SIMATIC
Process Control System PCS 7
PCS 7 Readme V8.1 including SP1
(Online)
Readme
Version: 2015-10-14 (Online)
10/2015
A5E35748131-AB
Security information 1
Overview 2
Notes on installation 3
Notes on usage 4
Software components in
SIMATIC PCS 7 V8.1 incl.
SP1 and changes to PCS 7
V8.1
5
Change history PCS 7
Readme (online) 6
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Siemens AG
Division Process Industries and Drives
Postfach 48 48
90026 NÜRNBERG
GERMANY
A5E35748131-AB
Ⓟ 10/2015 Subject to change
Copyright © Siemens AG 2015.
All rights reserved
Table of contents
1 Security information......................................................................................................................................7
2Overview.......................................................................................................................................................9
3Notes on installation...................................................................................................................................11
3.1 General information................................................................................................................11
3.2 Type of delivery......................................................................................................................13
3.2.1 Delivery package....................................................................................................................13
3.2.2 Notes on the license contract for the SQL server..................................................................13
3.3 Hardware requirements..........................................................................................................14
3.3.1 PC hardware..........................................................................................................................14
3.3.1.1 Recommended PC hardware configuration...........................................................................14
3.3.1.2 Compatibility matrix SIMATIC IPC and accessories for PCS 7 V8.1 incl. SP1......................16
3.3.1.3 Network..................................................................................................................................17
3.3.2 AS hardware..........................................................................................................................17
3.4 Installation of the software, software requirements................................................................18
3.4.1 Software installation...............................................................................................................18
3.4.1.1 Requirements.........................................................................................................................18
3.4.1.2 Notes on installing the software.............................................................................................24
3.4.1.3 Notes on updating the software.............................................................................................26
3.4.2 Microsoft Windows settings....................................................................................................27
3.4.3 Installation of Engineering System (ES) and Operator Station (OS) on a single PC.............27
3.4.4 Installation of SIMATIC NET products...................................................................................27
3.4.5 Use of the Media Redundancy Protocol (MPR) for PROFINET fieldbus...............................28
3.4.6 Settings for standard network adapters (BCE and Softnet)...................................................29
3.4.6.1 Plant bus with TCP/IP protocol..............................................................................................29
3.4.6.2 BCE and time synchronization...............................................................................................29
3.4.7 Installation of older versions of PCS 7 libraries......................................................................29
3.4.8 Using antivirus software and whitelisting protection mechanisms.........................................30
3.4.9 Use of Multi-VGA graphics cards...........................................................................................31
3.4.10 Using a DCF 77 client............................................................................................................31
3.4.11 Shutting down Windows, standby mode / hibernation...........................................................31
3.4.12 SIMATIC Logon......................................................................................................................32
3.4.13 Using smart card readers.......................................................................................................32
3.4.14 Using Microsoft Office............................................................................................................33
3.4.15 Ethernet settings....................................................................................................................33
3.4.16 Changing the storage location for projects/multiprojects.......................................................33
3.4.17 Remote service and remote operation...................................................................................34
3.4.18 Remote access to OS projects...............................................................................................35
3.4.19 Installation of WinAC software...............................................................................................35
3.4.20 Information on changing faceplate style variants from Classic style to APL style for
SIMATIC Batch or Route Control faceplates..........................................................................35
3.5 Licensing................................................................................................................................36
3.5.1 PCS 7 licenses and quantity structures.................................................................................36
3.5.2 Managing AS runtime licenses...............................................................................................36
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 3
4 Notes on usage..........................................................................................................................................37
4.1 Automation system (AS)........................................................................................................37
4.1.1 Switching times for H CPU in connection with a fail-safe application....................................37
4.1.2 ET 200S.................................................................................................................................37
4.1.2.1 ET 200S diagnostics of load voltage failure...........................................................................37
4.1.2.2 ET 200S counter module (article number 6ES7 138-4DA04-0AB0)......................................38
4.1.3 ET 200SP...............................................................................................................................38
4.1.4 ET 200pro..............................................................................................................................38
4.1.5 Using S7 PLCSIM..................................................................................................................38
4.1.6 Changing the address range of HART modules in ET 200iSP/ET 200M/ET 200SP leads
to address displacements......................................................................................................39
4.1.7 Fast Mode functionality for HART devices ............................................................................39
4.1.8 Configuration in RUN (CiR) with FM 350-1, FM 350-2, FM 355, FM 355-2, CP 341.............40
4.1.9 Isochronous mode in PCS 7..................................................................................................40
4.1.10 Fault-tolerant connections via internal ETHERNET/PROFINET interface.............................40
4.1.11 Using PROFINET...................................................................................................................40
4.1.12 Using HART auxiliary variables with 4 F-AI HART modules..................................................41
4.1.13 Using PROFIBUS field devices with IE/PB Link.....................................................................41
4.1.14 Using Foundation Fieldbus (FF).............................................................................................42
4.2 Engineering system (ES).......................................................................................................42
4.2.1 Client engineering..................................................................................................................42
4.2.2 Notes on Configuration in RUN..............................................................................................42
4.2.3 Settings when using two or more network adapters..............................................................42
4.2.4 CFC/SFC: Download of the automation system (AS)............................................................43
4.2.5 Special characters for the nomenclature................................................................................43
4.2.6 Notes on exporting SNMP variables......................................................................................43
4.2.7 Compiling and downloading S7 connections – downloading to an AS...................................44
4.2.8 Download...............................................................................................................................44
4.2.9 Notes on cross AS interconnections......................................................................................44
4.2.10 F-monitoring time of F modules and F field devices after Y Link/DP-PA Link .......................45
4.2.11 Configuration of fail-safe modules in ET 200M PROFINET stations......................................45
4.2.12 Merging projects after distributed editing (multiproject engineering)......................................45
4.2.13 Updating SFC blocks to use new functionality in SIMATIC BATCH......................................46
4.2.14 Note on upgrading process objects of a CPU 410-5H system expansion card.....................46
4.2.15 Using the D7 SYS add-on package.......................................................................................46
4.3 PCS 7 libraries.......................................................................................................................46
4.3.1 Diagnostic alarms for digital input modules SM 321-7BH00 and SM 321-7BH01.................46
4.3.2 Software update to PCS 7 V8.1 incl. SP1..............................................................................47
4.4 Operator station (OS).............................................................................................................47
4.4.1 OS-specific information and notes on installation and use....................................................47
4.4.2 Customized user programs....................................................................................................47
4.4.3 Starting process mode on the OS server...............................................................................48
4.4.4 Deactivating a redundant OS server......................................................................................48
4.4.5 OS change download.............................................................................................................48
4.4.6 Setting access permissions in the operating system.............................................................48
4.4.7 Controls..................................................................................................................................49
4.4.8 User interface and design......................................................................................................49
4.4.9 Delaying the transfer of archives............................................................................................49
4.4.10 Disabling / enabling messages using the WinCC Alarmcontrol.............................................49
4.4.11 Language setting for C scripts...............................................................................................50
Table of contents
PCS 7 Readme V8.1 including SP1 (Online)
4Readme, 10/2015, A5E35748131-AB
4.4.12 Consistency between the plant hierarchy and the Picture Tree Manager for SFC
visualization............................................................................................................................50
4.4.13 Prevent operating system access through key combinations................................................50
4.4.14 Activating OS Runtime on the engineering station (ES)........................................................50
4.5 SIMATIC BATCH...................................................................................................................50
4.5.1 Compiling and loading BATCH with the "Compile and Download Objects" function.............50
4.5.2 Access permissions...............................................................................................................51
4.5.3 Common server for PCS 7 OS and SIMATIC BATCH...........................................................51
4.6 SIMATIC PDM........................................................................................................................51
4.6.1 Using the Device Integration Manager...................................................................................51
4.6.2 Canceling the module redundancy for HART modules of ET 200M remote IOs....................51
4.6.3 Note on project migration.......................................................................................................51
4.7 Process Historian (PH)...........................................................................................................52
4.8 Information Server (IS)...........................................................................................................52
4.9 PCS 7 Web server.................................................................................................................53
4.10 DataMonitor (DM)...................................................................................................................54
4.11 OpenPCS 7............................................................................................................................54
4.12 Redundant systems...............................................................................................................54
4.13 SIMATIC NET........................................................................................................................55
4.14 SIMATIC Management Console............................................................................................56
4.15 SIMATIC PCS 7 Industrial Workstation or SIMATIC IPC.......................................................56
4.16 Microsoft .NET Framework....................................................................................................56
4.17 SIMATIC IPC DiagMonitor.....................................................................................................57
4.18 SIMATIC Safety Matrix and S7 F Systems............................................................................57
5 Software components in SIMATIC PCS 7 V8.1 incl. SP1 and changes to PCS 7 V8.1.............................59
6 Change history PCS 7 Readme (online)....................................................................................................61
Table of contents
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 5
Table of contents
PCS 7 Readme V8.1 including SP1 (Online)
6Readme, 10/2015, A5E35748131-AB
Security information 1
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly that
you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should also
be considered. For more information about industrial security, visit:
Internet link (http://www.siemens.com/industrialsecurity)
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. For more information, visit:
Internet link (https://support.industry.siemens.com)
Version of the security information: Version 3.4 (14 November 2013)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 7
Security information
PCS 7 Readme V8.1 including SP1 (Online)
8Readme, 10/2015, A5E35748131-AB
Overview 2
Note
Read these notes carefully; they contain information that will be important to you and upgrades
to PCS 7.
The information given in this Readme file takes precedence over all the PCS 7 manuals.
You have received the software package SIMATIC PCS 7 with the version V8.1 incl. SP1.
SIMATIC PCS 7 is the future-oriented process control system used in the "Totally Integrated
Automation" concept by Siemens.
Based on robust, industrial standard SIMATIC hardware and software components
Modern, distributed system architecture
Simple and quick system expansion and optimization in runtime
Scalable from a small laboratory system to networks of plants
For all applications: continuous and batch applications
For all industries: process, production and hybrid sectors
Efficient, plant-wide engineering
Flexible and simple integration of field devices and drives based on PROFINET, PROFIBUS
or Foundation Fieldbus
Homogeneously integrated safety technology, certified by the TÜV (German Technical
Inspectorate)
Support for open source interfaces based on international standards such as OPC
Increased availability through redundancy at all levels
Modular structured and scalable batch system, SIMATIC BATCH
Flexible route control system, SIMATIC Route Control
21 CFR Part 11 compliance
We hope that you enjoy using SIMATIC PCS 7 and have great success with it.
Your PCS 7 team
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 9
Overview
PCS 7 Readme V8.1 including SP1 (Online)
10 Readme, 10/2015, A5E35748131-AB
Notes on installation 3
3.1 General information
Information about PCS 7 on the Internet
All product and order information regarding PCS 7:
Internet link (http://www.siemens.com/PCS7)
Overview of the most important technical information and solutions for PCS 7 in the Industry
Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/63481413)
All information on Support and Service in the Industry Online Support:
Internet link (https://support.industry.siemens.com)
Here, you can also subscribe to the newsletter, which keeps you constantly up-to-date with
current information about our products.
Content of the PCS 7 Readme file
The PCS 7 Readme for PCS 7 V8.1 incl. SP1 is available in two versions:
1. PCS 7 Readme (offline)
This is the version that is installed during the PCS 7 setup.
This file only contains general notes and links to documents on the internet.
2. PCS 7 Readme (online)
This is the version which contains all information on the installation and use of PCS 7 in
the format you are already familiar with.
This file is now only available on the internet so that we can keep it up to date.
You can find the current version of this document for download under the entry ID
109474283 in the Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/109474283)
Note
It is vital that you use the information from the most recent version of the PCS 7 Readme
(online) before you begin the installation or use of PCS 7 V8.1 incl. SP1.
Each of the products comes with product-specific information in the form of readme files.
The information contained in these readme files also applies to using products in PCS 7.
