209 SERIES AGENCY APPROVALS
Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps)
Voltage (V) Frequency (Hz) Min. Poles UL/CSA VDE UL 489 & CSA VDE
65 DC 1 .10-100 - 25000 -
125 DC 1 .10-100 .10-100 10000 4000
125/250 DC 2 .10-20 - 5000 -
120 50/60 1 only .10-50 - 10000 -
120/240 50/60 2 .10-100 - 5000 -
120/240 50/60 2 only .10-50 - 10000 -
240 50/60 1 .10-100 .10-100 5000 4000
240 400 1 .10-100 - 2500 -
279 Circuit Breakers for use in Communications Equipment
Voltage (V) Frequency (Hz) Min. Poles UL/CSA VDE UL489A VDE
160 DC 1 .10-100 - 5000 -
219 MANUAL MOTOR CONTROLLERS AGENCY APPROVALS
Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps)
Voltage (V) Frequency (Hz) Min. Poles UL VDE UL 508 VDE
125 DC 1 .10-100 .10-100 5000 4000
120/240 50/60 2 .10-100 - 5000 -
120/240 50/60 2 .10-100 - 10000 -
240 50/60 1 .10-100 .10-100 5000 4000
240/415 50/60 2 - .10-100 - 4000
277 50/60 1 .10-100 - 5000 -
277/480 50/60 2 .10-100 - 5000 -
277/480 50/60 2 .10-100 - 10000(1) -
480 50/60 2 .10-100 - 10000(1) -
600 50/60 2 .10-77 - 10000(1) -
250 400 1 .10-100 - 5000 -
Notes: (1) With 225 A maximum series fuse
229 SUPPLEMENTARY PROTECTORS* AGENCY APPROVALS
Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps)
Voltage (V)
Frequency
(Hz) UG FW Phase
Min.
Poles TC OL UL/CSA VDE UL 1077 & CSA No. 235 VDE
125 DC A, D 0 - 1 1 0 .10-100 .10-100 U2, 10000 / U1, 5000 4000
125 DC A, D 0, 3 - 1 1 0 .10-100 .10-100 U2, 5000 / U1, 5000 4000
125/250 DC A, D 0, 3 - 2 1 1 .10-20 - U1, 5000 -
300 DC A, D 0, 3 - 2 1 0 .10-100 - U1, 5000 -
125/250 50/60 A, D 0 1 2 1 1 .10-100 - U2, 5000 -
125/250 50/60 A, D 0 1 2 1 0 .10-100 - U1, 10000 -
250 50/60 A, D 0, 3 1 1 1 0 .10-100 - U1, 5000 -
277 50/60 A, D 0, 3 1 1 1 1 .10-100 - U1, 5000 -
277/480 50/60 A, D 0 1 & 3 2 1 1 .10-100 - C2, 10000(1) / C1, 10000 -
277/480 50/60 A, D 0, 3 1 & 3 2 1 0 .10-100 - U2, 5000 / U1, 5000 -
347/600 50/60 A, D 0 1 & 3 2 1 0 .10-100 - C1, 10000(1) -
347/600 50/60 A, D 0, 3 1 & 3 2 1 0 .10-100 - U1, 5000 -
480 50/60 A, D 0 3 3 1 0 .10-100 - C2, 10000(1) / C1, 10000 -
600 50/60 A, D 0 3 3 1 0 .10-77 - C2, 10000(1) / C1, 10000 -
125/250 400 A, D 0, 3 1 2 2 0 .10-100 - U2, 1500 / U1, 2000 -
229D Supplementary Protectors (Ignition Protected)
Voltage (V) Frequency
(Hz)
UG FW Phase Min.
Poles
TC OL UL/CSA VDE UL1500 & CSA VDE
65 DC A, D 0, 3 - 1 1 1, (0,
CSA )
.10-100 - U2, 1000/U1,1000 -
250 50/60 A, D 0, 3 1 1 1 1, (0,
CSA)
.10-100 - U2, 1000/U1, 1000
229G Supplementary Protectors (Generator Use – UL489 Field wired)
Voltage (V) Frequency
(Hz)
UG FW Phase Min.
Poles
TC OL UL/CSA VDE UL1077 & CSA VDE
277/480 50/60 A, D 0, 3 3 3 1 1 .10-100 - U2, 2500 -
347/600 50/60 A, D 0, 3 3 3 1 1 .10-77 - U2, 2000 -
239 Supplementary Protectors (Marine)
Voltage (V) Frequency
(Hz)
UG FW Phase Min.
Poles
TC OL UL/CSA VDE UL1077 & CSA VDE
250 50/60 A, D 0, 3 1 & 3 1 1 1 .10-100 - U1, 5000 -
125/250 50/60 A, D 0, 3 1 2 1 1 .10-100 - U1, 5000 -
240 50/60 - - 1 & 3 1 - - - .10-100 - 4000
240/415 50/60 - - 3 3 - - - .10-100 - 4000
Notes: (1) With 225A maximum series fuse
General notes
All supplementary protectors are of the overcurrent (OC) type
The family of protectors has been evaluated for end use application for
use group (UG) A and D
The terminals (FW) – Terminals are coded as follows:
0 – Suitable for factory wiring only
1 – Line terminals evaluated for field wiring
2 – Load terminals evaluated for field wiring
3 – Line and Load terminals evaluated for field wiring
The maximum voltage ratings for which the protectors have been tested
are shown in the chart
The current is the amperage range that the protectors have been tested
The tripping current (TC) – Tripping Current is coded as a percentage of
the ampere rating:
0 – Tripping current is less than 125% of ampere rating
1 – Tripping current is in the range of 125% to 135% of ampere rating
2 – Tripping current is more than 135% of ampere rating
3 – Tripping current is 135% and meets MCCB trip time requirements
The overload rating (OL) - Designates whether the protector or family of
protectors has been tested for general use or motor starting applications.
0 – tested at 1.5 times amp rating for general use
1 – tested at 6 times AC rating or 10 times DC rating for motor starting
The short circuit current rating (SC) – The short circuit rating in amperes
following a letter and number designating the test conditions and any
calibration following the short circuit test is defined below:
C – Indicates short circuit test was conducted with series overcurrent
protection
U – Indicates short circuit test was conducted without series overcurrent
protection
1 – Indicates a recalibration was not conducted as part of the short
circuit testing
2 – Indicates a recalibration was performed as part of the short circuit
testing
3 – Indicates recalibration was performed along with the dielectric and
voltage withstand for “Suitable for Further Use” rating
*219 also applicable for CSA approval only.
209 Series - Agency Approvals
209 (E-frame)
200