FieldIT Data Sheet SS/264BS_2 2600T Series Pressure Transmitters Model 264BS Differential for high static maximum working pressure up to 41MPa, 5945psi Base accuracy : 0.075% Span limits - 0.2 to 2000kPa; 0.8inH2O to 290psi Reliable sensing system coupled with very latest digital technologies - provides large turn down ratio up to 100:1 Comprehensive sensor choice - optimize in-use total performance and stability 5-year stability Consistent conformance to all requirements - offers improvement in quality, delivery and service areas Flexible configuration facilities - provided locally via local keys combined with LCD indicator or via hand held terminal or PC configuration platform Multiple protocol availability - provides integration with HART(R), PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities Full compliance with PED Category III ABB 2600T Series Engineered solutions for all applications 2600T Pressure Transmitters Model 264BS SS/264BS_2 Functional Specifications Operative limits Range and span limits Temperature limits C (F) : Sensor Code Ambient (is the operating temperature) Upper Range Limit (URL) 6kPa 60mbar 24inH2O Lower Range Limit (LRL) -6kPa -60mbar -24inH2O 0.2kPa 2mbar 0.8inH2O F 40kPa 400mbar 160inH2O -40kPa -400mbar -160inH2O 0.4kPa 4mbar 1.6inH2O L 250kPa 2500mbar 1000inH2O -250kPa -2500mbar -1000inH2O 2.5kPa 25mbar 10inH2O N 2000kPa 20bar 290psi -2000kPa -20bar -290psi 20kPa 0.2bar 2.9psi C Minimum span Silicone oil filling: -40C and +85C (-40F and +185F) Inert filling: -20C and +85C (-4F and +185F) Lower ambient limit for LCD indicators: -20C (-4F) Upper ambient limit for LCD indicators: +70C (+158F) Note : For Hazardous Atmosphere applications see the temperature range specified on the certificate/approval relevant to the aimed type of protection Process Lower limit - Refer to lower ambient limits; -20C (-4F) for Viton gasket Upper limit - Silicone oil: 121C (250F) for working pressure above 10kPa abs, 100mbar abs, 1.45psia(1) Span limits Maximum span = URL (can be further adjusted up to URL (TD = 0.5) for differential models, within the range limits) IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. - Inert fluid: 121C (250F) (2) for working pressure above atmospheric pressure (1) 85C (185F) for application below 10kPa abs, 100mbar abs, 1.45psia down to 3.5 kPa abs, 35mbar abs, 0.5psia (2) 85C (185F) for application below atmospheric pressure down to 40kPa abs, 400mbar abs, 5.8psia Storage Zero suppression and elevation Zero and span can be adjusted to any value within the range limits detailed in the table as long as: - calibrated span minimum span Damping Selectable time constant : 0, 0.25, 0.5, 1, 2, 4, 8 or 16s. This is in addition to sensor response time Turn on time Operation within specification in less than 1s with minimum damping. Insulation resistance > 100M at 1000VDC (terminals to earth) Lower limit: -50C (-58F); -40C (-40F) for LCD indicators Upper limit: +85C (+185F) Pressure limits Overpressure limits (without damage to the transmitter) Lower limit - 0.5kPa abs, 5mbar abs, 0.07psia for silicone oil - 40kPa abs, 400mbar abs, 5.8psia for inert fluid Upper limit - 41MPa, 410bar, 5945psi Static pressure Transmitters for high static differential pressure model 264BS operates within specifications between the limits of: Lower limit - 0.5kPa abs, 5mbar abs, 0.07psia for silicone oil - 40kPa abs, 400mbar abs, 5.8psia for inert fluid Upper limit - 41MPa, 410bar, 5945psi Proof pressure The transmitter can be exposed without leaking to line pressure of up 1.5 times the nominal pressure simultaneously on both sides. 2 2600T Pressure Transmitters Model 264BS SS/264BS_2 Hazardous atmospheres Environmental limits Electromagnetic compatibility (EMC) Comply with EN 61000-6-3 for emission and EN 61000-6-2 for immunity requirements and test; Radiated electromagnetic immunity level: (according to IEC 1000-4-3, EN61000-4-3) 30V/m Conducted electromagnetic immunity level : (according to IEC 1000-4-6, EN 61000-4-6) 30V Surge immunity level (with surge protector): (according to IEC 1000-4-5 EN 61000-4-5) 4kV Fast transient (Burst) immunity level: (according to IEC 1000-4-4 EN 61000-4-4) 4kV Pressure equipment directive (PED) Comply with 97/23/EEC Category III Module H. Humidity Relative humidity: up to 100% annual average Condensing, icing: admissible Vibration resistance Accelerations