker IC at Rating Magnetic 1 pole, 277VAC List
277VAC trip catalog number price
10kA 15A 1000A T1B015TL-1
20A 1000A T1B020TL-1
25A 1000A T1B025TL-1
30A 1000A T1B030TL-1 $ 230
40A 1000A T1B040TL-1
T1B 18kA 50A 1500A T1B050TL-1
60A 1500A T1B060TL-1
70A 1500A T1B070TL-1
80A 1500A T1B080TL-1 262
90A 1500A T1B090TL-1
100A 1500A T1B100TL-1
Breaker Interrupting Rating Magnetic 480VAC/500VDC List
capacity 3 trip catalog number price
T1-D 240V, 50kA 100A 1000A T1N100DL $ 431
Tmax
MCCBs
Low Voltage Products & Systems 16.7
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T2
100A, 480V ∆
Thermal-magnetic/electronic/current limiting
T2
General
The T2 breaker family ranges from 15 through 100 amperes. The T2 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays
for overcurrent trip protection as well as a version with microprocessor-based
electronic trip unit. Thermal overload protection is provided by heat sensitive
bimetals. State of the art construction in contacts and arcing chambers aid in
limiting damaging fault currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T2 also carries an IEC-60947-2 rating.
Versions
The T2 frame is available in four versions:
T = Thermal-magnetic, xed
B = Adjustable LS/I electronic
M = Magnetic only (MCP)
E5 = Electronic instantaneous only (MCP)
Trip functions
These tripping functions are available:
L = Long time
S = Short time
I - Instantaneous
Performance levels
The T2 breaker has two performance levels available:
S = Standard
H = High - UL Current Limiting
Number of poles
The T2 is available in three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage Continuous rating S H
240VAC 15 – 100A 65 150
480VAC ∆ 15 – 100A 35 65
Dimensions 3P Fixed Version 5.12H x 3.54W x 2.76D
Weight 2.84 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage Continuous rating S H
230VAC 15 – 100A 85 100
415VAC 15 – 100A 50 70
690VAC 15 – 100A 78
500VDC 2 pole series 15 – 100A 50 70
Tmax
MCCBs
16.8 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Breaker IC at Rating Magnetic 3 pole, 480VAC List
480VAC trip catalog number price
Discount schedule S2T [T2]
T2
100A, 480V ∆
Thermal-magnetic/current limiting
15A 500A T2S015TW
20A 500A T2S020TW
25A 500A T2S025TW
30A 500A T2S030TW $ 690
40A 500A T2S040TW
T2S 35kA 50A 500A T2S050TW
60A 600A T2S060TW
70A 700A T2S070TW
80A 800A T2S080TW 793
90A 900A T2S090TW
100A 1000A T2S100TW
T2 — 100A TMF thermal magnetic xed
15A 500A T2H015TW
20A 500A T2H020TW
25A 500A T2H025TW
30A 500A T2H030TW $ 942
40A 500A T2H040TW
T2H 65kA 50A 500A T2H050TW
UL Current 60A 600A T2H060TW
Limiting 70A 700A T2H070TW
80A 800A T2H080TW 1,153
90A 900A T2H090TW
100A 1000A T2H100TW
Breaker IC at Rating Magnetic 3 pole, 480VAC List
480VAC trip catalog number price
15A 500A T2SQ015TW
20A 500A T2SQ020TW
25A 500A T2SQ025TW
30A 500A T2SQ030TW $ 760
40A 500A T2SQ040TW
T2S 35kA 50A 500A T2SQ050TW
60A 600A T2SQ060TW
70A 700A T2SQ070TW
80A 800A T2SQ080TW
90A 900A T2SQ090TW 872
100A 1000A T2SQ100TW
Breaker IC at Rating Magnetic 3 pole, 480VAC List
480VAC trip catalog number price
T2 – 100A TMF, 100% rated thermal magnetic xed
15A 500A T2HQ015TW
20A 500A T2HQ020TW
25A 500A T2HQ025TW
30A 500A T2HQ030TW $ 1,025
T2H 40A 500A T2HQ040TW
UL Current 65kA 50A 500A T2HQ050TW
Limiting 60A 600A T2HQ060TW
70A 700A T2HQ070TW
80A 800A T2HQ080TW 1,268
90A 900A T2HQ090TW
100A 1000A T2HQ100TW
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Breaker IC at Rating Magnetic 3 pole, 480VAC List
480VAC trip catalog number price
Tmax
MCCBs
Low Voltage Products & Systems 16.9
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
25A T2S025BW $ 1,240
T2S 35kA PR221DS-LS/I 60A T2S060BW 1,240
100A T2S100BW 1,343
T2H 25A T2H025BW 1,492
UL Current 65kA PR221DS-LS/I 60A T2H060BW 1,492
Limiting 100A T2H100BW 1,703
Breaker IC at Trip unit CT 3 pole, 480VAC List
480VAC type rating catalog number price
T2 — 100A Frame, electronic trip unit (AC only)
20A 120 - 240 T2S020MW $ 598
T2S 35kA Mag only 50A 300 - 600 T2S050MW 670
100A 600 – 1200 T2S100MW 804
20A 120 - 240 T2H020MW 673
T2H 65kA Mag only 50A 300 - 600 T2H050MW 754
100A 600 – 1200 T2H100MW 904
Breaker IC at Trip unit Rating Adjustment 3 pole, 480VAC List
480VAC type range catalog number price
T2 — 100A Frame, instantaneous only (MCP)
Breaker IC at Trip unit Rating Adjustment 3 pole, 480VAC List
480VAC type range catalog number price
35kA
Instantaneous 25A 25 - 250 T2S025E5W $ 1,178
T2S only 60A 60 - 600 T2S060E5W 1,178
100A 100 - 1000 T2S100E5W 1,276
65kA
Instantaneous 25A 25 - 250 T2H025E5W 1,417
T2H only 60A 60 - 600 T2H060E5W 1,417
100A 100 - 1000 T2H100E5W 1,618
T2 — 100A Frame, instantaneous only, electronic (MCP - AC only)
T2
100A, 480V ∆, 100% rated
Electronic/Current limiting/MCP
25A T2SQ025BW $ 1,363
T2S 35kA PR221DS-LS/I 60A T2SQ060BW
100A T2SQ100BW 1,477
T2H 25A T2HQ025BW 1,640
UL Current 65kA PR221DS-LS/I 60A T2HQ060BW
Limiting 100A T2HQ100BW 1,873
Breaker IC at Trip unit CT 3 pole, 480VAC List
480VAC type rating catalog number price
T2 – 100A Frame 100% rated, electronic trip unit (AC only)
Discount schedule S2T [T2]
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
16.10 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
T3
225A, 600Y/347V, 480V ∆
Thermal-magnetic
T3
General
The T3 breaker family ranges from 60 through 225 amperes. The T3 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays
for overcurrent trip protection. Thermal overload protection is provided by heat
sensitive bimetals. Short circuit protection begins at 10 times the thermal rating of
the breaker using a precise magnetic coil. State of the art construction in contacts
and arcing chambers aid in limiting damaging fault currents through the protected
circuits.
Standards
The UL489/CSA 22.2 version of T3 also carries an IEC-60947-2 rating.
Versions
The T3 frame is available in three versions:
T = Thermal-magnetic, xed
M = Magnetic only (MCP)
D = Molded case switch
Performance levels
The T3 breaker has two performance levels available:
N = Normal
S = Standard
Number of poles
The T3 molded case circuit breaker is available in three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB
sales person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage Continuous rating N S
240VAC 60 – 225A 50 65
480VAC ∆ 60 – 225A 25 35
600Y/347VAC 60 – 225A 10 10
250VDC 2 pole series 60 – 225A 25 35
500VDC 3 pole series 60 – 225A 25 35
Dimensions 3P Fixed Version 5.9H x 4.13W x 2.76D
Weight 5.45 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage Continuous rating N S
230VAC 60 – 225A 50 85
415VAC 60 – 225A 36 50
690VAC 60 – 225A 58
750VDC 3 pole series 60 – 225A 36 50
Tmax
MCCBs
Low Voltage Products & Systems 16.11
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Discount schedule S3T [T3]
T3
225A, 600Y/347V, 480V ∆
Thermal-magnetic
60A 600A T3N060TW $ 615
70A 700A T3N070TW
80A 800A T3N080TW 740
90A 900A T3N090TW
100A 1000A T3N100TW
T3N 25kA 125A 1250A T3N125TW
150A 1500A T3N150TW 1,560
175A 1750A T3N175TW
200A 2000A T3N200TW 1,560
225A 2250A T3N225TW
Breaker IC at Rating Magnetic 3 pole, 480VAC/500VDC List
480VAC trip catalog number price
T3 — 225A Frame TMF, thermal magnetic xed
60A 600A T3S060TW $ 790
70A 700A T3S070TW
80A 800A T3S080TW 970
90A 900A T3S090TW
100A 1000A T3S100TW
T3S 35kA 125A 1250A T3S125TW
150A 1500A T3S150TW 2,160
175A 1750A T3S175TW
200A 2000A T3S200TW 2,160
225A 2250A T3S225TW
Breaker IC at Rating Magnetic 3 pole, 480VAC/500VDC List
480VAC trip catalog number price
60A 600A T3NQ060TW $ 656
70A 700A T3NQ070TW
80A 800A T3NQ080TW
90A 900A T3NQ090TW 812
100A 1000A T3NQ100TW
T3N 25kA 125A 1250A T3NQ125TW
150A 1500A T3NQ150TW 1,717
175A 1750A T3NQ175TW
200A 2000A T3NQ200TW 1,717
225A 2250A T3NQ225TW
Breaker IC at Rating Magnetic 3 pole, 600/347V VAC/500VDC List
480VAC trip catalog number price
T3 – 225A Frame TMF, 100% rated thermal magnetic xed
60A 600A T3SQ060TW $ 778
70A 700A T3SQ070TW
80A 800A T3SQ080TW
90A 900A T3SQ090TW 1,065
100A 1000A T3SQ100TW
T3S 35kA 125A 1250A T3SQ125TW
150A 1500A T3SQ150TW 2,399
175A 1750A T3SQ175TW
200A 2000A T3SQ200TW 2,399
225A 2250A T3SQ225TW
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Breaker IC at Rating Magnetic 3 pole, 600/347V VAC/500VDC List
480VAC trip catalog number price
Tmax
MCCBs
16.12 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Discount schedule S3T [T3]
T3
225A, 600Y/347V, 480V ∆
MCP/Molded case switch
1 When protected by a OCPD with appropriate ratings.
100A 600 – 1200 T3S100MW $ 1,074
T3S 35kA Mag only 125A 750 - 1500 T3S125MW 1,108
150A 900 - 1800 T3S150MW 1,299
200A 1200 - 2400 T3S200MW 1,382
Breaker IC at Trip unit Rating Adjustment 3 pole, 480VAC List
480VAC type range catalog number price
T3 — 225A Frame instantaneous only, (MCP)
T3S-D 240V, 65kA 150A 1500A T3S150DW $ 1,078
480V, 35kA 225A 2250A T3S225DW 1,515
Breaker Interrupting 1 Rating Magnetic 3 pole, 480VAC/500VDC List
capacity trip catalog number price
T3S-D — Molded case switch
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 16.13
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic
General
The Ts3 breaker family ranges from 15 through 225 amperes. The Ts3 trip
mechanisms are non-interchangeable and use sensitive electromagnetic relays
for overcurrent trip protection. Heat sensitive bimetals are used for thermal
overcurrent protection. Short circuit current protection begins at 10 times the
thermal rating of the breaker and uses a magnetic coil principle.
Standards
The UL489/CSA 22.2 version of Ts3 also carries an IEC-60947-2 rating.
Versions
To meet all application needs, the Ts3 is available in various versions:
T =Thermal-magnetic
D = Molded case switch
M = Magnetic only (MCP)
Performance level
Each version is also available in different maximum fault interrupting levels
N = Normal
H = High
L = Extra high
Number of poles
The Ts3 is available in two, three and four pole versions. Estimate 4 pole pricing
by adding 35% to the 3 pole price and contact your ABB sales person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
1 15-30A are 65kA at 480VAC
Ts3
Dimensions 3P Fixed Version 6.7H x 4.13W x 4.07D
Weight 6.75 (Ibs)
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Voltage N H L
150AF, 15A-150A
240 VAC 65 100 150
480 VAC 25 50 85 1
600 VAC 14 14 25
500 VDC 35 50 65
600 VDC 20 35 50
225AF, 175A-225A
240 VAC 65 100 150
480 VAC 25 50 65
600 VAC
500 VDC 20 35 50
600 VDC
IEC-60947-2 Interrupting capacity (kA RMS)
230 VAC 65 100 170
415 VAC 35 65 85
690 VAC 14 18 20
750 VDC 220 35 50
Discount schedule S3T [T3]
Tmax
MCCBs
16.14 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic
Ts3
150A 600VAC/225A 480VAC
Thermal Magnetic Trip Units
Breaker IC at 480VAC kA Rating Magnetic
trip
2 pole,
600VAC/500VDC
catalog number
List price 3 pole, 600VAC/DC
catalog number List price
Ts3N 25
15A 500A Ts3N015TW-2 Ts3N015TW
20A 500A Ts3N020TW-2 Ts3N020TW
25A 500A Ts3N025TW-2 Ts3N025TW
30A 500A Ts3N030TW-2 $ 814 Ts3N030TW $ 958
35A 500A Ts3N035TW-2 Ts3N035TW
40A 500A Ts3N040TW-2 Ts3N040TW
50A 500A Ts3N050TW-2 Ts3N050TW
60A 600A Ts3N060TW-2 Ts3N060TW
70A 700A Ts3N070TW-2 Ts3N070TW
80A 800A Ts3N080TW-2 948 Ts3N080TW 1,115
90A 900A Ts3N090TW-2 Ts3N090TW
100A 1000A Ts3N100TW-2 Ts3N100TW
125A 1250A Ts3N125TW-2 1,471 Ts3N125TW 1,610
150A 1500A Ts3N150TW-2 Ts3N150TW
Breaker IC at 480VAC kA Rating Magnetic
trip
2 pole,
600VAC/500VDC
catalog number
List price 3 pole, 600VAC/DC
catalog number List price
Ts3H 50
15A 500A Ts3H015TW-2 Ts3H015TW
20A 500A Ts3H020TW-2 Ts3H020TW
25A 500A Ts3H025TW-2 Ts3H025TW
30A 500A Ts3H030TW-2 $ 939 Ts3H030TW $ 1,105
35A 500A Ts3H035TW-2 Ts3H035TW
40A 500A Ts3H040TW-2 Ts3H040TW
50A 500A Ts3H050TW-2 Ts3H050TW
60A 600A Ts3H060TW-2 Ts3H060TW
70A 700A Ts3H070TW-2 Ts3H070TW
80A 800A Ts3H080TW-2 1,071 Ts3H080TW 1,260
90A 900A Ts3H090TW-2 Ts3H090TW
100A 1000A Ts3H100TW-2 Ts3H100TW
125A 1250A Ts3H125TW-2 2,323 Ts3H125TW 2,733
150A 1500A Ts3H150TW-2 Ts3H150TW
Breaker IC at 480VAC kA Rating Magnetic
trip
2 pole,
600VAC/500VDC
catalog number
List price 3 pole, 600VAC/DC
catalog number List price
Ts3L
65
15A 500A Ts3L015TW-2 Ts3L015TW
20A 500A Ts3L020TW-2 $ 1,518 Ts3L020TW $ 1,786
25A 500A Ts3L025TW-2 Ts3L025TW
30A 500A Ts3L030TW-2 Ts3L030TW
85
35A 500A Ts3L035TW-2 Ts3L035TW
40A 500A Ts3L040TW-2 1,518 Ts3L040TW 1,786
50A 500A Ts3L050TW-2 Ts3L050TW
60A 600A Ts3L060TW-2 Ts3L060TW
70A 700A Ts3L070TW-2 Ts3L070TW
80A 800A Ts3L080TW-2 1,692 Ts3L080TW 1,990
90A 900A Ts3L090TW-2 Ts3L090TW
100A 1000A Ts3L100TW-2 Ts3L100TW
125A 1250A Ts3L125TW-2 3,636 Ts3L125TW 4,278
150A 1500A Ts3L150TW-2 Ts3L150TW
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Discount schedule S3T [T3]
Tmax
MCCBs
Low Voltage Products & Systems 16.15
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Ts3
150A, 600V ∆, 225A, 480V ∆, 100% rated
Thermal magnetic
Ts3
150A 600VAC/225A 480VAC
Thermal Magnetic Trip Units 100% Rated
Breaker IC at
480VAC Rating Magnetic
trip
3 pole 600VAC/DC
catalog number List price
Ts3NQ 25
15A 500A Ts3NQ015TW
20A 500A Ts3NQ020TW
25A 500A Ts3NQ025TW
30A 500A Ts3NQ030TW $ 1,054
35A 500A Ts3NQ035TW
40A 500A Ts3NQ040TW
50A 500A Ts3NQ050TW
60A 600A Ts3NQ060TW
70A 700A Ts3NQ070TW
80A 800A Ts3NQ080TW 1,227
90A 900A Ts3NQ090TW
100A 1000A Ts3NQ100TW
125A 1250A Ts3NQ125TW 1,771
150A 1500A Ts3NQ150TW
Breaker IC at
480VAC Rating Magnetic
trip
3 pole
catalog number List price
Ts3HQ 50kA
15A 500A Ts3HQ015TW
20A 500A Ts3HQ020TW
25A 500A Ts3HQ025TW
30A 500A Ts3HQ030TW $ 1,216
35A 500A Ts3HQ035TW
40A 500A Ts3HQ040TW
50A 500A Ts3HQ050TW
60A 600A Ts3HQ060TW
70A 700A Ts3HQ070TW
80A 800A Ts3HQ080TW 1,386
90A 900A Ts3HQ090TW
100A 1000A Ts3HQ100TW
125A 1250A Ts3HQ125TW 3,006
150A 1500A Ts3HQ150TW
Breaker IC at
480VAC Rating Magnetic
trip
3 pole
catalog number List price
Ts3LQ
65kA
15A 500A Ts3LQ015TW
$ 1,965
20A 500A Ts3LQ020TW
25A 500A Ts3LQ025TW
30A 500A Ts3LQ030TW
85kA
35A 500A Ts3LQ035TW
40A 500A Ts3LQ040TW
50A 500A Ts3LQ050TW
60A 600A Ts3LQ060TW
70A 700A Ts3LQ070TW
80A 800A Ts3LQ080TW 2,189
90A 900A Ts3LQ090TW
100A 1000A Ts3LQ100TW
125A 1250A Ts3LQ125TW 4,706
150A 1500A Ts3LQ150TW
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Discount schedule S3T [T3]
