209 Series Magnetic Circuit Protectors Introduction * 187 249 Power Selector System * 189 Multi-Pole * 191 Configurations * 193 Operating Characteristics * 195 Delay Curves * 196 Specifications * 199 Decision Tables * 201 209/219/229/249/279 Series Hydraulic Magnetic Circuit Protectors INTRODUCTION The 209, E-Frame circuit breaker combines power switching with accurate, reliable circuit protection in a compact single or multipole unit. The unit is ideal for branch circuit applications such as EDP, air conditioners, panel boards and lighting controls. The 209 is actually a family of circuit breakers available in one through six pole assemblies with a variety of configurations and terminal styles to meet your application needs. First in this family is the 209, a general purpose E-Frame circuit breaker which complies with UL Standard 489. Other members of the family include the 219, for manual controller applications, which complies to UL Standard 508, the 229, for supplementary protectors applications, which complies to UL Standard 1077, and the 299, a Special Construction version. 187 209 Series - Introduction Utilizing the hydraulic-magnetic principle, the 209 family adapts itself to local applications and environments. Temperature conditions, which affect fuses and other thermal devices, are not a concern. The magnetic /ampere turn principle minimizes nuisance tripping due to temperature variations. Inrush currents, due to ferroresonant transformers, lamps and capacitive filters, are now becoming more significant. Recognizing the need for this type of protection, Airpax offers the unique inertial delay which is standard for all 50/60Hz time delay units, but may be deleted where inrush is not a problem. No extra cost or special order is required. The 209 family of circuit breakers withstands high pulses without tripping or affecting normal delay curves. This performance, however, does not derate or sacrifice protection. http://airpax.sensata.com 209 (E-frame) 209/219/229 MAGNETIC CIRCUIT PROTECTORS Terminal Style 209 E-Frame circuit breakers may be specified with either screw terminals, stud or solderless connectors. DIMENSION "A" Number of Poles Dimensions "A" 1 1.026 .010 [26.06 3.30] 2 2.072 [52.63] Max 3 3.108 [78.94] Max 4 4.144 [105.26] Max 5 5.180 [131.57] Max 6 6.216 [157.89] Max A choice of front or back connected terminal styles is available. The back connected terminal style is available with stud terminals only. Front terminal style is available with either screw terminals or solderless connectors. Refer to Sixth Decision Table for front connected terminal information. Barriers for back connected terminal styles are supplied on multi-pole units only. Line and load connections may be made to either terminal and terminals will be identified as shown. Front Connected Solderless Connector (Back Mounted) .700 [17.78] MAX. A .562 [14.27] 2.610 [66.29] .220 [5.59] 1.220 [30.99] .125 [3.18] .530 [13.46] .485 [12.32] +.015 -.005 +0.38 -0.13 2.250 [57.15] 2.750 [69.85] 5.800 [147.32] 2.156 [54.76] 35 1.125 [28.58] 1.375 [34.92] .200 [5.08] 35 4.750 [120.65] 4.844 [123.04] 2.375 [60.32] 2X 6-32 MTG. INSERT .160 MIN. SCREW DEPTH [4.06] .310 MAX. SCREW DEPTH [7.87] 3.0 MM ISO THD. OPTIONAL Back Connected Stud Terminal (Front Mounted) A .220 [5.59] .700 [17.78] MAX. .220 [5.59] 2.610 [66.29] 3.550 [90.17] 2.156 [54.76] 2.750 [69.85] 1.375 [34.92] 2.250 [57.15] +.015 -.005 +0.38 -0.13 1.125 [28.58] 5.125 [130.18] 3.550 [90.17] 4.750 [120.65] 2X 6-32 MTG. INSERT .160 MIN. SCREW DEPTH [4.06] .310 MAX. SCREW DEPTH [7.87] 3.0 MM ISO THD. OPTIONAL Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. 