Digital Controller E5CK I-63
Temperature
Controller
Digital Controller
E5CK
Advanced, Compact Digital Controllers
IP66/NEMA4 (indoor use) front face.
Modular structure, one-stock type.
Heating/cooling control.
Serial communications (RS-232C and RS-485).
Temperature and analog inputs.
High-accuracy: 100 ms sampling (for analog input).
Advanced tuning which includes fuzzy self-tuning.
Conforms to international EMC and safety standards.
AC/DC24V types are also available.
®
Model Number Structure
Model Number Legend
Refer to the following when ordering set models.
1. Control Output 1/Control Output 2
AA: Without Output Unit (field interchangeable)
RR: Relay/Relay
QR: Pulse (NPN)/Relay
CR: Linear (4 to 20 mA)/Relay
VR: Linear (0 to 10 V)/Relay
QQ: Pulse (NPN)/Pulse (NPN)
2. Auxiliary Output
1: Auxiliary output (1 point)
3. Option
01: RS-232C serial communication
03: RS-485 serial communication
B: Event input (1 point)
F: Transfer output (4 to 20 mA)
Note: E5CK-VR1 and E5CK-QQ1 are not available, but with options.
Ordering Information
List of Models
Note: A single Output Unit and Option Unit can be mounted to each Base Unit.
1 2 3
E5CK-@@@
Description Model Specification
Base Unit E5CK-AA1 AC100-240 Base Unit
E5CK-AA1-500 AC100-240 Base Unit with terminal cover
E5CK-AA1 AC/DC24 Base Unit
E5CK-AA1-500 AC/DC24 Base Unit with terminal cover
Description Model Specification
Output Unit E53-R4R4 Relay/Relay
E53-Q4R4 Pulse (NPN)/Relay
E53-Q4HR4 Pulse (PNP)/Relay
E53-C4R4 Linear (4 to 20 mA)/Relay
E53-C4DR4 Linear (0 to 20 mA)/Relay
E53-V44R4 Linear (0 to 10 V)/Relay
E53-Q4Q4 Pulse (NPN)/Pulse (NPN)
E53-Q4HQ4H Pulse (PNP)/Pulse (PNP)
I-64 Digital Controller E5CK
Inspection Report
The Digital Controller can be provided together with an inspection report.
Refer to the following legend with the suffix K when ordering a model provided together with an inspection report.
E5CK-AA1-K, E53-CKF-K
Accessories (Order Separately)
Specifications
Ratings
Input Ranges
Platinum Resistance Thermometer
Description Model Specification
Option Unit E53-CK01 RS-232C
E53-CK03 RS-485
E53-CKB Event input: 1 point
E53-CKF Transfer output (4 to 20 mA)
Name Model
Terminal Cover E53-COV07
Item AC100-240V type AC/DC24V type
Supply voltage AC100 to 240V, 50/60 Hz AC/DC24V, 50/60 Hz
Power consumption 15 VA 6 VA, 3.5 W
Operating voltage range 85% to 110% of rated supply voltage
Input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
Current input: 4 to 20 mA, 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 1 to 10 V
Input impedance Current input: 150
Voltage input: 1 M min.