Tmax
MCCBs
16.16 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
1 When protected by a OCPD with appropriate ratings.
2 480 VAC maximum
Ts3
150/225A 600VAC
MCP/Molded case switch
Molded Case Switch 2
Type IC at 480V (2) Magnetic trip Amps 3 pole 600V
catalog number
List
price
Ts3H 50 1500 150 Ts3H150DW $ 1,060
50 2250 225 1Ts3H225DW 1,188
Magnetic only (MCP)
Breaker IC at 480VAC Trip unit type Rating Adjustment
range
3 pole 600VAC
Catalog number
List
Price
Ts3L
25 Magnetic only 3 12-36 Ts3L003MW $ 726
25 Magnetic only 5 20-60 Ts3L005MW 726
25 Magnetic only 10 40-120 Ts3L010MW 726
25 Magnetic only 25 100-300 Ts3L025MW 726
85 Magnetic only 50 200-600 Ts3L050MW 920
Ts3L
85 Magnetic only 100 400-1200 Ts3L100MW 1,095
85 Magnetic only 125 500-1500 Ts3L125MW 1,448
85 Magnetic only 150 600-1500 Ts3L150MW 1,448
65 Magnetic only 175 1700-2100 Ts3L175MW 1,448
65 Magnetic only 200 1800-2400 Ts3L200MW 1,517
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Discount schedule S3T [T3]
Tmax
MCCBs
Low Voltage Products & Systems 16.17
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T4
250A, 600V ∆
Electronic and thermal magnetic
T4
General
The T4 breaker is a 250 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit.
Standards
The UL489/CSA 22.2 version of T4 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T4 is available in the following versions:
T = Thermal-magnetic
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting
Number of poles 3
The T4 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage N S H L V
240VAC 65 100 150 200 200
480VAC 25 35 65 100 150
600VAC 18 25 35 65 100
500VDC 1 25 35 50 65 100
600VDC 2 16 25 35 50 65
1 2 poles in series.
2 3 poles in series.
3 2 pole breakers available in N version only. 4 pole breakers available in N and H version only.
Dimensions 3P Fixed Version 8.07H x 4.13W x 4.07D
Weight 6.18 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage N S H L V
230VAC 70 85 100 200 200
415VAC 36 50 70 120 200
690VAC 20 25 40 70 80
750VDC 2 16 25 36 50 70
Tmax
MCCBs
16.18 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Discount schedule S4T [T4]
T4
250A, 600V ∆
Adjustable thermal magnetic
20A - 250A Frame
Breaker IC at
480VAC Rating Magnetic
trip
2 pole, 600VAC/600VDC
catalog number
List
price
3 pole, 600VAC/600VDC
catalog number
List
price
T4N 25
125A 625-1250 T4N125TW-2 T4N125TW
150A 750-1500 T4N150TW-2 $ 1,584 T4N150TW $ 1,667
200A 1000-2000 T4N200TW-2 T4N200TW
250A 1250-2500 T4N250TW-2 1,631 T4N250TW 1,717
T4S 35
125A 625-1250 T4S125TW
150A 750-1500 T4S150TW 2,067
200A 1000-2000 T4S200TW
250A 1250-2500 T4S250TW 2,092
T4H
UL Current
Limiting
65
125A 625-1250 T4H125TW
150A 750-1500 T4H150TW 3,767
200A 1000-2000 T4H200TW
250A 1250-2500 T4H250TW 3,832
T4L 100
125A 625-1250 T4L125TW
150A 750-1500 T4L150TW 5,995
200A 1000-2000 T4L200TW
250A 1250-2500 T4L250TW 6,110
T4V
UL Current
Limiting
150
125A 625-1250 T4V125TW
150A 750-1500 T4V150TW 6,847
200A 1000-2000 T4V200TW
250A 1250-2500 T4V250TW 6,887
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 16.19
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
30A - 250A Frame 100% rated
Breaker
IC at 480 VAC
kA Rating
Magnetic
trip
3 pole,
600VAC/600VDC
Catalog number
List
price
T4N 25
125A 625-1250 T4NQ125TW
$ 1,839150A 750-1500 T4NQ150TW
200A 1000-2000 T4NQ200TW
250A 1250-2500 T4NQ250TW 1,894
T4S 35
125A 625-1250 T4SQ125TW
150A 750-1500 T4SQ150TW 2,280
200A 1000-2000 T4SQ200TW
250A 1250-2500 T4SQ250TW 2,307
T4H
UL Current
Limiting
65
125A 625-1250 T4HQ125TW
150A 750-1500 T4HQ150TW 4,155
200A 1000-2000 T4HQ200TW
250A 1250-2500 T4HQ250TW 4,227
T4L 100
125A 625-1250 T4LQ125TW
6,612150A 750-1500 T4LQ150TW
200A 1000-2000 T4LQ200TW
250A 1250-2500 T4LQ250TW 6,739
T4V
UL Current
Limiting
150
125A 625-1250 T4VQ125TW
150A 750-1500 T4VQ150TW 7,552
200A 1000-2000 T4VQ200TW
250A 1250-2500 T4VQ250TW 7,569
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
T4
250A, 600V ∆ 100% rated
Adjustable thermal magnetic
Discount schedule S4T [T4]
Tmax
MCCBs
16.20 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
T4
250A, 600V ∆
Electronic (AC only)
Discount schedule S4T [T4]
100A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
List
price
3 pole, 600V
catalog number
List
price
PR221 LS/I T4N100BW-2 $ 1,808 T4N100BW $ 1,903
T4N 25 PR222 LSI T4N100CW-2 2,413 T4N100CW 2,540
PR222 LSIG T4N100EW-2 3,164 T4N100EW 3,330
PR221 LS/I - -T4S100BW 2,370
T4S 35 PR222 LSI - -T4S100CW 3,164
PR222 LSIG - -T4S100EW 4,148
T4H
UL Current
Limiting
PR221 LS/I - -T4H100BW 4,498
65 PR222 LSI - -T4H100CW 4,845
PR222 LSIG - -T4H100EW 5,877
PR221 LS/I - -T4L100BW 5,954
T4L 100 PR222 LSI - -T4L100CW 6,063
PR222 LSIG - -T4L100EW 7,091
T4V
UL Current
Limiting
PR221 LS/I - -T4V100BW 8,555
150 PR222 LSI - -T4V100CW 9,213
PR222 LSIG - -T4V100EW 9,957
150A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
List
price
3 pole, 600V
catalog number
List
price
PR221 LS/I T4N150BW-2 $ 1,948 T4N150BW $ 2,050
T4N 25 PR222 LSI T4N150CW-2 2,600 T4N150CW 2,737
PR222 LSIG T4N150EW-2 3,409 T4N150EW 3,588
PR221 LS/I - -T4S150BW 2,542
T4S 35 PR222 LSI - -T4S150CW 3,394
PR222 LSIG - -T4S150EW 4,449
T4H
UL Current
Limiting
PR221 LS/I - -T4H150BW 4,633
65 PR222 LSI - -T4H150CW 5,024
PR222 LSIG - -T4H150EW 6,094
PR221 LS/I - -T4L150BW 6,174
T4L 100 PR222 LSI - -T4L150CW 6,288
PR222 LSIG - -T4L150EW 7,354
T4V
UL Current
Limiting
PR221 LS/I - -T4V150BW 8,872
150 PR222 LSI - -T4V150CW 9,555
PR222 LSIG - -T4V150EW 10,326
250A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
List
price
3 pole, 600V
catalog number
List
price
PR221 LS/I T4N250BW-2 $ 2,006 T4N250BW $ 2,112
T4N 25 PR222 LSI T4N250CW-2 2,678 T4N250CW 2,819
PR222 LSIG T4N250EW-2 3,511 T4N250EW 3,696
PR221 LS/I - -T4S250BW 2,573
T4S 35 PR222 LSI - -T4S250CW 3,435
PR222 LSIG - -T4S250EW 4,503
T4H
UL Current
Limiting
PR221 LS/I - -T4H250BW 4,713
65 PR222 LSI - -T4H250CW 5,127
PR222 LSIG - -T4H250EW 6,219
PR221 LS/I - -T4L250BW 6,300
T4L 100 PR222 LSI - -T4L250CW 6,416
PR222 LSIG - -T4L250EW 7,504
T4V
UL Current
Limiting
PR221 LS/I - -T4V250BW 9,053
150 PR222 LSI - -T4V250CW 9,750
PR222 LSIG - -T4V250EW 10,537
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 16.21
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T4
250A, 600V ∆, 100% Rated
Electronic (AC only)
Discount schedule S4T [T4]
100A Frame - 100% rated, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
List
price
PR221 LS/I T4NQ100BW $ 2,124
T4N 25 PR222 LSI T4NQ100CW 2,835
PR222 LSIG T4NQ100EW 3,716
PR221 LS/I T4SQ100BW 2,645
T4S 35 PR222 LSI T4SQ100CW 3,531
PR222 LSIG T4SQ100EW 4,629
T4H
UL Current
Limiting
PR221 LS/I T4HQ100BW 5,020
65 PR222 LSI T4HQ100CW 5,383
PR222 LSIG T4HQ100EW 6,530
PR221 LS/I T4LQ100BW 6,616
T4L 100 PR222 LSI T4LQ100CW 6,737
PR222 LSIG T4LQ100EW 7,879
T4V
UL Current
Limiting
PR221 LS/I T4VQ100BW 9,506
150 PR222 LSI T4VQ100CW 10,237
PR222 LSIG T4VQ100EW 11,063
150A Frame - 100% rated, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
List
price
PR221 LS/I T4NQ150BW $ 2,288
T4N 25 PR222 LSI T4NQ150CW 3,055
PR222 LSIG T4NQ150EW 4,004
PR221 LS/I T4SQ150BW 2,837
T4S 35 PR222 LSI T4SQ150CW 3,788
PR222 LSIG T4SQ150EW 4,965
T4H
UL Current
Limiting
PR221 LS/I T4HQ150BW 5,171
65 PR222 LSI T4HQ150CW 5,582
PR222 LSIG T4HQ150EW 6,771
PR221 LS/I T4LQ150BW 6,860
T4L 100 PR222 LSI T4LQ150CW 6,987
PR222 LSIG T4LQ150EW 8,171
T4V
UL Current
Limiting
PR221 LS/I T4VQ150BW 9,858
150 PR222 LSI T4VQ150CW 10,616
PR222 LSIG T4VQ150EW 11,473
250A Frame - 100% rated, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
List
price
PR221 LS/I T4NQ250BW $ 2,357
T4N 25 PR222 LSI T4NQ250CW 3,146
PR222 LSIG T4NQ250EW 4,125
PR221 LS/I T4SQ250BW 2,872
T4S 35 PR222 LSI T4SQ250CW 3,834
PR222 LSIG T4SQ250EW 5,025
T4H
UL Current
Limiting
PR221 LS/I T4HQ250BW 5,260
65 PR222 LSI T4HQ250CW 5,697
PR222 LSIG T4HQ250EW 6,910
PR221 LS/I T4LQ250BW 7,000
T4L 100 PR222 LSI T4LQ250CW 7,129
PR222 LSIG T4LQ250EW 8,338
T4V
UL Current
Limiting
PR221 LS/I T4VQ250BW 10,058
150 PR222 LSI T4VQ250CW 10,833
PR222 LSIG T4VQ250EW 11,708
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
16.22 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
1 When protected by a OCPD with appropriate ratings.
T4
250A, 600V ∆
Instantaneous only, MCP/Molded case switch
Discount schedule S4T [T4]
Instantaneous only MCPs
T4 - 250A Frame magnetic only (MCP - AC only)
Breaker IC at 480VAC Trip unit type Rating Adjustment range 3 pole, 600VAC
Catalog number
List
price
T4N 25kA Instantaneous
only
100A 100-1000 T4N100E5W $ 1,808
150A 150-1500 T4N150E5W 1,948
250A 250-2500 T4N250E5W 2,006
T4S 35kA Instantaneous
only
100A 100-1000 T4S100E5W 2,252
150A 150-1500 T4S150E5W 2,415
250A 250-2500 T4S250E5W 2,444
T4H 65kA Instantaneous
only
100A 100-1000 T4H100E5W 4,273
150A 150-1500 T4H150E5W 4,401
250A 250-2500 T4H250E5W 4,477
T4L 100kA Instantaneous
only
100A 100-1000 T4L100E5W 5,656
150A 150-1500 T4L150E5W 5,865
250A 250-2500 T4L250E5W 5,985
Molded case switch 1
Type IC at 480VAC Amps Magnetic
trip
3 pole 600V
catalog number
List
price
T4N-D 25kA 250 3000 T4N250DW $ 1,354
T4S-D 35kA 250 3000 T4S250DW 1,510
T4H-D 65kA 250 3000 T4H250DW 2,154
T4L-D 100kA 250 3000 T4L250DW 3,419
T4V-D 150kA 250 3000 T4V250DW 3,842
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 16.23
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T5
400/600A, 600V ∆
Electronic and thermal magnetic
T5
General
The T5 breaker is a 400/600 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit. 3
Standards
The UL489/CSA 22.2 version of T5 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T5 is available in the following versions:
T = Thermal-magnetic
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting
Number of poles 4
The T5 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage N S H L V
240VAC 65 100 150 200 200
480VAC 25 35 65 100 150
600VAC 18 25 35 65 100
500VDC 1 25 35 50 65 100
600VDC 2 16 25 35 50 65
1 2 poles in series.
2 3 poles in series.
3 T5 600A not available with thermal magnetic trip unit.
4 2 pole available in N version only. 4 pole available in N and H version only.
Dimensions 3P Fixed Version 8.07H x 5.51W x 4.07D
Weight 8.55 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage N S H L V
230VAC 70 85 100 200 200
415VAC 36 50 70 120 200
690VAC 20 25 40 70 80
750VDC 16 25 36 50 70
Tmax
MCCBs
16.24 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Discount schedule S5T [T5]
T5
400/600A, 600V ∆
Thermal magnetic 1
300A - 400A Frames - thermal-magnetic trip units
Breaker IC at 480VAC
kA Rating Magnetic
trip
2 pole, 600VAC/600VDC
catalog number
List
price
3 pole, 600VAC/600VDC
catalog number
List
price
T5N 25 300A 1500-3000 T5N300TW-2 $ 2,481 T5N300TW $ 2,612
400A 2000-4000 T5N400TW-2 T5N400TW
T5S 35 300A 1500-3000 T5S300TW 2,880
400A 2000-4000 T5S400TW
T5H
UL Current Limiting 65 300A 1500-3000 T5H300TW 4,950
400A 2000-4000 T5H400TW
T5L 100 300A 1500-3000 T5L300TW 6,400
400A 2000-4000 T5L400TW
T5V
UL Current Limiting 150 300A 1500-3000 T5V300TW 9,873
400A 2000-4000 T5V400TW
1 T5 600A not available with Thermal Magnetic trip unit.
300A - 400A Frames - 100% rated, thermal-magnetic
Breaker IC at 480VAC Rating Magnetic
trip 3 pole,
600VAC/600VDC
Catalog number
List
price
T5N 25 300A 1500-3000 T5NQ300TW $ 2,888
400A 2000-4000 T5NQ400TW
T5S 35 300A 1500-3000 T5SQ300TW 3,185
400A 2000-4000 T5SQ400TW
T5H
UL Current Limiting 65 300A 1500-3000 T5HQ300TW 5,475
400A 2000-4000 T5HQ400TW
T5L 100 300A 1500-3000 T5LQ300TW 7,078
400A 2000-4000 T5LQ400TW
T5V
UL Current Limiting 150 300A 1500-3000 T5VQ300TW 10,920
400A 2000-4000 T5VQ400TW
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 16.25
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Discount schedule S5T [T5]