0-50 AMPS 10-32 STUDS .625 .062 [15.88 1.57] LONG 51-100 AMPS 1/4-20 STUDS .750 .062 [19.05 1.57] LONG IELR Series - Introduction 188 249 POWER SELECTOR BREAKER SYSTEM The 249 Power Selector Breaker System combines magnetic-hydraulic branch circuit overload protection and a power system selector switch in one device. The 249 is designed to allow selection of any one of two, three or four independent power systems. This is accomplished with fool-proof sliding-gate handle covers. The number of sliding covers is one less than the number of power systems. With this arrangement, it is impossible to switch "ON" more than one power system at a time. Since the 249 Power Selector Breaker System is listed as a Branch Circuit Breaker per UL 489 and power switching is accomplished by UL listed breakers, it is usually not necessary to include additional branch service protection. Trip Time Delay Three inverse time delays are available to permit close coordination with various loads. Delays 51 and 61 are short delays for electronic loads. Delays 52 and 62 are medium delays for mixed loads. Delays 53 and 63 are long delays for motor loads. Current and Voltage Ratings Single pole and multi-pole breaker ratings are available up to 100 amperes, 240Vac or 125Vdc. The special configuration for Marine use has a 120V/240Vac rating for current rating up to 100 amperes. Master Drawing Standard circuit breaker terminal and configurations are shown. For other types, consult factory. Standard options available include terminals for front or back connections, choice of trip time delay, current ratings to 100 amperes and single or multi-pole sections. 189 209 Series - 249 Power Selector Breaker System http://airpax.sensata.com 209 (E-frame) 249 Master Drawing (SEE TABLE) 6-32 MTG. Insert .160 [4.06] MIN. screw depth .310 [7.87] MAX. screw depth (TYP) .562 [14.27] 2.610 [66.29] 1.220 [30.99] .125 [3.18] .530 [13.46] .200 (TYP.) [5.08] .485 [12.32] +.015 2.250 -.005 +0.38 [57.15] -0.13 2.156 [54.76] 2.750 [69.85] 5.800 [147.32] 1.125 [28.58] 1.375 [34.92] 4.750 [120.65] 209/219/229/279 .800 [20.32] MAX. Width 4.844 [123.04] 2.375 [60.32] .220 [5.59] 1.026 [26.06] (TYP.) 4X MTG. SLOT Clearance for 8-32 Screw (TYP.) 10 - 32 or 1/4 - 20 Screw Terminals 1/4 - 20 Studs .390 [9.91 3.550 2.610 [90.17] [66.29] .375 [9.53] 2.156 [54.76] 5.125 [130.18] 3.550 [90.17] Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. 4.750 [120.65] (REF) .750 [19.05] DIMENSIONS Number of Poles Width 9 9.324 [236.83] Max 8 8.288 [210.52] Max 6 6.216 [157.89] Max 4 4.144 [105.26] Max 2 2.072 [52.63] Max 209 Series - 249 Power Selector Breaker System 190 209/219/229 MULTI-POLE CIRCUIT PROTECTORS Common-Trip Construction All multi-pole protectors contain an internal trip bar which opens all poles in the event of an overload in any pole. Handles are ganged externally for simultaneous actuation. Three Phase, Four Pole Includes Control Protector Remote shutdown of equipment is sometimes necessary or desirable in today's sophisticated equipment. The 219 four pole assembly fills this need for three phase operation. Three of the four poles are designed for the circuit's proper operating current and over-current protection. The fourth pole may be designed for instantaneous tripping by logic circuitry, interlocks or from a manual remote site or control. The control power required would be quite low, with voltages from 5 to 125Vdc, or 5 to 240Vac available. The fourth pole construction is optional. It may be either series, shunt or relay, depending on the application required. When specifying, both the minimum trip voltage and Hz are required. Factory consultation is readily available. Individual poles may differ in ratings, delays and configurations, providing an almost limitless number of combinations. Multi-pole protectors (up to 6 poles) easily satisfy special modern day circuitry. Series, shunt, relay