1
Introduction
2
Product line
3
Product combination
4
Functions
Filter
TRFI suppression filterT 5
Operation planning
6
Assembly
TSystem ManualT 7
Connection
8
Commissioning
9
Service and maintenance
10
Technical specifications
Circuit diagrams and
damping curves 11
A
Appendix
B
Index
T12/2007T
THBF 05-002-02-1BT
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
willindicates that death or severe personal injury result if proper precautions are not taken.
WARNING
mayindicates that death or severe personal injury result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description and only
in connection with devices or components from other manufacturers which have been approved or
recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage,
positioning and assembly as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG Ordernumber: HBF 05-002-02-1B Copyright © Siemens AG .
Automation and Drives Ⓟ 12/2007 Technical data subject to change
Postfach 48 48
90327 NÜRNBERG
GERMANY
Table of contents
1 Introduction............................................................................................................................................. 5
1.1 Structure and content of the manual..............................................................................................5
1.2 Laws and directives .......................................................................................................................6
2 Product line............................................................................................................................................. 7
2.1 Components...................................................................................................................................7
2.2 Device description..........................................................................................................................9
3 Product combination ............................................................................................................................. 11
3.1 Functional optimization ................................................................................................................11
4 Functions.............................................................................................................................................. 13
4.1 Method of operation .....................................................................................................................13
5 Operation planning................................................................................................................................ 15
5.1 Transport......................................................................................................................................15
5.2 Storage.........................................................................................................................................15
5.3 Configuration................................................................................................................................16
5.4 EMC-compliant configuration of drive systems............................................................................17
6 Assembly.............................................................................................................................................. 23
6.1 Assembly......................................................................................................................................23
6.2 Installation instructions.................................................................................................................26
7 Connection ........................................................................................................................................... 27
7.1 Prerequisites and definitions........................................................................................................27
7.2 Connection options ......................................................................................................................28
8 Commissioning ..................................................................................................................................... 31
8.1 Operation .....................................................................................................................................31
9 Service and maintenance...................................................................................................................... 33
9.1 Service/Maintenance ...................................................................................................................33
10 Technical specifications ........................................................................................................................ 35
10.1 Rating data...................................................................................................................................35
10.2 Additional technical specifications ...............................................................................................35
11 Circuit diagrams and damping curves.................................................................................................... 37
11.1 Circuit diagrams ...........................................................................................................................37
11.2 Damping curves ...........................................................................................................................39
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 3
Table of contents
A Appendix .............................................................................................................................................. 43
A.1 Latest information........................................................................................................................ 43
A.2 Correction sheet.......................................................................................................................... 44
B Index .................................................................................................................................................... 45
B.1 Index............................................................................................................................................ 45
RFI suppression filter
4 System Manual, 12/2007, HBF 05-002-02-1B
1
TIntroductionT
1.1 TStructure and content of the manualT
Purpose of the manual
This manual contains all the information required for connecting and using the 4EF15 RFI
suppression filter. The 4EF15 RFI suppression filter is a converter component.
This manual describes EMC-compliant connection of the 4EF15 RFI suppression filter, as
well as its functions.
Target group
This manual is intended for any user involved in:
Installing
Servicing and maintaining
Planning and configuring systems
Required basic knowledge
A general knowledge of the field of electrical engineering is required to understand this
manual.
Standards and certifications
EN133200 is the standard that applies to the RFI suppression filter.
Correction sheet
The Appendix contains a correction sheet. Please use it to record your suggestions for
improvements, additions and corrections, and return the sheet to us. This will help us to
improve the next edition of the manual.
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 5
TTIntroductionTT
1.2 TTLaws and directivesTT
1.2 TLaws and directivesT
Disclaimer of liability
It is the responsibility of the manufacturer to ensure that a system or machine is functioning
properly as a whole. SIEMENS AG, its regional offices, and associated companies
(hereinafter referred to as "SIEMENS") cannot guarantee all the properties of a whole plant
system or machine that has not been designed by SIEMENS.
Nor can SIEMENS assume liability for recommendations that appear or are implied in the
following description. No new guarantee, warranty, or liability claims beyond the scope of the
SIEMENS general terms of supply are to be derived or inferred from the following
description.
RFI suppression filter
6 System Manual, 12/2007, HBF 05-002-02-1B
2
TProduct lineT
2.1 TComponentsT
Reactors and filters
SIDAC reactors and filters are drive components. SIDAC reactors and filter components are
used with AC and DC drives.