1 T5 600A not available in 2 pole version.
T5
400/600A, 600V ∆
Electronic (AC only)
300A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
List
price
3 pole, 600V
catalog number
List
price
PR221 LS/I T5N300BW-2 $ 3,097 T5N300BW $ 3,260
T5N 25 PR222 LSI T5N300CW-2 3,672 T5N300CW 3,865
PR222 LSIG T5N300EW-2 4,717 T5N300EW 4,965
PR221 LS/I - -T5S300BW 3,350
T5S 35 PR222 LSI - -T5S300CW 3,945
PR222 LSIG - -T5S300EW 5,138
T5H
UL Current
Limiting
PR221 LS/I - -T5H300BW 5,395
65 PR222 LSI - -T5H300CW 5,893
PR222 LSIG - -T5H300EW 7,148
PR221 LS/I - -T5L300BW 6,860
T5L 100 PR222 LSI - -T5L300CW 7,375
PR222 LSIG - -T5L300EW 8,625
T5V
UL Current
Limiting
PR221 LS/I - -T5V300BW 10,406
150 PR222 LSI - -T5V300CW 11,206
PR222 LSIG - -T5V300EW 12,111
400A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
List
price
3 pole, 600V
catalog number
List
price
PR221 LS/I T5N400BW-2 $ 3,097 T5N400BW $ 3,260
T5N 25 PR222 LSI T5N400CW-2 3,672 T5N400CW 3,865
PR222 LSIG T5N400EW-2 4,717 T5N400EW 4,965
PR221 LS/I - -T5S400BW 3,350
T5S 35 PR222 LSI - -T5S400CW 3,945
PR222 LSIG - -T5S400EW 5,138
T5H
UL Current
Limiting
PR221 LS/I - -T5H400BW 5,395
65 PR222 LSI - -T5H400CW 5,893
PR222 LSIG - -T5H400EW 7,148
PR221 LS/I - -T5L400BW 6,860
T5L 100 PR222 LSI - -T5L400CW 7,375
PR222 LSIG - -T5L400EW 8,625
T5V
UL Current
Limiting
PR221 LS/I - -T5V400BW 10,406
150 PR222 LSI - -T5V400CW 11,206
PR222 LSIG - -T5V400EW 12,111
600A Frame, electronic trip unit (AC only) 1
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
List
price
PR221 LS/I T5N600BW $ 5,750
T5N 25 PR222 LSI T5N600CW 6,460
PR222 LSIG T5N600EW 8,360
PR221 LS/I T5S600BW 5,910
T5S 35 PR222 LSI T5S600CW 6,595
PR222 LSIG T5S600EW 8,645
PR221 LS/I T5H600BW 8,170
T5H 65 PR222 LSI T5H600CW 8,805
PR222 LSIG T5H600EW 10,890
PR221 LS/I T5L600BW 9,860
T5L 100 PR222 LSI T5L600CW 10,440
PR222 LSIG T5L600EW 12,630
PR221 LS/I T5V600BW 13,550
T5V 150 PR222 LSI T5V600CW 14,375
PR222 LSIG T5V600EW 16,350
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
Tmax
MCCBs
16.26 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
T5
400/600A, 600V ∆, 100% Rated 1
Electronic (AC only)
Discount schedule S5T [T5]
400A Frame – 100% rated, electronic trip units (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
List
price
PR221 LS/I T5NQ400BW $ 3,628
T5N 25 PR222 LSI T5NQ400CW 4,302
PR222 LSIG T5NQ400EW 5,526
PR221 LS/I T5SQ400BW 3,729
T5S 35 PR222 LSI T5SQ400CW 4,391
PR222 LSIG T5SQ400EW 5,719
T5H
UL Current
limiting
PR221 LS/I T5HQ400BW 6,005
65 PR222 LSI T5HQ400CW 6,559
PR222 LSIG T5HQ400EW 7,956
PR221 LS/I T5LQ400BW 7,635
T5L 100 PR222 LSI T5LQ400CW 8,208
PR222 LSIG T5LQ400EW 9,600
T5V
UL Current
limiting
PR221 LS/I T5VQ400BW 11,582
150 PR222 LSI T5VQ400CW 12,473
PR222 LSIG T5VQ400EW 13,480
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
300A Frame – 100% rated, electronic trip units (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
List
price
PR221 LS/I T5NQ300BW $ 3,628
T5N 25 PR222 LSI T5NQ300CW 4,302
PR222 LSIG T5NQ300EW 5,526
PR221 LS/I T5SQ300BW 3,729
T5S 35 PR222 LSI T5SQ300CW 4,391
PR222 LSIG T5SQ300EW 5,719
T5H
UL Current
limiting
PR221 LS/I T5HQ300BW 6,005
65 PR222 LSI T5HQ300CW 6,559
PR222 LSIG T5HQ300EW 7,956
PR221 LS/I T5LQ300BW 7,635
T5L 100 PR222 LSI T5LQ300CW 8,208
PR222 LSIG T5LQ300EW 9,600
T5V
UL Current
limiting
PR221 LS/I T5VQ300BW 11,582
150 PR222 LSI T5VQ300CW 12,473
PR222 LSIG T5VQ300EW 13,480
1 T5 600A not available in 100% rated frame.
Tmax
MCCBs
Low Voltage Products & Systems 16.27
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T5
400/600A, 600V ∆
Instantaneous only, MCP/Molded case switch
Discount schedule S5T [T5]
T5 - 400A Frame, magnetic only (MCP - AC only)
Breaker IC at 480VAC Trip unit type Rating Adjustment
range 3 pole, 600VAC
Catalog number
List
price
T5N 25kA Instantaneous
only
300A 300-3000 T5N300E5W $ 3,097
400A 400-4000 T5N400E5W
T5S 35kA Instantaneous
only
300A 300-3000 T5S300E5W 3,183
400A 400-4000 T5S400E5W
T5H 65kA Instantaneous
only
300A 300-3000 T5H300E5W 5,125
400A 400-4000 T5H400E5W
T5L 100kA Instantaneous
only
300A 300-3000 T5L300E5W 6,517
400A 400-4000 T5L400E5W
T5 - 600A Frame, magnetic only (MCP - AC only)
Breaker IC at 480VAC Trip unit type Rating Adjustment
range 3 pole, 600VAC
Catalog number
List
price
T5N 25kA Instantaneous
only 600A 600-6000 T5N600E5W $ 5,615
T5S 35kA Instantaneous
only 600A 600-6000 T5S600E5W 5,770
T5H 65kA Instantaneous
only 600A 600-6000 T5H600E5W 7,761
T5L 100kA Instantaneous
only 600A 600-6000 T5L600E5W 9,370
Molded case switch 1
Type IC at 480VAC Amps Magnetic
trip
3 pole 600V
catalog number
List
price
T5N-D 25kA 400 5000 T5N400DW $ 2,393
T5S-D 35kA 400 5000 T5S400DW 2,659
T5H-D 65kA 400 5000 T5H400DW 4,585
T5L-D 100kA 400 5000 T5L400DW 5,878
T5V-D 150kA 400 5000 T5V400DW 7,536
T5N-D 25kA 600 6000 T5N600DW 3,419
T5S-D 35kA 600 6000 T5S600DW 3,799
T5H-D 65kA 600 6000 T5H600DW 6,550
T5L-D 100kA 600 6000 T5L600DW 8,350
T5V-D 150kA 600 6000 T5V600DW 11,575
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
1 When protected by a OCPD with appropriate ratings.
Tmax
MCCBs
16.28 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
T6
General
The T6 breaker is an 800 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit. The T6 is available
as a 600 or 800A frame.
Standards
The UL489/CSA 22.2 version of T6 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T6 is available in the following versions:
T = Thermal-magnetic, xed
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High
L = Extra high
Number of poles 3
The T6 is available as a three and four pole breaker. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
Dimensions 3P Fixed Version 10.55H x 8.26W x 4.07D
Weight 20.9 (Ibs)
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage N S H L
240VAC 65 100 200 200
480VAC 35 50 65 100
600VAC 20 25 35 42
500VDC 135 35 50 65
600VDC 220 20 35 50
1 2 poles in series.
2 3 poles in series.
3 4 pole available N and H version only.
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage N S H L
230VAC 70 85 100 200
415VAC 36 50 70 100
600VAC 20 22 25 30
750VDC 216 20 36 50
Tmax
MCCBs
Low Voltage Products & Systems 16.29
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T6
800A, 600V
Electronic Trip Units
Breaker IC at 480VAC Trip type Adjustment 3 pole, 600VAC catalog
number List price
T6N 35
PR221 LS/I T6N800BW $ 8,100
PR222 LSI T6N800CW 8,600
PR222 LSIG T6N800EW 10,600
T6S 50
PR221 LS/I T6S800BW 9,100
PR222 LSI T6S800CW 9,600
PR222 LSIG T6S800EW 11,600
T6H 65
PR221 LS/I T6H800BW 9,300
PR222 LSI T6H800CW 9,800
PR222 LSIG T6H800EW 11,800
T6L 100
PR221 LS/I T6L800BW 10,965
PR222 LSI T6L800CW 11,465
PR222 LSIG T6L800EW 13,465
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
T6
600A, 800A, 600V
Thermal Magnetic Trip Units 100% rated
Breaker IC at 480 VAC kA Rating Magnetic trip 3 pole, 600VAC/600VDC
catalog number List price
T6N 35 600A 3000 - 6000A T6NQ600TW $ 7,370
800A 4000 - 8000A T6NQ800TW 8,140
T6S 50 600A 3000 - 6000A T6SQ600TW 7,810
800A 4000 - 8000A T6SQ800TW 8,580
T6H 65 600A 3000 - 6000A T6HQ600TW 8,030
800A 4000 - 8000A T6HQ800TW 8,855
T6L 100 600A 3000 - 6000A T6LQ600TW 10,230
800A 4000 - 8000A T6LQ800TW 10,965
T6
600A, 800A, 600V
Thermal Magnetic Trip Units
Breaker IC at 480 VAC kA Rating Magnetic trip 3 pole, 600VAC/600VDC
catalog number List price
T6N 35 600A 3000 - 6000A T6N600TW $ 6,700
800A 4000 - 8000A T6N800TW 7,400
T6S 50 600A 3000 - 6000A T6S600TW 7,100
800A 4000 - 8000A T6S800TW 7,800
T6H 65 600A 3000 - 6000A T6H600TW 7,300
800A 4000 - 8000A T6H800TW 8,050
T6L 100 600A 3000 - 6000A T6L600TW 9,300
800A 4000 - 8000A T6L800TW 9,968
T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
Discount schedule S6T [T6]
T6
600A, 600V
Electronic Trip Units
Breaker IC at 480VAC Trip type Adjustment 3 pole, 600VAC catalog
number List price
T6N 35
PR221 LS/I T6N600BW $ 6,900
PR222 LSI T6N600CW 6,560
PR222 LSIG T6N600EW 8,400
T6S 50
PR221 LS/I T6S600BW 7,300
PR222 LSI T6S600CW 7,800
PR222 LSIG T6S600EW 8,800
T6H 65
PR221 LS/I T6H600BW 7,550
PR222 LSI T6H600CW 8,050
PR222 LSIG T6H600EW 9,050
T6L 100
PR221 LS/I T6L600BW 9,550
PR222 LSI T6L600CW 10,425
PR222 LSIG T6L600EW 11,557
Tmax
MCCBs
16.30 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
T6
600A, 600V ∆
Electronic Trip Units 100% Rated
Breaker IC at 480VAC Trip type Adjustment 3 pole, 600VAC
catalog number List price
PR221 LS/I T6NQ600BW $ 7,590
T6N 35 PR222 LSI T6NQ600CW 7,216
PR222 LSIG T6NQ600EW 9,240
PR221 LS/I T6SQ600BW 8,030
T6S 50 PR222 LSI T6SQ600CW 8,580
PR222 LSIG T6SQ600EW 9,680
PR221 LS/I T6HQ600BW 10,230
T6H 65 PR222 LSI T6HQ600CW 10,780
PR222 LSIG T6HQ600EW 12,980
PR221 LS/I T6LQ600BW 10,505
T6L 100 PR222 LSI T6LQ600CW 11,605
PR222 LSIG T6LQ600EW 12,713
T6
800A, 600V
Electronic Trip Units 100% Rated
Breaker IC at 480VAC Trip type Adjustment 3 pole, 600VAC
catalog number List price
PR221 LS/I T6NQ800BW $ 8,910
T6N 35 PR222 LSI T6NQ800CW 9,460
PR222 LSIG T6NQ800EW 11,660
PR221 LS/I T6SQ800BW 10,010
T6S 50 PR222 LSI T6SQ800CW 10,560
PR222 LSIG T6SQ800EW 12,760
PR221 LS/I T6HQ800BW 10,230
T6H 65 PR222 LSI T6HQ800CW 10,780
PR222 LSIG T6HQ800EW 12,980
PR221 LS/I T6LQ800BW 12,062
T6L 100 PR222 LSI T6LQ800CW 12,612
PR222 LSIG T6LQ800EW 14,812
T6
600A, 600V ∆
Electronic Trip Units Instantaneous Only
Breaker IC at 480VAC kA Trip type Adjustment Range 3 pole, 600VAC
catalog number List price
T6N 35 PR221 600-6000 T6N600E5W $ 5,929
T6S 50 PR221 600-6000 T6S600E5W 6,407
T6H 65 PR221 600-6000 T6H600E5W 6,623
T6L 100 PR221 600-6000 T6L600E5W 8,635
T6
800A, 600V
Electronic Trip Units Instantaneous Only
Breaker IC at 480VAC kA Trip type Adjustment Range 3 pole, 600VAC
catalog number List price
T6N 35 PR221 800-8000 T6N800E5W $ 6,254
T6S 50 PR221 800-8000 T6S800E5W 6,733
T6H 65 PR221 800-8000 T6H800E5W 6,948
T6L 100 PR221 800-8000 T6L800E5W 8,961
T6
800A, 600V
Molded Case Switch
Breaker IC at 480VAC 1Amp Magnetic Trip 3 pole, 600VAC
catalog number List price
T6H 65 800 10,000 T6H800DW $ 4,824
NOTE: See pages 16.57 - 16.70 for electrical/mechanical accessories.
1 When protected by a OCPD with appropriate ratings.
Discount schedule S6T [T6]
Tmax
MCCBs
Low Voltage Products & Systems 16.31
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
T7 (Toggle)
1000A, 1200A, 600V ∆
Electronic
T7
General
The T7 breaker is a 1200 amp frame with a microprocessor based over current
protective trip system.
Standards
The UL489/CSA 22.2 version of T7 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T7 is available in the following versions:
B = Selectable & adjustable LI or LS — Dip switch settings
C = Adjustable LSI — Dip switch settings
E = Adjustable LSIG — Dip switch settings
D = Molded Case Switch
P = LI — LCD display
R = LSI — LCD display
S = LSIG — LCD display
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
S = Standard
H = High
L = Extra high
Number of poles 1
The T7 is available as a 3 and 4 pole breaker. Estimate 4 pole pricing by adding
35% to the 3 pole price and contact your ABB sales person for details.
Dimensions 3P Fixed Version 10.55H x 8.26W x 6.06D
Weight 21.4 (Ibs)
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage S H L
240VAC 65 100 150
480VAC 50 65 100
600VAC 25 50 65
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage S H L
230VAC 85 100 200
415VAC 50 70 120
690VAC 30 42 50
1 4 Pole available S, H and L version.
Tmax
MCCBs
16.32 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T7
1000A, 1200A, 600V ∆
Electronic
T7S, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7S 50
PR231/P LS/I T7S1000BW $ 9,803
PR232/P LSI T7S1000CW 10,303
PR331/P LSIG T7S1000EW 12,303
PR332/P LI T7S1000PW 10,362
PR332/P LSI T7S1000RW 11,362
PR332/P LSIG T7S1000SW 12,606
T7S, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7S 50
PR231/P LS/I T7S1200BW $ 13,235
PR232/P LSI T7S1200CW 13,451
PR331/P LSIG T7S1200EW 14,063
PR332/P LI T7S1200PW 13,792
PR332/P LSI T7S1200RW 14,790
PR332/P LSIG T7S1200SW 16,036
T7H, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7H 65
PR231/P LS/I T7H1000BW $ 10,380
PR232/P LSI T7H1000CW 10,606
PR331/P LSIG T7H1000EW 12,540
PR332/P LI T7H1000PW 10,947
PR332/P LSI T7H1000RW 11,947
PR332/P LSIG T7H1000SW 13,191
T7H, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7H 65
PR231/P LS/I T7H1200BW $ 14,025
PR232/P LSI T7H1200CW 14,252
PR331/P LSIG T7H1200EW 15,924
PR332/P LI T7H1200PW 14,593
PR332/P LSI T7H1200RW 15,591
PR332/P LSIG T7H1200SW 16,837
Discount schedule S7T [T7]
T7L, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7L 100
PR231/P LS/I T7L1000BW $ 10,965
PR232/P LSI T7L1000CW 11,191
PR331/P LSIG T7L1000EW 12,863
PR332/P LI T7L1000PW 11,532
PR332/P LSI T7L1000RW 12,532
PR332/P LSIG T7L1000SW 13,776
T7L, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7L 100
PR231/P LS/I T7L1200BW $ 14,826
PR232/P LSI T7L1200CW 15,053
PR331/P LSIG T7L1200EW 16,725
PR332/P LI T7L1200PW 15,394
PR332/P LSI T7L1200RW 16,393
PR332/P LSIG T7L1200SW 17,638
NOTE:Seepages16.57-16.70forelectrical/mechanicalaccessories.