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 11
Electronic manuals and help system on PCS 7
Pre-installed manuals
Once you have installed PCS 7 on your computer, the following PCS 7 documentation is
immediately available:
You can find this documentation in the section SIMATIC > Documentation or the product
information in the Start menu of Windows:
PCS 7 - Catalog Overview (PDF)
PCS 7 - Operating Instructions - OS Process Control (PDF)
PCS 7 - Installation Manual - PC Configuration (PDF)
PCS 7 - Configuration Manual - Engineering System (PDF)
PCS 7 - Configuration Manual - Operator Station (PDF)
You can also access this documentation at any time on the SIMATIC PCS 7 DVD 1/2 in the
folder "_Manuals\English" or "_Product_Information\English".
Complete documentation for PCS 7 on the internet and document updates
The complete PCS 7 documentation is available in multiple languages at the following Internet
site:
Internet link (http://www.siemens.com/pcs7-documentation)
You also have the option of updating the installed PCS 7 help system installing the PCS 7
system documentation later. The "PCS 7 Documentation Portal Setup" required for this is
available for download under the entry ID 101140601 in the Industry Online Support:
Download link (https://support.industry.siemens.com/cs/ww/en/view/101140601)
Note
Timeliness of online documents
Documents available online may be more up-to-date than the version of documents installed
with PCS 7 Setup. The statements in documents available online should therefore be given
priority over installed documents.
Information on modified documents
In order to keep yourself informed about changes to the PCS 7 readme and the other PCS 7
documentation, we recommend that you activate the relevant notification in the Industry Online
Support:
Internet link (https://support.industry.siemens.com)
Notes on installation
3.1 General information
PCS 7 Readme V8.1 including SP1 (Online)
12 Readme, 10/2015, A5E35748131-AB
3.2 Type of delivery
3.2.1 Delivery package
The products listed in the table below are delivered with the installation media required for the
respective product:
SIMATIC PCS 7 DVD:
2 DVDs in a jewel case or as software download
Certificate of License
or
SIMATIC PCS 7 DVD ASIA:
2 DVDs in a jewel case
Certificate of License
The license keys required to operate the software for the supplied product are located on the
License Key memory stick.
To simplify your license management, you can also save the license keys for other SIMATIC
PCS 7 products on this memory stick. Authorizations for older SIMATIC products must be
saved on authorization disks.
3.2.2 Notes on the license contract for the SQL server
Note that SIMATIC PCS 7 also includes the SQL Server software licensed by Microsoft
Corporation. With the use of SIMATIC PCS 7, you agree to be bound by and to abide by the
attached Microsoft terms and conditions for end customers for the Microsoft SQL Server.
The Microsoft "SQL Server" supplied with PCS 7 may not be used outside the PCS 7
environment without prior written consent from Siemens.
Notes on installation
3.2 Type of delivery
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 13
3.3 Hardware requirements
3.3.1 PC hardware
3.3.1.1 Recommended PC hardware configuration
Recommended basic hardware configuration
We recommend the following configuration for PC components (the higher the quality of the
equipment, the better):
Parameters Central engineering station with server oper‐
ating system, Process Historian1), Informa‐
tion Server,
PCS 7 OS / SIMATIC BATCH / SIMATIC
Route Control on a PC,
Engineering station,
OS server,
OS single station,
Maintenance Station,
PCS 7 Web server, OS client, and BATCH
client on a PC,
BATCH server,
BATCH single station,
Route Control server,
Route Control single station
OS client,
BATCH client,
Route Control client
Basic PC (see catalog) SIMATIC IPC 847C / 847D / 647C / 647D /
547D / 547E
SIMATIC IPC 847C / 847D / 647C /
647D / 547C / 547D / 547E
Processor min. INTEL Core 2 Duo; >=2.4GHz, INTEL Core 2 Quad
Work memory (RAM) 4 GB (32-bit operating system)
>=6 GB (64-bit operating system)
4 GB (32-bit operating system)
>=4 GB (64-bit operating system)
Hard disk
Partition size
>=200 GB HDD/SSD
C:\ 100 GB
>=160 GB HDD/SSD
C:\ 100 GB
Network adapter/communica‐
tions interfaces
For terminal bus
communication
For plant bus communication
RJ45 on-board gigabit Ethernet
CP 1613 A2 / CP 1623 or BCE network
adapter for engineering station and OS
server
RJ45 on-board gigabit Ethernet
Opt. drive DVD DVD
Parameters OS client
Basic PC (see catalog) SIMATIC IPC427C / IPC427D / IPC477D
Processor Intel Core2 Duo / Intel Core i7-3517UE
Notes on installation
3.3 Hardware requirements
PCS 7 Readme V8.1 including SP1 (Online)
14 Readme, 10/2015, A5E35748131-AB
Parameters OS client
Work memory (RAM) 4.0 GB
Hard disk
Partition size
>=200 GB HDD or >=50 GB SSD
C:\ 100 GB HDD or >=C:\ 35 GB SSD
Network adapter/communications
interfaces
2 x RJ45 on-board Gigabit Ethernet
without PROFINET or PROFIBUS interface
Purpose Approved for OS/Batch client operation only
We recommend the following configuration for Box / Microbox components (the higher the
quality of the equipment, the better):
Parameters SIMATIC IPC627C / IPC677C / IPC627D /
IPC677D
SIMATIC IPC427C / IPC427D
Processor min. Intel Core i7-610E Prozessor Intel Core2 Duo / Intel Core i7-3517UE
Clock-pulse rate 2.53 GHz >=1.2 GHz
Work memory (RAM) 4.0 GB 2.0 - 4.0 GB
Hard disk
Partition size
>=200 GB HDD / SSD
C:\ 100 GB
Compact Flash card: 8.0 GB / SSD: 80
GB
Network adapter/communica‐
tions interfaces
2 x RJ45 on-board Gigabit Ethernet
onBoard PROFIBUS CP 5611 / CP 5622
onBoard PROFINET CP 1616
2 x RJ45 on-board Gigabit Ethernet
onBoard PROFIBUS CP 5611 /
CP 5622
onBoard PROFINET CP 1616
Opt. drive DVD -
Purpose SIMATIC IPC627C / IPC677C / IPC627D /
IPC677D (BOX PC) is released as part of the
PCS 7 BOX systems.
PCS 7 AS RTX based on SIMATIC
IPC427C / IPC427D only released for AS
operation.
Note
Please note the following:
In the case of multiproject engineering, it is beneficial for the engineering stations if you
use PCs with high clock-pulse rates, large main memories and hard disks, and high-speed
disk drives. In addition to the Microsoft recommendation of "15% free space", we
recommend that you reserve at least 2 GB of free space (depending on the size of the
project) on the system partition.
1) When using the Process Historian, also read the notes in the "Hardware requirements"
section in the Process Historian 2014 SP1 installation manual.
Additional information
Catalog
ST PCS 7 for V8.1
Add-on catalog
ST PCS 7 for V8.1
Notes on installation
3.3 Hardware requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 15
3.3.1.2 Compatibility matrix SIMATIC IPC and accessories for PCS 7 V8.1 incl. SP1
Compatibility matrix SIMATIC IPC and accessories for PCS 7 V8.1 incl. SP1
PCS 7 V8.1 incl. SP1 MLFB Windows
Embedded
Standard 2009
Windows 7
Ultimate / Enter‐
prise
32bit SP1
Windows 7
Ultimate / Enter‐
prise
64bit SP1
Windows Serv‐
er
2008 R2 Stand‐
ard
64bit SP1
RACK IPC
IPC547C 6ES7 660-0....-.... - X
(OS client only)
- -
IPC547D 6ES7 660-3....-.... - - X X
IPC547E 6ES7 660-4....-.... - - X X
IPC647C 6ES7 660-1....-.... - - X X
IPC647D 6ES7 660-5....-.... - - X X
IPC847C 6ES7 660-2....-.... - - X X
IPC847D 6ES7 660-6....-.... - - X X
BOX IPC
IPC627C, IPC677C BOX
with/without RTX 2010
6ES7 650-4A...-.... - X - -
IPC627D, IPC677D BOX
with/without RTX 2010
6ES7 650-4B...-.... - X
(with WinAC
RTX)
X
(without WinAC
RTX)
-
Microbox
IPC427B, AS RTX (RTX
2008)
6ES7 654-0UE12-0X
X0
X - - -
IPC427C, AS RTX (RTX
2010)
6ES7 654-0UE13-0X
X0
X - - -
IPC427C, OS clients 6ES7 650-0RG..-.... - X - -
IPC427D, AS RTX (RTX
2010)
6ES7654-0UE23-0X
X1
6ES7654-0UE23-0X
X2
- X - -
IPC427D, IPC477D OS cli‐
ents
6ES7 650-0UG..-.... - - X -
CPs
CP 1613 A2 6GK1 161-3AA01 - X X X
CP 1623 6GK1 162-3AA00 - X X X
CP 1628 6GK1 162-8AA00 - - X X
Accessories
Notes on installation
3.3 Hardware requirements
PCS 7 Readme V8.1 including SP1 (Online)
16 Readme, 10/2015, A5E35748131-AB
PCS 7 V8.1 incl. SP1 MLFB Windows
Embedded
Standard 2009
Windows 7
Ultimate / Enter‐
prise
32bit SP1
Windows 7
Ultimate / Enter‐
prise
64bit SP1
Windows Serv‐
er
2008 R2 Stand‐
ard
64bit SP1
Redundant terminal bus
adapter package PCIe
6ES7 652-0XX01-1X
F1
- X X X
Multi monitor card X2 (M
series) PCIe
6ES7 652-0XX04-1X
E0
- X X X
Multi monitor card X4 (M
series) PCIe
6ES7 652-0XX04-1X
E1
- X X X
SIMATIC PCS 7 USB smart
card reader (OK3121)
6ES7 652-0XX02-1X
C0
- X
(with SIMATIC
Logon)
X
(with SIMATIC
Logon)
X
(with SIMATIC
Logon)
Signal module, PCI card for
installation in an operator
station
6DS1 916-8RR - X X X
3.3.1.3 Network
Network configuration
The network for the PCS 7 systems must be isolated via switches, routers or gateways in such
a way that no external interference can affect the PCS 7 network.
You can find recommendations for this in the document:
PCS 7 Security Concept PCS 7 & WinCC (Basic)
The document is available for download under the Entry ID 60119725 in the Industry Online
Support:
Download link (https://support.industry.siemens.com/cs/ww/en/view/60119725)
3.3.2 AS hardware
Documentation on hardware
The versions of the AS hardware components that are approved for PCS 7 V8.1 incl. SP1 are
described in the manual "PCS 7 - Released Modules". This document is located on the website
for SIMATIC PCS 7 Technical Documentation:
Internet link (www.siemens.com/pcs7-documentation)
Notes on installation
3.3 Hardware requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 17
CPUs 6ES7 414-3EM05-0AB0, 6ES7 416-3ER05-0AB0, 6ES7 414-3EM06-0AB0 and
6ES7 416-3ES06-0AB0
Time synchronization
These CPU types can only be synchronized using the NTP method when using the internal
ETHERNET/PROFINET interface. We recommend that you use the central SICLOCK TC
400 system clock. For the previous CPU types, we continue to recommend that you use
the SIMATIC mode.
You can find notes on SICLOCK TC 100 / TC 400 in the function manual "PCS 7 – Time
synchronization".
This document is located on the website for SIMATIC PCS 7 Technical Documentation:
Internet link (www.siemens.com/pcs7-documentation)
3.4 Installation of the software, software requirements
3.4.1 Software installation
3.4.1.1 Requirements
Released operating systems
The following operating systems are supported in PCS 7 V8.1 incl. SP1 :
Windows 7 Ultimate / Enterprise SP1 (32Bit)
Windows 7 Ultimate / Enterprise SP1 (64Bit)
Windows Server 2008 R2 SP1 Standard Edition (64 Bit)
Note
Released processor architectures
Only the x64 platform is used for processor architectures which support 64-bit memory
addressing.
Systems with Intel Itanium CPU architecture (IA64) are not supported.
Not all configurations are suitable for every operating system. The following table shows the
relationship of the most common configurations of PCS 7 to the operating systems. Before
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
18 Readme, 10/2015, A5E35748131-AB
performing the installation, refer to the product-specific readme files to ensure that the product
being installed is suitable for the desired operating system.
