Moeller series products > > > > > Interchangeable trip module makes changing tripping characteristics a snap, even after wiring Adjustable thermal and magnetic trip settings See Next Page for UL/CSA Application Ratings Guide Overcurrent, short-circuit protection and motor switching functions are combined in one compact unit; all functions are ambient compensated and phase failure sensitive Worldwide approvals, including UL 508/CSA 22.2 No. 14 One frame size simplifies engineering and reduces stocking cost Manual motor controller with adjustable magnetic and thermal standard trip module Adjustable Adjustable thermal trip setting range set current of to motor magnetic FLC trips UL/CSA Shortcircuit current rating kA RMS sym @ Manual Motor Controllers C 480 V AC 600 V AC (yellow dial) (red dial) [A] [A] 65 42 0.4 - 0.6 5-8 65 42 0.6 - 1 8 - 14 "Typical" Maximum Horsepower Typical Single Phase [HP] 115V 200V Typical Three Phase [HP] 240V 200V 240V See note below 480V 1/2 600V 1/2 Auxiliary Contacts Catalog NO NC Number 0 0 PKZ2/ZM-0,6 0 0 PKZ2/ZM-1 13 3/4 1 0 0 PKZ2/ZM-1,6 1/2 1 11/2 0 0 PKZ2/ZM-2,4 65 42 1 - 1.6 14 - 22 65 42 1.6 - 2.4 20 - 35 65 42 2.4 - 4 35 - 55 18 1/4 13 1 1 2 3 0 0 PKZ2/ZM-4 65 42 4-6 50 - 80 1/4 1/2 1/2 11/2 11/2 3 5 0 0 PKZ2/ZM-6 110 18 16 1/2 65 42 6 - 10 80 - 140 1/2 1 11/2 2 3 5 71/2 0 0 PKZ2/ZM-10 65 42 10 - 16 130 - 220 1 2 2 3 5 10 10 0 0 PKZ2/ZM-16 65 42 16 - 25 200 - 350 2 3 3 5 71/2 20 25 0 0 PKZ2/ZM-25 65 42 24 - 32 275 - 425 2 5 5 10 10 20 30 0 0 PKZ2/ZM-32 65 42 32 - 42 350 - 500 3 5 71/2 10 15 30 30 0 0 PKZ2/ZM-40 Price Horsepower ratings shown in the table are for reference only. The final selection of the manual starter depends on the actual motor full load current and service factor on the motor nameplate. Overload should be set at motor FLA full load current and is calibrated to 1.15 S.F. Specified values to NEC table 430-150. Ordering Instructions 1 2 3 4 C50 Determine the motor FLA and Service Factor. Use the application rating guide on next page. Locate the desired manual motor controller. See pages C53 - C59 for auxiliaries and accessories. moellerNA.com * eaton.com All types have adjustable dial for setting motor full load current. Trip current is 125% of set value. For motors with a service factor (SF) of 1.0, set dial to 90% of motor full load current. Rating applies to manual motor controller only. Does not apply to combination motor starter. Discount Code A31 MAIN-CAT-1210 Dimensions Moeller series products PKZ2 Manual Motor Controller with Trip Module Dimensions are in millimeters. Not intended for manufacturing purposes. PKZ2/ZM-... 133.5 109 M4 44.5 45 83 105 105 + 0 68 6 62 15 19 62.5 71.5 Standard Auxiliary Contacts Trip-indicating Auxiliary Contacts NHI...-PKZ2 AGM2-11-PKZ2 18 18 18 NHI22 NHI11 68 31.5 AGM 44 77 Remote Operator A-PKZ2... / U-PKZ2... RE-PKZ2... / RS-PKZ2... 105 Shunt / Undervoltage Release 105 Manual Motor Controllers 105 45 C 18 44 109 113 36 45 109 122 126 C72 moellerNA.com * eaton.com MAIN-CAT-1210