Tmax
MCCBs
Low Voltage Products & Systems 16.33
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
T7
1000A, 1200A, 600V ∆
Electronic, 100% rated
T7S, 1000A, 600V
Electronic, 100% rated
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7S 50
PR231/P LS/I T7SQ1000BW $ 10,783
PR232/P LSI T7SQ1000CW 11,333
PR331/P LSIG T7SQ1000EW 13,533
PR332/P LI T7SQ1000PW 11,398
PR332/P LSI T7SQ1000RW 12,498
PR332/P LSIG T7SQ1000SW 13,867
T7S, 1200A, 600V
Electronic, 100% rated
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7S 50
PR231/P LS/I T7SQ1200BW $ 14,559
PR232/P LSI T7SQ1200CW 14,769
PR331/P LSIG T7SQ1200EW 15,469
PR332/P LI T7SQ1200PW 15,171
PR332/P LSI T7SQ1200RW 16,269
PR332/P LSIG T7SQ1200SW 17,640
Discount schedule S7T [T7]
T7H, 1000A, 600V
Electronic, 100% rated
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7H 65
PR231/P LS/I T7HQ1000BW $ 11,418
PR232/P LSI T7HQ1000CW 11,667
PR331/P LSIG T7HQ1000EW 13,794
PR332/P LI T7HQ1000PW 12,042
PR332/P LSI T7HQ1000RW 13,142
PR332/P LSIG T7HQ1000SW 14,510
T7H, 1200A, 600V
Electronic, 100% rated
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7H 65
PR231/P LS/I T7HQ1200BW $ 15,428
PR232/P LSI T7HQ1200CW 15,677
PR331/P LSIG T7HQ1200EW 17,516
PR332/P LI T7HQ1200PW 16,052
PR332/P LSI T7HQ1200RW 17,150
PR332/P LSIG T7HQ1200SW 18,521
T7L, 1000A, 600V
Electronic, 100% rated
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7L 100
PR231/P LS/I T7LQ1000BW $ 12,062
PR232/P LSI T7LQ1000CW 12,310
PR331/P LSIG T7LQ1000EW 14,149
PR332/P LI T7LQ1000PW 12,685
PR332/P LSI T7LQ1000RW 12,785
PR332/P LSIG T7LQ1000SW 15,154
T7L, 1200A, 600V
Electronic, 100% rated
Breaker ICat480VACkA Trip type Adjustment 3 pole, 600VAC catalog
number List price
T7L 100
PR231/P LS/I T7LQ1200BW $ 16,309
PR232/P LSI T7LQ1200CW 16,558
PR331/P LSIG T7LQ1200EW 18,398
PR332/P LI T7LQ1200PW 16,933
PR332/P LSI T7LQ1200RW 18,032
PR332/P LSIG T7LQ1200SW 19,402
NOTE:Seepages16.57-16.70forelectrical/mechanicalaccessories.
Tmax
MCCBs
16.34 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T7
1200A, 600V ∆
Electronic/Moldedcaseswitch
T7
1200A, 600V
Moldedcaseswitch
Breaker ICat480VACkA1Amp Magnetic
trip
3 pole, 600VAC catalog
number List price
T7H -1200 20,000 T7H1200DW Consult
factory
NOTE:Seepages16.57-16.70forelectrical/mechanicalaccessories.
1WhenprotectedbyaOCPDwithappropriateratings.
Discount schedule S7T [T7]
Call for availability!
Tmax
MCCBs
Low Voltage Products & Systems 16.35
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
T7M (Stored energy)
1000A, 1200A, 600V ∆
Electronic
General
TheT7Mbreakerisastoredenergy1200Aframewithamicroprocessorbased
overcurrentprotectivetripsystem.
Standards
TheUL489/CSA22.2versionofT7MalsocarriesanIEC-60947-2rating.
Versions
Tomeetallapplicationrequirements,theT7Misavailableinthefollowing
versions:
B=Selectable&adjustableLIorLS—Dipswitchsetting
C=AdjustableLSI—Dipswitchsetting
E=AdjustableLSIG—Dipswitchsetting
D=MoldedCaseSwitch
P=LI—LCDdisplay
R=LSI—LCDdisplay
S=LSIG—LCDdisplay
Trip functions
Thesetripfunctionsareavailable:
L = Long time
S=Shorttime
I = Instantaneous
G=Groundfault
Performance levels
Eachversionisalsoavailableindifferentmaximumfaultinterruptinglevels:
S = Standard
H=High
L=Extrahigh
Number of poles
TheT7Misavailableasathreeandfourpolebreaker.
Dimensions 3PFixedVersion 10.55Hx8.26Wx7D
Weight 24.25(Ibs)
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage S H L
240VAC 65 100 150
480VAC 50 65 100
600VAC 25 50 65
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage S H L
230VAC 85 100 200
415VAC 50 70 120
690VAC 30 42 50
T7M
Tmax
MCCBs
16.36 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T7M
1000A, 1200A, 600V ∆
Electronic
T 7 M
Accessories:
X = None
A=Mechanicalcounter
B = Trip signal
C=Tripsignalandreset24-30VAC/DC
D=Tripsignalandreset110-130VAC/DC
E=Tripsignalandreset200-240VAC/DC
F = A+C; G=A+D; H=A+E
Locking provisions:
X = None
A = Keylock; B = Button guard
C=Padlockprovision(open)
D=Withdrawablepositionlock
(Connected,testanddisconnectedpositions)
E=Withdrawablepositionlock(Disconnectedposition)
Undervoltage:
0 = None; A=24VAC/DC;B=30VAC/DC;
C=48VAC/DC;D=60VAC/DC;E=110...120VAC/DC
F=120...127VAC/DC;G=220...240VAC/DC;
H=240…250VAC/DC;J=380…400VAC;K=415…440VAC
Shunt trip:
0 = None; A = 24VAC/DC;B = 30VAC/DC;
C = 48VAC/DC;D = 60VAC/DC;E = 110…120VAC/DC
F = 120…127VAC/DC;G = 220…240VAC/DC;H = 240…250VAC/DC
J = 380…400VAC;K = 415…440VAC
Spring Charging Motor:
0 = None; A = 24…30VAC/DC;
B = 48…60VAC/DC;C = 100...130VAC/DC;D = 220…250VAC/DC
E = 380…415VAC;F = Springscharged24VDC;G=Springscharged250VAC/DC;
H=A+F; J=B+F; K=C+F; L=D+F; M=E+F; N=A+G; P=B+G; Q=C+G; R=D+G; S=E+G
Auxilary Contacts:
0 = None A=2FormC(400VAC);B = 2 Form C (24 VDC); C=Ready to close 24 VDC;
D =Readytoclose250VAC/DC
Closing Coil:
0 = None; A = 24VAC/DC;B = 30VAC/DC;C = 48VAC/DC;
D = 60VAC/DC;E = 110…120VAC/DC;F = 120…127VAC/DC;
G = 220…240VAC/DC;H = 240…250VAC/DC;J = 380…400VAC;
K = 415…440VAC
Trip Unit Accessories:
0 = None; A = PR330V; B = PR330/D-M;C = A+B(PR332/Ponly)
Trip Unit:
B = PR231/P-LS/I;C = PR232/P-LSI;D = Non-Automatic(MCS);
E = PR331/P-LSIG;P = PR332/P-LI;R = PR332/P-LSI;S = PR332P-/LSIG
Rating Plug:
0=None;Non–Automatic(MCS)A = 400A; B = 600/630A;C = 800A;D = 1000A; E = 1200/1250A F=1600A(IEConly)
Frame Ampere rating:
A3=800A(3P)IEConly;P3=1000A(3P);B3=1200/1250A(3P);C31600A(3PIEConly)
A4=800A(4P)IEConly;P4=1000A(4P);B4=1200/1250A(4P);C41600A(4PIEConly)
Version:
O=Fixednon-automatic(MCS);B=ULxed;Q=ULxed100%rated;F=IECxed
Breaking Capacity:
S, H, L, V =IEC,T7800,1000,1250Aonly)CallfactoryforIECbreakerpricing
Tmax
MCCBs
Low Voltage Products & Systems 16.37
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
Discount schedule S7T [T7]
T7M-S, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSBP3DB000000XX $ 11,264
PR232/P-LSI T7MSBP3DC000000XX 11,524
PR331/P-LSIG T7MSBP3DE000000XX 13,447
PR332/P-LI T7MSBP3DP000000XX 11,916
PR332/P-LSI T7MSBP3DR000000XX 13,066
PR332/P-LSIG T7MSBP3DS000000XX 14,497
T7M-H, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHBP3DB000000XX $ 11,937
PR232/P-LSI T7MHBP3DC000000XX 12,197
PR331/P-LSIG T7MHBP3DE000000XX 14,120
PR332/P-LI T7MHBP3DP000000XX 12,589
PR332/P-LSI T7MHBP3DR000000XX 13,739
PR332/P-LSIG T7MHBP3DS000000XX 15,170
T7M-L, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLBP3DB000000XX $ 12,299
PR232/P-LSI T7MLBP3DC000000XX 12,870
PR331/P-LSIG T7MLBP3DE000000XX 14,793
PR332/P-LI T7MLBP3DP000000XX 13,262
PR332/P-LSI T7MLBP3DR000000XX 14,412
PR332/P-LSIG T7MLBP3DS000000XX 15,842
T7M-S, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSBB3EB000000XX $ 15,208
PR232/P-LSI T7MSBB3EC000000XX 15,469
PR331/P-LSIG T7MSBB3EE000000XX 17,392
PR332/P-LI T7MSBB3EP000000XX 15,861
PR332/P-LSI T7MSBB3ER000000XX 17,009
PR332/P-LSIG T7MSBB3ES000000XX 18,441
T7M-H, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHBB3EB000000XX $ 16,129
PR232/P-LSI T7MHBB3EC000000XX 16,390
PR331/P-LSIG T7MHBB3EE000000XX 18,313
PR332/P-LI T7MHBB3EP000000XX 16,782
PR332/P-LSI T7MHBB3ER000000XX 17,930
PR332/P-LSIG T7MHBB3ES000000XX 19,363
T7M-L, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLBB3EB000000XX $ 17,050
PR232/P-LSI T7MLBB3EC000000XX 17,311
PR331/P-LSIG T7MLBB3EE000000XX 19,234
PR332/P-LI T7MLBB3EP000000XX 17,703
PR332/P-LSI T7MLBB3ER000000XX 18,852
PR332/P-LSIG T7MLBB3ES000000XX 20,284
T7M
1000A,1200A,600VΔ-ThreePole
Electronic
Tmax
MCCBs
16.38 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T7M
1000A,1200A,600VΔ-ThreePole
Electronic 100% Rated
Discount schedule S7T [T7]
T7M-S, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSQP3DB000000XX $ 12,390
PR232/P-LSI T7MSQP3DC000000XX 12,676
PR331/P-LSIG T7MSQP3DE000000XX 14,792
PR332/P-LI T7MSQP3DP000000XX 13,108
PR332/P-LSI T7MSQP3DR000000XX 14,373
PR332/P-LSIG T7MSQP3DS000000XX 15,947
T7M-H, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHQP3DB000000XX $ 13,131
PR232/P-LSI T7MHQP3DC000000XX 13,417
PR331/P-LSIG T7MHQP3DE000000XX 15,532
PR332/P-LI T7MHQP3DP000000XX 13,848
PR332/P-LSI T7MHQP3DR000000XX 15,113
PR332/P-LSIG T7MHQP3DS000000XX 16,687
T7M-L, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLQP3DB000000XX $ 13,529
PR232/P-LSI T7MLQP3DC000000XX 14,157
PR331/P-LSIG T7MLQP3DE000000XX 16,272
PR332/P-LI T7MLQP3DP000000XX 14,588
PR332/P-LSI T7MLQP3DR000000XX 15,853
PR332/P-LSIG T7MLQP3DS000000XX 17,426
T7M-S, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSQB3EB000000XX $ 16,729
PR232/P-LSI T7MSQB3EC000000XX 17,016
PR331/P-LSIG T7MSQB3EE000000XX 19,131
PR332/P-LI T7MSQB3EP000000XX 17,447
PR332/P-LSI T7MSQB3ER000000XX 18,710
PR332/P-LSIG T7MSQB3ES000000XX 20,285
T7M-H, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHQB3EB000000XX $ 17,742
PR232/P-LSI T7MHQB3EC000000XX 18,029
PR331/P-LSIG T7MHQB3EE000000XX 20,144
PR332/P-LI T7MHQB3EP000000XX 18,460
PR332/P-LSI T7MHQB3ER000000XX 19,723
PR332/P-LSIG T7MHQB3ES000000XX 21,299
T7M-L, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 3pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLQB3EB000000XX $ 18,755
PR232/P-LSI T7MLQB3EC000000XX 19,042
PR331/P-LSIG T7MLQB3EE000000XX 21,157
PR332/P-LI T7MLQB3EP000000XX 19,473
PR332/P-LSI T7MLQB3ER000000XX 20,737
PR332/P-LSIG T7MLQB3ES000000XX 22,312
Tmax
MCCBs
Low Voltage Products & Systems 16.39
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
Discount schedule S7T [T7]
T7M
1000A,1200A,600VΔ-FourPole
Electronic
T7M-S, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSBP4DB000000XX $ 15,206
PR232/P-LSI T7MSBP4DC000000XX 15,557
PR331/P-LSIG T7MSBP4DE000000XX 18,153
PR332/P-LI T7MSBP4DP000000XX 16,087
PR332/P-LSI T7MSBP4DR000000XX 17,639
PR332/P-LSIG T7MSBP4DS000000XX 19,571
T7M-H, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHBP4DB000000XX $ 16,115
PR232/P-LSI T7MHBP4DC000000XX 16,466
PR331/P-LSIG T7MHBP4DE000000XX 19,062
PR332/P-LI T7MHBP4DP000000XX 16,995
PR332/P-LSI T7MHBP4DR000000XX 18,548
PR332/P-LSIG T7MHBP4DS000000XX 20,480
T7M-L, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLBP4DB000000XX $ 16,604
PR232/P-LSI T7MLBP4DC000000XX 17,375
PR331/P-LSIG T7MLBP4DE000000XX 19,971
PR332/P-LI T7MLBP4DP000000XX 17,904
PR332/P-LSI T7MLBP4DR000000XX 19,456
PR332/P-LSIG T7MLBP4DS000000XX 21,387
T7M-S, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSBB4EB000000XX $ 20,531
PR232/P-LSI T7MSBB4EC000000XX 20,883
PR331/P-LSIG T7MSBB4EE000000XX 23,479
PR332/P-LI T7MSBB4EP000000XX 21,412
PR332/P-LSI T7MSBB4ER000000XX 22,962
PR332/P-LSIG T7MSBB4ES000000XX 24,895
T7M-H, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHBB4EB000000XX $ 21,774
PR232/P-LSI T7MHBB4EC000000XX 22,127
PR331/P-LSIG T7MHBB4EE000000XX 24,723
PR332/P-LI T7MHBB4EP000000XX 22,656
PR332/P-LSI T7MHBB4ER000000XX 24,206
PR332/P-LSIG T7MHBB4ES000000XX 26,140
T7M-L, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLBB4EB000000XX $ 23,018
PR232/P-LSI T7MLBB4EC000000XX 23,370
PR331/P-LSIG T7MLBB4EE000000XX 25,966
PR332/P-LI T7MLBB4EP000000XX 23,899
PR332/P-LSI T7MLBB4ER000000XX 25,450
PR332/P-LSIG T7MLBB4ES000000XX 27,383
Tmax
MCCBs
16.40 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T7M
1000A,1200A,600VΔ-FourPole
Electronic 100% Rated
Discount schedule S7T [T7]
T7M-S, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSQP4DB000000XX $ 16,727
PR232/P-LSI T7MSQP4DC000000XX 17,113
PR331/P-LSIG T7MSQP4DE000000XX 19,969
PR332/P-LI T7MSQP4DP000000XX 17,695
PR332/P-LSI T7MSQP4DR000000XX 19,403
PR332/P-LSIG T7MSQP4DS000000XX 21,528
T7M-H, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHQP4DB000000XX $ 17,726
PR232/P-LSI T7MHQP4DC000000XX 18,113
PR331/P-LSIG T7MHQP4DE000000XX 20,968
PR332/P-LI T7MHQP4DP000000XX 18,695
PR332/P-LSI T7MHQP4DR000000XX 20,402
PR332/P-LSIG T7MHQP4DS000000XX 22,527
T7M-L, 1000A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLQP4DB000000XX $ 18,264
PR232/P-LSI T7MLQP4DC000000XX 19,112
PR331/P-LSIG T7MLQP4DE000000XX 21,968
PR332/P-LI T7MLQP4DP000000XX 19,694
PR332/P-LSI T7MLQP4DR000000XX 21,402
PR332/P-LSIG T7MLQP4DS000000XX 23,525
T7M-S, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-S 50
PR231/P-LS/I T7MSQB4EB000000XX $ 22,584
PR232/P-LSI T7MSQB4EC000000XX 22,971
PR331/P-LSIG T7MSQB4EE000000XX 25,827
PR332/P-LI T7MSQB4EP000000XX 23,554
PR332/P-LSI T7MSQB4ER000000XX 25,258
PR332/P-LSIG T7MSQB4ES000000XX 27,385
T7M-H, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-H 65
PR231/P-LS/I T7MHQB4EB000000XX $ 23,952
PR232/P-LSI T7MHQB4EC000000XX 24,339
PR331/P-LSIG T7MHQB4EE000000XX 27,195
PR332/P-LI T7MHQB4EP000000XX 24,921
PR332/P-LSI T7MHQB4ER000000XX 26,626
PR332/P-LSIG T7MHQB4ES000000XX 28,754
T7M-L, 1200A, 600V
Electronic
Breaker ICat480VACkA Trip unit 4pole,600Vcatalognumber List price
T7M-L 100
PR231/P-LS/I T7MLQB4EB000000XX $ 25,319
PR232/P-LSI T7MLQB4EC000000XX 25,707
PR331/P-LSIG T7MLQB4EE000000XX 28,562
PR332/P-LI T7MLQB4EP000000XX 26,289
PR332/P-LSI T7MLQB4ER000000XX 27,995
PR332/P-LSIG T7MLQB4ES000000XX 30,122
Tmax
MCCBs
Low Voltage Products & Systems 16.41
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
T7
1200A, 600V
Moldedcaseswitch
Breaker ICat480VACkA Amp Magnetic
override
3 pole, 600VAC catalog
number List price
T7M-H - 1200 20,000 T7MH0B30D000000XX Consult
factory
Call for availability!