Control output According to Output Unit (see “Output Unit Ratings and Characteristics”)
Auxiliary output SPST-NO, 1 A at 250 VAC (resistive load)
Control method ON/OFF or 2-PID control (with auto-tuning)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and LEDs
Other functions According to Option Unit (see “Option Unit Ratings and Characteristics”)
Input (switch selectable) JPt100 Pt100
Range °C199.9 to 650.0 199.9 to 650.0
°F199.9 to 999.9 199.9 to 999.9
Resolution (°C/°F)
(main setting and alarm)
01
Digital Controller E5CK I-65
Temperature
Controller
Thermocouple
Note: Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Input (switch
selectable)
(see note)
K1 K2 J1 J2 T E L1 L2 U N R S B W PLII
Range °C200
to
1,300
0.0 to
500.0
100
to 850
0.0 to
400.0
199.9
to 400.0
0 to
600
100
to 850
0.0 to
400.0
199.9
to 400.0
200
to
1,300
0 to
1,700
0 to
1,700
100 to
1,800
0 to
2,300
0 to
1,300
°F300
to
2,300
0.0 to
900.0
100
to
1,500
0.0 to
750.0
199.9
to 700.0
0 to
1,100
100
to
1,500
0.0 to
750.0
199.9
to 700.0
300
to
2,300
0 to
3,000
0 to
3,000
300 to
3,200
0 to
4,100
0 to
2,300
Resolution (°C/
°F) (main setting
and alarm)
23456 78910111213141516
Input (switch selectable) Current input Voltage input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Range One of following ranges depending on results of scaling
1999 to 9999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
Resolution (°C/°F)
(main setting and alarm)
17 18 19 20 21
I-66 Digital Controller E5CK
Characteristics
Note: The indication accuracy of the K1, T, and N thermocouples at a temperature of 100°C or less is ±2°C ±1 digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
Indication accuracy (see note) Thermocouple:
(±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 or 199.9 or 999.9 (decimal point position dependent on input type)
Sampling period Temperature input: 250 ms
Current/voltage input: 100 ms
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance Malfunction: 10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 200 m/s2 min. (approx. 20G), 3 times each in 6 directions
(100 m/s2 (approx. 10G) applied to the relay)
Destruction: 300 m/s2 min. (30G), 3 times each in 6 directions
Ambient temperature Operating: 10°C to 55°C (with no icing)/3-year warranty period: 10°C to 50°C
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Degree of protection Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight Approx. 170 g;
Adapter: approx. 10 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL1092, CSA22.2 No. 142, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/ part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
Digital Controller E5CK I-67
Temperature
Controller
Output Unit Ratings and Characteristics
Option Unit Ratings and Characteristics
Relay output SPST, 250 VAC, 3 A (resistive load)
Mechanical life expectancy: 10,000,000 operations min.
Electrical life expectancy: 100,000 operations min.
Voltage output NPN: 20 mA at 12 VDC (with short-circuit protection)
PNP: 20 mA at 12 VDC (with short-circuit protection)
Linear voltage output 0 to 10 VDC:
Permissible load impedance: 1 k min.
Resolution: approx. 2,600
Linear current output 4 to 20 mA:
Permissible load impedance: 500 max.
Resolution: approx. 2,600
Event inputs Contact input:
ON: 1 k max., OFF: 100 k min.
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
Communications Interface: RS-232C or RS-485
Transmission method: Half-duplex
Synchronization method: Start-stop synchronization (asynchronous method)
Baud rate: 1.2/2.4/4.8/9.6/19.2 kbps
Transmission code: ASCII
Transfer output 4 to 20 mA:
Permissible load impedance: 500 max.
Resolution: approx. 2,600
I-68 Digital Controller E5CK
Nomenclature
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Operation Indicators
A/M Key
No. 1 Display
No. 2 Display
Up Key/Down Key
Display Key
OUT1
Lights when the pulse output
function assigned to control
output 1 turns ON.
OUT2
Lights when the pulse output
function assigned to control
output 2 turns ON.
SUB1
Lights when the output func-
tion assigned to auxiliary
output 1 turns ON.
MANU
Lights when the manual op-
eration mode.
STOP
Lights during operation has
stopped.
RMT
Lights during remote opera-
tion.
AT
Flashes during auto-tuning.
Press to select the auto operation or
manual operation.
Press for less than 1 s to shift the
display to the next parameter. When
this key is pressed for 1 s or more,
the menu screen will be displayed in
any case.
Press to increase or decrease the
value on the No.2 display.
Displays the set point, set point dur-
ing SP ramp, manipulated variable,
or parameter settings.
Displays the process value or pa-
rameter symbols.
58
53 x 53 13 100
44.8 x 44.8
48
45
+0.6
0
45
+0.6
0
E5CK
Panel Cutouts
65 min.
60 min.