Windows
Embedded
Standard 2009
Windows 7
Ultimate / Enter‐
prise
32bit SP1
Windows 7
Ultimate / Enter‐
prise
64bit SP1
Windows Server
2008 R2 Standard
64bit SP1
ES X X X
OS-Single Station X X X
ES/OS-Single Station X X X
OS-Server X
OS-Client X X X
Web-Server X1) X1) X
Web-Client X X X
Process Historian X2)
Information Server X X X
SIMATIC Management Console X X X
SIMATIC Batch Single Station X X
SIMATIC Batch Client X X X
SIMATIC Batch Server X
PCS 7 BOX X X
PCS 7 BOX RTX X
OS-Client Microbox X X
PCS 7 AS mEC RTX X
PCS 7 AS RTX X X
1) only on ES or OS single-station system
2) Also with Windows Server 2008 R2 Enterprise Edition
Microsoft Internet Explorer
Only Internet Explorer 11 is permitted.
Internet link (http://windows.microsoft.com/en-US/internet-explorer/ie-11-worldwide-
languages)
Note:
Internet Explorer 11 attempts to automatically install the required Microsoft Patches (KB)
during the installation. If this installation fails, for example because no Internet connection can
be made, the installation procedure is aborted. In this case, you need to install the required
KBs manually before you can install Internet Explorer 11.
Internet link (http://support.microsoft.com/kb/2872074)
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 19
Microsoft .NET Framework
The Microsoft. NET Framework feature must be enabled prior to the installation of the PCS 7
software for operating systems based on Windows 7 and Windows Server 2008 R2.
For Windows 7 under: Control Panel -> Programs and Features -> Turn Windows features
on or off
For Windows Server 2008 R2 under: Control Panel -> Programs and Features -> Turn
Windows features on or off -> Server Manager -> Features
Microsoft SQL Server
The Microsoft SQL Server 2008 R2 Service Pack 2 is installed automatically by the PCS 7
system setup. The computer name must be set before SQL Server is installed. The computer
name must not be changed afterwards.
Notes on installing the operating system
Before installing PCS 7, ensure that the correct operating system variant for the planned PCS 7
role is installed on the computer. If needed, re-install the operating system for the computer.
The use of tools such as Windows Easy Transfer to transfer data and settings between different
operating systems or to perform a direct upgrade from Windows Vista to Windows 7 has not
been approved.
The use of the following operating system features has not been approved for PCS 7:
XP mode (only available with Windows 7)
HomeGroup (only available with Windows 7)
Parental Control (only available with Windows 7 Ultimate)
Windows Defender
BitLocker
Fast User Switching (The use of this feature can be disabled by the administrator via a
group policy. You can find additional information on the procedure on the SIMATIC PCS 7
DVD 1/2 in the folder _Manuals\English "PCS 7 - PC Configuration.pdf" in the section "How
to disable user switching")
Using INTEL network adapters
If you use an INTEL network adapter, install the driver corresponding to your device type and
operating system variant located on the "PCS 7 Software Support & Tools DVD 2014.02" in
the separately available "PCS 7 V8.x Software Support Package" (article number
6ES7 650-4XX08-0YT8) under "01_Drivers\NETWORK\Intel".
Windows Software Update Service (WSUS)
The WSUS cannot install software versions that are not described in this document as a
minimum system requirements. This includes service packs for Microsoft operating systems,
SQL Server, Office or new versions of Internet Explorer.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
20 Readme, 10/2015, A5E35748131-AB
This guideline does not apply to security patches published under entry ID 18490004:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/18490004)
Permitted domain controllers (DC)
Domain Controller (DC) based on Windows Server 2008 R2 SP1 (Standard Edition)
Domain Controller (DC) based on Windows Server 2012 R2 (Standard Edition)
Operating system languages
When you use PCS 7, you will have to set the required language and region at every point in
the Windows language settings. This affects all the settings available under “Region and
Language”.
If you use PCS 7 ASIA, make the following settings in the Windows regional and language
options:
Select "Chinese (PRC)" for "Language for non-Unicode programs". You need to make these
settings before installing the PCS 7 software.
For the "Display language", select "English (USA)" if you have set the language of the
PCS 7 user interfaces to English.
For the "Display language", select "English (USA)" or "Chinese (Simplified)" if you have set
the language of the PCS 7 user interfaces to Chinese.
For the "Format", select "Chinese (PRC)".
Rules for computer names
The selection of the computer name is critical for the entire project configuration:
Invalid characters: . , ; : ! ? " ' ^ ´ ` ~ - + = / \ ¦ @ * # $ % & § ° ( ) [ ] { } < > space character,
hyphen ("-"), underscore ("_")
Max. 15 characters
Uppercase letters only
The first character must be a letter.
It is always advisable that only alphanumeric characters are used for the computer name. You
should choose a name consisting of uppercase Latin letters (A-Z) and digits (0-9) only, starting
with a letter and containing a maximum of 15 characters.
Before installing the PCS 7 software
Message queuing must be installed for PCS 7.
When required, the following Microsoft Patches are installed automatically by the PCS 7
system setup depending on the installed operating system and type of installation:
KB979231 for Windows Server 2008
KB2483185 for Windows Server 2008
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 21
KB908002 for Microsoft .NET Framework 2.0
KB2905569 for 64-bit operating systems (installation of this Microsoft patch requires a
restart of the computer)
KB2516889 for Windows Server 2008 R2 and Windows 7
KB2554746 for Windows Server 2008 R2 and Windows 7 (installation of this Microsoft patch
requires the computer to be rebooted)
KB2938478 for Windows Server 2008 R2
Security settings
You can find information about the security settings in the "_Manuals\English" folder, "PCS 7
- PC Configuration.pdf" file on the SIMATIC PCS 7 DVD 1/2 in the sections "Security settings
for the PC configuration" and "Firewall".
Settings need to be made in the registry, the DCOM configuration and the exception list of the
Windows firewall for the PCS 7 software to operate correctly.
Before the installation begins, the "Setup - System Settings" dialog appears. There, the system
settings to be changed are listed. To continue the setup, you need to agree to the change to
these system settings.
Note
Please note the following:
The settings must be applied again if the work environment changes (domain, workgroups)
using the menu command Start > Program Files > Siemens Automation > Security
Controller > Repeat Settings . Start the Security Controller after the PC has been added to
the domain and rebooted. Remember that the Windows services that are required for the
Security Controller are not immediately available after Windows logon. If the tool is started
without entries,restart it after a brief interval.
The settings in the exception list of the Windows firewall are applied to the area of the local
network (subnet). If your PC stations are located in different networks (subnets), you need
to change this area manually and make this change again after each execution of the
"Security Controller".
If you need to make local Windows firewall settings that differ, they should be adapted
afterwards.
The settings in the exception list of the Windows firewall are made when the Windows
firewall is disabled.
Security patches
You can find information on the use of the latest Microsoft security patches in the Industry
Online Support under entry ID 18490004:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/18490004)
To ensure secure and stable operation of the operating system and therefore PCS 7, we
recommend the installation of "Security Updates" and "Critical Updates".
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
22 Readme, 10/2015, A5E35748131-AB
Activation of the revised Windows Authenticode signature verification
The change of the Windows Authenticode signature verification described in Microsoft Security
Advisory 2915720 cannot be activated in PCS 7.
Internet link (https://technet.microsoft.com/library/security/2915720)
Additional information on the topic of industrial security and plant security
You can find additional documents and information on the topic of industrial security and plant
security in the Industry Online Support, in the "All-round protection with Industrial Security -
Plant Security" entry list and the "PCS 7 Compendium Part F - Industrial Security" document:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/50203404)
Internet link (https://www.siemens.com/industry/onlinesupport/pcs7)
OPC XML DA
OPC XML DA has not been released.
Setting the permissions for restarting the system
When using Windows Server operating systems, users without administrator rights must be
provided authorization for "System Shutdown".
Without these rights, the system cannot be restarted.
As an administrator, you can set the permission for other user groups using a group policy as
follows:
1. In the Windows Start menu, open the "Run" dialog box and enter gpedit.msc.
2. In the "Group Policy Object Editor" dialog box, select the folder "Local Computer Policy >
Computer Configuration > Windows Settings > Security Settings > Local Policies > User
Rights Assignment."
3. Add the required user groups for the "System Shutdown" object.
Notes on installing the software via a network
To be able to install on multiple computers at the same time, you need to make the contents
of the two SIMATIC PCS 7 DVDs available in one storage location (shared network path).
The following rules apply to the storage:
The folders must be called "DVD_1" and "DVD_2" and must be located within a shared
folder (see example).
The name of the access path to the network copy of the DVDs (including the folder "DVD_1"
or "DVD_2") cannot contain more than 85 characters.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 23
Example:
Create a network copy of the two SIMATIC PCS 7 DVDs with the following structure:
…\PCS7_Vxx\
DVD_1\
DVD_2\
Use of additional software for creating and viewing PDF documents
The PDF-XChange 5.5.x software for creating and viewing PDF documents has been tested
for compatibility with PCS 7 V8.1 incl. SP1 and can be installed subsequently.
3.4.1.2 Notes on installing the software
New installation
There are two possible ways to install PCS 7:
1. Installation of a previously backed up image of the operating system.
This image cannot contain a PCS 7 installation.
You can then install PCS 7 on this image.
2. New installation of the operating system followed by new installation of PCS 7.
You can find detailed information about the installation requirements and procedure in the
"PCS 7 - PC Configuration.pdf" document located in the "_Manuals\English" folder on the
SIMATIC PCS 7 DVD 1/2.
Steady state
During the installation of the PCS 7 software, the system must be in steady state:
Make sure that no updates are being performed for antivirus software or the Windows Software
Update Services (WSUS) during the installation. You can ensure this by temporarily disabling
the corresponding options in each program.
Installation on computers with multi-core processor
When you install the PCS 7 software on PC hardware with multi-core processors in which the
number of processors does not equal 2n, or when you use NUMA (Non Uniform Memory
Access), you must follow the instructions under entry ID 59703368:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/59703368)
PC hardware based on SIMATIC IPC recommended for PCS 7 is not affected by this.
Installation via network
When performing a network installation of PCS 7 on computers with an operating system based
on Windows 7 and Windows Server 2008 R2, ensure that access to the setup procedure is
guaranteed, even if the computer reboots during the PCS 7 Setup. If the computer is not in a
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
24 Readme, 10/2015, A5E35748131-AB
domain, you must enter the logon information of the user in order to access the network share
for the server in the Windows Credential Manager.
Installation of keyboard filter for 32-bit operating systems
Once the PCS 7 software has been successfully installed, you are prompted to reboot the
computer. When you subsequently log on with user or power user rights, you may see a dialog
for installing the drivers for "Keyboard_Filter_01" or "Keyboard_Filter_02". Enter the name and
password for a user with administrator rights in this dialog and confirm the dialog with "OK".
Close the Internet Explorer (IE11) before starting the installation
Before starting the PCS 7 Setup, make sure you have correctly closed IE11. Close any
processes still running (ieexplore.exe), for example, using the Windows Task Manager.
Installation via SIMATIC Management Console
You cannot install the following products from the "Additional_Products" folder of the SIMATIC
PCS 7 DVD 2/2 using the SIMATIC Management Console:
DiagMonitor
MTU
ReportBuilder3
SDT_2014_3
SimaticRights
You can find a list of all products and PCS 7 components that can be installed via the SIMATIC
Management Console under entry ID 107796665 in Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/107796665)
Installation of the SIMATIC Management Agent
The SIMATIC Management Agent is automatically installed with every installation of PCS 7 to
facilitate the integration of your computers in a plant managed with the SIMATIC Management
Console.
However, if the SIMATIC Management Agent has not been selected for installation, the
corresponding service with the same name is deactivated subsequently. The computer cannot
be managed through the SIMATIC Management Console in this state.
To enable its active use, proceed as follows:
1. Select the following depending on your operating system
Windows 7: "Computer Management > Services and Applications > Services".
Windows Server 2008 R2: "Server Manager > Configuration > Services".