M
~3 AC




M
= DC
Three-phase AC drive Three-phase DC drive
1 AC drive 3-ph. supply
2 Line reactor
3 RFI suppression filter
4 Output reactor
5 Sine-wave filter
6 DC drive 3-ph. supply
7 Commutating reactor
8 Smoothing reactor
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 7
TTProduct lineTT
2.1 TTComponentsTT
SIDAC line reactors/commutating reactors
SIDAC line reactors and commutating reactors have the following properties:
SIDAC line reactors/commutating reactors are installed upstream of the three-phase DC
drive or three-phase AC drive.
Line reactors/commutating reactors reduce the proportion of low-frequency harmonics on
the line, thereby improving the power factor.
Line reactors/commutating reactors avoid mutual interference caused by low-frequency
noise and protect the converter input. The capacitive DC link of frequency converters is
protected.
SIDAC RFI suppression filters
SIDAC RFI suppression filters have the following properties:
SIDAC RFI suppression filters are installed upstream of the three-phase DC drive or
three-phase AC drive.
RFI suppression filters avoid mutual interference caused by high-frequency interference
currents.
SIDAC output reactors and sine-wave filters
SIDAC output reactors and sine-wave filters have the following properties:
SIDAC output reactors and sine-wave filters are installed downstream of the three-phase
AC drive (frequency converter).
SIDAC output reactors and sine-wave filters increase the service life of the motor and
improve system reliability.
SIDAC smoothing reactors
SIDAC smoothing reactors have the following properties:
SIDAC smoothing reactors are used in the load circuit of DC drives.
SIDAC smoothing reactors reduce the harmonic content for the DC motor as well as the
rate of current rise, thereby enabling the use of DC high-speed circuit breakers.
RFI suppression filter
8 System Manual, 12/2007, HBF 05-002-02-1B
TTProduct lineTT
2.2 TTDevice descriptionTT
2.2 TDevice descriptionT
Device versions
RFI suppression filters are available in single-phase and three-phase versions. Each device
is assigned to a converter requiring radio-interference suppression in respect of the line.
Most devices are equipped with finger-safe terminals and these filters offer IP20 degree of
protection. All filters with flat connectors are designed for IP00 degree of protection.
Application
RFI suppression filters are installed in the line-side supply, upstream of a converter. AC
currents with the mains frequency as the fundamental frequency flow through them.
EMC regulations
Compliance with EMC regulations must be ensured in individual cases by means of an
application-specific measurement. The converter's rating data must be taken into account
when selecting a filter.
Capacitor discharge
The filters feature built-in discharge resistors so that the energy stored in the capacitors can
be quickly reduced, thereby ensuring that the voltage at the terminals drops to within
permissible levels.
However, before carrying out any work on the filter, check that it is safely isolated from the
supply.
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 9
TTProduct lineTT
2.2 TTDevice descriptionTT
RFI suppression filter
10 System Manual, 12/2007, HBF 05-002-02-1B
3
TProduct combinationT
3.1 TFunctional optimizationT
You can make the most of RFI suppression filters by combining them with other products
from the same product line.
Line reactors
To benefit from an additional reduction in phase effects on the system, combine the RFI
suppression filter with a SIDAC line reactor/commutating reactor.
SIDAC output reactors/sine-wave filters
To ensure optimum operation of the RFI suppression filter, a motor-cable length of 50 m is
recommended as the absolute maximum. When using an RFI suppression filter, the
maximum possible motor-cable length can be increased by using SIDAC output reactors or
sine-wave filters.
Application-specific measurement is required
Ensure compliance with EMC regulations in individual cases by means of an application-
specific measurement. This measurement must be requested and ordered separately. The
converter's rating data must be taken into account when selecting a filter.
For more detailed advice, please send an e-mail to: MD_Anfrage@brmr.siemens.de
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 11
TTProduct combinationTT
3.1 TTFunctional optimizationTT
RFI suppression filter
12 System Manual, 08/2005, HBF 05-002-02-1B
4
TFunctionsT
4.1 TMethod of operationT
Functions
RFI suppression filters support the following functions:
RFI suppression filters damp and limit conducted high-frequency
(>150 kHz ... 30 MHz) interference voltages.
Line filters for compliance with EN 55011 Class A are designed to reduce converter
interference voltages to within the limit values for industrial supplies.
Line filters for compliance with EN 55011 Class B are designed to reduce converter
interference voltages to within the limit values for public supplies.
Radio interference level B can generally only be achieved through the additional use
of a line reactor.
These filters also ensure compliance with Class A limit values.
Ensure compliance with EMC regulations in individual cases by means of an application-
specific measurement.
