Technical Data 1002
Effective August 2018
LPS-RK — 600 Vac/300 Vdc, 70-600 A, dual element, time-delay fuses
Eaton.com/bussmannseries
Recommended fuse blocks
Amps
Catalog no.
1-Pole 2-Pole 3-Pole
100 RM60100-1CR RM60100-2CR RM60100-3CR
200 RM60200-1CR RM60200-2CR RM60200-3CR
400 RM60400-1CR RM60400-2CR RM60400-3CR
600 RM60600-1CR RM60600-2CR RM60100-3CR
For additional information on the RM600 600 volt fuse blocks, see
product brochure no. 3192.
Fuse reducers for Class R fuses
Equipment fuse clips
Desired fuse (case)
size
Catalog no. (pairs)
600V
200 A 100 A NO.2621-R
400 A 100 A NO.2641-R
200 A NO.642-R
600 A
100 A NO.2661-R
200 A NO.2662-R
400 A NO.2664-R†
† Single reducer only (pair not required).
For additional information on Class R fuse reducers, see data sheet
no. 1118.
Dimensions — in
Fuse amps A B
70-100 7.88 1. 11
110-200 9.63 1.61
225-400 11.63 2.36
450-600 13.38 2.88
A
B
Current-limitation curves
A
600A
400A
200A
100A
AMP RATING
400,000
100,000
1000
INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS
200,000
RMS SYMMETRICAL CURRENT IN AMPS
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)
100,000
10,000
1000
10,000
300,000
Current-limiting effects
Prosp. S.C.C. Let-through current (apparent RMS Sym. vs. fuse rating)
—100A 200A 400A 600A
1000 1000 1000 1000 1000
2000 2000 2000 2000 2000
3000 2000 3000 3000 3000
5000 2000 3000 5000 5000
10,000 3000 4000 7000 10,000
15,000 3000 5000 8000 11,000
20,000 3000 5000 9000 12,000
25,000 4000 6000 9000 12,000
30,000 4000 6000 10,000 13,000
35,000 4000 6000 10,000 13,000
40,000 4000 6000 10,000 14,000
50,000 5000 7000 11,000 15,000
60,000 5000 7000 12,000 15,000
70,000 5000 8000 13,000 16,000
80,000 5000 8000 13,000 16,000
90,000 5000 8000 13,000 17,000
100,000 6000 9000 14,000 17,000
150,000 6000 10,000 15,000 19,000
200,000 7000 11,000 16,000 21,000
250,000 7000 12,000 17,000 22,000
300,000 7000 12,000 18,000 23,000