Note: 1. Recommended panel thickness is 1 to 5 mm.
2. Maintain the specified vertical and horizontal mount-
ing space between each Unit. Units must not be
closely mounted vertically or horizontally.
Digital Controller E5CK I-69
Temperature
Controller
Installation
Installation
Main Parts
Draw-out
First, draw out the internal mechanism from the housing.
Pull out the internal mechanism while pressing the hooks on the left
and right sides of the front panel.
Setting Up the Output Unit
1. Two rectangular holes are provided on the power board (right side
of Controller). Fit the two protrusions of the Output Unit into these
two holes.
2. With the Output Unit fitted into the power board, fit the Output Unit
into the connector on the control board (left side of Controller).
Setting Up the Option Unit
1. Place the Controller with its bottom facing up, and fit the board
horizontally into the Connector on the power board (right side of
controller).
2. With the power board connected, fit the board vertically into the
Connector on the control board (left side of controller).
Terminals
Output Unit
Rear case
Front panel
Option Unit
Input type jump-
er connector
1
2
1
2
I-70 Digital Controller E5CK
Mounting
1. Insert the E5CK Controller into the panels mounting hole at the
position shown in the figure below.
2. Push the adapter along the Controller body from the terminals up
to the panel, and fasten temporarily.
3. Tighten the two fixing screws on the adapter. When tightening
screws, tighten the two screws alternately keeping the torque to
approximately 0.29 to 0.39 N·m, or 3 to 4 kgf·cm.
Terminal Cover
The E5CK-AA1-500 Controller is provided with a Terminal Cover
(E53-COV07). Fasten the Terminal Cover as follows by using the
snap pin.
Adapter
Panel
Watertight
packing
Digital Controller E5CK I-71
Temperature
Controller
Wiring
Terminal Arrangement
Precautions
Use ducts to separate input leads and power lines in order to protect
the Controller and its lines from external noise.
Solderless terminals are recommended when wiring the Controller.
Tighten the terminal screws using a torque no greater than 0.78 N·m,
or 8 kgf·cm max. Take care not to tighten the terminal screws too
tightly.
Power Blocks
The E5CK has independent power supplies for each of the terminal
blocks shown below. However, note that the power supplies for
blocks C (exclude relay output) and D are shared for the following
option unit.
Option unit: E53-CKB or E53-CKF
Wiring
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 4 and 5 according to the specification.
Input
Connect the input to terminal numbers 6 to 8 as follows according to the input type.
Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set the inputs
to a common position (TC/PT) as the temperature input.
Control Output
Terminal numbers 11 and 12 are for control output 1 (OUT1). The five output types and internal equalizing circuits are available according to the
Output Unit.
5
4
3
2
1
10
9
8
7
6
13 14
11 12
AC100240V~
(AC/DC24V~)
OUT1
OUT2
SUB1
OPTION
IN
SOURCE
AC
5
4
3
2
1
10
9
8
7
6
C
DB
11 12
13 14
5
4
3
2
1
10
9
8
7
6
13 14
11 12
8
7
6
8
7
6
8
7
6
8
7
6
+
+
+
VmA
TCPT V I
5
4
3
2
1
10
9
8
7
6
13 14
11 12
Thermocouple Voltage input Current inputPlatinum resistance
thermometer
5
4
3
2
1
10
9
8
7
6
13 14
11 12 11
12
11
12
L
11
12
L
11
12
L
11
12
L
+v ++++
mA
V
+v
E53-R4R4 E53-V44R4
NPN PNP 0 to 10 V 4 to 20mA
GND
Relay
GND
E53-Q4R4
E53-Q4Q4 E53-Q4HR4
E53-Q4HQ4H E53-C4R4
E53-C4DR4
−−
I-72 Digital Controller E5CK
Terminal numbers 9 and 10 are for control output 2 (OUT2). The three output types and internal equalizing circuits are available according to the
Output Unit.
The following table shows the specifications for each output type.
