SPECIFICATION CONTROL DRAWING 55A1121 Title Date Revision TWO CONDUCTOR CABLE, SHIELDED, JACKETED, GENERAL PURPOSE, 600 VOLT 28MAR 11 Bi This specification sheet forms a part of the latest issue of Raychem Specification 55A. COMPONENT WIRES 55A0111 SHIELD TIN-COATED GOPPER JACKET - RADIATION-CROSSLINKED, MODIFIED ETFE _ g eo y ROS LE AI CABLE CONSTRUCTION DETAILS CONDUCTOR SHIELD JACKET THICKNESS OUTSIDE DIAMETER MAXIMUM PART NY MBER SIZE SIZE (in.) (in.) WEIGHT = (AWG) (AWG) (Ib/1000 ft) MINIMUM | NOMINAL | NOMINAL | MAXIMUM 55A1121-30-* 30 38 .006 .008 .081 .086 5.4 55A1121-28-* 28 38 .006 .008 .087 .092 6.3 55A1121-26-* 26 38 006 008 097 102 7.9 55A1121-24-* 24 38 006 .008 107 112 9.8 55A1121-22-* 22 38 006 .008 119 125 12.2 55A1121-20-* 20 38 .006 .008 .135 141 16.2 55A1121-18-* 18 38 .006 .008 .155 .162 21.9 55A1121-16-* 16 38 .006 .008 171 178 26.7 55A1121-14-* 14 38 006 008 205 213 38.4 55A1121-12-* 12 38 007 009 243 251 55.1 55A1121-10-* 19 38 007 009 291 306 83.1 55A1121- 8-* 8 36 .008 .010 417 .438 152. CABLE RATINGS AND ADDITIONAL REQUIREMENTS TEMPERATURE RATING: 150C LIFE CYCLE: 200 + 3C for 168 hours Maximum continuous conductor temperature LOW TEMPERATURE-COLD BEND: -65 + 2C for 4 hours VOLTAGE RATING: 600 volts {rms} at sea level SHIELD COVERAGE: 85% (minimum) ACCELERATED AGING: 300 + 3C for 7 hours VOLTAGE WITHSTAND TEST (Post Environmental): BLOCKING: 200 + 3C for 6 hours 1000 volts (rms), 60 Hz, 1 minute DIELECTRIC WITHSTAND: 1500 valts (rms), 60 Hz FLAMMABILITY: Procedure 1, 3 seconds (maximum); 3 inches (maximum); PART NUMBER: no flaming of facial tissue The "*" in the part numbers above shall be replaced by color JACKET COLOR: White preferred code designators with a slash separating the component JACKET ELONGATION AND TENSILE STRENGTH: wire colors and a dash separating the component wire colors Elongation, 50% (minimum) from the jacket color. Tensile Strength, 5000 Ibf/in? (minimum) d/ Example: AWG 22, blue and white component wires; JACKET FLAWS: white jacket: 5541121-22-6/9-9 Spark Test, 1000 volts (rms) Impulse Dielectric Test, 6.0 KV (peak) NOTE: Nominal values are for information only. Nominal values are not requirements. Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice. TE Connectivity 2/so reserves the right to make changes in materials or processing, which do not affect compliance with any specification, without notification to Buyer. 1/ GOLORS AND COLOR CODE DESIGNATGRS SHALL BE IN ACCORDANGE WITH MIL-STD-681. HOWEVER, DUE TO LENGTH LIMITATIONS OF THE RAYCHEM PART NUMBER, AN ALTERNATIVE COLOR CODE MAY REPLACE MIL-STD-681 COLOR CODE DESIGNATORS. (EXAMPLE: "801/002..." MAY BE REPLACED BY "Axxx".) OTHER CODES AND SUFFIXES MAY BE ADDED TO THE PART NUMBER, AS NECESSARY, TO CAPTURE ANY ADDITIONAL REQUIREMENTS IMPOSED BY THE PURCHASE ORDER DIMENSIONS ARE IN INGHES AND, UNLESS OTHERWISE DESIGNATED, ARE NOMINAL a= TE Ay oakatte Aven e Gable Page 1 of 1 , Redwoed City, CA 94063-3800 THIS SPECIFIGATION SHEET TAKES PRECEDENGE OVER DOCUMENTS REFERENCED HEREIN TE Connectivity Phone: 1-300-227-8816 REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID Fay: 1-650-361-6297