Technical data KFD2-SR2-Ex2.W
103368_eng 06.03.2002
Power supply
Connection type Power Rail or terminals 14+, 15-
Rated operational voltage 20 ... 30 V DC
Rated operational current £ 50 mA
Safety maximum voltage Um125 V DC ; 253 V AC
Ripple £ 10 %
Power loss 0.7 W
Power consumption < 1.3 W
Input (intrinsically safe)
Connection type terminals 1+, 2+, 3-; 4+, 5+, 6-
Nominal data in accordance with IEC 60947-5-6 (NAMUR, DIN 19234); see system description for electrical
data
Quiescent voltage/Short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/Switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Input pulse length/Input pulse interval Š 20 ms / Š 20 ms
Lead monitoring breakage J £ 0.1 mA , short-circuit J > 6 mA
Details of certificate of conformity
Certification number PBT 00 ATEX 2080 ; for additional certifications refer to the approval list
Group, category, ignition protection method ¬ II (1) G D [EEx ia] IIC
Voltage U010.5 V
Current I013 mA
Power P034 mW
Allowable circuit values
Ignition protection class, category [EEx ia and
EEx ib] Explosion group IIA IIB IIC
External capacitance 75 µF 16.8 µF 2.41 µF
External inductance 1000 mH 840 mH 210 mH
Entity parameter
Certification number J.I.3002773
FM control drawing No. 116-0035
Suitable for installation in division 2 yes
Connection type terminals 1, 3; 2, 3; 4, 6; 5, 6
Input IVoltage VOC 12.9 V
Current ISC 19.8 mA
Explosion group A&B C&E D, F&G
Max. external capacitance Ca1.273 µF 3.82 µF 10.18 µF
Max. external inductance La84.8 mH 254.4 mH 678.4 mH
Safety parameter
UL control drawing E 106378
CSA control drawing LR 36087-13
Control drawing No. 116-0047
Connection type terminals 1, 3; 2, 3; 4, 6; 5, 6
Input ISafety parameter 12.6 V / 650 Ohm
Voltage VOC 12.9 V
Current ISC 19.8 mA
Explosion group A&B C&E D, F&G
Max. external capacitance Ca1.273 µF 3.82 µF 10.18 µF
Max. external inductance La84.88 mH 298.7 mH 744.4 mH
Output (not intrinsically safe)
Connection type output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I and II signal ; relay
Contact loading 253 V AC / 2 A / cos j > 0.7; 40 V DC / 2 A ohmic load; from january 2002 increase of the con-
tact rating to 4 A for 115 V AC switching voltage. The respective connection data are shown
on the type plate.
Mechanical life 107 switchings
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Transfer characteristics
Switching frequency £ 10 Hz
Galvanic is olation
Input/Output safe galvanic isolation acc. to EN 50020, voltage peak value 375 V