TVS4HWA50X Product data sheet Characteristics Surge Protect - HWA - 50kA - 480Y/277VAC 3P4W - T4X Product availability : Stock - Normally stocked in distribution facility Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Price* : 2,640.00 USD Main Product Surge protection device Range Surgelogic Device Short Name HWA Complementary Surge Current 50 kA per phase System Voltage 480Y/277 V AC Phase 3 phases Wiring Configuration 4-wire Connection Wire phase and neutral AWG 10 copper Wire ground AWG 10 copper Wire dry contacts AWG 22 copper MCOV 320 V Nominal Discharge Current 20 kA SCCR 200 kA Local Signalling Status LED, green = normal operation per phase Status LED, red = fault per phase Alarm = fault Mounting Location Bottom of enclosure Device Mounting Surface Flush with fixing kit Height 4.8 in (122 mm) Width 8.62 in (219 mm) Depth 3.11 in (79 mm) Environment Enclosure Rating NEMA 4X Jul 13, 2019 1 Enclosure Material Plastic, colour : black Standards CSA C22.2 No 8 1986 UL 1283 ed. 5 UL 1449 ed. 4 Ambient Operating 149 F (65 C) Ordering and shipping details Category 08466 - SURGE PROTECTION HWA Discount Schedule DE1B GTIN 00785901406242 Nbr. of units in pkg. 1 Package weight(Lbs) 5.1500000000000004 Returnability Y Country of origin US Offer Sustainability RoHS (date code: YYWW) Compliant - since 1743 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 DINP which is known to the State of California to cause cancer and - - - - - - - Substance 2 DIDP which is known to the State of California to cause birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov Contractual warranty Warranty period 2 18 months