Specifications are subject to change without notice (12.09.07) 1
Input current Output current Switch position Type no.
0- 5 AAC 4 - 20 mA 5 E83-20 50
0-10 AAC 4-20 mA 10 E83-20 50
0-15 AAC 4 - 20 mA 15 E83-20 50
0-20 AAC 4-20 mA 20 E83-20 50
0-25 AAC 4 - 20 mA 25 E83-20 50
0-30 AAC 4-20 mA 30 E83-20 50
0-50 AAC 4 - 20 mA 50 E83-20 50
Monitoring Relays
AC Current Transformer
Type E 83-20-50
7 input ranges in one unit: 0 - 5 AAC
0-10 AAC
0-15 AAC
0-20 AAC
0-25 AAC
0-30 AAC
0-50 AAC
Output 4-20 mADC
Easy interface to PLC or setpoint relays
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm small Euronorm housing
Product Description
Small AC current metering
transformer with 7 knob se-
lectable ranges. Output from
the transformer is 4-20
mADC in accordance with
IEC 60381-1. Can be used
with relays DIB01, PIB01,
DIC01 or PIC01 or directly
connected to a PLC.
Power supply ON is indicat-
ed by a green LED.
12 mm hole for isolated cur-
rent carrying wire makes it
suitable for most applica-
tions. For mounting on DIN-
rail or directly on surface by
screws.
Type
Output
Input current (highest range)
Ordering Key
Type Selection
Input Specifications
Current range 0-5AAC 0 - 10 AAC 0 - 15 AAC 0 - 20 AAC
Max. current (continuously) 100 AAC 100 AAC 100 AAC 100 AAC
Max. overload current (t = 30 s) 300 AAC 300 AAC 300 AAC 300 AAC
Overvoltage category III (IEC 60664) III (IEC 60664) III (IEC 60664) III (IEC 60664)
Frequency range 40 Hz - 1 kHz 40 Hz - 1 kHz 40 Hz - 1 kHz 40 Hz - 1 kHz
E83-20 50
Current range 0-25 AAC 0 - 30 AAC 0 - 50 AAC
Max. current (continuously) 100 AAC 100 AAC 100 AAC
Max. overload current (t = 30 s) 300 AAC 300 AAC 300 AAC
Overvoltage category III (IEC 60664) III (IEC 60664) III (IEC 60664)
Frequency range 40 Hz - 1 kHz 40 Hz - 1 kHz 40 Hz - 1 kHz
2Specifications are subject to change without notice (12.09.07)
Mode of Operation
The E 83-20 is a small AC
current metering transformer
with standardized 4-20
mADC output. This makes it
very useful as an AC current
interface to a PLC with 4-20
mADC input.
Used with relays DIB01,
PIB01, DIC01 or PIC01, one
or moresetpoints can moni-
tor the current and signal
alarm.
In the 5 A range the E 83-20
is often used as a 4-20
mADC signal converter for
larger standard AC current
transformers with 5 AAC
secondaryoutput.
The metered conductor is
drawn through the central
hole of the current metering
transformer.It is possible to
measure currents below the
nominal range by drawing
the conductor through the
hole several times. If the
conductor is drawn through
the central hole e.g. 5 times,
the transformer will register
5AAC when the current in
the conductor is 1 AAC.
Resistance/Voltage Curve Input/Output Curve
20
16
12
8
4
50 100 Input
(% of range)
Output
(mADC)
Max. load resistance versus loop voltage
(V)
Loop voltage
Max. R load ()
Output Specifications
Output current (sink)
4-20 mADC
Maximum output current 30 mADC
Tolerance of output current
@50 Hz ± 2%
Temperature variation ± 400 ppm/°C
Frequency variation 10 ppm/Hz
Power supply (loop voltage) 10-40 VDC
General Specifications
Power ON delay <2s
Reaction time T<200 ms
Indication for
Power supply ON LED, green
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature -20° to +50°C (-4° to +122°F)
Housing
Dimensions 22.5 x 56 x 49 mm
Material ABS
Weight 70 g
Approval UL
CE Marking Yes
EMC Electromagnetic Compatibility
Immunity According to
EN 61000-6-1
(tolerance of output current:
± 2%)
According to
EN 61000-6-2
(tolerance of output current:
± 5%)
Emission According to
EN 61000-6-3
E83-20-50
Specifications are subject to change without notice (12.09.07) 3
E83-20-50
Dimensions
22.5
47.4
15
4 x ø3.4
Ø 12
20
55.4
56
49
Wiring Diagram
1
Rload
I~⁄⁄ I
2
ø12