Auxiliary Output 1
Terminal numbers 2 and 3 are for auxiliary output 1 (SUB1).
The internal equalizing circuit for auxiliary output 1 is as follows:
Relay specifications are as follows:
SPST-NO, 250 VAC, 1 A
Option
Terminal numbers 1, 13, and 14 are valid only when the Option Unit is set in the Controller.
The following four connections are possible depending on the model of the Option Unit.
Use event inputs under the following conditions:
The polarity for no-contact input is as follows:
Transfer output specifications are as follows:
4 to 20 mA, load: 500 max., resolution approx. 2600
10
9
10
9
L
10
9
L
+V
+
+
+V
GND
E53-Q4Q4 E53-Q4HQ4H
NPN PNPRelay
GND
E53-R4R4/E53-V44R4
E53-Q4R4/E53-C4R4
E53-Q4HR4/E53-C4DR4
Output type Specifications
Relay
Voltage (NPN)
Voltage (PNP)
3 A at 250 VAC
20 mA at 12 VDC (with short-circuit protection)
20 mA at 12 VDC (with short-circuit protection)
0 to 10 V
4 to 20 mA
0 to 10 VDC, permissible load impedance: 1 k min., resolution: approx. 2,600
4 to 20 mA, permissible load impedance: 500 max., resolution: approx. 2,600
5
4
3
2
1
10
9
8
7
6
13 14
11 12 3
2
Contact input ON: 1 k max., OFF: 100 k min.
No-contact input ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
5
4
3
2
1
10
9
8
7
6
13 14
11 12 13
14
1
13
14
1
13
14
1
13
14
1
A
B
+
SD
RD
SG
4 to 20mA
E53-CK01
RS-232C
E53-CK03
RS-485
E53-CKB E53-CKF
Event input Transfer output
13
14
1
+
Digital Controller E5CK I-73
Temperature
Controller
Operation
Parameter Operation List
Switching to modes other than manual or protect mode is carried out using mode selection in the menu display.
The figure below shows all parameters in the order that they are displayed. Some parameters are not displayed depending on the protect mode
setting and conditions of use.
Parameters and Menus
Note: For more details on the functions of each part and display contents, refer to the E5CK User’s Manual (H78).
Protect Mode Limits use of the menu and A/M Keys. The protect function prevents unwanted modification of parameters and
switching between the auto and manual operation.
Manual Mode The Controller can be switched to manual operation. The manipulated variable can be manipulated manually only
in this mode.
Level 0 Mode Set the Controller to this mode during normal operation. In this mode, change the set point during operation, and
start or stop Controller operation. The process value, SP ramp, and manipulated variable can only be monitored
in this mode.
Level 1 Mode The main mode for adjusting control. In this mode, execute AT (auto-tuning), and set alarm values, the control pe-
riod, and PID parameters.
Level 2 Mode The auxiliary mode for adjusting control. In this mode, set the parameters for limiting the manipulated variable and
set point, switch between the remote and local modes, and set the loop break alarm (LBA), alarm hysteresis, and
the digital filter value of inputs.
Setup Mode The mode for setting the basic specifications. In this mode, set parameters that must be checked or set before
operation such as the input type, scaling, output assignments and direct/reverse operation.
Expansion Mode The mode for setting expanded functions. In this mode, set ST (self-tuning), SP setting limiter, select advanced
PID or ON/OFF control, specify the standby sequence resetting method, initialize parameters, and set the time for
automatic return to the monitoring display.
Option Mode The mode for setting option functions. Select this mode only when the Option Unit is set in the Controller. In this
mode, set the communications conditions, transfer output and event input parameters to match the type of Option
Unit set in the Controller.
Calibration Mode The mode for calibrating inputs and transfer output.
When calibrating input, the selected input type is calibrated. Whereas, transfer output can be calibrated only when
the Communications Unit (E53-CKF) is set in the Controller.
A/M
A/M
A/M
A/M
A/M
++
+
1 second min.
Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
1 second min.
Manual mode
Protect mode
1 second min.
1 second min. 1 second min.