Discount schedule S7T [T7]
T7M
1200A,600VΔ-MoldedCaseSwich
Tmax
MCCBs
16.42 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
KT7MXM*
KT7XU*
1NotSuitableforT7toggleversion.
2AlwayssuppliedwithPR332/Ptripunits
Closing coils 1Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7M
415…440VAC
$ 535
KT7MXC1
$ 490
380…400VAC KT7MXC2
240…250VAC/DC KT7MXC3
220…240VAC/DC KT7MXC4
120…127VAC/DC KT7MXC5
110…120VAC/VDC KT7MXC6
60VAC/DC KT7MXC7
48VAC/DC KT7MXC8
30VAC/DC KT7MXC9
24VAC/DC KT7MXC0
Stunt trip Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7/T7M
415…440VAC
$ 535
KT7XS1
$ 490
380…400VAC KT7XS2
240…250VAC/DC KT7XS3
220…240VAC/DC KT7XS4
120…127VAC/DC KT7XS5
110…120VAC/DC KT7XS6
60VAC/DC KT7XS7
48VAC/DC KT7XS8
30 VAC/DC KT7XS9
24VAC/DC KT7XS0
Undervoltage Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7/T7M
415…440VAC
$ 535
KT7XU1
$ 490
380…400VAC KT7XU2
240…250VAC/DC KT7XU3
220…240VAC/DC KT7XU4
120…127VAC/DC KT7XU5
110…120VAC/DC KT7XU6
60VAC/DC KT7XU7
48VAC/DC KT7XU8
30 VAC/DC KT7XU9
24VAC/DC KT7XU0
Spring charging motor 1Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7M
380…415VAC
$ 1917
KT7MXM2
$ 1867
220…250VAC/DC KT7MXM3
100…130VAC/DC KT7MXM5
48…60VAC/DC KT7MXM7
24…30VAC/DC KT7MXM9
Auxiliary contacts Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7/T7M 2 Form C 400 VAC $ 446 KT7XAS2 $ 396
2 Form C 24 VDC KT7XAS2-AU
Trip signal Field/factory
installation
catalognumber
Field/factory
installation
list price adder
T7M Contactforsignallingelectronictripunittripped1KT7MTS $ 295
Accessories
Electrical
T7M
Discount schedule SAT (TO)
Ready to close auxiliaries (IEC) Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7M 24 VDC $ 726 KT7MX-RTC24V $ 676
250VAC/DC KT7MX-RTC250V
Signalsthecircuitbreakerisreadytoacceptaclosesignalifthefollowingveconditionsaremet:
•Circuitbreakerisopen •Anyopeningcoilde-energized •Openingsolenoidarmed
•Closingspringsarecharged •Anyundervoltagecoilenergized
Spring charged contacts (IEC) Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7M Contactsignallingspringscharged24VDC $ 361 KT7MX-SC24V $ 311
Contactsignallingspringscharged250VAC/DC
KT7MX-SC250V
Trip reset (IEC) Factory installation
list price adder
Field installation
catalognumber
Field installation
list price
T7M
Tripresetcommand24-30VAC/DC
$ 818
KT7MX-TR9
$ 768
Tripresetcommand110-130VAC/DC
KT7MX-TR5
Tripresetcommand200-240VAC/DC
KT7MX-TR4
Allowsremotecircuitbreakerresettingfollowingatripoftheovercurrentrelease
Tmax
MCCBs
Low Voltage Products & Systems 16.43
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
Discount schedule SAT [TO]
Accessories
Mechanical
T7M
KT7MXMC
KT7XPG
KT7MKL*
1Comesstandardwithhighproleterminalcovers.
2Fixedbreakersonly
3 NotSuitableforT7toggleversion
Terminal lugs
FrameSizerWireSize Catalognumber
(3pieces)
List
Price
Catalognumber
(4pieces)
List
Price
T7/T7M1(4)4/0-500kxmil KT7X1200-3 1$ 560 KT7X1200-4 1 $ 747
Terminal covers - Low profile - kit includes two pieces-fixed breakers
FrameSizerCatalognumber
(3pole)
List
Price
Catalognumber
(4pole)
List
Price
T7/T7M2KT7XLTC-3 $ 80 KT7XLTC-4 $ 108
Terminal covers - High profile - kit includes two pieces
FrameSizerCatalognumber
(3pole)
List
Price
Catalognumber
(4pole)
List
Price
T7/T7M KT7XHTC-3 $ 90 KT7XHTC-4 $ 115
Phase barriers - Low profile 100mm - 3.93 in
FrameSizerCatalognumber
4pcs(3pole)
List
Price
Catalognumber
6pcs(4pole)
List
Price
T7/T7M KT7PBL-3 2$ 50 KT7PBL-4 $ 68
Phase barriers - High profile 200mm - 7.87 in
Frame Catalognumber
4pcs(3pole)
List
Price
Catalognumber
6pcs(4pole)
List
Price
T7/T7M KT7PBH-3 $ 67 KT7PBH-4 $ 90
Mechanical operation counter 3
Frame Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T7M Mechanicalcounter3KT7MXMC $ 866
Transparent protection for buttons 3
Frame Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T7M Button Guard 3KT7MXPG $ 112
Padlock provision 3
Frame Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T7M Padlock-open3KT7MXLDO $ 260
IP54 door protection 3
Frame Field Installation
catalognumber List price
T7M Protectivecover3KT7MXDC $ 1,200
Key locks
FrameSizerKey lock
open position
Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T7M
Keylockonbreaker
open position
keylock#200053
KT7MKL2 $ 121
Keylockonbreaker
open position
differentkeys3
KT7MKL1 121
Mechanical interlock
Frame Catalog
partnumber List price
T7M/T7M
CableT7 KT7XMLC $ 270
Mechanicalinterlockplate-drawout KT7XMLPW 670
Mechanicalinterlockplate-xed KT7XMLPF 670
Tmax
MCCBs
16.44 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
Sliding contact blocks
T7M-Drawout Movingpart
breaker List price Fixedpart
cradle List price
Left Block
Springchargingmotor
Springchargedcontact
Ready to close contact
Earlyauxiliarycontact
Contactfortripcoiltriprelease
Trip reset
KT7XSCMP-L $ 160 KT7XSCFP-L $ 310
Center Block
PR331
PR332
KT7XSCMP-C 160 KT7XSCFP-C 310
Right Block
Auxiliarycontacts
Shunttrip
Closing coil
Undervoltagerelease
KT7XSCMP-R 160 KT7XSCFP-R 310
Ifatleastoneoftheaccessoriesinthetableisinstalledonthebreaker-respectivepairofcontactblocksmustbeinstalledonthexedpart(cradle)
andthemovingpart(breaker)
Sliding Contacts
Position key lock
Locksdrawoutbreakerin
racked-in/test-isoloated/racked-out Catalognumber List price
Key#20005
Differentkeys
KT7XPL2 $ 252
KT7XPL1
Position lock accessory
Addedtopositionlockallowsbreaker
tobelockedinrackedoutpostiononly Catalognumber List price
Position lock accessory KT7XPLA $ 35
Draw-out kits
Frame Adaptormovingpart List price FixedPart List price
T7M3Polewithhorizontal/verticalterminals KT7XWMK $ 755 KT7WFHR $ 2,567
Discount schedule SAT (TO)
Accessories
Mechanical
T7M
PR330/D-M
Rating plugs (UL) Catalognumber Field installation
List price
T7/T7M
400A Rating plug KT7X0400RP
$ 125
600A Rating plug KT7X0600RP
800ARatingplug KT7X0800RP
1000A Rating plug KT7X1000RP
1200A Rating plug KT7X1200RP
Modules for T7M PR332 trip units Catalognumber Factory installation
list price adder
Field installation
list price
T7/T7M Voltage module 1
Communicationmodule(ModbusRTU)
PR330/VT7MX1 $ 5,050
PR330/D-M 4,500 $ 4,500
External units Catalognumber Field installation
list price
T7/T7M
Battery power supply unit 2PR030/B $ 275
ExternalBluetoothcommunicationmodule
Includesdiagnosticsoftwarefor
Modbus/Bluetoothnetworks
BT030 3335
Test conguration unit PR010/T 12,500
AllowstrippingofallelectronictripunitsforTmax
(exceptPR33x) K7TUT 210
Tmax
MCCBs
Low Voltage Products & Systems 16.45
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
Technical data T7/T7M
Shunttips,closingcoil,
Undervoltage&springchargingmotor
Standard shunt trip
Inrush Power Consumption T7/T7M
Voltage AC(VA) DC(W)
24VAC/DC 300 300
30VAC/DC 300 300
48VAC/DC 300 300
60VAC/DC 300 300
110…120VAC/DC 300 300
120…127VAC/DC 300 300
220…240VAC/DC 300 300
240…240VAC/DC 300 300
380…400VAC 300
415…440VAC 300
Openingtime(ms) 20 20
Closing coil
Inrush Power Consumption T7M
Voltage AC(VA) DC(W)
24VAC/DC 300 300
30VAC/DC 300 300
48VAC/DC 300 300
60VAC/DC 300 300
110…120VAC/DC 300 300
120…127VAC/DC 300 300
220…240VAC/DC 300 300
240…240VAC/DC 300 300
380…400VAC 300
415…440VAC 300
Openingtime(ms) 20 20
Undervoltage
Inrush Power Consumption T7/T7M
Voltage AC(VA) DC(W)
24VAC/DC 3.5 3.5
30VAC/DC 3.5 3.5
110…120VAC/DC 3.5 3.5
120…127VAC/DC 3.5 3.5
220…240 VAC 3.5 3.5
240…250VAC/DC 3.5 3.5
380…400VAC 3.5
415…440VAC 3.5
Openingtime(ms) 25 25
Spring charging motor
Power Consumption T7M
Voltage AC(VA) DC(W)
24….30VAC/DC ≤ 100 ≤ 100
48…60VAC/DC ≤ 100 ≤ 100
100…130VAC/DC ≤ 100 ≤ 100
220…250VAC/DC ≤ 100 ≤ 100
380…415VAC ≤ 100
Openingvoltage(%Un) 85-110 85-110
Chargingtime(s) 8-10 8-10
Tmax
MCCBs
16.46 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T8
1600/2000/2500/3000A,600VACΔ
Electronic trip
General
TheT8isavailableina1600A,2000A,2500A,3000Aframewithamicroprocessor
overcurrentprotectivetripsystem.
Standards
TheUL489/CSA22.2versionoftheT8alsocarriesanIEC-60947-2rating.
Versions
TomeetallapplicationrequirementstheT8isavailableinthefollowingversions:
C=AdjustableLSIPR232/P-T8Dipswitchsettings
D=MoldedCaseSwitch
E=AdjustableLSIGPR331/PDipswitchsettings
P=AdjustableLIPR332/PLCDDisplay
R=AdjustableLSIPR332/PLCDDisplay
S=AdjustableLSIGPR332/PLCDDisplay
Trip functions
Thesetripfunctionsareavailable:
L = Long time
S=Shorttime
I = Instantaneous
G=Groundfault
Performance levels
Eachversionisalsoavailableatthefollowingmaximumfaultinterruptinglevel:
V=Veryhigh
Number of poles
TheT8isavailableinthreeandfourpoleversions.
Dimensions 3PFixedVersion15.0Hx16.8Wx11.2D
Weight 161lbs(1600,2000,2500A)
236lbs(3000A)
UL489/CSA C22.2 Interrupting capacity (kA RMS)
Voltage V
240VAC 125
480VAC 125
600VAC 100
DC
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage V
230VAC 130
415VAC 130
440VAC 100
690VAC 80
DC
T8
Tmax
MCCBs
Low Voltage Products & Systems 16.47
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
T 8 V
Trip Unit Accessories: PR332/P ONLY
0 = None
B = Voltage measuring module; C=Modbusmodule
Trip Unit:
C=PR232/P-T8-LSI;D=Non-Automatic(MCS);E=PR331/P-LSIG;
P=PR332/P-LI;R=PR332/P-LSI;S=PR332/P-LSIG
Rating Plug:
D = 1000; E = 1200; F = 1600; G = 2000; H=2500;J = 3000, 3200; 0=Non-Automatic(MCS)
Frame Amp Rating:
C3=1600(3PULonly);D3=2000(3P);E3=2500(3P);F3=3000UL/3200IEC(3P)
C4=1600(4PULonly);D4=2000(4P);E4=2500(4P);F4=3000UL/3200IEC(4P)
Version:
B=ULFixed;Q=ULFixed100%Rated;0=FixedNon-Automatic(MCS)
Breaking capacity:
V=VeryHigh;L(IEConly.CallfactoryforIECbreakerpricing.)