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 13
TTFunctionsTT
4.1 TTMethod of operationTT
RFI suppression filter
14 System Manual, 08/2005, HBF 05-002-02-1B
5
TOperation planningT
5.1 TTransportT
Transport
Products must be transported with care and if possible in their original packaging. If
necessary, suitable and sufficiently dimensioned transport equipment (e.g., rope guides,
lifting beams, etc.) must be used.
5.2 TStorageT
Storage
If the devices are not going to be assembled and put into operation immediately, they must
be stored in a dry and dust-free location in accordance with the permissible storage
conditions below:
Storage temperature -25°C to +85°C
Transport temperature range -25°C to +85°C
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 15
TTOperation planningTT
5.3 TTConfigurationTT
5.3 TConfigurationT
Use the following flowchart to configure use of a RFI suppression filter.
RFI-suppression-filter decision chart
<HV
$Q5),VXSSUHVVLRQILOWHULVQRWQHFHVVDU\
7RPDLQWDLQUDGLRVXSSUHVVLRQOHYHO%
VKLHOGHGPRWRUFDEOHVDUHUHTXLUHG
5),VXSSUHVVLRQILOWHU%()
1R
<HV
<HV
1R
1R
8VHRIDFRQYHUWHU
,QUHVLGHQWLDODUHDV
RURIILFHV
)LOWHU&ODVV%
LQWHJUDWHGLQ
WKHFRQYHUWHU
,QGXVWULDOQHWZRUN
ZLWKUHTXLUHG
UDGLRVXSSUHVVLRQ
OHYHO$
)LOWHU&ODVV$
LQWHJUDWHGLQ
WKHFRQYHUWHU

$Q5),VXSSUHVVLRQILOWHULVQRWQHFHVVDU\
<HV
1R
5),VXSSUHVVLRQILOWHU()
Figure 5-1 Configuring, RFI suppression filter
1) If a Class A RFI suppression filter is already integrated into the converter, it is not possible
to connect another RFI suppression filter in series. This could result in the malfunction of the
converter system and in turn damage the converter or individual components.
RFI suppression filter
16 System Manual, 12/2007, HBF 05-002-02-1B
TTOperation planningTT
5.4 TTEMC-compliant configuration of drive systemsTT
5.4 TEMC-compliant configuration of drive systemsT
The basic rules of EMC
The following 20 rules must be adhered to for the configuration of EMC-compliant drive
systems. Rules 1 to 13 apply on a general level. Rules 14 to 20 are particular important for
limiting emitted interference.
General rules
Rule 1
Ensure that all metal parts of the control cabinet are surface-connected with good
conductivity (not paint on paint). If necessary, use contact washers or serrated lock
washers.
When connecting the control-cabinet door to the control cabinet, use bonding strips that
are as short as possible (also see Rule 20).
Suitable line/commutating reactors are recommended as a means of counteracting low-
frequency phase effects on the system and protecting the converter. You must install
these between the line connection and the RFI suppression filter inside a metal cabinet.
Ensure that the control-cabinet configuration, system configuration and wiring are carried
out in compliance with the rules of EMC-compliant configuration.
On the line side, route the grounding to the motor via the reactor, filter and converter.
 

  
TN M
3~
4EF15
L1
L2
L3
L1’
L2’
L3’
Figure 5-2 Mounting on mounting plate
1 TN system
2 Line reactor
3 Supply system
4 Load
5 Frequency converter
6 Shielded motor cable
7 Metal mounting plate
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 17
TTOperation planningTT
5.4 TTEMC-compliant configuration of drive systemsTT
Grounding systems/machines and grounding drives
The grounding of systems/machines is a protective measure.
In the case of drives, grounding affects emitted interference and interference immunity.
System grounding can be carried out point-to-point or two-dimensionally.
For drives, select two-dimensional grounding, i.e. all the parts of the system that need to
be grounded are connected two-dimensionally or as a mesh.
The motor must be connected using a shielded cable.
Unshielded motor cables must only be used in conjunction with a sine-wave filter.
The shield must be applied to the surface of the motor and converter.
 

Figure 5-3 Shield connection of motor cables inside control cabinet
1 Connect to cabinet enclosure on both sides ensuring good conductivity and maximum
contact area
2 Shielding bus
3 Cable propping bar
Rule 2
When laying the signal cables and power cables, ensure that sufficient space is left
between them (minimum distance: 20 cm).
Avoid data links
Provide separators between electric power cables and signal cables.
Ensure multiple grounding of separators
Rule 3
Connect contactors, relays, solenoid valves, electromechanical hours counters, etc., inside
control cabinet using interference suppression combination, e.g. RC elements, diodes,
varistors. Install the protective circuit directly on the relevant coil.