1 second min.
1 second min.
Power ON
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
Parameters in a mode can be
switched by the Display Key. The
parameter following the last param-
eter is the top parameter.
I-74 Digital Controller E5CK
Parameters Operation
Level 0 Mode
0
1 3 0 0
0
s p - m
50.0
o
c - o
50.0
r - 5
run
PV/SV
Set Point During SP Ramp
Monitors the set point when the SP ramp function is used.
MV Monitor (Heat)
MV Monitor (Cool)
Used when the Unit is in heating and cooling control operation.
Run/Stop
The process value is displayed on the No.1 display and the set point is displayed on the No.2 display.
When the multi-SP function is in use, the value of whichever is set, set point 0 or 1, is linked.
1
off
s e c r
k e y p
01234
xxxx
xxx
xxx
xxx
xx
x
16.0
3 8. 8
Security
A/M Key Protect
Invalidate the function of the A/M Key.
MV Manual
Mode Set value
Calibration
Option
Expansion
Setup
Level 2
Level 1, 0
Process value
Manipulated variable
MANU indicator
Any mode marked with "X" in the following table is not displayed on the menu when this parameter is set to
"0" to "3."
The Unit will be in only level 0 mode and the menu will not be available when this parameter is set to "4" to
"6."
Only the "PV/SP monitor" and "set point" parameter can be used when this parameter is set to "5."
Only the "PV/SP monitor" parameter can be used when this parameter is set to "6."
Digital Controller E5CK I-75
Temperature
Controller
Level 1 Mode
off
a
t
0
s
p
-
0
0
0
0
10.0
p
233
i
d
40
1.00
0.0
c
-
d
b
50.0
h
y
s
0.10
0.10
s
p
-
1
a
l
-
1
a
l
-
2
c
-
s
c
o
f
-
r
c
h
y
s
20
c
p
20
c
-
c
p
AT Execute/Cancel
Set Point 0
Used with multi-SP function.
Set Point 1
Used with multi-SP function.
Alarm Value 1
Available only when the alarm output function of the Controller is selected.
Alarm Value 2
Available only when the alarm output function of the Controller is selected.
Proportional Band
Integral Time
Derivative Time
Cooling Coefficient
Used when the Controller is in heating and cooling control.
Dead Band
Used when the Controller is in heating and cooling control.
Manual Reset Value
Available when the integral time parameter of the Controller in standard control is "0."
Hysteresis (Heat)
Available when the Controller is in ON/OFF control.
Hysteresis (Cool)
Available when the Controller is in ON/OFF control in heating and cooling control.
Control Period (Heat)
Available when the Controller has a relay or voltage output, or is in advanced PID control.
Control Period (Cool)
Available when the Controller has a relay or voltage output, or is in advanced PID control in heating and
cooling control.
I-76 Digital Controller E5CK
Level 2 Mode
lcl
m
s p r u
0
0
0.0
0.0
105.0
-5.0
0.0
0
i n f
0.02
0.02
0.0
s p r t
l b a
m U - s
o r l
a l h 1
i n s h
r - l
m U - e
o l - h
o l - l
a l h 2
0.0
i n s l
Remote/Local
Used for the communications function.
SP Ramp Time Unit
SP Ramp Set Value
LBA Detection Time
Available only when the LBA (loop break alarm) function of the Controller is selected.
MV at Stop
MV at PV Error
MV Upper Limit
MV Lower Limit
MV Change Rate Limit
Input Digital Filter
Alarm 1 Hysteresis
Available only when the Controller has an alarm output.
Alarm 2 Hysteresis
Available only when the Controller has an alarm output.
Input Shift Upper Limit
Input Shift Lower Limit
Available if the input type connected to the Controller is a thermocouple or platinum resistance
thermometer.
Available if the input type connected to the Controller is a thermocouple or platinum resistance
thermometer.