up to 2g at frequency up to 1000Hz (according to IEC 60068-2-26) With or without output meter/integral display - INTRINSIC SAFETY/EUROPE: ATEX/ZELM approval II 1 GD T50C, EEx ia IIC T6 (-40C Ta +40C) T95C, EEx ia IIC T4 (-40C Ta +85C) - TYPE "N"/EUROPE: ATEX/ZELM type examination (for HART) II 3 GD T50C, EEx nL IIC T6 (-40C Ta +40C) T95C, EEx nL IIC T4 (-40C Ta +85C) (FOUNDATION Fieldbus/PROFIBUS PA): pending - FLAMEPROOF/EUROPE: ATEX/CESI approval II 1/2 GD T85C, EEx d IIC T6 (-40C Ta +75C) - CANADIAN STANDARDS ASSOCIATION and FACTORY MUTUAL: - Explosionproof: Class I, Div. 1, Groups A, B, C, D - Dust ignitionproof : Class II, Div. 1, Groups E, F, G - Suitable for : Class II, Div. 2, Groups F, G; Class III, Div. 1, 2 - Nonincendive: Class I, Div. 2, Groups A, B, C, D - Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G AEx ia IIC T6/T4, Zone 0 (FM) - STANDARDS AUSTRALIA (SAA): pending TS/WCA Approval Ex d IIC T5 (Tamb +85C)/T6 (Tamb +70C) Class 1 Zone 1; Ex ia IIC T4 (Tamb +85C) /T5 (Tamb +55C) T6 Class 1 Zone 0 Shock resistance Acceleration: 50g Duration: 11ms (according to IEC 60068-2-27) Wet and dust-laden atmospheres The transmitter is dust and sand tight and protected against immersion effects as defined by EN 60529 (1989) to IP 67 (IP 68 on request) or by NEMA to 4X or by JIS to C0920. 3 2600T Pressure Transmitters Model 264BS SS/264BS_2 Electrical Characteristics and Options Optional surge protection HART digital communication and 4 to 20mA output Power Supply Up to 4kV - voltage 1.2s rise time / 50s delay time to half value - current 8s rise time / 20s delay time to half value The transmitter operates from 10.5 to 42VDC with no load and is protected against reverse polarity connection (additional load allows operations over 42VDC). For EEx ia and other intrinsically safe approval power supply must not exceed 30VDC. Output signal Two-wire 4 to 20mA, user-selectable for linear or square root output, power of 3/2 or 5/2, 5th order or two 2nd order switching point selectable programmable polynomial output. HART(R) communication provides digital process variable (%, mA or engineering units) superimposed on 4 to 20mA signal, with protocol based on Bell 202 FSK standard. Ripple 20mV max on a 250 load as per HART specifications MINIMUM OPERATING VOLTAGES Output current limits (to NAMUR standard) no link on output indicator plugs Overload condition with CoMeter indicator and HART communication - Lower limit: 3.8mA - Upper limit: 20.5mA with ProMeter output indicator Transmitter failure mode (to NAMUR standard) with optional surge protection The output signal can be user-selected to a value of 3.7 or 22mA on gross transmitter failure condition, detected by self-diagnostics. with optional output analog indicator In case of CPU failure the output is driven <3.7mA or >22mA. with integral display (volts) 10.5 10.7 12.3 12.5 13.3 15.3 Load limitations 4 to 20mA and HART total loop resistance : Supply voltage - min. operating voltage (VDC) --------------------------------------- 22.5 A minimum of 250 is required for HART communication. R(k) = Optional indicators Output meter CoMeter and Prometer LCD : 5-digit (99999 counts) programmable with 7.6mm. high (3in), 7-segment numeric characters plus sign and digital point for digital indication of output value in percentage, current or engineer unit; 10-segment bargraph display (10% per segment) for analog indication of output in percentage; 7-digit with 6mm. high (2.3in), 14-segment alphanumeric characters, for engineer units and configuration display Analog : 36mm (1.4in) scale on 90. Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of analog output in percentage. User-definable matrix display mode with HART communication: - process variable in pressure unit or - output signal as percentage, current or engineering units Display also indicates in/out transfer function, static pressure, sensor temperature and diagnostic messages and provides configuration facilities. 