RFI suppression filter
18 System Manual, 12/2007, HBF 05-002-02-1B
TTOperation planningTT
5.4 TTEMC-compliant configuration of drive systemsTT
Rule 4
Twist unshielded cables from the same electric circuit (go and return conductors) or ensure
that the surface area between the go and return conductors is as small as possible to avoid
unnecessary frame antennae.
Rule 5
Avoid unnecessarily long cables Thus coupling capacities and coupling inductivities are kept
small.
Rule 6
Ground spare cores at both ends. This achieves an additional shielding effect.
Rule 7
Lay cables close to grounded plates to reduce interference injection. You should not,
therefore, route wiring and spare cables randomly within the cabinet; instead, keep them
close to the cabinet enclosure/mounting plates.
Rule 8
Use a shielded cable to connect tachometers, encoders and resolvers. Connect the shield to
the tachometer, encoder or resolver and to the converter, ensuring maximum contact area.
The shield must not be broken at any point, e.g. by intermediate terminals.
Rule 9
Ground the shields of digital signal cables on both sides (sender and receiver), ensuring
maximum contact area and good conductivity.
In the event of poor equipotential bonding between the shield connections, run an
additional equalizing conductor with a cross-section of at least
10 mm² parallel to the shield for the purpose of reducing the shield current.
Multiple grounding of the shields (= connection to cabinet enclosure) is possible. Multiple
grounding of the shields is even possible outside the control cabinet.
Foil shields are at least 5 times less effective than braided shields.
Rule 10
Ground the shields of analog signal cables with good equipotential bonding on both
sides. Good equipotential bonding is achieved if Rule 1 is followed.
If low-frequency interference occurs on the analog lines, e.g.: Speed/measured value
fluctuations as a result of equalizing currents (hum) then connect the analog signal shield
to the signal sink on one side, e.g. analog input of the converter. Ground the other side of
the shield via a capacitor (e.g. 10 nF/100 V Type MKT). The use of the capacitor means
that the shield is connected for high frequencies on both sides.
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 19
TTOperation planningTT
5.4 TTEMC-compliant configuration of drive systemsTT


Cable tie
Shield connection of signal cables
1 Shield clip
2 Cable tie
Rule 11
Only route signal cables into the cabinet from one side
Rule 12
If converters are to be operated by means of an external 24 V power supply, this supply
must not be connected to a number of loads that have been installed separately inside
different control cabinets (hum loops!).
Ensure that there is a separate power supply for each converter.
Rule 13
Avoid interference injection via the line connection.
Connect the converter and PLCs/control electronics to different line supplies.
If only one common line supply is available, isolate the PLCs/control electronics from the
line supply by means of an isolating transformer.
RFI suppression filter
20 System Manual, 12/2007, HBF 05-002-02-1B
TTOperation planningTT
5.4 TTEMC-compliant configuration of drive systemsTT
Rules for limiting emitted interference
Rule 14
An RFI suppression filter must be used to ensure compliance with limit class A or B (EN
55011) even in cases where sine-wave filters or dv/dt filters have been installed between
the motor and the converter.
The issue of whether an additional filter is required for further loads depends on the
controller used and how the rest of the control cabinet is wired.
Rule 15
Ensure that the RFI suppression filter is located in the vicinity of the source.
Ensure that the filter is surface-connected to the control-cabinet enclosure, mounting
plate, etc. A bright, metallic mounting plate is preferable (e.g. stainless steel, galvanized
steel), since the entire contact surface establishes the electrical contact. If a painted
mounting plate is used, the screw positions for mounting the frequency converter and and
RFI suppression filter must be paint-free to ensure electrical contact with the mounting
plate.
Physically separate the input and output cables of the RFI suppression filter.
Rule 16
Use shielded cables to connect all variable-speed motors in order to limit emitted
interference.
Connect both sides of the shields to the relevant enclosures in a manner that ensures low
inductance (short and maximum possible contact area).
Shield the motor cables inside the control cabinet or shield them by means of grounded
separators. Suitable motor cables include, for example, Siemens PROTOFLEX-EMV-CY
(4 x 1.5 mm² ... 4 x 120 mm²) with Cu shield. Cables with steel shields are not suitable.
Use a suitable screwed joint with shield contact on the motor for the shield connection.
Make sure that there is a low-impedance connection between the motor terminal box and
motor housing. If necessary, use an additional flexible grounding wire. The motor terminal
box must not be made of plastic.
1 Motor terminal box
2 Metric/heavy-gauge threaded joint
Shield connection on motor
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 21
TTOperation planningTT
5.4 TTEMC-compliant configuration of drive systemsTT
Rule 17
Install a line reactor between the RFI suppression filter and the line supply.