and auxiliary switch construction add to the versatility of design engineering. Airpax's sales engineering force is ready to assist in proper unit selection, both for equipment protection and economical design. Front Connected Solderless Connector (Back Mounted) 2.072 (52.63) MAX. .700 [17.78] MAX. .562 [14.27] .530 [13.46] 2.610 [66.29] .220 [5.59] 1.220 [30.99] .125 [3.18] .200 [5.08] .485 [12.32] 2.250 [57.15] +.015 -.005 +0.38 -0.13 2.156 [54.76] 2.750 [69.85] 5.800 [147.32] 1.125 [28.58] 1.375 [34.93] 4.750 [120.65] 4X 6-32 MTG. INSERT .160 MIN. SCREW DEPTH [4.06] .310 MAX. SCREW DEPTH [7.87] 3.0 MM ISO THD. OPTIONAL 10 - 32 or 1/4 - 20 Screw Terminals .390 [9.91] See available mounting brackets below 4.844 [123.04] 2.375 [60.32] .220 [5.59] Slotted Mounting Bracket terminal codes -2, -3, -5, -7, -3M, -5M, -7M 2X MTG. SLOT CLEARANCE FOR 8-32 SCREW 1.026 [26.06] Short Mounting Bracket terminal codes -2C, -3C, -5C, -7C .145 [3.68] SCALE: 3/1 191 209 Series - Multi-Pole SCALE: 3/1 http://airpax.sensata.com 209 (E-frame) DIMENSIONS Number of Poles Width 1 1.026 .010 [26.06 .254] 2 2.072 [52.63] Max 3 3.108 [78.94] Max 4 4.144 [105.26] Max 5 5.180 [131.57] Max 6 6.216 [157.89] Max Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters Caution: Elongation of mounting holes may be necessary for units with more than 6 poles and units up to 12 poles due to tolerance compounding 209 Series - Multi-Pole 192 229D (MARINE) & 279 (COMMUNICATION) 209/219/229 CONFIGURATIONS UL-1500 Ignition Protection The 229D family is certified to UL-1500 which covers Ignition Protected circuit protectors. This specification requires devices to be used in accordance with the requirements of U.S. Coast Guard and Fire Protection Standard for Pleasure and Commercial Motor Craft, ANSI/ MFPA No. 302. Series Trip The most popular configuration for magnetic protectors is the series trip, where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional overcurrent protection, it's simultaneously used as an ON-OFF switch. The ratings available are 100 amperes or less at 65Vdc or 240Vac. Maximum IC, 1000 amperes. Consult factory for application details. SEE NOTE A LINE The 299D series is available with interlocking to prevent on board and shore power being used simultaneously. LOAD Combination of ON-OFF switching the protection function offers a simplified solution for your electrical systems. 3.550 [90.17] UL 489A Communications Equipment Protection The 279 Series complies with the requirements of UL 489A, Circuit Breakers for use in Communication Equipment, meeting the need for protection at higher DC voltages. The available ratings are 100 amperes or less at 160Vdc. Maximum short circuit interrupting current is 5000 amperes. The 279 series available only in a series trip configuration. .750 [19.05] Please consult Sensata for specific application details. Auxiliary Switch This is furnished as an integral part of a series pole in single or multi-pole assemblies. Isolated electrically from the protector's circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector's ON-OFF status. (Applies to Series Trip Only) C NO NC 3.550 [90.17] 3.128 MAX. [79.45] REF. FROM BACK OF MOUNTING PANEL. .295 [7.49] .110 [2.79] 1.563 [39.70] -IREC4 -IREG4 Quick Connect Terminals .312 [7.92] .750 [19.05] 193 209 Series - Configurations .187 [4.75] -IREC5 -IREG5 http://airpax.sensata.com 209 (E-frame) 219/229 CONFIGURATIONS Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, interlock and emergency/rapid shutdown circuitry. Trip may be accomplished by voltage or current, which must be removed after trip. Dual Coil Providing for both a voltage trip and a current trip function in a magnetic circuit protector is common practice. These two coil protectors provide