Digital Controller E5CK I-77
Temperature
Controller
Setup Mode
2
100
i n - h
0
0
c
no
heat
al-1
al-2
2
n-o
2
n-o
i n - l
d p
d - u
a l 1 n
a l 2 n
i n i t
o u t 1
o u t 2
a l t 2
or-r
o r e U
i n - t
s u b 1
a l t 1
Input Type
Codes are used to determine the input types connected to terminals 6 to 8.
Scaling Upper Limit
Used if the input type connected to the Controller is an analog input (voltage or current input).
Scaling Lower Limit
Used if the input type connected to the Controller is an analog input (voltage or current input).
Decimal Point
Used if the input type connected to the Controller is an analog input (voltage or current input).
°C/°F Selection
Parameter Initialize
Control Output 1 Assignment
Control Output 2 Assignment
Auxiliary Output 1 Assignment
Alarm 1 Type
Alarm 1 Open in Alarm
Alarm 2 Type
Alarm 2 Open in Alarm
Direct/Reverse Operation
Available only when the Controller has an alarm
output (see the table on the next page).
Enables the Controller to have alarm 1, alarm 2, alarm 3, LBA (loop break alarm), error 1, and error 2
outputs.
Enables the Controller to have heating control, cooling control, alarm 1, alarm 2, alarm 3, and LBA
(loop break alarm) outputs.
Enables the Controller to have heating control, cooling control, alarm 1, alarm 2, alarm 3, and LBA
(loop break alarm) outputs.
Used if the input type connected to the Controller is a temperature input (thermocouple or platinum
resistance thermometer).
I-78 Digital Controller E5CK
Switch
setting
Alarm operation Alarm output
When X is positive When X is negative
1 Upper- and lower-limit alarm (deviation) Always ON
2 Upper-limit alarm (deviation)
3 Lower-limit alarm (deviation)
4 Upper- and lower-limit range alarm (deviation) Always OFF
5 Upper- and lower-limit alarm with standby se-
quence (deviation)
Always OFF
6 Upper-limit alarm with standby sequence (devia-
tion)
7 Lower-limit alarm with standby sequence (devia-
tion)
8 Absolute-value upper-limit alarm
9 Absolute-value lower-limit alarm
10 Absolute-value upper-limit alarm with standby se-
quence
11 Absolute-value lower-limit alarm with standby se-
quence
XX
ON
OFF SP
X
SP
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
XX
SP
ON
OFF
XX
SP
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
X
0
ON
OFF 0
X
ON
OFF
X
0
ON
OFF
0
X
ON
OFF
X
0
ON
OFF 0
X
ON
OFF
X
0
ON
OFF
0
X
ON
OFF
Digital Controller E5CK I-79
Temperature
Controller
Expansion Mode
1300
-200
s
l
-
l
pid
off
15.0
0.65
1.0
0
1
0.2
0.2
c
n
t
l
s
t
l
b
a
b
a
l
f
a
a
t
-
g
r
s
e
t
s
l
-
h
r
e
t
a
t
-
h
s
t
-
b
SP Setting Upper Limit
SP Setting Lower Limit
PID/ON/OFF
ST
Available if the Controller in standard control or advanced PID control has a temperature input.
ST Stable Range
α
Available if the Controller is in advanced PID control with the ST set to OFF.
AT Calculated Gain
Available if the Controller is in advanced PID control with the ST set to OFF.
Standby Sequence Reset Method
Automatic Return of Display Mode
AT Hysteresis
Available if the Controller is in advanced PID control with the ST set to OFF.
LBA Detection Width
Available only when the LBA (loop break alarm) function of the Controller is selected.
Available if the Controller in standard control or advanced PID control with the ST set to ON has a tem-
perature input.
I-80 Digital Controller E5CK
Option Mode
0
stop
e U - 1
2
7
eUen
96
0
sp
1300
-200
b p s
u - n o
t r - t
e U - m
p r t y
s b i t
l e n
t r - h
t r - l
Multi-SP Function
Available for the event input function.
Event Input Assignment 1
Available for the event input function.
Communication Stop Bit
Used when the communications function is being used.