Rule 18
Physically separate the power supply cable and motor cables, e.g. by using grounded
separators.
Rule 19
The shield between the motor and converter must not be broken at any point as a result of
integrating components such as output reactors, sine-wave filters, dv/dt filters, fuses and
contactors. Assemble the components on a mounting plate, which will simultaneously serve
as the shield connection for the incoming and outgoing motor cables. It may be necessary to
use grounded separators for the purpose of shielding the components.
Rule 20
To limit interference radiation (particularly in the case of limit class B), all cables
connected to the control cabinet from the outside must be shielded in addition to the
power supply cable.
When mounting inside a cabinet, install the RFI suppression filter (and if necessary a
reactor) in the direct vicinity of the converter.
When laying cables, keep them as short as possible.
When connecting the power supply cable to the RFI suppression filter (or reactor), ensure
that it is kept separate from other cables so that no interference can be injected into the
interference-suppressed power supply cable that would partially cancel out the effects of
the RFI suppression filter.
Connect the housing of the converter and RFI suppression filter with low resistance for
high-frequency interference currents. This can be achieved by placing the converter and
RFI suppression filter on the same mounting plate. Ensure that the converter and RFI
suppression filter are surface-connected to this mounting plate. The best solution here is
to use a bare metal mounting plate (e.g. made of stainless steel or galvanized sheet-
steel), since the total contact surface establishes the electrical contact. If a painted
mounting plate is used, the screw positions for the converter and RFI suppression filter
must be paint-free to ensure electrical contact with the mounting plate.
RFI suppression filter
22 System Manual, 12/2007, HBF 05-002-02-1B
6
TAssemblyT
6.1 TAssemblyT
Assembly/Installation
Install the RFI suppression filter on a bare metal plate.
Proceed as follows to install the RFI suppression filter inside a control cabinet:
Install the RFI suppression filter (and reactor, if required) directly upstream of or next to
the converter.
When laying cables, keep them as short as possible.
When connecting the power supply cable to the RFI suppression filter (or reactor), ensure
that it is kept separate from other cables so that no interference can be injected into the
interference-suppressed power supply cable that would partially cancel out the effects of
the RFI suppression filter.
Some installation examples are illustrated below:
4EF15
L1´L2’L3’
L1 L2 L3
< 0,5 m
M
3
~
L1´L2’L3’
L1 L2 L3
< 0,5 m
M
3
~
4EF15
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 23
TTAssemblyTT
6.1 TTAssemblyTT
Boring dimensions
8
4 x
8
4 x
8
4 x
b
a
a
b
b
a
Figure 6-1 Boring dimensions
RFI suppression filter
24 System Manual, 12/2007, HBF 05-002-02-1B
TTAssemblyTT
6.1 TTAssemblyTT
Dimensions (mm) a (mm) b (mm)MLFB
4EF1510-1AA00 133 x 50.8 x 44.5 60.4 101.6
4EF1510-2AA00 99 x 84.0 x 68.0 95.2 50.8
4EF1510-3AA00 121 x 86.0 x 61.0 100 70
4EF1510-4AA00
4EF1510-5AA00
4EF1510-6AA00 156 x 86.0 x 81.0 100 70
4EF1510-1AA10 133.7 x 51.4 x 63 38 155
4EF1510-2AA10 199.5 x 46.4 x 70 38 221
4EF1510-3AA10 199.5 x 46.4 x 83 38 221
4EF1510-4AA10 200.0 x 57.0 x 90 35 255
4EF1510-5AA10
4EF1510-6AA10 200.0 x 58.0 x 141.5 35 255
4EF1510-7AA10 240.0 x 80.0 x 135 60 255
4EF1510-8AA10 240.0 x 90.0 x 150 60 255
4EF1512-7AA10 240.0 x 90.0 x 150 65 255
4EF1511-0AA10 400 x 110 x 220 85 415
4EF1511-1AA10 200 x 140 x 110 155 145
4EF1511-2AA10 230 x 140 x 116 165 170
4EF1511-3AA10
4EF1511-4AA10
4EF1511-5AA10 300 x 210 x 140 235 240
4EF1511-6AA10
4EF1511-7AA10 200 x 50 x 80 25 215
4EF1511-8AA10
4EF1512-8AA10 250 x 60 x 150 35 265
4EF1512-0AA10
4EF1512-1AA10 300 x 60 x 150 35 315
4EF1512-2AA10 300 x 80 x 150 55 315
4EF1512-3AA10 300 x 80 x 200 55 315
4EF1512-4AA10 350 x 90 x 200 65 365
4EF1512-5AA10
4EF1512-6AA10 400 x 110 x 220 85 415
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 25
TTAssemblyTT
6.2 TTInstallation instructionsTT
6.2 TInstallation instructionsT
EMC-compliant configuration
To ensure problem-free operation of the filter, the configuration of the drive system must be
EMC-compliant. The basic rules for the EMC-compliant configuration of drive systems are
outlined in the previous section.