Closing Coil:
0 = None
A = 24 VDC; B=30VAC/DC;C=48VAC/DC;D=60VAC/DC;E=110..120VAC/DC;
F=120..127VAC/DC;G=220..240AC/DC;H=240..250VAC/DC;J=380..400VAC;K = 440VAC
Contacts:
0 = None
A=4auxcontacts;(suppliedasstandardforbreakerswithPR332tripunits)
B=4auxcontactsdigital(24V)
D = UV energ NO; E = UV energ NC;
F = A+D; G = A+E; H = B+D; G = B+E
Accessories
X = None; A=Mechanicalcounter;B = Bell Alarm
C=BellAlarmw/remotereset,24..30VAC/DC
D=BellAlarmw/remotereset110..130VAC/DC
E=BellAlarmw/remotereset220..240VAC/DC
F = A+B; G = A+C; H = A+D; J = A+E
Undervoltage
0 = None
A = 24 VDC; B=30VAC/DC
C=48VAC/DC;D=60VAC/DC
E=110..120VAC/DC;F=125..127VAC/DC
G=220..240VAC/DC;H=250VAC/DC
J=380..400VAC;K = 440 VAC
Second shunt trip:
L = 24 VDC; M=30VAC/DC
N=48VAC/DC;P=60VAC/DC
Q=110..120VAC/DC;R=125..127VAC/DC
S=220..240VAC/DC;T=250VAC/DC
U=380..400VAC;V=440..480VAC
Spring charging Motor:
0 = None
A=24..30VAC/DC;B=48..60VAC/DC;
C=100..130VAC/DC;D=220..250VAC/DC
Shunt trip
0 = None
A = 24 VDC; B=30VAC/DC;C=48VAC/DC;
D=60VAC/DC;E=110..120VAC/DC
F=120..127VAC/DC;G=220..240VAC/DC;
H=240..250VAC/DC;J=380…400VAC;
K = 440 VAC
Locking provisions:
X = None; A = Keylock
B = Button guard
C=PadlockProvision
D = A+B; E = A+C
General Information
Catalognumberexplanation
Tmax
MCCBs
16.48 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
2000AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBD3GC000000XX $ 24,922
PR331LSIG(DipSwitch) T8VBD3GE000000XX 27,414
PR332LI(LCD) T8VBD3GP00A000XX 128,434
PR332LSI(LCD) T8VBD3GR00A000XX 129,359
PR332LSIG(LCD) T8VBD3GS00A000XX 130,839
2500AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBE3HC000000XX $ 33,577
PR331LSIG(DipSwitch) T8VBE3HE000000XX 37,213
PR332LI(LCD) T8VBE3HP00A000XX 138,416
PR332LSI(LCD) T8VBE3HR00A000XX 139,433
PR332LSIG(LCD) T8VBE3HS00A000XX 140,595
3000AFrame,electronictripunit(AConly)standardwithverticalterminals-Required
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBF3JC000000XX $ 56,472
PR331LSIG(DipSwitch) T8VBF3JE000000XX 60,618
PR332LI(LCD) T8VBF3JP00A000XX 161,185
PR332LSI(LCD) T8VBF3JR00A000XX 162,431
PR332LSIG(LCD) T8VBF3JS00A000XX 163,911
1600AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBC3FC000000XX $ 21,244
PR331LSIG(DipSwitch) T8VBC3FE000000XX 24,016
PR332LI(LCD) T8VBC3FP00A000XX 124,972
PR332LSI(LCD) T8VBC3FR00A000XX 125,866
PR332LSIG(LCD) T8VBC3FS00A000XX 127,346
T8
1600/2000/2500/3000A600VΔ-ThreePole
Electronic(ACOnly)
1Includes4open/closedauxillarycontactsasstandard
Discount schedule S8T (T8)
Tmax
MCCBs
Low Voltage Products & Systems 16.49
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
T8
1600/2000/2500/3000A600VΔ-ThreePole
Electronic(ACOnly)100%Rated
2000AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQD3GC000000XX $ 27,414
PR331LSIG(DipSwitch) T8VQD3GE000000XX 30,155
PR332LI(LCD) T8VQD3GP00A000XX 131,277
PR332LSI(LCD) T8VQD3GP00A000XX 132,295
PR332LSIG(LCD) T8VQD3GR00A000XX 133,923
2500AFrame,electronictripunit(AConly)standardwithverticalterminals-Required
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQE3HC000000XX $ 36,934
PR331LSIG(DipSwitch) T8VQE3HE000000XX 40,934
PR332LI(LCD) T8VQE3HP00A000XX 142,258
PR332LSI(LCD) T8VQE3HR00A000XX 1 43,376
PR332LSIG(LCD) T8VQE3HS00A000XX 1 44,655
3000AFrame,electronictripunit(AConly)standardwithverticalterminals-Required
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQF3JC000000XX $ 62,119
PR331LSIG(DipSwitch) T8VQF3JE000000XX 66,680
PR332LI(LCD) T8VQF3JP00A000XX 167,304
PR332LSI(LCD) T8VQF3JR00A000XX 168,674
PR332LSIG(LCD) T8VQF3JS00A000XX 170,302
1600AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 3 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQC3FC000000XX $ 23,368
PR331LSIG(DipSwitch) T8VQC3FE000000XX 26,418
PR332LI(LCD) T8VQC3FP00A000XX 127,469
PR332LSI(LCD) T8VQC3FR00A000XX 128,453
PR332LSIG(LCD) T8VQC3FS00A000XX 130,080
1Includes4open/closedauxillarycontactsasstandard
Discount schedule S8T (T8)
Tmax
MCCBs
16.50 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T8
1600/2000/2500/3000A600VΔ—Fourpole
Electronic(ACOnly)
2000AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBD4GC000000XX $ 33,645
PR331LSIG(DipSwitch) T8VBD4GE000000XX 37,009
PR332LI(LCD) T8VBD4GP00A000XX 138,386
PR332LSI(LCD) T8VBD4GR00A000XX 139,635
PR332LSIG(LCD) T8VBD4GS00A000XX 141,632
2500AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBE4HC000000XX $ 45,329
PR331LSIG(DipSwitch) T8VBE4HE000000XX 50,238
PR332LI(LCD) T8VBE4HP00A000XX 151,862
PR332LSI(LCD) T8VBE4HR00A000XX 153,234
PR332LSIG(LCD) T8VBE4HS00A000XX 154,803
3000AFrame,electronictripunit(AConly)standardwithverticalterminals-Required
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBF4JC000000XX $ 76,237
PR331LSIG(DipSwitch) T8VBF4JE000000XX 81,834
PR332LI(LCD) T8VBF4JP00A000XX 182,600
PR332LSI(LCD) T8VBF4JR00A000XX 184,282
PR332LSIG(LCD) T8VBF4JS00A000XX 186,280
1600AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VBC4FC000000XX $ 28,679
PR331LSIG(DipSwitch) T8VBC4FE000000XX 32,422
PR332LI(LCD) T8VBC4FP00A000XX 133,713
PR332LSI(LCD) T8VBC4FR00A000XX 134,919
PR332LSIG(LCD) T8VBC4FS00A000XX 136,917
1Includes4open/closedauxillarycontactsasstandard
Discount schedule S8T (T8)
Tmax
MCCBs
Low Voltage Products & Systems 16.51
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
T8
1600/2000/2500/3000A600VΔ—Fourpole
Electronic(ACOnly)100%Rated
2000AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQD4GC000000XX $ 37,009
PR331LSIG(DipSwitch) T8VQD4GE000000XX 40,710
PR332LI(LCD) T8VQD4GP00A000XX 142,224
PR332LSI(LCD) T8VQC4GR00A000XX 143,598
PR332LSIG(LCD) T8VQD4GS00A000XX 145,796
2500AFrame,electronictripunit(AConly)standardverticalterminals-Required
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQE4HC000000XX $ 49,862
PR331LSIG(DipSwitch) T8VQE4HE000000XX 55,261
PR332LI(LCD) T8VQE4HP00A000XX 157,048
PR332LSI(LCD) T8VQE4HR00A000XX 158,558
PR332LSIG(LCD) T8VQE4HS00A000XX 160,284
3000AFrame,electronictripunit(AConly)standardwithverticalterminals-Required
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQF4JC000000XX $ 83,861
PR331LSIG(DipSwitch) T8VQF4JE000000XX 90,017
PR332LI(LCD) T8VQF4JP00A000XX 190,860
PR332LSI(LCD) T8VQF4JR00A000XX 192,710
PR332LSIG(LCD) T8VQF4JS00A000XX 194,907
1600AFrame,electronictripunit(AConly)standardhorizontalterminals
Breaker ICat480VACkA Trip Unit 4 pole, 600V
catalognumber List price
T8V 125
PR232LSI(DipSwitch) T8VQC4FC000000XX $ 31,547
PR331LSIG(DipSwitch) T8VQC4FE000000XX 35,664
PR332LI(LCD) T8VQC4FP00A000XX 137,084
PR332LSI(LCD) T8VQC4FR00A000XX 138,410
PR332LSIG(LCD) T8VQC4FS00A000XX 140,609
Discount schedule S8T (T8)
1Includes4open/closedauxillarycontactsasstandard
Tmax
MCCBs
16.52 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
T8
2000/2500/3000A600VΔ
MoldedCaseSwitch
Discount schedule S8T (T8)
2000AFrame,standardhorizontalterminals
Breaker 3 pole, 600V
catalognumber List price
T8V-D T8V0D30D3000000XX Consult factory
2500AFrame,standardhorizontalterminals
Breaker 3 pole, 600V
catalognumber List price
T8V-D T8V0E30D000000XX Consult factory
3000AFrame,standardwithverticalterminals-Required
Breaker 3 pole, 600V
catalognumber List price
T8V-D T8V0F30D000000XX Consult factory
T8V-D
Rated Voltage
AC 600VAC
DC
MagneticOveride 40000
Call for availability!
Tmax
MCCBs
Low Voltage Products & Systems 16.53
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
UL Rating plugs Catalog number List price
T8
1000A Rating plug KT81000RP
$ 125
1200A Rating plug KT81200RP
1600A Rating plug KT81600RP
2000A Rating plug KT82000RP
2500A Rating plug KT82500RP
3000A Rating plug KT83000RP
Current sensor for external neutral Field installation
catalog number
Field installation
list price
T8 Current sensor for external neutral 1000A-3000A KT8NCT Consult factory
Accessories for trip units Field/factory installation
catalog number
Field/factory
installation
list price
T8
Communication module (Modbus (RTU) PR330/D-M 2$ 4,500
External wireless communication module BT030 3,335
Power supply unit PR030/B 275
Voltage module, 3 pole 3
Voltage module, 4 pole 3
PR330/V-T83
PR330/V-T84
Consult
factory
Contact signaling undervoltage de-energized Field/factory installation
catalog number
Field/factory
installation
list price
T8 NC UV signaling contact KE6UE01 $ 82
NO UV signaling contact KE6UE10
Bell alarm with remote reset command Field/factory installation
catalog number
Field/factory
installation
list price
T8
Remote setting of circuit breaker after opening by overcurrent
release 220-240 VAC/DC DE6TBAR4
$ 545
Remote setting of circuit breaker after opening by overcurrent
release 110-130 VAC/DC DE6TBAR5
Remote setting of circuit breaker after opening by overcurrent
release 24-30 VAC/DC DE6TBAR9
Bell alarm Field/factory installation
catalog number
Field/factory
installation
list price
T8 Allows visual signaling (mechanical) and remote signaling (electri-
cal) of circuit breaker opening by overcurrent release DE6TBA $ 348
Closing coil Field/factory installation
catalog number
Field/factory
installation
list price
T8
440 VAC KE6C1
$ 374
380…400VAC KE6C2
240…250 VAC/DC KE6C3
220…240 VAC/DC KE6C4
120…127 VAC/DC KE6C5
110…120 VAC/DC KE6C6
60 VAC/DC KE6C7
48 VAC/DC KE6C8
30 VAC/DC KE6C9
24 VDC KE6C0
Auxiliary contacts Field/factory installation
catalog number
Field/factory
installation
list price
T8
4 open/closed PR232-T8/PR331 KT8A4
$ 600
4 open/closed PR332 1KT8A4-PR332
4 open/closed 24V PR232-T8/PR331 KT8A4D
4 open/closed 24V PR332 KT8A4D-PR332
Spring charging motor Field/factory installation
catalog number
Field/factory
installation
list price
T8
24…30 VAC/DC KE6M9
$ 1,613
48…60 VAC/DC KE6M7
100…130 VAC/DC KE6M5
220…250 VAC/DC KE6M3
KE6C*
KT8A4
KE6M*
Discount schedule EDX (P0)
1 Included as standard on breakers ordered with PR332 trip unit
2 Discount schedule SAT (T0)
3 Factory install only.
Accessories
Electrical
T8
Tmax
MCCBs
16.54 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
Shunt trip Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8
440 VAC KE6S1
$ 374
380…400VAC KE6S2
240…250VAC/DC KE6S3
220…240VAC/DC KE6S4
120…127VAC/DC KE6S5
110…120VAC/DC KE6S6
60VAC/DC KE6S7
48VAC/DC KE6S8
30VAC/DC KE6S9
24 VDC KE6S0
Second shunt trip 1Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8
440 VAC KE6S1-2
$ 456
380…400VAC KE6S2-2
240…250VAC/DC KE6S3-2
220…240VAC/DC KE6S4-2
120…127VAC/DC KE6S5-2
110…120VAC/DC KE6S6-2
60VAC/DC KE6S7-2
48VAC/DC KE6S8-2
30VAC/DC KE6S9-2
24 VDC KE6S0-2
Undervoltage Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8
440 VAC KE6U1
$ 456
380…400VAC KE6U2
240…250VAC KE6U3
220…240VAC/DC KE6U4
120…127VAC/DC KE6U5
110…120VACV/DC KE6U6
60VAC/DC KE6U7
48VAC/DC KE6U8
30VAC/DC KE6U9
24 VDC KE6U0
KE6S*
KE6U*
Accessories
Electrical
T8
Discount schedule EDX (P0)
1Maybeusedinplaceundervoltage.
Tmax
MCCBs
Low Voltage Products & Systems 16.55
ABBInc.•888-385-1221•www.abb.us/lowvoltage 1SXU000023C0202
16
KE6PG
Key lock in open position Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8
Keylockn.200051KT8KL2
$ 202
Key lock n. 20006 KT8KL3
Key lock n. 20007 KT8KL4
Keylockn.20008 KT8KL5
Keylockdifferentkeys KT8KL1
Vertical terminals Field installation
catalognumber
Field installation
list price
T8 RearVerticalTerminals(2) Setofsix KT82500VR-6 $ 2225
Setofeight KT82500VR-8 3035
Cable terminals Wiresize Field installation
catalognumber
Field installation
list price
T8 MechanicalLugs(setof3) 1/0-750kcmil(4) K8TL $ 274
1/0-750kcmil(6) K8TM 315
Padlocking button cover Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8 3-4mmlocks(padlocksnotsupplied) KE6PD1 $ 162
Button guard Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8 Protectivecoverforopeningand
closingpushbuttons KE6PG $ 48
Mechanical operation counter Field/factoryinstallation
catalognumber
Field/factory
installation
list price
T8 Indicatesthenumberofmechanicaloperations KE6MC $ 418
IP54 door protection Field installation
catalognumber
Field installation
list price
T8 Protectivecover KE6DC $ 557
Phase barriers-top terminals only Field installation
catalognumber
Field installation
list price
T8
Low100mm2pcs(3P) KT8PBL-3 $ 50
Low100mm3pcs(4P) KT8PBL-4 68
High200mm2pcs(3P) KT8PBH-3 67
High200mm4pcs(4P) KT8PBH-4 90
Accessories
Mechanical
T8
Discount schedule EDX (P0)
1Keylocknumberwhenfactoryinstalledis20005.
Tmax
MCCBs
16.56 Low Voltage Products & Systems
1SXU000023C0202 ABBInc.•888-385-1221•www.abb.us/lowvoltage
16
Absorbed power on inrush
Shunt trip, Second shunt trip, closing coil
Voltage AC DC
24 VDC 200
30VAC/DC 200 200
48VAC/DC 200 200
60VAC/DC 200 200
110…120VAC/DC 200 200
120…127VAC/DC 200 200
220…240VAC/DC 200 200
380…400VAC 200
440 VAC 200
Openingtimeshunttrip-Secondshunttrip(ms) ≤ 60 ≤ 60
Closingtimeclosingcoil(ms) 80 80
Spring charging motor
Shunt trip, Second shunt trip, closing coil
Rated Voltage AC DC
24…30 24…30
48…60 48…60
100…130 100…130
220…250 220…250
Operatingvoltage(%Un) 85-110 85…110
Powerconsumptiononinrush 500VA 500W
Inrushtime(s) 0.2 0.2
Chargingtime(s) 4-5 4-5
Technical data
T8
Tmax
MCCBs
Low Voltage Products & Systems 16.57
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Accessories
Electrical
T1 - T7
KT3S4
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for eld installation.
3 SAT5 Discount schedule.
T1 with KT3S4
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
T7 X1 Shunt trip - UVR
Shunt trips -(Standard) 1
For remote opening of circuit breaker. Guaranteed operation for a voltage of between 75-110%
of the rated power supply voltage. T1-T6 mounts in the left hand cavity cannot be used with UVR on 2-3P breakers
Factory Installation 1Field Installation
Frame Size Voltage Catalog number
sufx
List price
adder Catalog number List
Price
T1-T3
480 - 500VAC S1
$ 535
KT3S1
$ 490
220-250VAC/DC S2 KT3S2
380 - 440VAC S3 KT3S3
110 - 125VAC/DC S4 KT3S4
48 - 60VAC/DC S7 KT3S7
24 - 30VAC/DC S8 KT3S8
12VDC S9 KT3S9
Ts3
480VAC/250VDC S1
535
KTS3S1
490
240 VAC S2 KTS3S2
120VAC/125VDC S4 KTS3S4
48VDC S7 KTS3S7
24VAC/VDC S8 KTS3S8
12VDC S9 KTS3S9
T4, T5, T6
3
480-500VAC S1
535
KT5S1
490
220/250VAC/DC S2 KT5S2
380-440VAC S3 KT5S3
110-125VAC/DC S4 KT5S4
48-60VAC/DC S7 KT5S7
24VAC/DC S8 KT5S8
12VDC S9 KT5S9
T7
415-440VAC S1
535
KT7XS1
490
380-400VAC S2 KT7XS2
240-250VAC/DC S3 KT7XS3
220-240VAC/DC S4 KT7XS4
120-127VAC/DC S5 KT7XS5
110-120VAC/DC S6 KT7XS6
60VAC/DC S7 KT7XS7
48VAC/DC S8 KT7XS8
30VAC/DC S9 KT7XS9
24VAC/DC S0 KT7XS0
Shunt trip connector (REQUIRED for Ts3) 2Field Kit
Ts3 Fixed Mount 2Included when shunt trip factory installed KTS3C-SU $ 45
Ts3 Draw-out 2Included when shunt trip factory installed KTS3C-SUP
Shunt trips (Permanent Supply) 1
For remote opening of circuit breaker. Guaranteed operation for a voltage of between 75-110% of the rated power supply
voltage. These shunt trips have much lower power consumption.
Factory Installation 1Field Installation
Frame Size Voltage Catalog number
sufx
List price
adder Catalog number List
Price
Ts3 24VDC SA $ 535 KTS3SA $ 490
120VAC SB KTS3SB
T4, T5, T6 324-30VDC SA 535 KT5SA 490
110/120/VAC SB KT5SB
Shunt trip connector (REQUIRED for Ts3) 2Field Kit
Ts3 Fixed Mount 2Included when shunt trip factory installed KTS3C-SU $ 45
Draw-out 2Included when shunt trip factory installed KTS3C-SUP
Tmax
MCCBs
16.58 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Accessories
Electrical
T1 - T7
T7 X1 Shunt trip - UVR
KT3U2
Undervoltage release - UVR
Will trip circuit breaker when connected voltage drops to 35-70% of the undervoltage release
voltage rating. Will allow circuit breaker to close when voltage is approximately 85% of the
rated voltage. T1-T6 mounts in the left hand cavity cannot be used with shunt trip on 2-3P breakers
Factory Installation 1Field Installation
Frame Size Voltage Catalog number
sufx
List price
adder Catalog number List
Price
T1-T3
480 - 500VAC U1
$ 535
KT3U1
$ 490
220-250VAC/DC U2 KT3U2
380 - 440VAC U3 KT3U3
110 - 125VAC/DC U4 KT3U4
60VAC/DC U5 KT3U5
48VAC/DC U7 KT3U7
24 - 30VAC/DC U8 KT3U8
Ts3
480VAC U1
535
KTS3U1
490
240VAC U2 KTS3U2
24VAC U3 KTS3U3
120VAC U4 KTS3U4
250VDC U5 KTS3U5
125VDC U6 KTS3U6
48VDC U7 KTS3U7
24VDC U8 KTS3U8
T4, T5, T6
3
480-500VAC U1
535
KT5U1
490
220/250VAC/DC U2 KT5U2
380-440VAC U3 KT5U3
110-125VAC/DC U4 KT5U4
60VAC/DC U5 KT5U5
48VAC/DC U7 KT5U7
24VAC/DC U8 KT5U8
T7
415-440VAC U1
535
KT7XU1
490
380-400VAC U2 KT7XU2
240-250VAC/DC U3 KT7XU3
220-240VAC/DC U4 KT7XU4
120-127VAC/DC U5 KT7XU5
110-120VAC/DC U6 KT7XU6
60VAC/DC U7 KT7XU7
48VAC/DC U8 KT7XU8
30VAC/DC U9 KT7XU9
24VAC/DC U0 KT7XU0
Undervoltage trip connector (REQUIRED for Ts3) 2Field Kit
Ts3 Fixed Mount 2Included when under voltage factory installed KTS3C-SU $ 45
Plug-In/Draw-out 2Included when under voltage factory installed KTS3C-SUP
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for eld installation.