Communication Data Length
Used when the communications function is being used.
Communication Parity
Used when the communications function is being used.
Communication Baud Rate
Used when the communications function is being used.
Communication Unit No.
Used when the communications function is being used.
Transfer Output Type
Set when the transfer output function is being used.
Transfer Output Upper Limit
Set when the transfer output function is being used.
Transfer Output Lower Limit
Set when the transfer output function is being used.
Digital Controller E5CK I-81
Temperature
Controller
How to Use the Error Display
When an error has occurred, the No.1 display alternately indicates error codes together with the current display item.
This section describes how to check error codes on the display, and the actions that must be taken to remedy the problem.
Meaning Input is in error.
Action Check the wiring of inputs, disconnections, and shorts, and check the input type and the input type jumper con-
nector.
Operation at Error For control output functions, output the manipulated variable matched to the setting of the MV at PV error param-
eter (level 2 mode). Alarm output functions are activated when the upper limit is exceeded.
Meaning Internal memory operation is in error
Action First, turn the power OFF then back ON again. If the display remains the same, the E5CK Controller must be re-
paired. If the display is restored to normal, the probable cause may be external noise affecting the control system.
Check for external noise.
Operation at Error Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in case of other
outputs). Alarm output functions turn OFF.
Meaning Internal circuits are in error.
Action First, turn the power OFF then back ON again. If the display remains the same, the E5CK Controller must be re-
paired. If the display is restored to normal, the probable cause may be external noise affecting the control system.
Check for external noise.
Operation at Error Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in case of other
outputs). Alarm output functions turn OFF.
This error is output only during temperature input and is displayed for two seconds when the power is turned ON.
Meaning Calibration data is in error.
Action Must repair.
Operation at Error Both control output functions and alarm output functions are active. However, note that the readout accuracy is not
assured.
Meaning Though not an error, this is displayed when the process value exceeds the display range when the control range
(setting range ±10%) is larger than the display range (1999 to 9999).
When less than 1999
When greater than 9999
Operation Control continues, allowing normal operation.
Input Error
Memory Error
A/D Converter Error
Calibration Data Error
Display Range Over
I-82 Digital Controller E5CK
Fuzzy Self-tuning
Fuzzy self-tuning is a function that enables the E5CK to calculate the
most suitable PID constants for the controlled object.
Features
The E5CK determines by itself when to perform fuzzy self-tuning.
Fuzzy Self-tuning Function
The fuzzy self-tuning function has three modes.
In SRT (step response tuning) mode, the PID constants are tuned
using a step response method at the time the set point is
changed.
In DT (disturbance tuning) mode, the PID constants are amended
so that the controlled temperature will be within the target range
set in advance when there is external disturbance.
In HT (hunting tuning) mode, when hunting occurs, the PID con-
stants are amended to suppress the hunting.
Note: Be sure to turn on the power supply to the load either before or
simultaneously with the start of Temperature Controller opera-
tion.
Dead time will be measured from the time the Temperature
Controller starts operating. If a load such as a heater is turned
on after the Temperature Controller is turned on, dead time
longer than the actual value will be measured and inappropri-
ate PID constants will be obtained. If an extremely large
amount of dead time is measured, the control amount will be
set to 0% for a short period of time before being returned to
100%, and the constants will then be retuned. Retuning is per-
formed only for large amounts of dead time, so be sure to follow
the precaution given above when starting operation.
Startup Conditions of SRT
SRT will start if the following conditions are satisfied simultaneously
when the E5CK is turned on or the set point is changed.
Note: The last SRT-executed set point is set to 0 before shipping and
when changing from advanced PID control to advanced PID
control with fuzzy self-tuning.
PID Constant Refreshing Conditions
If the step control amount is applied before the maximum tempera-
ture slope (R) is obtained, SRT will not renew any PID constant. If the
proportional band obtained from the R and L values that were mea-
sured before the imposition had been completed is larger than the
present proportional band, the PID constants will be renewed
because the measured value is in the direction towards the suitable
proportional band value, and the set point at that time will be the
SRT-executed set point.