Mounting and interference suppression
RFI suppression filters feature a metallic housing. The 4 screws used for screw mounting
ensure:
Mechanical fastening
That the RFI suppression filter is shielded by means of a generous contact-area
connection to the reference ground.
High-frequency interference currents
The housing of the converter and RFI suppression filter must be connected with low
resistance for high-frequency interference currents. To achieve this, proceed as follows:
Install the converter and RFI suppression filter on a single bare metal mounting plate
(stainless steel or galvanized sheet-steel). The total contact surface establishes the
electrical contact.
If a painted mounting plate is used, ensure that the screw positions for the converter and
RFI suppression filter are paint-free so that electrical contact with the mounting plate can
be ensured.
Note
Shielded cable for motor connection
If an output filter is not used in conjunction with a frequency converter, the motor must be
connected by means of a shielded cable. Ensure that the shield makes full surface
contact with the motor and converter.
RFI suppression filter
26 System Manual, 12/2007, HBF 05-002-02-1B
7
TConnectionT
7.1 TPrerequisites and definitionsT
Use in TN systems
RFI suppression filters must only be used in TN systems (grounded neutral point).
Definition: TN system
TN systems have one point directly grounded. The exposed conductive parts of the electrical
installation are connected to this point by protective conductors.
There are 3 different subsystems:
TN-S system
TN-C system
TN-C-S system
Distribution systems
The figure below shows the naming structure used for distribution systems:
7 1   &  6 
6 ,Q DGGLWLRQ D SDUW RI
V\VWHPIHDWXUHVVHSDUDWH1
DQG3(FRQGXFWRUV
3RZHUVXSSO\
,LQVXODWHG
7JURXQGHG
,QVWDOODWLRQERG\
1FRQQHFWHGWR3(
7GLUHFWO\JURXQGHG
1DQG3(
&FRQQHFWHG
6VHSDUDWH
Figure 7-1 Naming of distribution systems
PE connection
For details about this and grounding, please see "EMC-compliant configuration of drive
systems".
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 27
TTConnectionTT
7.2 TTConnection optionsTT
Materials to be used
The following materials must be used for the connection:
Busbar material: Copper
Bolt: Strength class 8.8 or higher in accordance with ISO 898 Part 1, tZn (hot-galvanized)
anti-corrosion protection
Nut: Strength class 8 or higher in accordance with ISO 898 Part 2, tZn (hot-galvanized)
anti-corrosion protection
Spring element on bolt and nut side:
Clamping washer to DIN 6796 Part 2, with anti-corrosion protection
Lubricant: based on MoS
2
7.2 TConnection optionsT
Connection via connection bolts
The tightening torques given in the following table apply to current-carrying and PE
connections to the filter, in cases where contact is made via threaded pins:
Nominal size:
Threaded pins
Tightening torque in Nm
(Tolerance details for set values)
M4 1.2 (1.10 ... 1.30)
M5 2.0 (1.9 0... 2.10)
M6 3.0 (2.85 ... 3.15)
M8 6.0 (5.70 ... 6.30)
M10 10.0 (9.0 ... 11.0)
M12 15.5 (14.0 ... 17.0)
Connection via terminal blocks
Use terminal blocks for the line-supply connection and the connection on the load side of the
filter. The tightening torques given in the following table apply:
Cross-section of connecting terminals Tightening torque in Nm
Up to 4 mm 0.5 ... 0.8
2
Up to 10 mm 1.2 ... 1.5
2
Up to 16 mm 2.0 ... 2.3
2
Up to 25 mm 4.0 ... 4.5
2
Up to 35 mm 3.2 ... 3.7
2
Up to 50 mm 6.0 ... 8.0
2
Up to 95 mm 15 ... 20
2
RFI suppression filter
28 System Manual, 12/2007, HBF 05-002-02-1B
TTConnectionTT
7.2 TTConnection optionsTT
Connection via busbars
Copper busbars sometimes have to be used as connection elements in conjunction with
EMC filters with rated currents >100 A. To ensure the necessary surface pressure with the
busbars, the tightening torques given in the following table apply:
Nominal size: Bolt/nut Tightening torque in Nm
M8 15
M10 30
M12 60
Flat connectors
The following graphic illustrates a flat connector:





Figure 7-2 Flat connector
Current A/Current Ithmax
Up to 250 A Up to 600 A Up to 1600 A
1 Hexagon bolt, DIN EN ISO 4017, strength class 8.8 M8 M10 M12
2 Hexagon bolt, DIN EN 24032, strength class 8 M8 M10 M12
3 Clamping washer, DIN 6796 8.4 x 16 10.5 x 20 13 x 29
4 Spring lock washer, DIN 128 8.2 x 14.4 10.5 x 17.4 12.7 x 21.1
5 Flat connector
Without Tightening torque, Nm 15 30 60
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 29
TTConnectionTT
7.2 TTConnection optionsTT
RFI suppression filter
30 System Manual, 12/2007, HBF 05-002-02-1B
8
TCommissioningT
8.1 TOperationT
Operation
The following must be observed when operating the RFI suppression filter:
Compliance with the rating data on the rating plate is necessary if proper use of the RFI
suppression filter is to be ensured.