3 SAT5 Discount schedule.
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
Low Voltage Products & Systems 16.59
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Accessories
Electrical
T1 - T7
KTS3AS
T1 with K3TAS
Auxiliary contacts - AUX 1
Auxiliary contacts are for indication of the circuit breaker open-closed. Bell alarm contacts (BA) can be
used to indicate circuit breaker tripped.
Frame Size
Factory Installation 1Field Installation
Catalog number
sufx
List price
adder Catalog number List
Price
T1-T3 2
1 Form C + 1BA A$ 433 KT3AS $ 380
3 Form C + 1BA A3 770 KT3AS3 725
3 Form C + 1BA 24VDC A3AU 770 KT3AS3-AU 725
T2 T2 PR221DS 1 Form C + 1BA A433 KT2AS-E 380
Ts3 2 Form C A430 KTS3AS 275
1 Form C+ 1 BA BA KTS3BA 380
T4, T5, T6 4
1 Form C + 1BA 250VAC/VDC A433 KT5AS 388
3 Form C + 1BA 250VAC/VDC A3 770 KT5AS3 725
3 Form C + 1BA 24VDC A3AU 770 KT5AS3-AU 725
T7
1 Form C + 1BA 400VAC/250VDC A
446
KT7AS
396
2 Form C 400VAC/250VDC A2 KT7XAS2
1 Form C + 1BA 24VDC AAU KT7AS-AU
2 Form C 24VDC A2AU KT7XAS2-AU
Auxiliary contact connector (REQUIRED for Ts3) 3Field Kit
Ts3 Fixed Mount 3Included
Included
KTS3C-AB $ 45
Plug-In /Drawout 3KTS3C-ABP
1 For factory installation add sufx to end of breaker part number per accessory format .
2 Not compatible for T2 with PR221DS trip unit.
3 Must be ordered separately for eld installation.
4 SAT5 Discount schedule.
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
16.60 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Accessories
Motor operators
T1 - T7
KT3M1
KTS3M2
KT5M2
Electrical operators
Allows remote opening and closing of circuit breaker
Frame size Voltage Catalog
number
List
price
Solenoid operator
T1-T3 48 - 60VDC KT3M1 $ 850
110 - 250VAC/DC KT3M2
Direct action motor operator
Ts3
240VAC/250VDC KTS3M2
1,799
120VAC/125VDC KTS3M4
48VDC KTS3M7
24VDC KTS3M8
Motor operator connector (REQUIRED for Ts3) 1
Ts3 Fixed Mount 1KTS3C-M 45
Plug-In / Draw-out 1KTS3C-MP
Stored energy motor operator
T4, T5
220-250VAC/DC KT5M2
2,385
110--125-VAC/DC KT5M4
48-60VDC KT5M7
24VDC KT5M8
Contact for remote/manual operation (stored energy operator)
T4, T5, T6 2-KT5MA 220
Stored energy motor operator
T6
220-250VAC/DC KT6M2
4,990
110--125-VAC/DC KT6M4
48-60VDC KT6M7
24VDC KT6M8
380VAC KT6M3
1 Must be ordered separately for eld installation
2 SAT5 Discount schedule.
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
Low Voltage Products & Systems 16.61
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Accessories
Trip units
T4 - T7
1 Always supplied with PR332/P trip unit.
3 Factory installed only.
Frame Size Rating plug Catalog
number
List
Price
Rating plugs (UL)
T7
400A Rating plug KT7X0400RP
$ 125
600A Rating plug KT7X0600RP
800 Rating plug KT7X0800RP
1000A Rating plug KT7X1000RP
1200 Rating plug KT7X1200RP
Modules for T7 PR332 trip units
T7 Voltage module 2PR330/VT7 3033
Communication module (Modbus RTU) PR330/D-M 4500
External units
Test and conguration unit 3PR010/T 12,500
Trip coil test-all Tmax electronic trip unit except PR33* K7TUT 210
External Bluetooth communication module 1
Includes diagnostic software for Modbus / Bluetooth networks BT030 3,335
Battery power supply unit 1PR030/B 275
Not suitable for UL applications.
T7 - Allows remote opening when used with PR330/D-M and shunt trip
T7M - Allows remote opening and closing when used with PR330//D-M. shunt trip and closing coil
Actuator module (IEC)
T7 Actuator module 2PR330/R-T7 700
Neutral current transformers (required for 4 wire ground fault systems)
T4
100A KT4NCT-100
300
150A KT4NCT-150
250A KT4NCT-250
T5 300A KT5NCT-300 300
400A KT5NCT-400
T6 600A KT6NCT-600 770
800A KT6NCT-800
Discount schedule SAT [T0] — T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
16.62 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Technical data
Shunt trips, Undervoltages
T1 - T7
Standard shunt trip
Voltage
Inrush Power Consumption
T1,T2,T3 Ts3 T4,T5,T6 T7
AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)
12 VDC - 50 - 120 - 150 - -
24 VAC/DC - - 100 100 or 4 1- - 300 300
24…30 VAC/DC 50 50 - - 150 150 - -
30 VAC/DC - - - - - - 300 300
48 VAC/DC - - - 120 - - 300 300
48…60 VAC/DC 60 60 - - 150 150 - -
60 VAC/DC - - - - - - 300 300
100…120 VAC/DC - - 100 or 4 1- - - 300 300
120…127 VAC/DC - - - - - - 300 300
110…127 VAC 110…125 VDC 50 50 - 120 150 150 - -
220…240 VAC/DC - - - - - - 300 300
220…240 VAC 220…250 VDC 50 50 100 120 150 150 - -
240…250 VAC/DC - - - - - - 300 300
380…400 VAC - - - - - - 300 -
380…440 VAC 55 - - - 150 - - -
415…440 VAC - - - - - - 300 -
480 VAC - - 100 - - - - -
480…525 VAC 55 - - - 150 - - -
Opening Time (ms) 15 15 ≤15 ≤15 15 15 20 20
Permanent supply shunt trip
Voltage T4,T5,T6
AC (VA) DC (W)
24 VAC/DC 4 4
100…120 VAC 4 -
Undervoltage
Voltage
Power consumption during permanent operation
T1,T2,T3 Ts3 T4, T5, T6 T7
AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)
24 VAC/DC - - 63 - - 3.5 3.5
24…30 VAC/DC 1.5 1.5 - - 63 - -
30 VAC/DC - - - - - - 3.5 3.5
48 VAC/DC 116363 - -
60 VAV/DC 1 1 - - 63 - -
110…120 VAC/DC - - 6- - - 3.5 3.5
120…127 VAC/DC - - - - - - 3.5 3.5
110…127 VAC 110…125 VDC 2 2 - - 63 - -
220…240 VAC/DC - - - - - - 3.5 3.5
220…240 VAC 220…250 VDC 2.5 2.5 - 3 63 - -
220…250 VAC - - 6-----
240…250 VAC/DC - - - - - - 3.5 3.5
380…400 VAC - - - - - - 3.5 -
380…440 VAC 3 - - - 6- - -
415 - 440 VAC - - - - - - 3.5 -
480…525 VAC 4 - - - 6- - -
480 VAC - - 6-----
Opening Time (ms) 15 15 ≤18 ≤18 ≤25 ≤25 ≤25 ≤25
1 Shunt trip permanent supply
Tmax
MCCBs
Low Voltage Products & Systems 16.63
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Technical data
Electrical operators
T1 - T6
Electrical operator, T1-T3
Rated Voltage AC DC
- 48…60
110...250 110...250
Operating Voltage 85…110% Un
Inrush power absorption during operation 1800 (VA) 1000 (W)
Power on stand by < 100 (mW)
Time opening (s) < 0.1
closing (s) < 0.1
Minimum control impulse time on
opening and closing (ms) >100
This unit is permanently supplied on stand by, a control is applied by means of
external contact in a low power circuit.
Contact characteristics:
Voltage AC/DC=24V
Current 50 mA
Electrical operator, Ts3
Rated Voltage AC DC
- 24
- 48…60
120 125
240 250
440 -
Operating Voltage 85…110 % Un
Inrush power absorption 500 (VA) 500 (W)
Service power absorption 350 (VA) 350 (W)
Time constant (ms) 18
Duration opening (s) 0.1
closing (s) 0.1
Minimum duration of the opening and closing
command impulse (ms) ≥150
Electrical operator, T4-T5
Voltage AC DC
- 24
- 48…60
110…125 110…125
220-250 220-250
380 -
Operating Voltage 85…110%
Inrush power consumption ≤ 300VA ≤ 300W
In service power consumption ≤150VA ≤150W
Duration
opening (s) 1.5
closing (s) < 0.1
resetting (s) 3
Minimum duration of the opening and closing
command impulse (ms) ≥100
Electrical operator, T6
Voltage AC DC
- 24
- 48…60
110-125 110-125
220-250 220-250
380 -
Operating Voltage 85…110%
Inrush power consumption ≤ 400VA ≤ 400W
In service power consumption ≤150VA ≤150W
Duration
opening (s) 3
closing (s) < 0.1
resetting (s) 5
Minimum duration of the opening and closing
command impulse (ms) ≥100
Tmax
MCCBs
16.64 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Accessories
Mechanical
T1 - T7
1 Comes standard with high prole terminal covers.
2 Uses front extended spreaded terminals... refer to technical catalog.
3 Discount schedule SA.
4 Not suitable for use on T5 600A.
Standard cable terminal
Frame Wire Size Catalog number
(set of 3)
List
Price
Catalog number
(set of 4)
List
Price
T1 14 AWG-1/0 Integral Integral
T2 14 AWG-1/0 KT2100-3 $ 9 KT2100-4 $ 12
T3 14 AWG - 1/0 KT3100-3 9KT3100-4 12
4 AWG - 300 kcmil KT3225-3 18 KT3225-4 24
Ts3
14-2 K3TA 36K3TA-4 38
14-1/0 K4TB 36K4TB-4 38
2-4/0 K4TC 36K4TC-4 38
4-300 kcmil K4TD 315 K4TD-4 320
T4 14 AWG-1/0 KT4100-3 9KT4100-4 12
6 AWG-350 kcmil KT4250-3 30 KT4250-4 40
T5 4250 kcmil-500 kcmil KT5300-3 45 KT5300-4 60
T5 14 (2) 3/0-250 kcmil KT5400-3 45 KT5400-4 60
T5 2(2) 3/0-500 kcmil KT5600-3 225
T6 (2) 250-500 kcmil 3K6TH 375 K6TH-4 3100
T6 1(3) 2/0-400 kcmil 3K6TJ 3135 K6TJ-4 3180
T7 1(4) 4/0-500 kcmil KT7X1200-3 560 KT7X1200-4 747
Standard cable lug kits with power control taps
Frame Wire Size Catalog number
(set of 3)
List
Price
Catalog number
(set of 4)
List
Price
T3 14 AWG - 1/0 KT3100-3C $ 16 KT3100-4C $ 19
4 AWG - 300 kcmil KT3225-3C 18 KT3225-4C 31
Ts3
14 AWG-1/0 K4TBC 12 K4TBC-4 20
2 AWG-4/0 K4TCC 12 K4TCC-4 20
4 AWG-300 kcmil K4TDC 21 K4TDC-4 31
T4 14 AWG-1/0 KT4100-3C 15 KT4100-4C 20
6 AWG-350 kcmil KT4250-3C 36 KT4250-4C 48
T5 4250 kcmil-500 kcmil KT5300-3C 51 KT5300-4C 68
T5 14 (2) 3/0-250 kcmil KT5400-3C 51 KT5400-4C 68
T6 (2) 250-500 kcmil K6THC 381 K6THC-4 3109
T6 1(3) 2/0-400 kcmil K6TJC 3141 K6TJC-4 3190
Terminal covers for fixed breakers - Low prole-kit includes two pieces
Frame Catalog number
(3 pole)
List
Price
Catalog number
(4 pole)
List
Price
T1 KT1LTC-3 $ 35 KT1LTC-4 $ 47
T2 KT2LTC-3 40 KT2LTC-4 54
T3 KT3LTC-3 50 KT3LTC-4 68
Ts3 KTS3LTC-3 55 KTS3LTC-4 74
T4 KT4LTC-3 55 KT4LTC-4 74
T5 KT5LTC-3 60 KT5LTC-4 81
T6 KT6LTC-3 75 KT6LTC-4 101
T7 KT7XLTC-3 80 KT7XLTC-4 108
Terminal covers for fixed breakers - High prole-kit includes two pieces
Frame Catalog number
(3 pole )
List
Price
Catalog number
(4 pole)
List
price
T1 KT1HTC-3 $ 37 KT1HTC-4 $ 50
T2 KT2HTC-3 43 KT2HTC-4 58
T3 KT3HTC-3 53 KT3HTC-4 72
Ts3 KTS3HTC-3 58 KTS3HTC-4 78
T4 KT4HTC-3 58 KT4HTC-4 78
T5 KT5HTC-3 63 KT5HTC-4 85
T6 KT6HTC-3 85 KT6HTC-4 108
T7 KT7XHTC-3 90 KT7XHTC-4 115
KT3100-3
KT1HTC-3
KT4LTC-3
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
Low Voltage Products & Systems 16.65
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Accessories
Mechanical
T1 - T7
KT2EF-3
KT2R-3
KT4EF-_
Phase barriers - Low prole 100mm-3.93 in
Frame 4 pcs (3p) List
Price 6 pcs (4p) List
Price
T1-T3 KT3PBL-3 $ 28 KT3PBL-4 $ 42
T4-T5 KT5PBL-3 28 KT5PBL-4 42
T6 KT6PBL-3 42 KT6PBL-4 57
T7 KT7PBL-3 50 KT7PBL-4 68
Phase barriers - High prole 200mm-7.87 in
Frame 4 pcs (3p) List
Price 6 pcs (4p) List
Price
T1-T3 KT3PBH-3 $ 42 KT3PBH-4 $ 63
T4-T5 KT5PBH-3 42 KT5PBH-4 63
T7 KT7PBH-3 67 KT7PBH-4 90
Saddle terminals for Copper Cables - IEC
Frame Catalog number
( Set of 3 )
List
Price
Catalog number
(Set of 4)
List
Price
T2 KT2100S-3 $ 34 KT2100S-4 $ 46
T3 KT3225S-3 52 KT3225S-4 70
Ts3 K4TES 330 K4TES-4 440
T4 KT4250S-3 41 KT4250S-4 55
T5 KT5300S-3 270 KT5300S-4 365
Extended front terminals
Frame Catalog number
(set of 3)
List
Price
Catalog number
(set of 4)
List
Price
T2 KT2EF-3 $ 26 KT2EF-4 $ 35
T3 KT3EF-3 33 KT3EF-4 44
Ts3 KTS3EF-3 65 KTS3EF-4 88
T4 KT4EF-3 55 KT4EF-4 73
T5 KT5EF-3 115 KT5EF-4 155
Rear terminals 1
Frame Catalog number
(set of 3)
List
Price
Catalog number
(set of 4)