2. Open the Properties dialog by double-clicking on "SIMATIC Management Agent".
3. Change the "Startup type" to "Automatic".
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 25
4. Start the service by pressing the "Start" button.
5. Click "OK" to close the dialog.
3.4.1.3 Notes on updating the software
Updating PCS 7 projects
When updating the software, read the manuals "Software Updates Without Utilization of New
Functions" or "Software Updates With Utilization of New Functions". You can find both of these
documents on the website for SIMATIC PCS 7 Technical Documentation:
Internet link (www.siemens.com/pcs7-documentation)
Software update with utilization of new functions from the PCS 7 Advanced Process Library
A software update of the Advanced Process Library (APL) from a version older than V8.1 to
V8.1.x with utilization of new functions can only be performed in STOP operating mode of the
AS and complete compilation of the OS.
You can find detailed update information in the Advanced Process Library Readme (V8.1.x).
Updating the PCS 7 Software
Computer reboot
If you use the "Update" function in the PCS 7 setup, we recommend you reboot the PC before
performing the installation.
During the software update, there may be some instances when a message appears prompting
you to reboot your PC. Reboot the PC. The installation is then automatically continued.
INTEL network adapter
If you use an INTEL network adapter, install the driver corresponding to your device type and
operating system variant located on the "PCS 7 Software Support & Tools DVD 2014.02" in
the separately available "PCS 7 V8.x Software Support Package" (article number
6ES7 650-4XX08-0YT8) under "01_Drivers\NETWORK\Intel" .
Updating a redundant Process Historian system
PCS 7 V8.1 incl. SP1 contains the version "Process Historian 2014 SP1".
If you want to update the Process Historian to this version, follow the instructions in the Process
Historian readme file, section 5.2 "Upgrading the Process Historian as a redundant system".
You can find the file "InstallNotesPRHIenEN.pdf" on the SIMATIC PCS 7 DVD 1/2 in the
"27b_PH+IS_Install_and_Release-Notes" folder.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
26 Readme, 10/2015, A5E35748131-AB
Updating a Process Historian System V8.0 Update 1
An update of Process Historian V8.0 Update 1 (included in PCS 7 V8.0 incl. Update 1) to
version 2014 SP1 (included in PCS 7 V8.1 incl. SP1) must be performed in an intermediate
step.
First, Process Historian V8.0 Update 1 must be updated to version 2013 (included in PCS 7
V8.0 SP1 and PCS 7 V8.0 SP2) before version 2013 is updated to version 2014 incl. SP1 in
the next step.
3.4.2 Microsoft Windows settings
General information
You can find information about the settings on the SIMATIC PCS 7 DVD 1/2 in the folder
_Manuals\English in the document "PCS 7 - PC Configuration.pdf".
Settings for the Microsoft Internet Information Service (IIS)
The Internet Information Service is a prerequisite for the installation and use of certain PC
stations (Web server, Information Server).
You can learn about the settings required to configure the IIS in the documentation for the
respective product used (e.g. the Web server installation instructions). You also need to read
the information on configuration of the IIS in the document "PCS 7 - PC Configuration.pdf".
3.4.3 Installation of Engineering System (ES) and Operator Station (OS) on a single
PC
If you wish to install an ES on an existing OS, it is absolutely essential to remove the installed
PCS 7 OS version first and then perform the "Engineering Station" installation.
3.4.4 Installation of SIMATIC NET products
Installation of the SIMATIC NET product
SIMATIC NET is a product which always has to be installed by the system setup for PCS 7.
Installation of the SIMATIC NET SOFTNET-IE RNA V12.0 product
The SIMATIC NET SOFTNET-IE RNA V12.0 product can be installed directly through the
PCS 7 system setup.
See also entry ID 77377603
Internet link (https://support.industry.siemens.com/cs/ww/en/view/77377603)
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 27
Possible applications for the SCALANCE S, CP 443-1 Advanced and CP 1628 security products in the
PCS 7 environment
You can learn how to use the SIMATIC security products SCALANCE S, CP 443-1 Advanced
and CP 1628 with PCS 7 from entry ID 67329379 in Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/67329379)
3.4.5 Use of the Media Redundancy Protocol (MPR) for PROFINET fieldbus
Network topologies
It is absolutely necessary to operate the PROFINET fieldbus ring with MRP (Media
Redundancy Protocol) when using rings with PROFINET. The media redundancy protocols
HRP (High Speed Redundancy Protocol) and MRP cannot be used simultaneously in the same
ring. The PROFINET fieldbus ring may only consist of devices that support MRP functionality.
The following Industrial Ethernet switches support the MRP function:
SCALANCE X-200 as of Firmware-Version V4.0
SCALANCE X-300 as of Firmware-Version V3.0
SCALANCE X-400 as of Firmware-Version V3.0
HRP
High Speed Redundancy
Protocol
MRP
Media Redundancy
Protocol
Separate terminal and plant bus X -
Common terminal and plant bus X -
PROFINET fieldbus - X
Configuration of the watchdog time
In the event of a transmission line failure, reconfiguration of the network (switching to the
redundant transmission line) can take up to 200 ms.
Increase the watchdog time for each station by:
Selecting the "Fixed update time" setting
Increasing the update time to a value that is smaller than the fastest update of the process
image partition (PIP) for this station
Increasing the number of accepted update cycles with missing I/O data, so that the
watchdog time is > 200 ms
See also Entry ID 46636225
Internet link (https://support.industry.siemens.com/cs/ww/en/view/46636225)
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
28 Readme, 10/2015, A5E35748131-AB
3.4.6 Settings for standard network adapters (BCE and Softnet)
3.4.6.1 Plant bus with TCP/IP protocol
Make the following settings for the plant bus:
Disable "File and Printer Sharing for Microsoft Networks"
Disable "Client for Microsoft Networks"
Activate the "SIMATIC Industial Ethernet (ISO)" log
Refer to the information in the PCS 7 Engineering System Configuration Manual, PCS 7
Operator Station Configuration Manual and the WinCC Information System: "Special aspects
of communication in a server with multiple network adapters".
3.4.6.2 BCE and time synchronization
When synchronizing the time via BCE, select the following settings:
1 - 10 sec. intervals on the external time transmitter.
The ISO protocol be installed and enabled for the network adapter.
Only a network adapter (BCE) can be used for time synchronization on an OS.
Otherwise, the settings and information for CP 1613 in the "PCS 7 time synchronization"
manual apply to the time synchronization.
When using time synchronization with BCE, the following destination address multicast
must be used: address 09-00-06-01-FF-EF.
Broadcast may not be used.
You can find additional information about the configuration of time synchronization in a PCS 7
plant in the manual "PCS 7 time synchronization".
3.4.7 Installation of older versions of PCS 7 libraries
If you install or remove an older version of the PCS 7 Library, PCS 7 Basis Library or PCS 7
Advanced Process Library following the installation of PCS 7 V8.1 incl. SP1 , you must re-
install the current versions of PCS 7 Basis Library or PCS 7 Advanced Process Library by
means of the PCS 7 system setup afterwards. Do not use the product setup of these libraries
to do this. This applies, for example, toPCS 7 libraries, which are located in the
Additional_Products folder of SIMATIC PCS 7 DVD 2/2.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 29
3.4.8 Using antivirus software and whitelisting protection mechanisms
Approved antivirus software
An overview of the approved virus scanners for each version of the software is available in the
Internet under entry ID 64847781:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/64847781)
You can find additional documents and information on the topic of industrial security and plant
security in the Industry Online Support, in the "All-round protection with Industrial Security -
Plant Security" entry list:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/50203404)
The following virus scanners have been tested for compatibility with PCS 7 V8.1 incl. SP1 and
can be installed subsequently even with an existing PCS 7 installation:
Trend Micro OfficeScan V11.0
Symantec Endpoint Protection V12.1.5
McAfee VirusScan Enterprise V8.8
Using Whitelisting protection mechanisms
Existing anti-malware protection for PC systems, from anti-virus programs for example, can
be effectively supplemented with Whitelisting protection mechanisms.
Whitelisting mechanisms provide additional protection for the installation of PC systems by
prohibiting the execution of unauthorized software or modification of installed applications.
Additional security applications are installed to enable such protection.
The following Whitelisting software has been tested for compatibility with PCS 7 V8.1 incl.
SP1:
McAfee Application Control V6.1.3
You can find more information about the "Utilization of Whitelisting with McAfee Application
Control in a PCS 7 / WinCC environment" in Industry Online Support under entry ID 88653385:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/88653385)
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
30 Readme, 10/2015, A5E35748131-AB
3.4.9 Use of Multi-VGA graphics cards
The following graphics cards and drivers are recommended for PC stations in PCS 7:
Windows 7 (32-bit) Windows 7 (64-bit)
Windows Server 2008 R2 (64-
bit)
M9120 Plus LP PCIe x16 (widescreen
resolution possible)
Article number:
6ES7 652-0XX04-1XE0
wddm32_404_03_002_whql.
exe
wddm64_404_03_002_whql.
exe
M9140 LP PCIe x16 (widescreen reso‐
lution possible)
Article number:
6ES7 652-0XX04-1XE1
wddm32_404_03_002_whql.
exe
wddm64_404_03_002_whql.
exe
Updating the BIOS graphics card
For M-series devices (Matrox_M91x0LP), we recommend updating the BIOS graphics card to
version 2.00.17.02:
Unzip the file "setup_pm200_17_002.exe" to a temporary folder with a double click.
Follow the instructions in the file "readme.txt", which you will find in the unzipped folder, for
the installation.
Availability of drivers and BIOS
You can find the drivers and the BIOS on the "PCS 7 Software Support & Tools DVD 2014.02"
in the separately available "PCS 7 V8.x Software Support Package" (article number:
6ES7 650-4XX08-0YT8) in the folder "01_Drivers\DISPLAY".
Detailed information is available on the SIMATIC PCS 7 DVD 1/2 in the folder _Manuals
\English in the section "How to activate a multi-VGA graphics card" of document "PCS 7 - PC
Configuration.pdf".
3.4.10 Using a DCF 77 client
Install the latest version V2.00 when using the DCF 77 client service. It is available on the
"PCS 7 Software Support & Tools DVD 2014.02" in the separately available "PCS 7 V8.x
Software Support Package" (article number: 6ES7 650-4XX08-0YT8) in the folder
"02_Timesynchronization\DCF77Client_V2.00".
Install "DCF 77 Client V2.00" with the default settings of the setup program.
3.4.11 Shutting down Windows, standby mode / hibernation
Whenever you shut down Windows on your PCS 7 computers, use the command "Start >
Shutdown Computer" and then select "Shutdown" or "Restart".
Do not use "standby mode" and "idle state".
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 31
3.4.12 SIMATIC Logon
SIMATIC Logon
The term "SIMATIC Logon Admin Tool" has been replaced by "SIMATIC Logon Role
Management".
Note on the use of smart cards
Make sure that you re-format all smart cards that were formatted with SIMATIC Logon < V1.3.
This is necessary because SIMATIC Logon uses improved encryption for smart cards as of
V1.3. If you attempt to log on with a smart card that is not updated, the attempt will fail. You
can always log on with your name and password via the keyboard, however.
If you log on with a smart card and then remove this during configuration in the SIMATIC Logon
role management, all changes you have made up to this point and not saved will be discarded.
Reinserting the card will not solve this problem.
Notes on the Windows workgroup
If you require high availability, you need to work in a domain environment, since no redundancy
is offered by SIMATIC Logon in a Windows workgroup.
Notes on the SIMATIC Logon Event Log Viewer
If you want to print the events in the event log, proceed as follows:
Click "Export" and export the events in PDF format.
Print out the exported file.
Instead of the file size of the event log, the number of recorded events corresponding to the
configured filter is displayed.
The filter dialog always shows the date and time based on the settings you have selected for
the date and time in Windows. Display in conformity to ISO 8601 is not possible.
3.4.13 Using smart card readers
When using the USB smart card reader, use the drivers on the "PCS 7 Software Support &
Tools DVD 2014.02" in the separately available "PCS 7 V8.x Software Support Package"
(article number: 6ES7 650-4XX08-0YT8) in the folder "01_Drivers\CHIPCARD".