If you notice any deviations from normal operation (increased power consumption,
temperature or levels of vibration, unusual noises or odors, monitoring devices tripping,
etc.), the device is probably no longer functioning correctly.
In such an event, you must notify the responsible service personnel immediately to
prevent faults that could result in personal injury or material damage.
If in doubt, shut down the equipment concerned immediately.
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 31
TTCommissioningTT
8.1 TTOperationTT
RFI suppression filter
32 System Manual, 08/2005, HBF 05-002-02-1B
9
TService and maintenanceT
9.1 TService/MaintenanceT
You must comply with the following safety regulations before commencing work on electrical
installations:
1. Isolate from the supply
2. Secure against accidental restart
3. Check safe isolation from supply
4. Grounding and short-circuiting
5. Cover all nearby live parts
Checking safe isolation from supply
WARNING
Danger, high voltage
Danger of death or serious injury. Before commencing work on a RFI suppression filter, you
must check that it is safely isolated from the supply (e.g., using a meter).
V
V
4EF15
L2’
L3’
L1’
Figure 9-1 Measuring voltage levels
Service
The following service operations should be carried out regularly (preferably on an annual
basis):
General visual check
Remove excessively large dust deposits using compressed air (max. 2.5 bar) and a
suitable vacuum cleaner.
Tighten up connection elements in accordance with the specified torques.
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 33
TTService and maintenanceTT
9.1 TTService/MaintenanceTT
RFI suppression filter
34 System Manual, 08/2005, HBF 05-002-02-1B
10
TTechnical specificationsT
10.1 TRating dataT
Rating data
Operating voltages 1 AC 250 V, 50/60 Hz
3 AC 480 V, 50/60 Hz
3 AC 520 V, 50/60 Hz
Rated frequency 50/60 Hz
Operating ambient air temperature 40°C
10.2 TAdditional technical specificationsT
Additional technical specifications
Test voltage 1770 V (2240 V) DC, 2 s phase/phase
2700 V DC, 2 s phase/housing
Overload 1.5 ILn for 3 mins/hour or
2.5 ILn for 30 s/hour
Climatic category 25/100/21 (–25°C/+100 °C/21 days humidity test)
The following applies to filters 4EF15 10-1AA10 ... 4EF15 10-
8AA10, 4EF15 12-7AA10:
25/85/21 (–25°C/+85 °C/21 days humidity test)
Environmental testing in accordance with EN 60068-1
Applicable standards
EN133200
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 35
TTTechnical specificationsTT
10.2 TTAdditional technical specificationsTT
RFI suppression filter
36 System Manual, 08/2005, HBF 05-002-02-1B
11
TCircuit diagrams and damping curvesT
11.1 TCircuit diagramsT
L
N
PD30_00022
L
N
LOAD
LINE
4EF1510-3AA00 4EF1510-5AA00
4EF1510-4AA00 4EF1510-6AA00
L
N
PD30_00023
L
N
LINE LOAD
4EF1510-1AA00 4EF1510-2AA00
PD30_00024
L1
L2
L3
L1
L2
L3
LOAD
LINE
4EF1511-7AA10 4EF1511-8AA10
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 37
TTCircuit diagrams and damping curvesTT
11.1 TTCircuit diagramsTT
4EF1512-0AA10 4EF1512-4AA10
PD30_00025
L1
L2
L3
L1
L2
L3
LOAD
LINE
4EF1512-1AA10 4EF1512-5AA10
4EF1512-2AA10 4EF1512-6AA10
4EF1512-3AA10 4EF1512-8AA10
PD30_00026
L1
L2
L3
L1
L2
L3
LOAD
LINE
4EF1510-6AA10 4EF1510-1AA10
4EF1510-7AA10 4EF1510-2AA10
4EF1510-8AA10 4EF1510-3AA10
4EF1512-7AA10 4EF1510-4AA10
4EF1510-5AA10
L1
L2
L3
L1
L2
L3
PD30_00027
LINE LOAD
4EF1511-4AA10 4EF1511-1AA10
4EF1511-5AA10 4EF1511-2AA10
4EF1511-6AA10 4EF1511-3AA10
4EF1511-0AA10
L1