remote or automatic opening of one or more circuits with a low level signal. The voltage coil will trip the protector instantaneously while the current coil provides normal inverse time delays. The voltage coil is not rated for continuous duty and therefore, the voltage must be removed when the breaker trips. SEE NOTE A LINE LOAD RELAY 1.000 [25.40] RELAY 3.550 [90.17] LINE COIL COIL Relay Trip LOAD 1.250 [31.75] .750 [19.05] Dual Coil .190 [4.83] Since both coils are housed within the same pole, the space savings are substantial. This option is not available with 64, 65 or 66 delays. Shunt Trip The shunt trip is designed for controlling two separate loads with one assembly. The control is established by providing overload protection for the critical load. When the current through this load becomes excessive and reaches the trip point, the protector will open and remove power from both loads simultaneously. The total current rating of both loads must not exceed the maximum contact rating. Voltage Trip Sometimes called "dump circuits" or "panic trip circuits," these units make it possible to open main power contacts with lower power inputs from one or more sources. This configuration is becoming increasingly more important for sensitive circuitry and denser packaging in automation systems. Available in series, shunt or relay configurations. SEE NOTE A LINE LOAD SHUNT 3.550 [90.17] V. COIL LINE LOAD Shunt Trip 1.250 [31.75] .750 [19.05] Dual Coil .190 [4.83] Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. A: 0-50 Amps, 10-32 Studs .625 .062 [15.88 .157 ] Long, 51-100 Amps, 1/4 - 20 Studs, .750 .062[19.05 .157 ] Long. 209 Series - Configurations 194 OPERATING CHARACTERISTICS Inrush Pulse Tolerance The table shown above provides a comparison of inrush pulse tolerance with and without the inertial delay feature for each of the 50/60Hz delays. Pulse tolerance is defined as a single pulse of half sine wave peak current amplitude of 8 milliseconds duration that will not trip the circuit breaker. INRUSH PULSE TOLERANCE The table at right provides a reference guide for selecting the inertial delay feature. Consult factory for further assistance. Delay Pulse Tolerance 61, 62, 63 8 times rated current 64 minimum 20 times rated current 65 minimum 25 times rated current 66 minimum 30 times rated current Note: These limits do not apply to dual coil and tapped coil units PERCENTAGE OF RATED CURRENT VS TRIP TIME IN SECONDS AT +25C Delay 100% 125% 150% 200% 400% 600% 800% 1000% 41 & 41F No Trip May Trip .6 to 7 .2 to 2 .03 to .40 .01 to .1 .009 to .060 .008 to .050 42 & 42F No Trip May Trip 7 to 70 2 to 20 .1 to 3 .01 to .2 .009 to .09 .008 to .08 43 & 43F No Trip May Trip 60 to 500 20 to 200 2 to 30 .01 to .1 .009 to .09 .008 to .08 51 & 51F No Trip .4 to 7 .2 to 2 .12 to 1 .03 to .3 .012 to .1 .009 to .07 .008 to .05 52 & 52F No Trip 8 to 80 2.5 to 45 .7 to 20 .2 to 3 .05 to 1 .01 to .5 .009 to .08 53 & 53F No Trip 100 to 900 50 to 500 20 to 200 2 to 25 .015 to 5 .01 to .15 .009 to .09 61 No Trip .6 to 5 .3 to 2 .1 to .8 .03 to .3 .015 to .1 .01 to .07 .009 to .06 62 No Trip 12 to 120 6 to 55 2 to 18 .3 to 3 .05 to 1 .016 to .1 .01 to .08 63 No Trip 70 to 800 45 to 450 20 to 200 2 to 30 .3 to 4 .02 to .25 .012 to .15 64 No Trip .6 to 5 .3 to 3 .1 to 1.5 .03 to .5 .02 to .4 .01 to .3 .008 to .25 65 No Trip 12 to 100 6 to 50 2 to 18 .3 to 3 .05 to 2 .016 to 1.6 .01 to 1 66 No Trip 70 to 800 45 to 450 20 to 200 2 to 30 .3 to 9 .02 to 5 .013 to 3 Notes: *279 is available only with DC delays 195 209 Series - Operating Characteristics http://airpax.sensata.com 209 (E-frame) 209/219/229 DELAY CURVES 10000 MAY TRIP 1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 10000 TIME IN SECONDS 1000 DELAY 62 100 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 10000 1000 TIME IN SECONDS All trip curves and trip currents are specified with the breaker mounted in the normal vertical position at ambient temperature of +25C. For test and measurement purposes, the breakers should not carry current prior to application of overload for calibration test. For other than vertical mount position, consult factory. 