Driver:
Windows 7 (32-bit) Windows 7 (64-bit)
Windows 2008 R2 (64-bit)
OMNIKEY CardMan 3121 USB OMNIKEY3x21_V1_2_6_5.exe OMNIKEY3x21_V1_2_6_5_x64.exe
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
32 Readme, 10/2015, A5E35748131-AB
3.4.14 Using Microsoft Office
The following Microsoft Office products have been tested for compatibility with PCS 7 V8.1
incl. SP1 :
Microsoft Office Professional 2010 32-bit SP2 (Excel, Word, Access and PowerPoint)
Microsoft Office Professional 2013 32-bit SP1 (Excel, Word, Access and PowerPoint)
Word Viewer 2003 SP3
Excel Viewer 2007 SP2
PowerPoint Viewer 2010
The Microsoft Office applications Word, Excel, and Access can be used in process mode on
client computers (OS, BATCH, Maintenance, WEB). However, their use may result in
significantly reduced performance in some situations. Office must not be used in process mode
on any other operator stations and BATCH stations.
You can find information on the compatibility of SIMATIC PCS 7 in the Industry Online Support
under entry ID 64847781:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/64847781)
3.4.15 Ethernet settings
Make sure there are no inconsistencies in Ethernet CPs, switches and network adapters in
terms of their settings/properties for data transmission rate and bus access procedure.
We recommend using the default Autonegotiation setting (procedure for the automatic
negotiation of the best transmission mode between two network interfaces which are directly
connected to one another).
You can find information in the section "How to change the transmission rate and operating
mode in the PC network" of the document "PCS 7 - PC Configuration.pdf" located on the
SIMATIC PCS 7 DVD 1/2 in the folder _Manuals\English.
3.4.16 Changing the storage location for projects/multiprojects
The project path in "Storage location for projects/multi-projects" is set by default to "SIEMENS
\STEP7\S7Proj" and all necessary access rights are set for this project path.
If you use another project path, you need to set the necessary access rights using the
"SimaticRights.exe" tool.
To do this, start the "SimaticRights.exe" program in the folder "Additional_Products
\SimaticRights" on the SIMATIC PCS 7 DVD 2/2 as an administrator. Enter the new project
path or select it in the dialog. The new project path must be available when the tool starts.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 33
3.4.17 Remote service and remote operation
Use of the Remote Desktop Protocol (RDP) is permitted only for remote maintenance of PCS 7
OS clients. The RealVNC software should be used for remote access to other computers in a
distributed PCS 7 plant (for example, OS servers, engineering stations). Only one remote
session is allowed per PCS 7 station at any given time.
RDP
Note the following constraints when using RDP:
No server services (for example, WebNavigator server, DataMonitor server, OPC server)
are permitted to be active on the PCS 7 OS clients. The reason for this lies in the handling
of remote desktop sessions by the Microsoft operating system.
The existing Windows session must be accepted using the account of the Windows user
logged on locally.
The remote station cannot be in the Windows logon screen.
VNC
The "RealVNC" Enterprise Edition software is approved for use for remote service access as
of PCS 7 V8.0.
You can find the RealVNC edition suitable for your PCS 7 version in the regularly updated
entry ID 64847781 in the Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/64847781)
CAUTION
Access to the operating system level of the local PCS 7 Operator Station (OS) with remote
access
During remote access to an OS via RealVNC, the remote operator has the possibility of
accessing the operating system level of the local OS. The local operator of the OS thus also
has the opportunity - for example via Windows Explorer opened by the remote operator - to
access the operating system level of the local OS at the same time as the remote operator.
You can find more information about the use of "RealVNC" in PCS 7 plants in the Industry
Online Support under entry ID 55422236:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/55422236)
SIMATIC Management Console
Remote access to the SIMATIC Management Console is generally not approved.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
34 Readme, 10/2015, A5E35748131-AB
3.4.18 Remote access to OS projects
All users must have been assigned to the "SIMATIC HMI" user group. This also applies to
users who want to open the OS projects remotely. Check in particular the following users:
Users who want to connect a Connectivity Pack Client to a Connectivity Pack Server:
These users must be registered members of the "SIMATIC HMI" group on the Connectivity
Pack Server.
Users accessing the Web center of DataMonitor:
1) If you set up a connection to the OS database, you require an additional Windows user
and password. Assign this user the necessary authorizations for access to the OS
database. For this purpose, set up a separate Windows user on the server and assign this
user to the "SIMATIC HMI Viewer" Windows group.
2) To enable access to a remote computer from the DataMonitor server, the Windows user
and the same password must have been set up on the DataMonitor server and relevant
remote servers. Register this user and the password in the connection administration of
the Web center. For this purpose, proceed as specified under point 1.
Users who want to connect an OPC client with an OpenPCS 7 server:
These users must be registered members of the "SIMATIC HMI" group on the OpenPCS 7
server.
3.4.19 Installation of WinAC software
You can find the software for WinAC controllers on the "PCS 7 Software Support & Tools DVD
2014.02 in the separately available "PCS 7 V8.x Software Support Package" (article number:
6ES7 650-4XX08-0YT8) under "03_WINAC_RTX\V4.6+SP2".
You can also find a previous version under "03_WINAC_RTX\V4.4+SP1+HF1" for the use on
IPC427B.
The latest corrected versions are available for download under entry ID 15227402 in the
Industry Online Support:
Download link (https://support.industry.siemens.com/cs/ww/en/view/15227402)
3.4.20 Information on changing faceplate style variants from Classic style to APL style
for SIMATIC Batch or Route Control faceplates
You can only install one of the two style variants (Classic style or APL style) at a time, and
change the style again by running PCS 7 Setup -> Install -> User-defined installation.
Notes on installation
3.4 Installation of the software, software requirements
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 35
3.5 Licensing
3.5.1 PCS 7 licenses and quantity structures
An overview of the PCS 7 licensing concept and the quantity structures associated with
licensing is available in the document "SIMATIC Process Control System PCS 7; Licenses
and configuration limits".
This document is located on the website for SIMATIC PCS 7 Technical Documentation:
Internet link (www.siemens.com/pcs7-documentation)
3.5.2 Managing AS runtime licenses
In order for the licenses to be available in sufficient quantities following the activation of the
license check, we recommend keeping these licenses on the engineering station from where
the controller usually loads them.
Note
Installation of the AS RT PO licenses
Select the appropriate AS RT PO license installation for your engineering environment:
1. AS RT PO license installed on the local engineering PC
Install the AS RT PO license(s) in sufficient numbers on the engineering PC. The favorites
list in the Automation License Manager (see menu "File > Settings") must not contain entries
or the PCs listed do not have AS RT PO licenses.
2. AS RT PO license installed on a license server
Install the AS RT PO license(s) in sufficient number on the license server PC. The favorites
list in the Automation License Manager (see menu "File > Settings") must contain the name
of the license server PC. The local engineering PC must not have an AS RT PO license.
Notes on installation
3.5 Licensing
PCS 7 Readme V8.1 including SP1 (Online)
36 Readme, 10/2015, A5E35748131-AB
Notes on usage 4
4.1 Automation system (AS)
4.1.1 Switching times for H CPU in connection with a fail-safe application
If you load F modules, you must select the monitoring time of each F sub-assembly as longer
than the switching time of the active channel in the H system. Notes on the high limit of this
changeover time can be found in the manual "S7 F-FH Systems - Configuring and
Programming," in Section "A.7".
Run, F-monitoring, and response times:
A table with formulas for calculating the high limit is available under Entry ID 22557362 in the
Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/22557362)
If you do not follow this instruction, F modules may malfunction when the active channel is
switched.
You can find additional information in the Safety Engineering in SIMATIC S7 system manual
under Entry ID 12490443:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/12490443)
4.1.2 ET 200S
4.1.2.1 ET 200S diagnostics of load voltage failure
The digital input/output modules of the ET 200S have no diagnostics in the event of load voltage
failure. This means that when the load voltage supply fails on the channel blocks, no "Bad" is
reported. When there is no voltage supply, outputs can no longer be switched via the
application program and the last available value is indicated on inputs.
You can get around this with the following configuration:
Use DI, DO modules with 24 V DC with power module PM-E DC 24 V:
6ES7 138-4CA00-0AA0
Because the entire station (IM151 and power modules) is supplied from a common 24 V
DC source, a failure in the voltage supply causes a station failure. This is reported in PCS 7
and causes passivation of all the modules involved, i.e. all channel blocks are set to "Bad".
Use of DI, DO modules with 120/230 VAC with power module PM-E AC 120/230 V: 6ES7
138-4CB10-0AB0: Applicative monitoring of load voltage in an application program.
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 37
4.1.2.2 ET 200S counter module (article number 6ES7 138-4DA04-0AB0)
When using the counter module in an ET 200S, an interface module >= article number 6ES7
151-1BA01-0AB0 must be used.
4.1.3 ET 200SP
Module AI ENERGY METER ST
The use of the ET 200SP module AI ENERGY METER ST (6ES7 134-6PA00-0BD0) is
approved for operation with PCS 7 V8.1 incl. SP1. However, the data from the process image
must be manually interconnected and evaluated. Observe the information about reading out
measured values under entry ID 81714201 in Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/81714201)
Value status
The functionality "Value status" for ET 200SP modules is not supported.
4.1.4 ET 200pro
The use of ET 200pro with CP 443-5 Extended is only approved with the
6GK7 443-5DX04-0XE0 module, firmware version V6.4 or later.
The modules from the ET 200pro series must be configured in DPV1 mode in HW Config. In
DPV0 mode, no interrupts are sent to the PCS 7 diagnostic blocks.
4.1.5 Using S7 PLCSIM
Simple application tests can be carried out with PLCSIM without the availability of AS hardware.
The project should be adapted as follows:
1. If the AS-OS connection is "NamedConnection" (PCS 7 Standard): compile OS "Change"
and change connection to network type "Industrial Ethernet."
2. Start PLCSim from the SIMATIC Manager.
3. Load HW Config.
4. Set the PG/PC interface in PLCSIM to PLCSIM(ISO) (if this has not already been done
automatically)
5. Load charts / programs.
6. Set PLCSIM to operating mode "RUN".
7. SIMATIC Manager: in the Project -> OS -> "Start OS Simulation" or "Open Object" and then
"activate".
Notes on usage
4.1 Automation system (AS)
PCS 7 Readme V8.1 including SP1 (Online)
38 Readme, 10/2015, A5E35748131-AB
Note
After using PLCSIM, it may be necessary to re-establish the real connection and recompile
the changes made to relevant AS including the real connection to the OS.
OS connections with a simulated WinAC Controller (WinLC RTX or WinAC Slot) are not
possible. See the notes on simulation of a WinAC Controller in the PLCSIM Readme.
4.1.6 Changing the address range of HART modules in ET 200iSP/ET 200M/ET 200SP
leads to address displacements
If HART auxiliary variables are configured retrospectively for HART modules, this leads to an
enlargement of the address field required for these modules. The I/O field may therefore be
redefined. In doing this, the ability to make configuration changes in RUN is lost. Note that
your project may need to be adapted (symbol tables, CFC charts).
We recommend configuring the modules with a "CiR" address placeholder in the address range
of the HART auxiliary variables during configuration. This ensures that the max. address range
is used and avoids address displacement.
4.1.7 Fast Mode functionality for HART devices
The HART Fast Mode functionality is supported as of configured module version 6ES7 33?-?
TF01-0AB0 V3.x.
Update 6ES7 33?-?TF01-0AB0 firmware to V3.x
Download firmware:
331-7TF01-0AB0:
Entry ID 33273268 (https://support.industry.siemens.com/cs/ww/en/view/33273268)
332-8TF01-0AB0:
Entry ID 32011516 (https://support.industry.siemens.com/cs/ww/en/view/32011516)
Replace modules 6ES7 33?-?TF00-0AB0 with 6ES7 33?-?TF01-0AB0 V3.x
To activate HART-Fast-Mode, you will have to replace the HART module in HW Config
(6ES7 33?-?TF00-0AB0 with 6ES7 33?-?TF01-0AB0 V3.x).
Then delete the HART field devices and renew the configuration.
Then activate "HART-Fast-Mode" in the module configuration and "HART RIO SHC Mode"
in the PDM settings.
Replace modules 6ES7 33?-?TF01-0AB0 with 6ES7 33?-?TF01-0AB0 V3.x
To activate HART-Fast-Mode, you will have to replace the HART module in HW Config
(6ES7 33?-?TF01-0AB0 with 6ES7 33?-?TF01-0AB0 V3.x).
