PHOENIX CONTACT Inc., USA Page 1 / 7
http://www.phoenixcon.com Feb 7, 2011
Extract from the online
catalog
IL PN BK DI8 DO4 2TX-PAC
Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PROFINET bus coupler, 8 inputs, 24 V DC, 4 outputs, 24 V DC, 500
mA, complete with I/O connectors
Commercial data
GTIN (EAN)
4 046356 041164
Note Made-to-order
sales group K410
Pack 1 pcs.
Customs tariff 85176200
Catalog page information Page 242 (AX-2009)
Product notes
WEEE/RoHS-compliant since:
03/27/2008
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The bus coupler for the PROFINET protocol has 4 digital outputs and 8 digital inputs. This package contains all the
necessary Inline connectors for connecting the supply and the I/Os.
The Inline terminals can be labeled using pull-out labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the ZBFM-6... Zack marker strip for labeling the terminal points.
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PHOENIX CONTACT Inc., USA Page 2 / 7
http://www.phoenixcon.com Feb 7, 2011
Technical data
Interface
Fieldbus system Lokalbus
Name Inline local bus
Type of connection Inline data jumper
Transmission speed 500 Kbit / 2 MBaud
500 kBit/s, 2 MBit/s (Automatic detection, no combined system)
Fieldbus system PROFINET
Name PROFINET
Type of connection RJ45 female connector, auto negotiation
Transmission speed 100 MBit/s (acc. to PROFINET standard)
Transmission physics Ethernet in RJ45 twisted pair
Digital inputs
Input name Digital inputs
Description of the input EN 61131-2 type 1
Type of connection Inline connectors
Connection method 2, 3-wire
Number of inputs 8
Typical response time Approx. 500 µs
Protective circuit Protection against polarity reversal Polarity protection diode
Input voltage 24 V DC
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input current at UIN Typ. 3 mA
Typical input current per channel Typ. 3 mA
Delay at signal change from 0 to 1 5 ms
Delay at signal change from 1 to 0 5 ms
Digital outputs
Output name Digital outputs
Type of connection Inline connectors
Connection method 2, 3-wire
Number of outputs 4
Protective circuit Short-circuit and overload protection Free running circuit
Output voltage 24 V DC -1 V (At nominal current)
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PHOENIX CONTACT Inc., USA Page 3 / 7
http://www.phoenixcon.com Feb 7, 2011
Nominal output voltage 24 V DC
Maximum output current per channel 500 mA
Maximum output current per module / terminal
block
2 A
Nominal load, inductive 12 VA (1.2 H; 48 Ω)
Nominal load, lamp 12 W
Nominal load, ohmic 12 W
Power supply for module electronics
Type of connection Spring-cage connection
Name Bus coupler supply UBC; Communications power UL (7.5V) and
the analog supply UANA (24 V) are generated from the bus coupler
supply.
Supply voltage 24 V DC (via Inline connector)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption max. 0.91 A (from UBK)
General data
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Specfications with male connectors
Weight 375 g
Note on weight specifications with male connectors
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -45 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PHOENIX CONTACT Inc., USA Page 4 / 7
http://www.phoenixcon.com Feb 7, 2011
Conformance with EMC directives Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2
Criterion B; 6 kV contact discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A;
Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast
transients (burst) EN61000-4-4/IEC61000-4-4 Criterion A; all
interfaces 1 kVCriterion B; all interfaces 2 kV
Noise immunity test in accordance with EN 61000-6-2 Transient
surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion
B; supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical);
fieldbus cable shield 1 kV
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000-4-6/IEC61000-4-6 Criterion A; Test
voltage 10 V
Noise emission test as per EN 61000-6-4 EN 55011 Class A
Mechanical tests Vibration resistance in acc. with IEC 60068-2-6 5 g
Shock test in acc. with IEC 60068-2-27 Operation: 25 g, 11 ms
duration, semi-sinusoidal shock impulse
Diagnostics messages Short-circuit / overload of the digital outputs Yes
Sensor supply failure Yes
Failure of the actuator supply Yes
Inline potential routing
Communications power UL7.5 V DC ±5%
Power supply at ULmax. 0.8 A DC
Main circuit supply UM24 V DC
Supply voltage range UM19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UMmax. 8 A DC (Sum of UM + US; 4A, maximum, when used in
potentially explosive areas.)
Current consumption from UMmax. 8 A DC (US-consumer project+)
Segment supply voltage US24 V DC
Supply voltage range US19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at USmax. 8 A DC (Sum of UM + US; 4A, maximum, when used in
potentially explosive areas.)
Current consumption from USmax. 8 A DC (US-consumer project+)
I/O supply voltage UANA 24 V DC
Supply voltage range UANA 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UANA max. 0.5 A DC
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PHOENIX CONTACT Inc., USA Page 5 / 7
http://www.phoenixcon.com Feb 7, 2011
Certificates / Approvals
Certification ABS, BV, CUL Listed, DNV, GL, LR, UL Listed
Certification Ex: PxC-EX
Accessories
Item Designation Description
Assembly
3022218 CLIPFIX 35 Snap-on end bracket, for 35 mm NS 35/7.5 or NS 35/15 DIN
rail, can be fitted with Zack strip ZB 8 and ZB 8/27, terminal strip
marker KLM 2 and KLM, width: 9.5 mm, color: gray
1201442 E/UK End clamp, for assembly on NS 32 or NS 35/7.5 DIN rail
Cable/conductor
2744830 FL CAT5 FLEX CAT5-SF/UTP cable (J-LI02YS(ST)C H 2 x 2 x 26 AWG), light-
duty, flexible installation cable 2 x 2 x 0.14 mm², stranded,
shielded, outer sheath: 5.75 mm ± 0.15 mm diameter
2744814 FL CAT5 HEAVY CAT5-SF/UTP cable (J-02YS(ST)C HP 2 x 2 x 24 AWG), heavy-
duty installation cable, 2 x 2 x 0.22 mm², solid conductor, shielded,
outer sheath: 7.8 mm diameter, inner sheath: 5.75 mm ± 0.15 mm
diameter
Marking
0809492 ESL 62X10 Insert strip for laser printer, lettering field: 62 x 10 mm
0809502 ESL 62X46 Insert strip for laser printer, lettering field: 62 x 46 mm
2727501 IB IL FIELD 2 Labeling field, width: 12.2 mm
2727515 IB IL FIELD 8 Labeling field, width: 48.8 mm
Plug/Adapter
2744571 FL PLUG RJ45 GN/2 RJ45 connector, shielded, with bend protection sleeve, 2 pieces,
green for crossed cables, for assembly on site. For connections
that are crossed, it is recommended that the connector set with
green bend protection sleeves is used.
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PHOENIX CONTACT Inc., USA Page 6 / 7
http://www.phoenixcon.com Feb 7, 2011
2744856 FL PLUG RJ45 GR/2 RJ45 connector, shielded, with bend protection sleeve, 2 pieces,
gray for straight cables, for assembly on site. For connections that
are not crossed, it is recommended that you use the connector set
with gray bend protection sleeve.
2878599 IL BKDIO-PLSET Connector set, for Inline bus coupler with I/Os mounted in rows
Tools
2744869 FL CRIMPTOOL Crimping pliers, for assembling the RJ45 connectors FL PLUG
RJ45..., for assembly on site
Diagrams/Drawings
Connection diagram
Diagram
Dimensioned drawing
IL PN BK DI8 DO4 2TX-PAC Order No.: 2703994
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2703994
PHOENIX CONTACT Inc., USA Page 7 / 7
http://www.phoenixcon.com Feb 7, 2011
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact
Technical modifications reserved;