4 2600T Pressure Transmitters Model 264BS SS/264BS_2 PROFIBUS PA output FOUNDATION Fieldbus output Device type Device type Pressure transmitter compliant to Profiles 3.0 Class A & B; ident. number 052B HEX. Power supply The transmitter operates from 10.5 to 32VDC , polarity independent. For EEx ia approval power supply must not exceed 17.5VDC. Intrinsic safety installation according to FISCO model. Current consumption operating (quiescent): 10.5mA fault current limiting: 20mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Output interface PROFIBUS PA communication according to Profibus DP50170 Part 2/ DIN 19245 part 1-3. Output update time 25ms Function blocks 2 analog input, 1 transducer, 1 physical Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of output in percentage of the analog input function block assigned to the primary variable. User-definable matrix display mode: - process variable in pressure units or - primary variable in engineering units (output of transducer block) or - output as percentage or engineering units of analog input function blocks Display also indicates diagnostic messages and provides configuration facilities. Secondary variable, static pressure and sensor temperature can be read. Transmitter failure mode On gross transmitter failure condition, detected by self-diagnostics, the output signal can be driven to defined conditions, selectable by the user as safe, last valid or calculated value. If electronic failure or short circuit occur the transmitter consumption is electronically limited at a defined value (20mA approx), for safety of the network. LINK MASTER DEVICE Link Active Scheduler (LAS) capability implemented. Power supply The transmitter operates from 9 to 32VDC, polarity independent. For EEx ia approval power supply must not exceed 24VDC (entity certification) or 17.5VDC (FISCO certification), according to FF-816. Current consumption operating (quiescent): 10.5mA fault current limiting: 20mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Function blocks/execution period 2 standard Analog Input blocks/25ms max (each) 1 standard PID block/70ms max. Additional blocks 1 standard Resource block, 1 custom Pressure with calibration transducer block. Number of link objects 25 Number of VCRs 24 Output interface FOUNDATION fieldbus digital communication protocol to standard H1, compliant to specification V. 1.5; FF registration number IT019000. Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of output in percentage of the analog input function block assigned to the primary variable. User-definable matrix display mode: - process variable in pressure units or - primary variable in engineering units (output of transducer block) or - output as percentage or engineering units of analog input function blocks Display also indicates diagnostic messages and provides configuration facilities. Secondary variable, static pressure and sensor temperature can be read. Transmitter failure mode The output signal is "frozen" to the last valid value on gross transmitter failure condition, detected by self-diagnostics which also indicate a BAD conditions. If electronic failure or short circuit occur the transmitter consumption is electronically limited at a defined value (20mA approx), for safety of the network. 5 2600T Pressure Transmitters Model 264BS Performance specifications Stated at reference condition to IEC 60770 ambient temperature of 20C (68F), relative humidity of 65%, atmospheric pressure of 1013hPa (1013mbar), mounting position with vertical diaphragm and zero based range for transmitter with isolating diaphragms in AISI 316 L ss or Hastelloy and silicone oil fill and HART digital trim values equal to 4-20mA span end points, in linear mode. SS/264BS_2 Operating influences Ambient temperature per 20K (36F) change between the limits of -20C to +65C (-4 to +150F) : Model Unless otherwise specified, errors are quoted as % of span. Some performance data are affected by the actual turndown (TD) as ratio between Upper Range Limit (URL) and calibrated span. IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. Dynamic performance (according to IEC 61298-1 definition) Standard configuration with turndown up to 30:1 and linear output characteristic. Dead time: 40ms 264BS Sensor Code for TD up to F, L, N 15:1 (0.04% URL + 0.065% span) C 10:1 (0.06% URL + 0.10% span) Optional CoMeter and ProMeter ambient temperature Total reading error per 20K (36F) change between the ambient limits of -20 and +70C (-4 and +158F) : 0.15% of max span (16mA). Static pressure (zero errors can be calibrated out at line pressure) Time constant (63.2% of total step change): per 10MPa, 100bar or 1450psi - sensors F, L, N: 150ms - sensor C: 400ms Model 264BS - zero error: - span error: Response time (total) = dead time + time constant Accuracy rating % of calibrated span, including combined effects of terminal based linearity, hysteresis and repeatability. For fieldbus versions SPAN refer to analog input function block outscale range - 0.075% for TD from 1:1 to 15:1 URL - 0.005% x Span for TD from 15:1 to 60:1 (30:1 for sensor code C) 0.15% of URL 0.15% of reading Supply voltage Within voltage/load specified limits the total effect is less than 0.005% of URL per volt. Load Within load/voltage specified limits the total effect is negligible. Radio frequency interference Total effect : less than 0.10% of span from 20 to 1000MHz and for field strengths up to 30V/m when tested with shielded conduit and grounding, with or without meter. Common mode interference No effect from 100Vrms @ 50Hz, or 50VDC Mounting position Rotations in plane of diaphragm have negligible effect. A tilt from vertical causes a zero shifts of sin x 0.35kPa (3.5mbar, 1.4inH2O) of URL which can be corrected with the zero adjustment. No span effect. Stability 0.10% of URL over a thirty-six-month period Vibration effect 0.10% of URL (according to IEC 61298-3) 6 2600T Pressure Transmitters Model 264BS SS/264BS_2 Physical Specification Optional extras (Refer to ordering information sheets for variant availability related to specific model or versions code) Mounting brackets For vertical and horizontal 60mm. (2in) pipes or wall mounting. Materials Output indicator Process isolating diaphragms (*) plug-in rotatable type, LCD or analog. AISI 316 L ss; Hastelloy C276TM; Monel 400TM; Tantalum; Supplemental customer tag Process flanges, adapters, plugs and drain/vent valves (*) AISI 316 L ss; Hastelloy C276TM; Monel 400TM. Sensor fill fluid Silicone oil; inert fill (carbon fluoride) Mounting bracket (**) Zinc plated carbon steel with chrome passivation; AISI 316 L ss. Gaskets (*) VitonTM; Perbunan (NBR), EPDM. Sensor housing AISI 316 L ss. AISI 316 ss tag screwed/fastened to the transmitter for customer's tag data up to a maximum of 20 characters and spaces on one line for tag number and tag name, and up to a maximum of 3 spaced strings of 10 characters each for calibration details (lower and upper values plus unit). Special typing evaluated on request for charges. Surge protection (only as external unit for PROFIBUS PA and FF) Hydrogen or special service preparation Test Certificates (test, design, calibration, material traceability) Tag and manual language Communication connectors Process connections on flanges : 1/4in NPT on process axis Bolts and nuts AISI 316 ss bolts and nuts Class A4-50 per UNI 7323 (ISO 3506), in compliance with NACE MR0175 Class II. Electronic housing and covers Barrel version - Copper-free content aluminium alloy with baked epoxy finish; on adapters : 1/2in NPT on process axis centre distance: 54mm (2.13in ) on flange; 51,54 or 57mm (2.01, 2.13 or 2.24in) as per adapters fittings. fixing threads: 7/16in-20 UNF at 41.3mm centre distance Electrical connections - Low-copper content aluminium alloy with baked epoxy finish; Two 1/2 NPT or M20x1.5 or PG 13.5 or 1/2 GK threaded conduit entries, direct on housing. - AISI 316 L ss. Special communication connector (on request) DIN version - HART : straight or angle Harting Han connector and one plug. - Low-copper content aluminium alloy with baked epoxy finish. - FOUNDATION Fieldbus, PROFIBUS PA: M12x1 or 7/8. Covers O-ring Buna N. Local zero and span adjustments: Glass filled polycarbonate plastic (removable). Tagging AISI 316ss data plate attached to the electronics housing. Calibration Standard: at maximum span, zero based range, ambient temperature and pressure; Optional: at specified range and ambient conditions. Terminal block HART version: three terminals for signal/external meter wiring up to 2.5mm2 (14AWG) and three connection points for test and communication purposes. Fieldbus versions: two terminals for signal wiring (bus connection) up to 2.5mm2 (14AWG) Grounding Internal and external 6mm2 (10AWG) ground termination points are provided. Mounting position Transmitter can be mounted in any position. Electronics housing may be rotated to any position. A positive stop prevents over travel. Mass (without options) 3.5kg approx (8lb); add 1.5kg (3.4lb) for AISI housing. Add 650g (1.5lb) for packing. Packing Carton 26 x 26 x 18cm approx (10 x 10 x 7in). 