Then activate "HART-Fast-Mode" in the module configuration and "HART RIO SHC Mode"
in the PDM settings.
Redundant modules
Notes on usage
4.1 Automation system (AS)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 39
HART-Fast-Mode is not possible for redundantly configured modules.
4.1.8 Configuration in RUN (CiR) with FM 350-1, FM 350-2, FM 355, FM 355-2, CP 341
The modules FM 350-1, FM 350-2, FM355, FM 355-2 and CP 341 are CiR-compatible, which
means that a configuration in RUN can be used so that they can be plugged or pulled via (hot-
swapped) when the AS is in RUN.
Note the following about these modules when configuring in operating mode RUN:
FM 350-1 and FM 350-2, CP 341:
Changing the module parameters when the CPU is in operating mode RUN resets the
module and is equivalent to restarting the module.
FM 355 and FM 355-2:
Bumpless channel-specific changes to module parameters when the CPU is in operating
mode RUN are possible to a limited extent; refer to the documentation of the FM modules.
4.1.9 Isochronous mode in PCS 7
PCS 7 does not support isochronous mode.
4.1.10 Fault-tolerant connections via internal ETHERNET/PROFINET interface
The S7-400 H as of firmware V6.0 supports fault-tolerant connections via your internal
ETHERNET/PROFINET interface.
If you would like to use fault-tolerant AS-AS connections via the internal interface of the V6.0
H-CPU, you need to be aware that the connections to the communication partner can only be
configured via the internal interface of the V6.0 H-CPU or CP 443-1 EX30.
4.1.11 Using PROFINET
Shared Device
The use of PROFINET shared devices with PCS 7 V8.1 incl. SP1 is not supported.
Assigning device numbers
Only device numbers up to 255 are supported by the driver generator in the PROFINET IO
system.
Notes on usage
4.1 Automation system (AS)
PCS 7 Readme V8.1 including SP1 (Online)
40 Readme, 10/2015, A5E35748131-AB
CiR functionality
If you would like to use the CiR functionality on the PROFIBUS master system for S7-400 PN/
DP CPU with firmware <= V6.0.2 (article number 6ES7 414-3EM06-0AB0 and article number
6ES7 416-3ES06-0AB0), you cannot configure PROFIBUS and PROFINET I/O
simultaneously for the internal interfaces.
Reporting module errors
With PROFINET IO, modules errors (e.g. no external auxiliary voltage) are reported by OB82
with a general error message. To obtain detailed diagnostic information, you must use HW
Config Online Diagnostics for the given module.
Firmware to be used with IM 153-4 PN IO
If you are using the PROFINET module IM 153-4 PN IO (article number 6ES7
153-4BA00-0AB0), you need to use a firmware version >= V4.0.1.
You can find information about updating the operating system and downloading the latest
firmware versions in Industry Online Support under entry ID 26331274:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/26331274)
4.1.12 Using HART auxiliary variables with 4 F-AI HART modules
The configured HART auxiliary variables of the following module are not supported by the PCS
7 channel blocks:
4 F-AI HART (article number 6ES7 138-7FA00-0AB0)
You can obtain additional information in the operating instructions "ET 200iSP Distributed I/O
Device - Fail-safe Modules" under Entry ID 47357221 in the Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/47357221)
4.1.13 Using PROFIBUS field devices with IE/PB Link
When using SIMATIC PCS 7 BOX RTX, SIMATIC PCS 7 AS-RTX and SIMATIC PCS 7 AS
mEC RTX you must observe the following:
parameter assignment of PROFIBUS field devices which are connected to an IE/PB Link
is not possible via Industrial Ethernet connections from the PCS 7 Engineering Station (ES)
or from SIMATIC PCS 7 BOX RTX in single-station operation.
to assign PROFIBUS field device parameters with SIMATIC PDM, connect the ES directly
to PROFIBUS of the IE/PB Link.
Notes on usage
4.1 Automation system (AS)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 41
4.1.14 Using Foundation Fieldbus (FF)
When using the IM 153-2 FF Link (article number 6ES7 153-2DA80-0XB0), you must have a
firmware version >= V1.0.2.
You can find information on updating the operating system and downloading the latest firmware
versions under Entry ID 68170195 in the Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/68170195)
4.2 Engineering system (ES)
4.2.1 Client engineering
Opening clients on the ES can in some circumstances take a very long time, since it involves
an implicit update of all server data (packages). Operator input to the SIMATIC Manager is not
possible during this time.
4.2.2 Notes on Configuration in RUN
Changes can be made to the distributed I/O of an S7-400 AS configuration during ongoing
operation; these are described in the following documents:
Method System configuration Documentation
CiR
Configuration in Run
Standard automation system
CPU S7-400
Fault-tolerant automation system in
1v1 mode
Configuration manual for PCS 7 Engi‐
neering System; Modifying the System
during Operation via CiR
H-CiR
Configuration in Run
Fault-tolerant automation system
CPU S7-400H
Fault-tolerant Systems
S7-400H, chapter 17
Internet link (https://
support.industry.siemens.com/cs/
ww/en/view/60458386)
4.2.3 Settings when using two or more network adapters
If multiple network adapters are used (for example, INTEL desktop adapters), the adapter for
the terminal bus must appear first in the list. (Network Properties: "Advanced > Advanced
Settings"). Any non-functioning network adapters must be disabled.
Following a PCS 7 installation, a dialog appears in which you have to select the network
adapter for the terminal bus. Select the correct adapter and confirm this with "OK".
Notes on usage
4.2 Engineering system (ES)
PCS 7 Readme V8.1 including SP1 (Online)
42 Readme, 10/2015, A5E35748131-AB
4.2.4 CFC/SFC: Download of the automation system (AS)
Programs created with CFC/SFC may only be downloaded with the following functions:
In CFC/SFC with menu command "PLC > Download"
In SIMATIC Manager (component view), select the project or station and then the menu
command "PLC > Compile and Download Objects"
In the SIMATIC Manager (component view), select charts and then the menu command
"PLC > Download".
Only the loading function of the CFC/SFC guarantees that the engineering data will be
consistent with the PLC data. Downloading changes to the CFC/SFC in the RUN mode of the
S7 CPU is only possible when the download is performed exclusively with these functions.
4.2.5 Special characters for the nomenclature
Only certain characters are allowed in names, depending on the language and components.
It is not recommended to use national special characters.
Special restrictions:
A comma "," in tag names (process tags, archive tags etc.) is generally not allowed.
The project name, picture name, and computer name may not contain multibyte characters
(e.g. Chinese).
For other naming conventions for projects, refer to:
"Engineering System Configuration Manual"
WinCC Online Help, using the search term "Illegal characters"
4.2.6 Notes on exporting SNMP variables
Access-protected PCS 7 projects
For projects with activated FDA access protection, you must open the OS project in SIMATIC
Manager before exporting the OPC configuration.
You can find additional information about exporting SNMP variables, for example, for the PCS
7 maintenance station, in the function manual "PCS 7 Maintenance
Station".
Notes on usage
4.2 Engineering system (ES)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 43
4.2.7 Compiling and downloading S7 connections – downloading to an AS
If connections are to be downloaded to an AS via "PLC > Compile and Download Objects",
the connections of all connection partners are compiled and loaded. Connection partners here
are also all the AS that have a configured connection to the same OS as the AS to be
downloaded. When downloading the connection data to the respective AS, there is a temporary
break in the connection between AS and OS or between the AS with AS-AS communication.
When using fault-tolerant S7 connections via TCP/IP, keep in mind that sufficient monitoring
times must be configured. Additional information on this topic is available in your SIMATIC
NET version under Entry ID 15227599 in the Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/15227599)
4.2.8 Download
When a "Download" performed from an ES to an OS, the Windows user logged on to the ES
must be known on the target station and a member in one of the following groups there: At
least "User", "SIMATIC HMI" "SIMATIC NET", "SIMATIC Batch" and required SIMATIC Route
Control "RC_..." groups. In addition, the user also needs full access rights for the folder into
which the project should be downloaded. This includes the sharing and security settings.
4.2.9 Notes on cross AS interconnections
When using cross AS interconnections, the S7 program names in the multiproject must be
different.
Hardware requirements:
S7-400 CPU with firmware version >= V3.1
Communications processor >= 443-1EX10 V2.1.
PCS 7 AS RTX and PCS 7 AS mEC RTX
The compact stations BOX RTX and BOX 416 cannot be used for AS-wide
interconnections. Use the communication blocks of the PCS 7 Advanced Process Library
for AS-AS communication.
If there is an overload on the S7-400 CPU or if there are network disruptions, the following
messages can appear: "Overload sender: S7 connection ID xxxx". This means that a data
transfer cycle could not be executed. The data will be transferred in the next cycle.
Notes on usage
4.2 Engineering system (ES)
PCS 7 Readme V8.1 including SP1 (Online)
44 Readme, 10/2015, A5E35748131-AB
4.2.10 F-monitoring time of F modules and F field devices after Y Link/DP-PA Link
By extending the calculation of the monitoring times for updating the reserve, it is possible as
of PCS 7 V7.1 SP1 to consider F-monitoring times of F modules and F field devices after Y
Link/DP-PA Link.
Note
When you activate the option "Calculate F modules after Y Link" you will change the CRC for
the F module configuration. You will have to compile the F program once again.
You may have to adjust the F monitoring times of the affected F modules and F field devices
prior to the calculation.
Use the Excel file "s7ftime" to determine the F monitoring times for F modules after Y Link and
F field devices on PROFIBUS-PA.
SIMATIC S7 F systems: execution times of fail-safe blocks, runtime of F shutdown group,
monitoring and reaction times.
Entry ID 22557362:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/22557362)
4.2.11 Configuration of fail-safe modules in ET 200M PROFINET stations
In order to operate fail-safe applications on PROFINET, the following requirements must be
met:
All configured devices and the employed F-drivers must support PROFIsafe V2 mode
The version of S7 F Configuration Pack used must be V5.5 SP11
Note the following before the first compilation of the hardware configuration:
For fail-safe operation on PROFINET, be sure to use only fail-safe modules that are listed
in the "PCS 7 V8.1" module filter under PROFINET IO -> I/O -> ET 200M.
Be sure to use a version >= V1.3 of the F-system library in your project. If you have not yet
used F-blocks in your project, place at least one F-block from the F-library version >= V1.3
within a CFC (for example, F-channel drivers).
4.2.12 Merging projects after distributed editing (multiproject engineering)
If you merge projects into a multiproject, you have to execute the following menu command:
"File > Save as... > With Reorganization (slow)".
Notes on usage
4.2 Engineering system (ES)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 45
4.2.13 Updating SFC blocks to use new functionality in SIMATIC BATCH
For SFC types/instances, the "Restart" command is now supported in the interface to SIMATIC
BATCH .
For this extension to be available, the block @SFC_BZL (FB 245) must be copied from the
SFC Library to the block folder of all programs and a complete compilation and a download of
changes must then be carried out.
In addition to updating the FB 245, the procedure described in the SIMATIC BATCH readme
file as of version V7.1 SP1 Hotfix 8 must be followed in order to use the extended functionality.
4.2.14 Note on upgrading process objects of a CPU 410-5H system expansion card
During the upgrade of the process objects of a CPU 410-5H system expansion card (SEC),
only one instance of the Automation License Manager (ALM) may be active.
4.2.15 Using the D7 SYS add-on package
If you use components of the D7 SYS add-on package in your PCS 7 project, you currently
cannot use the Step 7 function "Save As with Reorganization".
4.3 PCS 7 libraries
4.3.1 Diagnostic alarms for digital input modules SM 321-7BH00 and SM 321-7BH01
Diagnostic evaluation for channel-based diagnostic interrupts of the module
When using digital input modules SM 321-7BH00 and SM 321-7BH01, the diagnostic
evaluation for a channel-based diagnostic interrupt is performed in channel groups.
When using digital input module SM 321-7BH01 HF, the channel-related diagnostic interrupt
takes place for each individual channel.
Diagnostic option: Missing encoder supply
SM 321-7BH00 and SM 321-7BH01
Digital input channels 0 to 7 are combined into channel group 0.