L2
L3
PD30_00028
L1
L2
L3
LINE LOAD
RFI suppression filter
38 System Manual, 12/2007, HBF 05-002-02-1B
TTCircuit diagrams and damping curvesTT
11.2 TTDamping curvesTT
11.2 TDamping curvesT
Insertion loss (CISPR 17, typical values at Z = 50 Ω)
____________________: unsymmetrical, adjacent branches terminated
_ . _ . _ . _ . _ . _ . _ . _: common mode, all branches in parallel (asymmetrical)
_ _ _ _ _ _ _ _ _ _ _ _ _: differential mode (symmetrical)
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 39
TTCircuit diagrams and damping curvesTT
11.2 TTDamping curvesTT
Insertion loss (CISPR 17, typical values at Z = 50 Ω)
____________________: unsymmetrical, adjacent branches terminated
_ . _ . _ . _ . _ . _ . _ . _: common mode, all branches in parallel (asymmetrical)
_ _ _ _ _ _ _ _ _ _ _ _ _: differential mode (symmetrical)
RFI suppression filter
40 System Manual, 12/2007, HBF 05-002-02-1B
TTCircuit diagrams and damping curvesTT
11.2 TTDamping curvesTT
Insertion loss (CISPR 17, typical values at Z = 50 Ω)
____________________: unsymmetrical, adjacent branches terminated
_ . _ . _ . _ . _ . _ . _ . _: common mode, all branches in parallel (asymmetrical)
_ _ _ _ _ _ _ _ _ _ _ _ _: differential mode (symmetrical)
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 41
TTCircuit diagrams and damping curvesTT
11.2 TTDamping curvesTT
Insertion loss (CISPR 17, typical values at Z = 50 Ω)
____________________: unsymmetrical, adjacent branches terminated
_ . _ . _ . _ . _ . _ . _ . _: common mode, all branches in parallel (asymmetrical)
_ _ _ _ _ _ _ _ _ _ _ _ _: differential mode (symmetrical)
RFI suppression filter
42 System Manual, 12/2007, HBF 05-002-02-1B
A
TAppendixT
A.1 TLatest informationT
Your regional contact for low-voltage switchgear will be happy to help you with any queries
you have regarding RFI suppression filters. A list of contacts and the latest version of the
manual are available on the Internet at:
http://www.siemens.de/lowvoltage/manuals
Contacts
For all technical queries, please contact:
Technical Assistance:
Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET)
Fax: +49 (0) 911-895-5907
E-mail: technical-assistance@siemens.com
Internet: www.siemens.de/lowvoltage/technical-assistance
Technical Support:
Telephone: +49 (0) 180 50 50 222
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 43
TTAppendixTT
A.2 TTCorrection sheetTT
A.2 TCorrection sheetT
Correction sheet
FROM (please complete):
Name
TO: Company/Department
SIEMENS AG
A&D CD MM 3
92220 Amberg
Address
Phone
Fax
Fax: 09621 / 80-3337
4EF15 RFI Suppression Filter Manual
Have you noticed any errors while reading this manual?
If so, please use this form to tell us about them.
We welcome comments and suggestions for improvement.
RFI suppression filter
44 System Manual, 12/2007, HBF 05-002-02-1B
B
TIndexT
B.1 TIndexT
Index
Output reactor 2-2; 3-1
EMC regulations 2-2; 5-3 ff
Discharge 2-3
Grounding 5-3; 5-4; 5-8; 9-1
Radio interference level 4-1; 5-2
Commutating reactor 2-2; 3-1; 5-3
Mounting plate 5-3; 5-7; 6-4
Motor 5-6; 5-8; 6-4
Line connection 5-6
Line/Supplies 5-6; 7-1
Line reactor 2-2; 3-1; 4-1; 5-8
Line harmonics 2-2
Standard 1-1; 10-1
Shield connection 5-4 5-8; 6-4
Degree of protection 2-3
Sine-wave filter 2-2
Converter 2-3; 4-1; 5-2; 5-3; 5-5; 5-7; 6-1
Cabling 7-1; 7-2
RFI suppression filter
System Manual, 12/2007, HBF 05-002-02-1B 45
TTIndexTT
B.1 TTIndexTT
RFI suppression filter
46 System Manual, 08/2005, HBF 05-002-02-1B