10 .1 Delay 63 is a long delay for special motor applications. Delays 64, 65 and 66 are the latest 50/60Hz delays with short, medium and long trip times respectively. The patented breaker design provides both increased tolerance to high inrush induced nuisance tripping and longer trip times at 600 percent. These delays are ideally suited for applications where thermal devices are presently used, such as motor protection or where short duration, high inrush currents are experienced. As shown in a typical motor start-up curve, the delay 66 will provide locked rotor and overload protection. Nuisance tripping is avoided, since acceptable short periods of overload will not trip the breaker. 100 MAY TRIP Delay 61 is a short delay for general purpose applications. Delay 62 is long enough to start certain types of motors and most transformer and capacitor loads. DELAY 61 MAY TRIP 50/60Hz Delay Curves (typ) A choice of delays is offered for 50/60Hz applications. TIME IN SECONDS 1000 DELAY 63 100 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 209 Series - Delay Curves 196 209/219/229/279 DELAY CURVES 60Hz Delay Curves (typ) MAY TRIP 10000 TIME IN SECONDS 1000 DELAY 64 100 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 900 1000 PERCENT OF RATED CURRENT MAY TRIP 10000 TIME IN SECONDS 1000 DELAY 65 100 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT MAY TRIP 10000 TIME IN SECONDS 1000 DELAY 66 100 10 1 .1 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 197 209 Series - Delay Curves http://airpax.sensata.com 209 (E-frame) 209/219/229 DELAY CURVES DC Delay Curves (typ) 400Hz Delay Curves(typ) (279 is available only with DC delays) 10000 10000 MAY TRIP 100 TIME IN SECONDS TIME IN SECONDS 100 1000 DELAY 51 10 1 .1 10 1 .1 .01 .01 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 .001 0 100 150 200 125 PERCENT OF RATED CURRENT 400 500 600 700 800 900 1000 900 1000 10000 TIME IN SECONDS 10 1 DELAY 42 MAY TRIP 100 1000 DELAY 52 MAY TRIP 1000 100 10 1 .1 .1 .01 .01 .001 .001 0 100 150 200 125 300 400 500 600 700 800 900 0 1000 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT MAY TRIP 1000 DELAY 53 TIME IN SECONDS 1000 MAY TRIP 10000 10000 TIME IN SECONDS 300 PERCENT OF RATED CURRENT 10000 TIME IN SECONDS DELAY 41 MAY TRIP 1000 100 10 1 DELAY 43 100 10 1 .1 .1 .01 .01 .001 0 .001 0 100 150 200 125 300 400 500 600 700 800 900 1000 100 150 200 300 400 500 600 700 800 125 PERCENT OF RATED CURRENT 900 1000 PERCENT OF RATED CURRENT 209 Series - Delay Curves 198 209/219/229 SPECIFICATIONS NOMINAL DCR / IMPEDANCE Current Ratings (Amps) Resistance (ohms) Impedance (Ohms) DC Delays AC, 50/60Hz Delays 51, 52, 53 61, 62, 63 0.10 112.0 117.0 1.0 0.97 1.0 5.0 .042 .044 10.0 .011 .012 20.0 .0042 .0043 30.0 .0030 .0031 50.0 .0018 .0019 80.0 .0014 .0015 100 .0008 .0009 Notes: DCR and impedance based on 100% rated current applied and stablized a minimum of one hour. Tolerance: .1 amperes to 1.0 amperes, 10%; 1.1 amperes to 5.0 amperes, 15%; 5.1 amperes to 15 amperes, 25%; 15.1 amperes to 100 amperes, 50% or = .001 Ohms, whichever is greater. APPROXIMATE CIRCUIT BREAKER WEIGHT # of Poles Ounces 1 9 oz 2 1 lb, 3 oz 3 2 lb 4 2 lb, 7 oz 5 3 lb 6 3 lb, 12 oz Trip Free Will trip open on overload, even when forcibly held on. This prevents the operator from damaging the circuit by holding the handle in the ON position. Trip Indication The operating handle moves positively to the OFF position on overload. Environmental Specifications Moisture and fungus resistance is provided by the use of moisture resistant finishes. Special springs and treatment for all ferrous parts eliminate inherent moisture-related problems. The use of fungi inert cases and handles avoids fungus-related problems. Current Ratings 209/219/229 may be supplied with these ratings: DC, 50/60Hz, 400Hz, 0.1 to 100 amperes. 