Digital input channels 8 to 15 are combined into channel group 1.
Eight alarms are output for each channel group if the encoder supply is missing.
"Error channel 00" .... "Error channel 07" or
"Error channel 08" .... "Error channel 15"
Notes on usage
4.3 PCS 7 libraries
PCS 7 Readme V8.1 including SP1 (Online)
46 Readme, 10/2015, A5E35748131-AB
Diagnostic option: Wire break
For SM 321-7BH01 only
Digital input channels 0 and 1 are combined into channel group 0.
Digital input channels 2 and 3 are combined into channel group 1.
.
.
Digital input channels 12 and 13 are combined into channel group 6.
Digital input channels 14 and 15 are combined into channel group 7.
The channel involved can therefore not be clearly identified in the text of the diagnostic interrupt/
diagnostic message.
4.3.2 Software update to PCS 7 V8.1 incl. SP1
Software update with utilization of new functions
A software update of the Advanced Process Library (APL) from a version older than V8.1 to
V8.1.x with utilization of new functions can only be performed in the STOP operating mode of
the AS and complete compilation of the OS.
You can find detailed update information in the APL Readme (V8.1.x).
Type update in RUN (TCiR) for blocks in a PCS 7 library
The type update in RUN for blocks of a PCS 7 library (APL and Basis Library) is only released
when the blocks of a library version >= V8.1 are loaded in the AS.
4.4 Operator station (OS)
4.4.1 OS-specific information and notes on installation and use
You will find PCS 7 OS-specific information and notes on installation and use of this component
in the readme file of the product.
4.4.2 Customized user programs
If you create your own applications, system tests in the relevant environment are necessary
to ensure the stability of the entire system.
Notes on usage
4.4 Operator station (OS)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 47
4.4.3 Starting process mode on the OS server
Process mode will not be started on an OS server if this server is not connected to the
network.
When you start process mode on a redundant server, make sure that the first server takes
over process mode completely before the redundant partner is started. No client should be
active before process mode is started on a server for the first time. The OS clients can then
be activated.
4.4.4 Deactivating a redundant OS server
Before deactivating a redundant server, ensure that the partner server is in an state that is
fault-free and operational (for example, there are no process coupling faults). Archive
synchronization must be competed before deactivation, which can be recognized with the
corresponding process control message.
4.4.5 OS change download
Procedure for extensive changes
If an AS has been added, a redundancy switchover and entries in the message system may
occur when changes are download. The following procedure is recommended when extensive
changes are involved: Configure the changes in single steps ("packet-by-packet") on the ES
and then transfer them to the OS in individual "packets".
Changes to tags with access to an OPC-DA-Client application
It may happen in the course of configuration that tags are deleted from a project that are
requested at this time by an OPC-DA-Client application using a Subscription . Restoration of
these tags in the project will not automatically initiate an update of the tags by means of OPC.
Provided the tags in question are available in an OS server project and the OPC DA server is
running on an OS client or OpenPCS 7 station, it is sufficient to initiate a redundancy switchover
of the corresponding OS server project to trigger an update of the tags. Otherwise, the OPC-
DA-Client application needs to re-register the tags in question.
4.4.6 Setting access permissions in the operating system
A PCS 7 OS automatically sets the "SIMATIC HMI" local user group following installation under
Windows. The currently logged on user and local administrator are registered in this user
group. Enter the users who should have access to PCS 7 OS in the "SIMATIC HMI" group
with their logon information.
You can find additional information in the WinCC Information System under "Installation Notes
> Installation Requirements > Access Permissions in the Operating System" and in the
document "PCS 7 - PC Configuration.pdf" located in the _Manuals\English folder on the
SIMATIC PCS 7 DVD 1/2 .
Notes on usage
4.4 Operator station (OS)
PCS 7 Readme V8.1 including SP1 (Online)
48 Readme, 10/2015, A5E35748131-AB
All Window users who work with PCS 7-, PCS 7 OS or Route Control projects must also be
members of the "SIMATIC NET" group.
4.4.7 Controls
Using controls from third-party suppliers may lead to errors such as performance problems or
system blockage. The user of the software must assume responsibility if problems are caused
by third-party controls. We highly recommend that you run a system test to ensure safe
operation before putting them into use.
4.4.8 User interface and design
In PCS 7, make the following setting for the appearance of the user interface in process mode:
Design "WinCC 3D"
The WinCC designs "Classic", "Glass" and "Simple" are not supported by PCS 7.
Note the following:
Make sure that the design is set in a uniform manner for all the projects of a plant.
If you change the setting of the design, check the visualization of self-generated objects
and adapt these if necessary.
Retain the setting if you update the software. During a software update, changing the setting
for the appearance of the user interface in process mode could cause considerable
changes.
4.4.9 Delaying the transfer of archives
If a redundant partner is not available or is deactivated, the transfer of the archives of the
redundant partner will be delayed. The transfer of archives is started or continued only when
the partner becomes available again and synchronization of the archives is completed.
You should therefore check the memory capacity of the circular buffer of archives in the Tag
Logging editor or in the Alarm Logging editor to avoid the risk of data loss if the redundant
partner fails for a long period of time.
4.4.10 Disabling / enabling messages using the WinCC Alarmcontrol
The disabling / enabling messages functionality using WinCC Alarmcontrol has not been
approved for PCS 7.
Notes on usage
4.4 Operator station (OS)
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 49
4.4.11 Language setting for C scripts
Note that WinCC now supports Unicode. To ensure your C scripts run without problems, you
need to make sure that the language set in the Global Script C editor is correct. If you select
"Dynamic: Project setting", scripts run in the language that was set globally for the project. You
can make this global project setting under "C scripts with language setting "Dynamic" in
Runtime" in the "Options" tab, which is located in the "Project properties" dialog of the WinCC
Explorer. The "Operating system language for non-Unicode programs" option is preset and
recommended as the global project setting for PCS 7. You can find additional information in
the WinCC documentation (WinCC Information System) and the WinCC readme.
4.4.12 Consistency between the plant hierarchy and the Picture Tree Manager for SFC
visualization
To prevent delays during the start of OS Runtime and during SFC operation on the OS client,
you need to ensure the following:
all areas of the plant hierarchy (PH) that contain SFC charts must also be created by name
in the WinCC Picture Tree Manager.
OS areas which should not be available for selection in WinCC Runtime can be configured as
invisible via the OS project editor.
4.4.13 Prevent operating system access through key combinations
With the option "Disable shortcut keys for operating system access" in the properties of the
PCS 7 OS computer, the key combinations for ease of access are also disabled.
To prevent access to the operating system via key combinations for activating high contrast
when using Windows 7 SP1 (64-bit) and Windows Server 2008 R2 SP1, you need to install
the Microsoft patch KB2516889:
Internet link (http://support.microsoft.com/kb/2516889)
4.4.14 Activating OS Runtime on the engineering station (ES)
An OS project can be unlocked in the OS project settings for local activation on the ES. Once
an unlocked project is activated on the ES, this setting cannot be undone.
4.5 SIMATIC BATCH
4.5.1 Compiling and loading BATCH with the "Compile and Download Objects" function
Note that when you modifying projects, compiling and loading should always be performed in
the following sequence: AS, OS, BATCH.
Notes on usage
4.5 SIMATIC BATCH
PCS 7 Readme V8.1 including SP1 (Online)
50 Readme, 10/2015, A5E35748131-AB
4.5.2 Access permissions
The following sharing is set for SIMATIC BATCH during the installation:
BATCH
The PCS 7 software manages the share permissions automatically.
4.5.3 Common server for PCS 7 OS and SIMATIC BATCH
A redundant server can be used at same time as a common server for PCS 7 OS and SIMATIC
BATCH.
4.6 SIMATIC PDM
4.6.1 Using the Device Integration Manager
Once you have installed SIMATIC PDM, you are prompted to import the devices you are using
onto the computer. Run the "Device Integration Manager" program for this.
After an update installation to PCS 7 V8.1 incl. SP1, you will need to re-import the "Device
Library" device catalog.
The devices supported by PDM are included on the supplied "Device Library". You can
download the latest version from the Support area of the SIMATIC PDM website.
Internet link (https://www.siemens.com/simatic-pdm)
4.6.2 Canceling the module redundancy for HART modules of ET 200M remote IOs
In order to cancel the module redundancy set in the hardware configuration (HWC), you need
to adhere to the following procedure:
1. Delete the module in question and then compile the hardware project
2. Remove the deleted module from the process device plant view or network view
3. Configure the module again in HWC
This ensures that the redundancy is removed correctly.
4.6.3 Note on project migration
When migrating a PDM project from a previous version, it is absolutely necessary to do the
following:
Install all add-on packages used in the project before you open the project for the first time.
Projects are migrated automatically when you first open them.
Notes on usage
4.6 SIMATIC PDM
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 51
You can find additional important information in the SIMATIC PDM readme in the section
"Migrating Projects".
4.7 Process Historian (PH)
Commissioning the Process Historian (PH)
If you want to integrate the Process Historian (PH) or a redundant PH partner into your system
for the first time or perform a software update, you need to consider the following:
The PH only starts to reference data from the OS servers and batch servers if it is activated
before they are. You therefore may need to restart the OS server or batch server to create this
sequence of events.
4.8 Information Server (IS)
Displaying messages
You can display reports on messages using the Information Server. If there are formatting
instructions for components of the comment dialog in the message texts (for example,
computer name, logged-on user, comments), they are currently not filled out.
Installing the Information Server 2014 SP1
During the installation of Information Server 2014 SP1, observe the instructions in
"InstallNotesINFSVenUS.pdf". You will find the file on the SIMATIC PCS 7 DVD 1/2 in the
folder "27b_PH+IS_Install_and_Release-Notes".
Notes on usage
4.8 Information Server (IS)
PCS 7 Readme V8.1 including SP1 (Online)
52 Readme, 10/2015, A5E35748131-AB
Updating from Information Server 2013 to Information Server 2014 SP1
When upgrading from IS 2013 to IS 2014 SP1, note that some settings and templates must
be recreated under certain circumstances.
1. Always recreate:
E-mail settings
Dashboards
Connections to WinCC data sources
Subscriptions that were created with a WinCC data source
Reports that were created with a WinCC data source
2. If created by a user other than the one who performed the upgrade, recreate:
Private templates
Private subscriptions
Private reports
Note
If the message "Input string was not in a correct format" appears after the migration when you
call a report template from the Information Server interface, check your data source in the
Microsoft Report Manager.
Follow the steps below:
Open an Internet browser on the Information Server computer.
Copy the following link to the address bar. If necessary, adapt the protocol, port and
instance name (Reports_WINCC or Reports_INFSERVER instead of
Reports_HISTORIAN) to your configuration:
http://localhost/Reports_HISTORIAN/Pages/DataSource.aspx?ItemPath=
%2fDatasources%2fInfoServer&ViewMode=Detail
In the editing field of the connection string, change the value of the "Initial Catalog" from
"Master" to "Webframe":
"Initial Catalog=Webframe;"
Leave the other parameters unchanged and save the change by pressing "Apply".
4.9 PCS 7 Web server
Information about the PCS 7 Web add-on package is available in the "PCS 7 - Web OS Option"
manual. This document is located on the website for SIMATIC PCS 7 Technical
Documentation:
Internet link (www.siemens.com/pcs7-documentation)
Notes on usage
4.9 PCS 7 Web server
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 53
4.10 DataMonitor (DM)
Operating and monitoring WEB
The "Process Screen" function is no longer used for operator control and monitoring via WEB
in DataMonitor. Instead, the "WinCCViewerRT" Web viewer can be used on the DataMonitor
client.
For more information, please see the "DataMonitor Release Notes".
Restrictions on usage of the DataMonitor server
Always use the DataMonitor server on a computer that is not operated in WinCC ServiceMode.
4.11 OpenPCS 7
Evaluation of "Active Time"
"Active Time" cannot be used for evaluations with Historical Alarm&Event.
Project languages
If you have project languages other than Western European Languages (code page Windows
– 1252), an OPC A&E Client may only use the languages “German” or “English”, as offered
by the OpenPCS 7 OPC server.
Changes to tags with access to an OPC-DA-Client application
Observe the section OS change download (Page 48).