Stable Temperature Status
If the temperature is within the stable range for a certain time, it is
deemed that the temperature is stable. This time is called stability
judgement time. Like PID constants, stability judgement time is
adjusted with fuzzy self-tuning according to the characteristics of the
object to be controlled. Fuzzy self-tuning will not be activated if the
temperature is stable because the Temperature Controller deems
that temperature control is smooth.
Balanced Status
If the process value is within the stable range for 60 s when there is
no output, it is deemed that the temperature is balanced.
Startup Conditions of DT
1. DT will start if the temperature that has been stable varies due to
external disturbance and the deflection of the temperature
exceeds the stable range, and then the temperature becomes
stable, provided that the number of maximum temperature values
is less than four.
2. DT will start if the set point is changed under the condition that
SRT does not start and the temperature becomes stable, pro-
vided that the number of maximum temperature values is less
than four.
If there are four or more maximum temperature values, HT will
start.
At the time the E5CK starts
operating
At the time set point is
changed
1. The set point at the time the
E5CK starts operating is dif-
ferent from the set point used
at the time SRT was last exe-
cuted (see note).
2. The process value at the time
the E5CK starts operating is
smaller than the set point in
reverse operation and larger
than the set point in normal
operation.
1. The new set point is different
from the set point used at the
time SRT was last executed
(see note).
2. The process value is in stable
condition before the set point
is changed.
3. A larger set point value is set
in reverse operation and a
smaller set point is set in nor-
mal operation.
Temperature Slope (R)
Stable range
Time
SP
Shorter than the stability judgement time
Stability judgement time
Stable Stable
Set
point
Stable
range
Stable
range
(Set to
15.0°C
before
shipping)
SP
Temperature
Extreme value 2 Set point change
Time
Extreme value 1
Digital Controller E5CK I-83
Temperature
Controller
Startup Conditions of HT
HT will be ON when there is hunting with four or more maximum tem-
perature values (extreme values) while SRT is not being executed.
Note: In specific applications where temperature varies periodically
due to disturbance, internal parameters need to be adjusted.
For details, refer to the E5CK User’s Manual.
Extreme value 2 Extreme value 4
Temperature
Time
SP
Extreme
value 1 Extreme
value 3
I-84 Digital Controller E5CK
Precautions
Period and Scope of Guarantee
Unit with Standard Specifications
Scope of Guarantee
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
The above does not apply in the following cases.
1. Any malfunction of the Unit due to the incorrect use or improper
handling of the Unit.
2. Any malfunction of the Unit not originating from the Unit.
3. Any malfunction of the Unit due to a modification of the Unit or
repairs to the Unit carried out by any person not authorized by
OMRON.
4. Any malfunction of the Unit due to any natural disaster.
OMRON shall not be responsible for any damage or loss induced by
any malfunction of the Unit.
Three-year Guarantee
Period of Guarantee
The guarantee period of the Unit is three years starting from the date
the Unit is shipped from the factory.
Scope of Guarantee
The Unit is guaranteed under the following operating conditions.
1. Average Operating Temperature (see note): 10°C to 50°C
2. Mounting Method: Standard mounting
Note: Average Operating Temperature
Refer to the process temperature of the Unit mounted to a con-
trol panel and connected to peripheral devices on condition that
the Unit is in stable operation, sensor input type K is selected
for the Unit, the positive and negative thermocouple input ter-
minals of the Unit are short-circuited, and the ambient temper-
ature is stable.
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
The above does not apply in the following cases.
1. Any malfunction of the Unit due to the incorrect use or improper
handling of the Unit.
2. Any malfunction of the Unit not originating from the Unit.
3. Any malfunction of the Unit due to a modification of the Unit or
repairs to the Unit carried out by any person not authorized by
OMRON.
4. Any malfunction of the Unit due to any natural disaster.
OMRON shall not be responsible for any damage or loss induced by
any malfunction of the Unit.
Top
Bottom
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H079-E1-05