279 types may be supplied with DC ratings only, 0.1 to 100 amperes. Voltage Ratings On 209/219/229, voltages up to and including 240Vac, 50/60Hz or 400Hz, or 125Vdc are available. Multi-pole units can be supplied for 277Vac/480Vac, 50/60Hz. 279 types are available with a voltage of 160Vdc. All units will be marked with the standard maximum voltage. UL Listed breakers will be labeled with the UL listed voltage. Auxiliary Switch Ratings When supplied shall be S.P.D.T. configuration with a maximum rating of 10 amperes 250Vac. Mounting Considerations A three-inch spacing must be provided between the circuit breaker and vent and any conductive surface. If closer than three inches is necessary, then an insulator must be installed on the conductive surface. RECOMMENDED TORQUE SPECIFICATIONS Component Torque (in-lbs) 6-32 Mounting Inserts 6 to 8 M3 Mounting Screws 4 to 5 1/4-20 Screw Terminals 35 to 40 10-32 Stud Terminals 13 to 14 M5 Stud Terminals 13 to 14 1/4 - 20 Stud Terminals 40 to 45 Solderless Connectors Connectors are rated AL9 CU. and accept either copper or aluminum conductors. Units are suitable for use with both 60 and 75 wire. Optional pressure plate for fine stranded wire is available. Contact factory for details. Where applicable, mechanical support must be provide to the terminals when applying torque 199 209 Series - Specifications http://airpax.sensata.com 209 (E-frame) 209 SERIES AGENCY APPROVALS 219 MANUAL MOTOR CONTROLLERS AGENCY APPROVALS Volts (Volts) Rated Current (Amps) Voltage (V) Frequency (Hz) Min. Poles UL/CSA VDE 65 DC 1 .10-100 125 DC 1 .10-100 .10-100 125/250 DC 2 .10-20 120 50/60 1 only .10-50 120/240 50/60 2 .10-100 120/240 50/60 2 only .10-50 240 50/60 1 .10-100 .10-100 240 400 1 .10-100 279 Circuit Breakers for use in Communications Equipment Voltage (V) Frequency (Hz) Min. Poles UL/CSA VDE 160 DC 1 .10-100 - Interrupting Capacity (Amps) UL 489 & CSA VDE 25000 10000 4000 5000 10000 5000 10000 5000 4000 2500 UL489A 5000 VDE - Volts (Volts) Voltage (V) 125 120/240 120/240 240 240/415 277 277/480 277/480 480 600 250 Frequency (Hz) DC 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 400 Min. Poles 1 2 2 1 2 1 2 2 2 2 1 Rated Current (Amps) UL VDE .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-77 .10-100 - Interrupting Capacity (Amps) UL 508 VDE 5000 4000 5000 10000 5000 4000 4000 5000 5000 10000(1) 10000(1) 10000(1) 5000 - Notes: (1) With 225 A maximum series fuse General notes 229 SUPPLEMENTARY PROTECTORS* AGENCY APPROVALS Volts (Volts) Frequency Voltage (V) (Hz) UG FW Phase 125 DC A, D 0 125 DC A, D 0, 3 125/250 DC A, D 0, 3 300 DC A, D 0, 3 125/250 50/60 A, D 0 1 125/250 50/60 A, D 0 1 250 50/60 A, D 0, 3 1 277 50/60 A, D 0, 3 1 277/480 50/60 A, D 0 1&3 277/480 50/60 A, D 0, 3 1&3 347/600 50/60 A, D 0 1&3 347/600 50/60 A, D 0, 3 1&3 480 50/60 A, D 0 3 600 50/60 A, D 0 3 125/250 400 A, D 0, 3 1 229D Supplementary Protectors (Ignition Protected) Voltage (V) Frequency UG FW Phase (Hz) 65 DC A, D 0, 3 - Min. Poles 1 1 2 2 2 2 1 1 2 2 2 2 3 3 2 250 50/60 A, D 0, 3 1 Interrupting Capacity (Amps) TC 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 OL 0 0 1 0 1 0 0 1 1 0 0 0 0 0 0 UL/CSA .10-100 .10-100 .10-20 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-100 .10-77 .10-100 VDE .10-100 .10-100 - UL 1077 & CSA No. 235 U2, 10000 / U1, 5000 U2, 5000 / U1, 5000 U1, 5000 U1, 5000 U2, 5000 U1, 10000 U1, 5000 U1, 5000 C2, 10000(1) / C1, 10000 U2, 5000 / U1, 5000 C1, 10000(1) U1, 5000 C2, 10000(1) / C1, 10000 C2, 10000(1) / C1, 10000 U2, 1500 / U1, 2000 VDE 4000 4000 - Min. Poles 1 TC OL UL/CSA VDE UL1500 & CSA VDE 1 - U2, 1000/U1,1000 - 1 1 1, (0, .10-100 CSA ) 1, (0, .10-100 CSA) - U2, 1000/U1, 1000 OL UL/CSA VDE UL1077 & CSA VDE 1 1 .10-100 .10-77 - U2, 2500 U2, 2000 - OL UL/CSA VDE UL1077 & CSA VDE 1 1 - .10-100 .10-100 - .10-100 .10-100 U1, 5000 U1, 5000 - 4000 4000 229G Supplementary Protectors (Generator Use - UL489 Field wired) Voltage (V) Frequency UG FW Phase Min. TC (Hz) Poles 277/480 50/60 A, D 0, 3 3 3 1 347/600 50/60 A, D 0, 3 3 3 1 239 Supplementary Protectors (Marine) Voltage (V) Frequency UG FW Phase Min. TC (Hz) Poles 250 50/60 A, D 0, 3 1&3 1 1 125/250 50/60 A, D 0, 3 1 2 1 240 50/60 1&3 1 240/415 50/60 3 3 Notes: (1) With 225A maximum series fuse *219 also applicable for CSA approval only. Rated Current (Amps) All supplementary protectors are of the overcurrent (OC) type The family of protectors has been evaluated for end use application for use group (UG) A and D The terminals (FW) - Terminals are coded as follows: 0 - Suitable for factory wiring only 1 - Line terminals evaluated for field wiring 2 - Load terminals evaluated for field wiring 3 - Line and Load terminals evaluated for field wiring The maximum voltage ratings for which the protectors have been tested are shown in the chart The current is the amperage range that the protectors have been tested The tripping current (TC) - Tripping Current is coded as a percentage of the ampere rating: 0 - Tripping current is less than 125% of ampere rating 1 - Tripping current is in the range of 125% to 135% of ampere rating 2 - Tripping current is more than 135% of ampere rating 3 - Tripping current is 135% and meets MCCB trip time requirements The overload rating (OL) - Designates whether the protector or family of protectors has been tested for general use or motor starting applications. 0 - tested at 1.5 times amp rating for general use 1 - tested at 6 times AC rating or 10 times DC rating for motor starting The short circuit current rating (SC) - The short circuit rating in amperes following a letter and number designating the test conditions and any calibration following the short circuit test is defined below: C - Indicates short circuit test was conducted with series overcurrent protection U - Indicates short circuit test was conducted without series overcurrent protection 1 - Indicates a recalibration was not conducted as part of the short circuit testing 2 - Indicates a recalibration was performed as part of the short circuit testing 3 - Indicates recalibration was performed along with the dielectric and voltage withstand for "Suitable for Further Use" rating 209 Series - Agency Approvals 200 209/219/229/279 DECISION TABLES How to Order The ordering code for 209, E-Frame Circuit Breakers may be determined by following the steps in the decision tables shown here. The coding given permits a self-assigning part number for standard configurations. Factory part numbers are assigned to units with mixed ratings, combinations of styles or construction not listed in the Third Decision Table, etc. With these, it is suggested that order entry be by description and/ or drawings, and a part number will be established. Additionally, it is standard policy to establish a factoryassigned part number whenever a descriptive drawing exists to insure cross reference, traceability and manufacturing control. When specifying a breaker for AC motor start or high inrush applications, the peak amplitude and surge duration should be specified for factory assistance in rating selection. 