Downloading the OpenPCS 7 station
Following installation or update of OpenPCS 7, you need to perform a "Download" of the
OpenPCS 7 station on the engineering station.
4.12 Redundant systems
PCS 7 as of V7.1 SP2 contains advanced self-diagnostics for redundant software systems
(servers). If this diagnostics routine detects an internal fault, if the redundant partner server is
fully functioning, all communication connections on the server affected by the fault are
disconnected (terminal and system bus).
Notes on usage
4.12 Redundant systems
PCS 7 Readme V8.1 including SP1 (Online)
54 Readme, 10/2015, A5E35748131-AB
Example:
WinCC und BATCH Server are running on server (A) .
The full function of the redundant partner server (B) is achieved when WinCC and BATCH
Server are running on server (B) and the runtime data of WinCC and BATCH are
synchronized.
Automatic restart of the affected server is only performed when this full functionality is achieved.
Requirements
Use of a PCS 7 OS (multi-station) redundant system, SIMATIC BATCH and SIMATIC Route
Control.
You must make the following configuration settings on the server systems:
Automatic Windows logon (not relevant for servers in WinCC service mode)
Automatic start of the PCS 7 server applications
Deactivate the "Display Shutdown Event Tracker".
Proceed as follows:
Call via Start > Run...: Enter "gpedit.msc"
In the "Group Policy" dialog: Select Computer Configuration > Administrative Templates >
System and open the properties of the "Display Shutdown Event Tracker". Select
"Disabled".
Before a PCS 7 server application is exited, an availability check is carried out on the
relevant redundant partner server. The aspect of the data synchronization is not taken into
account in the availability check.
If the partner server is not fully functional, the user is informed of this status and can proceed
accordingly.
The availability check is only carried out in service mode if a user is logged on.
Activation of automatic logon in Microsoft Windows
You can find a description of the options for activating automatic logon in Microsoft Windows
under entry ID 23598260 in the Industry Online Support:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/23598260)
Additional information
You can find additional information in the corresponding application descriptions (manual and
readme for PCS 7 OS, SIMATIC BATCH, SIMATIC Route Control, SIMATIC NET).
4.13 SIMATIC NET
S7-RedConnect based on TCP/IP
Be aware of the following restrictions when using S7-RedConnect based on TCP/IP:
Notes on usage
4.13 SIMATIC NET
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 55
CP 1613 (A1 and A2) is not supported
VLAN architectures for PCS 7
You can find information about configurations with virtual LANs (VLAN) available with PCS 7
in the Industry Online Support under Entry ID 66807297:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/66807297)
Using SIMATIC NET Softnet IE-RNA in connection with WinCC secure communication
If you use secure communication between PC stations, you have to use the "Automation
Firewall" released for PCS 7 as a back firewall for communication across the plant.
You can find more information in the PCS 7 manual "PC Configuration" in section "Setting
package size for communication (MTU size)".
4.14 SIMATIC Management Console
Using whitelisting with McAfee Application Control
The following functions of the SIMATIC Management Console are not available using active
whitelisting with McAfee Application Control:
Creating setup package
Starting computer-specific installation
Generating an installation report
4.15 SIMATIC PCS 7 Industrial Workstation or SIMATIC IPC
Updating Management Engine firmware and Intel LAN driver
For operation of a SIMATIC PCS 7 Industrial Workstation or SIMATIC IPC, read entry ID
63647548 in the Industry Online Support regarding possible interference with the network
adapter:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/63647548)
4.16 Microsoft .NET Framework
The Microsoft .NET Framework versions required by PCS 7 are installed automatically by the
PCS 7 system setup.
Notes on usage
4.16 Microsoft .NET Framework
PCS 7 Readme V8.1 including SP1 (Online)
56 Readme, 10/2015, A5E35748131-AB
You can find information on the compatibility of SIMATIC PCS 7 in the Industry Online Support
under entry ID 64847781:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/64847781)
4.17 SIMATIC IPC DiagMonitor
DiagMonitor V4.4+SP4 has been tested for compatibility with PCS 7 V8.1 incl. SP1.
If a version of DiagMonitor < V4.4 is already installed on the system, take note of the following
for installation of DiagMonitor V4.4+SP4:
Uninstall the installed version of DiagMonitor under Windows Control Panel > Programs
and Features.
Reboot the computer once the program has been uninstalled.
Run the following files one after the other on the SIMATIC PCS 7 V8.1 incl. SP1DVD 2/2 under
Additional_Products > DiagMonitor_V4.4+SP4 to perform the installation:
DiagMonitor_Silent_Install.bat
CM_Activate.exe
You can find additional information on the installation and the approved types of computers in
the document "GettingStarted.pdf" in the installation folder.
4.18 SIMATIC Safety Matrix and S7 F Systems
S7 F Systems
S7 F Systems V6.1 SP1 and V6.1 SP2 have been tested for compatibility with PCS 7 V8.1
incl. SP1 .
Additional up-to-date information on S7 F Systems is available in the Industry Online Support
at:
Internet link (https://support.industry.siemens.com/cs/ww/en/ps/14363)
The manual for configuring and programming S7 F/FH Systems is available under Entry ID
101509838 in the Industry Online Support at:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/101509838)
For S7 F systems, use the S7 F ConfigurationPack V5.5 SP11.
You can find more information under Entry ID 15208817 in the Industry Online Support at:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/15208817)
SIMATIC Safety Matrix
SIMATIC Safety Matrix V6.2 SP1 and V6.2 SP2 have been tested with PCS 7 V8.1 incl. SP1
for compatibility.
Notes on usage
4.18 SIMATIC Safety Matrix and S7 F Systems
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 57
Please observe the section "Migrating to S7 F Systems V6.1" in the S7 F/FH Systems
configuring and programming manual:
Internet link (https://support.industry.siemens.com/cs/ww/en/view/101509838)
Additional up-to-date information on SIMATIC Safety Matrix is available in the Industry Online
Support at:
Internet link (https://support.industry.siemens.com/cs/ww/en/ps/14364)
Note on the use of Safety Matrix V6.2 SP1
When using PCS 7 V8.1 incl. SP1 and SIMATIC Safety Matrix V6.2 SP1, you must install the
software package SIMATIC Safety Matrix AS-OS Engineering V6.2 SP2. Compiling of the
"Entire OS with memory reset" must be performed in this case the first time you compile the
OS. The rest of the SIMATIC Safety Matrix products and libraries do not necessarily need to
be upgraded.
The software package SIMATIC Safety Matrix AS-OS-Engineering V6.2 SP2 is available on
the SIMATIC PCS 7 V8.1 incl. SP1 DVD 2/2 under Additional_Products >
SAFETY_MATRIX__V6.2+SP2
Notes on usage
4.18 SIMATIC Safety Matrix and S7 F Systems
PCS 7 Readme V8.1 including SP1 (Online)
58 Readme, 10/2015, A5E35748131-AB
Software components in SIMATIC PCS 7 V8.1 incl.
SP1 and changes to PCS 7 V8.1 5
SIMATIC PCS 7 DVD
SW components
PCS 7 V8.1 PCS 7 V8.1 incl. SP1
_Product Information
Automation License Manager V5.3 + SP1 + Upd1 V5.3 + SP2 + Upd2
STEP 7 Basis V5.5 + SP4 + Upd2 V5.5 + SP4 + Upd5
CFC V8.1 V8.1 + Upd2
S7-SCL V5.3 + SP6 + Upd3 V5.3 + SP6 + Upd3
SFC V8.1 V8.1
TH V8.1 V8.1 + Upd2
IEA-PO V8.1 V8.1 + Upd2
PCS 7 Basis Library V8.1 V8.1 + SP1
PCS 7 Advanced Process Library V8.1 V8.1 + Upd2
VersionCrossManager V7.1 + SP3 + Upd2 V7.1 + SP3 + Upd2
Version Trail V8.1 V8.1
PCS 7 PID Tuner V8.0 + SP1 V8.0 + SP1 + Upd1
DOCPRO V5.4 + SP2 + Upd1 V5.4 + SP2 + Upd1
PLCSIM V5.4 + SP5 + Upd1 V5.4 + SP5 + Upd1
SIMATIC WinCC V7.3 + Upd1 V7.3 + Upd4
WebNavigator V7.3 + Upd1 V7.3 + Upd4
DataMonitor V7.3 + Upd1 V7.3 + Upd4
Process Historian Version 2014 Version 2014 SP1
Information Server Version 2014 Version 2014 SP1
OpenPCS 7 V8.1 V8.1 + Upd1
SFC Visualization V8.1 V8.1 + Upd2
AS-OS-Engineering V8.1 + Upd1 V8.1 + Upd3
PV InsInfo Server V8.1 V8.1 + Upd1
PCS 7 Basis Faceplates V8.1 V8.1 + SP1
PCS 7 Advanced Faceplates V8.1 V8.1 + Upd1
SIMATIC NET PCSW V12 + SP2 V12 + SP2 + Upd3
SIMATIC Management Console V8.1 V8.1 + SP1
SIMATIC Management Agent V8.1 V8.1 + SP1
SIMATIC BATCH V8.1 V8.1 + SP1 + Upd2
SIMATIC Logon V1.5 + SP2 V1.5 + SP3
SIMATIC PDM V8.2 + Upd1 V8.2 + SP1
SIMATIC PDM Devices Internet download (https://
www.siemens.com/simatic-pdm)
Internet download (https://
www.siemens.com/simatic-pdm)
SIMATIC Route Control V8.1 V8.1 + Upd1
PCS 7 System Documentation V8.1 V8.1 + SP1
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 59
SIMATIC PCS 7 DVD
SW components
PCS 7 V8.1 PCS 7 V8.1 incl. SP1
PCS 7 Tools V8.1 V8.1 + SP1
SQL Server 2008 R2 SP2 2008 R2 SP2
WinCC_Options : DVD 2/2 DVD 2/2
WinCC_WebNavigator V7.3 + Upd1 V7.3 + Upd4
Additional_Products : DVD 2/2 DVD 2/2
DiagMonitor V4.4 + SP3 + Upd1 V4.4 + SP4
Information Server BATCH Options - V8.0 + SP1 + Upd13
MTU - V1.0
PCS 7 Advanced Process Library V7.1 + SP5 + Upd5 V7.1 + SP5 + Upd5
PCS 7 Basis Library V7.1 + SP3 + Upd9 V7.1 + SP3 + Upd10
PCS 7 Faceplates V7.1 + SP3 V7.1 + SP3
PCS 7 Library V7.1 + SP3 + Upd2 V7.1 + SP3 + Upd3
Report Builder V3.0 V3.0
S7 Block Privacy V1.0 + SP3 V1.0 + SP3
S7 F Systems V6.1 + SP2 V6.1 + SP2
SIMATIC Safety Matrix V6.2 + SP2 V6.2 + SP2
Simatic Diagnose Tool (SDT) SDT_2013_3 SDT_2014_3
SimaticRights
SIMATIC Management Agent V8.1 V8.1 + SP1
SIMATIC Management Console
InventoryDataProfile
V8.1 V8.1 + SP1
Sonstiges :
PKZIP V12.4 V12.4
DotNetFramework V2.0 SP2, V3.0 SP2, V3.5 SP1,
V4.5.1
V2.0 SP2, V3.0 SP2, V3.5 SP1,
V4.5.1
Software components in SIMATIC PCS 7 V8.1 incl. SP1 and changes to PCS 7 V8.1
PCS 7 Readme V8.1 including SP1 (Online)
60 Readme, 10/2015, A5E35748131-AB
Change history PCS 7 Readme (online) 6
Changes since delivery release PCS 7 V8.1 including SP1
Version Edition Change
2015-03-24 (ONLINE) 03/2015 Delivery version PCS 7 V8.1 including SP1
2015-10-14 (ONLINE) 10/2015 Section 3.4.14 Using Microsoft Office:
Restriction of 32-bit versions with Microsoft Office 2013 amended
PCS 7 Readme V8.1 including SP1 (Online)
Readme, 10/2015, A5E35748131-AB 61
Change history PCS 7 Readme (online)
PCS 7 Readme V8.1 including SP1 (Online)
62 Readme, 10/2015, A5E35748131-AB