List
Price
T2 KT2R-3 $ 78 KT2R-4 $ 105
T3 KT3R-3 98 KT3R-4 131
T4 KT4R-3 60 KT4R-4 80
T5 KT5R-3 122 KT5R-4 163
T6 KT6R-3 350 KT6R-4 473
T7 KT7R-3 407 KT7R-4 550
1 Includes low prole terminal cover.
2 Includes high prole terminal cover.
3 Set of six, Discount schedule SA.
4 Set of eight, Discount schedule SA.
Distribution cable lug kit 2
Frame Wire Size Catalog number
(set of 3)
List
Price
Catalog number
(set of 4)
List
Price
T3 (6) #14-6 KT3TN $ 125 KT3TN-4 $ 167
Ts3 (6) #14-6 KTS3TN 125 KTS3TN-4 169
T4 (6) #14-6 KT4TN 125 KT4TN-4 167
T5 (6 )#14-1/0 KT5TGD 240 KT5TGD-4 320
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
16.66 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Accessories
Mechanical
T1 - T7
KT3LD
OHB65J6
KT5RH
OHB125J10
Padlock locking device
Frame Style Locking Position Breaker
Mounting Catalog number List
Price
T1,T2,T3 PLL OPEN/CLOSED Fixed KT3LD $ 35
OPEN KT3LDO
Ts3 FLD OPEN Fixed, Plug-In KTS3FLD 87
Draw-0ut KTS3FLDW 125
T4-T5 FLD OPEN Fixed, Plug-In KT5FLD 40
Draw-out KT5FLDW 55
T6 FLD OPEN Fixed, Plug-In KT6FLD 220
Draw-out KT6FLDW 240
T7 PLL OPEN Fixed, Drawout KT7LDO 260
Keylocks-rotary handle mechanism
Frame Style Locking Position Keys Catalog number List
Price
T1,T2,T3 RHL OPEN/CLOSED Different KT3RHL3 $ 94
Ts3 - OPEN Different KTS3KLFD 58
T4-T5 KLF-D OPEN Different KT5KLFD 58
T6 KLF-D OPEN Different KT6KLFD 68
T7 KLF-D OPEN Different KT7KLFD 79
Direct mount rotary operator handle
Frame Breaker
Mounting Catalog number List
Price
T1, T2, T3 Fixed, Plug-In KT3RH $ 146
Ts3 Fixed, Plug-In KTS3RH 150
Ts3 Draw-out KTS3RHW 150
T4-T5 Fixed, Plug-In KT5RH 135
T4-T5 Draw-0ut KT5RHW 135
T6 Fixed, Draw-out KT6RH 450
T6 Draw-out KT6RHW 450
T7 Fixed, Draw-out KT7RH 450
Variable depth handle operators
Frame NEMA rating Mechanism
catalog number
List
Price Shaft catalog number List
Price
Handle catalog
number
List
Price
T1—T3
1,3R,12 OHB65J6 1
OHY65J6 1$ 80
4, 4X KT3VD-M $ 72 OXP6X430 (16.9”) 2$ 28 OHB80L6 1
OHY80L6 1130
1 KT3VD-S (11.8”) 35 KT3VD-H 87
Ts3
1,3R,12 OXP10X148 (5.8") 224 OHB95J10 1
OHY95J10 180
4,4X KTS3VD-M 72 OXP10X225 (8.9") 126 OHB95L10 1
OHY95L10 1120
OXP10X500 (19.7") 132
1 KT3VD-S (20") 35 KTS3VD-H 87
T4-T5
1,3R,12 OXP10X148 (5.8") 124 OHB95J10 1
OHY95J10 80
4,4X KT5VD-M 65 OXP10X225 (8.9") 126 OHB95L10 1
OHY95L10 1120
OXP10X500 (19.7") 132
1 KT5VD-S (19.7") 36 KT5VD-H 87
T6
1,3R,12 OXP10X148 (5.8") 124 OHB125J10 1
OHY125J10 190
4,4X KT6VD-M 370 OXP10X225 (8.9") 126 OHB125L10 1130
OXP10X500 (19.7") 132
1 KT5VD-S (19.7) 36 KT6VD-H 210
T7
1,3R,12 OXP10X148 (5.8") 124 OHB175J10 1
OHY175J10 1100
KT7VD-M 370 OXP10X225 (8.9") 126 OHB175L10 1140
OXP10X500 (19.7") 132
1 KT7VD-S (19.7") 130 KT7VD-H 231
1 Discount schedule SH.
2 Discount schedule H6.
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
Low Voltage Products & Systems 16.67
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
KT4PMK (on back of
breaker)
KT4PFVR
KT2PFF + KT2PMK (on back of breaker) +
breaker
Accessories
Mechanical
T1 - T7
Plug-in kits 1
Frame Catalog number
Adapter moving part
List
Price
Catalog number
xed part
List
Price
T2 - 3 pole with front terminals KT2PMK $ 171 KT2PFF $ 238
T3 - 3 pole with front terminals KT3PMK 190 KT3PFF 264
T2-T3 Fixed parts accept the same cable and rear terminal kits as the circuit breakers
Ts3 3 pole with front terminals KTS3PMK 250 KTS3PFF 305
Ts3 3 pole with rear terminals KTS3PFR
T4 3 pole with extended front terminal KT4PFEF 710
T4 3 pole with rear horizontal terminals KT4PMK 250 KT4PFHR 766
T4 3 pole with rear vertical terminals KT4PFVR 766
T5, 400A
T5 400A 3 pole with extended front terminal KT5PFEF 810
T5 400A 3 pole with rear horizontal terminal KT5PMK 350 KT5PFHR 866
T5 400A 3 pole with rear vertical terminal KT5PFVR 866
T5, 600A
T5 600A 3 pole with extended front terminal KT56PFEF 1,158
T5 600A 3 pole with rear horizontal terminal KT56PMK 501 KT56PFHR 1,238
T5 600A 3 pole with rear vertical terminal KT56PFVR 1,238
1 Plug connectors (T2-T3), Adaptors (T4-T5), required when adding accessories to plug-in breakers.
2 SAT5 Discount schedule.
Plug connectors, T1-T3
Required when adding accessories to plug-in breakers
Plug Connector Catalog
number
List
price
Shunt trip or UVR KT3PC-3 $ 18
1 form C plus 1 BA KT3PC-6 21
3 form C plus 1 BA KT3PC-12 24
Adaptors, T4-T6 2
Required when adding accessories to plug-in or drawout breakers
Adaptors Catalog
number
List
price
1 form C plus 1 BA KT5ADP-6 $ 24
Shunt trip/UVR KT5ADP-6 24
Stored energy operator KT5ADP-10 30
Stored energy operator plus shunt trip/UVR KT5ADP-10 30
3 form C plus 1BA KT5ADP-12 35
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
16.68 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
1 Adaptors (T4-T6), Sliding contact blocks (T7) required when adding accessories to draw-out breakers.
2 Comes standard with horizontal terminals eld convertible to vertical
3 IEC
4 SAT5 Discount schedule.
KT4WMK (on back of
breaker)
KT5WFVR
Accessories
T1 - T7
Draw-out kits 1
Item Catalog number
Adaptor moving part
List
Price
Catalog Number
Fixed part
List
Price
Ts3 3 pole with front terminals KTS3WMK $ 290 KTS3WFF 3 $ 790
Ts3 3 pole with rear terminals KTS3WFR 3
T4 3 pole with extended front terminal
KT4WMK 290
KT4WFEF 816
T4 3 pole with rear horizontal terminals KT4WFHR 1,021
T4 3 pole with rear vertical terminals KT4WFVR 1,021
T5 3 pole with extended front terminal KT5WFEF 931
T5 3 pole with rear horizontal terminal KT5WMK 407 KT5WFHR 1,154
T5 3 pole with rear vertical terminal KT5WFVR 1,154
T5 3 pole with extended front terminal KT56WFEF 1,331
T5 3 pole with rear horizontal terminal KT56WMK 582 KT56WFHR 1,650
T5 3 pole with rear vertical terminal KT56WFVR 1,650
T6 3 pole with extended front terminal KT6WFEF 3 1,844
T6 3 pole with rear horizontal terminal KT6WMK 670 KT6WFHR 3 1,844
T6 3 pole with rear vertical terminal KT6WFVR 2,144
T7 3 pole with horizontal/vertical terminals KT7XWMK 755 KT7WFHR 22,567
Adaptors — T4-T6 4
Required when adding accessories to plug-in or drawout breakers
Adaptors Catalog
number
List
price
1 form C plus 1 BA KT5ADP-6 $ 24
Shunt trip/UVR KT5ADP-6 24
Stored energy operator KT5ADP-10 30
Stored energy operator plus shunt trip/UVR KT5ADP-10 30
3 form C plus 1BA KT5ADP-12 35
Sliding contact blocks — T7-Draw-out
Item Moving Part
Breaker
List
Price
Fixed Part
Cradle
List
Price
Left Block
KT7XSCMP-L $ 160 KT7SCFP-L $ 185
Spring charging motor
Spring charged contact
Ready to close contact
Early auxiliary contact
Contact for trip coil release trip
Trip rest
Center Block
PR331 KT7XSCMP-C 160 KT7XSCFP-C 310
PR332
Right Block
Auxiliary contacts
KT7XSCMP-R 160 KT7XSCFP-R 310
Shunt trip
Closing Coil
Undervoltage release
If at least one of the accessories in table is installed on the breaker - respective pair of contact blocks must be installed on the
xed part (cradle) and the moving part. (breaker)
Position key lock — T7 - T7M-X1
Item Catalog
number
List
Price
Key #20005 KT7XPL2 $ 202
Different key KT7XPL1
Locks drawout breaker in racked-in / test isolation / racked-out position.
Position key lock accessory — T7 - T7M-X1
Item Catalog
number
List
Price
Key lock accessory KT7XPLA $ 35
Accessory added to position key lock allows breaker to be locked in racked-out position only.
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
Low Voltage Products & Systems 16.69
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Accessories
T1 - T7
KT3MIF2
DIN rail adapters
Item Catalog Number List Price
T1/T2 (mounts on 35 mm DIN rail 15mm high) KT2DIN $ 33
T3 (mounts on 35mm DIN rail 15mm high) KT3DIN 41
Ts3 (mounts on 75 mm DIN rail) KTS3DIN 51
Mechanical interlocks
T1-T3 Catalog Number List Price
Sliding bar interlock-front mounted (2 Breakers) KT3MIF2 $ 625
Sliding bar interlock-front mounted (3 Breakers) KT3MIF3 844
T3
Rear Interlock-horizontal KT3MI-H 896
Rear Interlock-vertical KT3MI-V 985
TS3
Horizontal KTS3MI-H 798
Vertical KTS3MI-V 798
T4-T5 1
Interlock frame
Mechanical Interlock frame-horizontal KT5MIR-HB 490
Mechanical Interlock frame-vertical KT5MIR-VB 588
Plate type
A T4 (F-P-W) T4 (F-P-W) KT5MIR-PA
B T4 (F-P-W) T5 400 (F-P-W) OR T5 600 (F) KT5MIR-PB
C T4 (F-P-W) T5 600 (P-W) KT5MIR-PC 210
D T5 (F-P-W) T5 400 (F-P-W) OR 630 (F) KT5MIR-PD
E T4 (F-P-W) T5 600 (P-W) KT5MIR-PE
F T4 (F-P-W) T5 600 (P-W) KT5MIR-PF
T6
620Horizontal KT6MI-H
Vertical KT6MI-V
T7 2
Cable T7-X1 KT7XMLC 270
Mech. interlock plate-xed KT7XMLPW 670
Mech. interlock plate-draw-out KT7XMLPF 670
1 T4-T5 Complete assembly consists of one interlock frame and one plate.
2 To interlock two circuit breakers, you have to order a cable kit and two plates.
Discount schedule SAT [T0] — T1-Ts3, T6, T7 Accessories
Discount schedule SAT5 [TZ] — T4-T5 Accessories
Tmax
MCCBs
16.70 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Enclosures
Type 1 & 3R/12
1 Padlocking provision must be ordered separately.
2 Must order KT5FLD (padlock device) separately.
3 Variable depth rotary handle must be ordered separately.
4 Consult ABB for breakers installed in enclosures.
Discount schedule SET [T9]
T3E-1 T4E-3R12 3
Enclosures (Price does not include circuit breaker; order as a separate item.) 4
NEMA Breaker Enclosure maximum rating Approximate dimensions1 Catalog List
designation type AL cables CU cables H x W x D (inches) number price
T1 100A 100A 15 x 8.5 x 4 T1E-1 $ 267
T2 100A 100A 15 x 8.5 x 4 T2E-1 267
Type 1 1 T3 175A 225A 20 x 11 x 4 T3E-1 315
T4 200A 250A 26 x 15 x 6.25 T4E-1 2 407
T5 325A 400A 26 x 15 x 6.25 T5E-1 2 435
T1 100A 100A 15 x 8.5 x 7 T1E-3R12 407
T2 100A 100A 15 x 8.5 x 7 T2E-3R12 407
Type 3R/123 T3 175A 225A 20 x 11 x 7 T3E-3R12 527
T4 200A 250A 26 x 15 x 9 T4E-3R12 625
T5 325A 400A 26 x 15 x 9 T5E-3R12 767
Breaker Neutral cable capacity Neutral kit List
type and wire range catalog number price
T1 – T2 Neutral #14-1/0 T2NK125 $ 140
Bonding Lug #14-1/0
T3 Neutral #6-250 kcmil T3NK225 150
Bonding Lug #14-1/0
T4 Neutral #6-250 kcmil T4NK250 155
Bonding Lug #14-1/0 kcmil
T5 Neutral (2) #6-250 kcmil T5NK400 295
Bonding Lug #14-1/0 kcmil
Neutral kits
NOTE: The list price adder for factory installation of an enclosed circuit breaker is 50% of the enclosure list price.
Description
Type 1
General purpose indoor enclosure intended for use in normal
environments to provide a degree of protection against contact with
enclosed equipment.
Sheet steel, surface mount.
Breaker is front-operable and can be padlocked via a separately
ordered padlock device.
Available through 400A, 600VAC
(SUSE) suitable for use as service equipment.
Type 3R/12
Type 3R is intended for outdoor use providing protection against
rain, sleet or snow.
Type 12 is for use in indoor atmospheres to provide a degree of
protection against circulating dust, lint, sawdust, falling dirt and
dripping non-corrosive liquids.
Surface-mounted, sheet steel enclosure.
Breaker can be operated via separately ordered handle
mechanism; door is interlocked with mechanism.
Available through 400A, 600VAC.
(SUSE) suitable for use as service equipment.
Tmax
MCCBs
Low Voltage Products & Systems 16.71
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Enclosures
Approximate dimensions, T1 – T5
NEMA 1, 3R & 12
NEMA 1
NEMA 3R, 12
JJ
SHOWN WITH BREAKER, PADLOCK DEVICE AND NEUTRAL KIT ORDERED SEPARATELY F MTG HOLES
4 PLACES
SHOWN WITH BREAKER, VARI-DEPTH MECHANISM, HANDLE, SHAFT AND NEUTRAL KIT, ORDERED SEPARATELY F MTG HOLES
4 PLACES
JJ
JH
FRONT VIEW SECTIONSIDE VIEW
B EG
C
FRONT VIEW SECTIONSIDE VIEW
B EG
C
Cat. # A B CD E F GH J
T1E-1 15.00
381
8.50
216
4.00
102
13.00
330
6.50
165
0.281
7
4.93
125
1, 1-1/4
25, 32
3/4, 1
19, 25
T2E-1 15.00
381
8.50
216
4.00
102
13.00
330
6.50
165
0.281
7
4.93
125
1, 1-1/4
25, 32
3/4, 1
19, 25
T3E-1 20.00
508
11.00
279
4.00
102
18.00
457
9.00
229
0.281
7
4.93
125
1, 1-1/4
25, 32
3/4, 1
19, 25
T4E-1 26.00
660
15.00
381
6.25
159
24.00
610
13.00
330
0.281
7
7.01
178
1, 1-1/4
25, 32
3/4, 1
19, 25
T5E-1 26.00
660
15.00
381
6.25
159
24.00
610
13.00
330
0.281
7
7.01
178
1, 1-1/4
25, 32
3/4, 1
19, 25
Cat. # A B CD E F G
T1E-3R12 15.00
381
8.50
216
7.00
178
15.75
400
5.00
127
0.313
8
9.06
230
T2E-3R12 15.00
381
8.50
216
7.00
178
15.75
400
5.00
127
0.313
8
9.06
230
T3E-3R12 20.00
508
11.00
279
7.00
178
20.75
527
7.50
191
0.313
8
9.06
230
T4E-3R12 26.00
660
15.00
381
9.00
229
26.75
679
11.50
292
0.313
8
11.06
281
T5E-3R12 26.00
660
15.00
381
9.00
229
26.75
679
11.50
292
0.313
8
11.06
281
Tmax
MCCBs
16.72 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
T1 & T2
T1 — 3 pole
T2 — 2 & 3 pole
T1 — Single pole
90
30 30
181
130
65
76.2
78
83
70
¯ 9.38
103
17
45 53.25
106.5
XX
Y
Y
>3 < 2
Tmax
MCCBs
Low Voltage Products & Systems 16.73
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T3
T3 — 2 & 3 pole
Door cut-out for Tmax without faceplate
Tmax
MCCBs
16.74 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
Ts3
Tmax
MCCBs
Low Voltage Products & Systems 16.75
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T4
Fixed circuit breaker
Flange for
compartment door
Drilling templates of the compartment door
Drilling templates for support sheet
For front terminals For rear terminals
3 POLES 4 POLES
Caption
1 Overall dimensions with
cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)
2 Overall dimensions with
cabled auxiliary contacts
mounted
(only 3Q 1SY)
3-4 POLES 3-4 POLES
With flange Without flange
Tmax
MCCBs
16.76 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
T5
Fixed circuit breaker
Flange for
compartment door
Drilling templates of the compartment door
Drilling templates for support sheet
For front terminals For rear terminals
3 POLES 4 POLES
3 POLES 4 POLES
Fixing on sheet
Caption
1 Overall dimensions with
cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)
2 Overall dimensions with
cabled auxiliary contacts
mounted
(only 3Q 1SY)
With flange (3-4 POLES) Without flange (3-4 POLES)
Tmax
MCCBs
Low Voltage Products & Systems 16.77
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T6
Tmax
MCCBs
16.78 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
T7
Tmax
MCCBs
Low Voltage Products & Systems 16.79
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T7M
Fixed, 3 Pole, front terminals
Tmax
MCCBs
16.80 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
T8, Fixed, 3 pole, front terminals
1600A, 2000A, 2500A
Tmax
MCCBs
Low Voltage Products & Systems 16.81
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T8, Fixed, Vertical rear terminals
80% rated 3000A; 100% rated 2500A, 3000A
Tmax
MCCBs
16.82 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
T8, Fixed, Optional vertical rear terminals (KT82500VR-x)
1600A/2000A/2500A
Tmax
MCCBs
Low Voltage Products & Systems 16.83
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T1 - T3
Variable depth mechanism with OHB handle
Tmax
MCCBs
16.84 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
Ts3
Variable depth mechanism with OHB handle
Tmax
MCCBs
Low Voltage Products & Systems 16.85
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T4 - T5
Variable depth mechanism with OHB handle
Tmax
MCCBs
16.86 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Approximate dimensions
T6
Variable depth mechanism
Tmax
MCCBs
Low Voltage Products & Systems 16.87
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
16
Approximate dimensions
T7
Variable depth mechanism
Tmax
MCCBs
16.88 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
16
Notes