209 is a UL listed circuit breakers under file no. E53739 per UL 489. * U 489 Listed units are rated to 100A maximum ** U 489A Listed units are rated to 160Vdc maximum 279 is a UL listed under file no. E192808 per UL 489A. 219 is a UL recognized "Manual Motor Controller" under file no. E41607 per UL 508. 229 is a UL recognized supplementary protector under file no. E66410 per UL 1077. For example, the following is the code for a single pole breaker with series trip, 50/60Hz, medium inertial delay, 120/240Vac maximum voltage ratings, solderless connector with mounting foot added to the line side of the breaker to facilitate back panel mounting and a current rating of 10.0 amperes. To determine the ordering number of your particular 209 unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have. Notes: 201 A6-32 inserts for front mounting are provided on all units. M3 ISO metric mounting inserts are available and are specified by adding -A at the end of the ordering code above. CLine terminals are 10-32 screws for bus connection to 100 amperes. Load terminals are 10-32 screws to 50 amperes and solderless connectors from 50 to 100 amperes. BThe auxiliary switch is located on the right-hand pole (viewed from terminal end) unless specified otherwise. Auxiliary switches are available on all front or back panel mounts (series construction only). If more than one auxiliary switch is specified use "2R" through "6R" as required. D An anti-flashover barrier is supplied between poles on all multi-pole versions with 10-32 stud and 1/4-20 stud terminals per UL requirement. 209 Series - Decision Tables EThe standard current values for 100% of rated current are those listed in the Seventh Decision Table. Non-listed values can be readily supplied, in general without delayed delivery. Please contact an Airpax office or sales representative. http://airpax.sensata.com Terminal Terminal Connect -1 Solderless connector front front (Note A) -2 Solderless connector front back* -2C -3 -3C -4 Panel Mount Solderless connector front back** 10-32 screw (100 amps max.) bus connect back (Note C)* 10-32 screw (100 amps max.) bus connect back (Note C)** 10-32 screw (50 amps max.) front front -5 10-32 screw (50 amps max.) front back* -5C 10-32 screw (50 amps max.) front back** -6 1/4 - 20 screw (100 amps max.) front front -7 1/4 - 20 screw (100 amps max.) front back* 1/4 - 20 screw (100 amps max.) front back** -8 10 - 32 stud (50 amps max.) back front (Note D) -9 1/4 - 20 stud (100 amps max.) back front (Note D) -3M M5 x 0.8 screw (100 amps max.) bus connect back (Note C)* -4M M5 x 0.8 screw (50 amps max.) front front -5M M5 x 0.8 screw (50 amps max.) front back* -6M M6 x 1.0 screw (100 amps max.) front front -7C -7M M6 x 1.0 screw (100 amps max.) front back* -8M M5 x 0.8 stud (50 amps max.) back front (Note D) -9M M6 x 1.0 stud (100 amps max.) front front (Note D) * Back panel mount style supplied with slotted mounting bracket. Solderless connector will accept #14 through 0 copper or #12 through 0 aluminum wire. ** Back panel mount style supplied with short mounting bracket. 209 (E-frame) Configurations 249 POWER SELECTOR BREAKER SYSTEM DECISION TABLES How to Order To evolve a convenient ordering system for most applications, the following code has been developed. If a system is required which is not covered below, please consult factory or describe in detail. The number shown as an example describes a 120 volt, three section system, such as may be used on a boat with a port and starboard shore power receptacle and an AC generator. The breaker rating for the shore power is 30 amperes and for the generator 20 amperes in this example. 1/4 -20 screw type terminals and a medium time delay are specified. 203 209 Series - Decision Tables http://airpax.sensata.com