7 2600T Pressure Transmitters Model 264BS Configuration Transmitter with HART communication and 4 to 20 mA Standard configuration Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the tag plate. If a calibration range and tag data are not specified, the transmitter will be supplied with the plate left blank and configured as follows: Engineering Unit Specify from table 4 mA Zero 20 mA Upper Range Limit (URL) Output Linear Damping 1 sec. Transmitter failure mode Upscale Software tag characters Blank Optional LCD indicator/display 0 to 100.0% linear Any or all the above configurable parameters, including Lower range-value and Upper range-value which must be the same unit of measure, can be easily changed using the HART hand-held communicator or by a PC running the configuration software SMART VISION with DTM for 2600T. The transmitter database is customized with specified flange type and material, O-ring and drain/vent materials and meter code option. Custom configuration (option) The following data may be specified in addition to the standard configuration parameters: Descriptor 16 alphanumeric characters Message 32 alphanumeric characters Date Day, month, year Transmitter with PROFIBUS PA communication Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the tag plate. If a calibration range and tag data are not specified, the transmitter will be supplied with the plate left blank and configured as follows: Measure Profile Pressure Engineering Unit kPa Output scale 0% Lower Range Limit (LRL) Output scale 100% Upper Range Limit (URL) Output Linear Hi-Hi Limit Upper Range Limit (URL) Hi Limit Upper Range Limit (URL) Low Limit Lower Range Limit (LRL) Low-Low Limit Lower Range Limit (LRL) Limits hysteresis 0.5% of output scale PV filter 0 sec. Address (settable by local key) 126 Tag 32 alphanumeric characters Any or all the above configurable parameters, including Lower range-value and Upper range-value which must be the same unit of measure, can be easily changed by a PC running the configuration software SMART VISION with DTM for 2600T. The transmitter database is customized with specified flange type and material, O-ring and drain/vent materials and meter code option. Custom configuration (option) The following data may be specified in addition to the standard configuration parameters: Descriptor 32 alphanumeric characters Message 32 alphanumeric characters Date Day, month, year 8 SS/264BS_2 Transmitter with FOUNDATION Fieldbus communication Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the tag plate. If a calibration range and tag data are not specified, the transmitter will be supplied with the plate left blank and the analog input function block FB1 is configured as follows: Measure Profile Pressure Engineering Unit kPa Output scale 0% Lower Range Limit (LRL) Output scale 100% Upper Range Limit (URL) Output Linear Hi-Hi Limit Upper Range Limit (URL) Hi Limit : Upper Range Limit (URL) Low Limit Lower Range Limit (LRL) Low-Low Limit Lower Range Limit (LRL) Limits hysteresis 0.5% of output scale PV filter time 0 sec. Tag 32 alphanumeric characters The analog input function block FB2 is configured for the sensor temperature measured in C. Any or all the above configurable parameters, including the range values, can be changed using any host compliant to FOUNDATION fieldbus. The transmitter database is customized with specified flange type and material, O-ring and drain/vent materials and meter code option. For any protocol available engineering units of pressure measure are : Pa, kPa, MPa inH2O@4C, mmH2O@4C, psi inH2O@20C, ftH2O@20C, mmH2O@20C inHg, mmHg, Torr g/cm2, kg/cm2, atm mbar, bar TM Hastelloy is a Cabot Corporation trademark TM Monel is an International Nickel Co. trademark TM Galden is a Montefluos trademark TM Viton is a Dupont de Nemour trademark (*) Wetted parts of the transmitter. (**) U-bolt material: AISI 400 ss; screws material: high-strength alloy steel or AISI 316 ss. 2600T Pressure Transmitters Model 264BS SS/264BS_2 MOUNTING DIMENSIONS (not for construction unless certified) - dimensions in mm (in) Transmitter with barrel aluminium housing on bracket for vertical or horizontal 60mm (2in) pipe mounting Adjustments Electronic side 36 (1.42) 17 (0.67) Barrel type housing Certification label Terminal side 135 (5.31) Min. clearance to remove the cover Identification tag 127 (5.00) 26 (1.02) 17 (0.67) Output meter housing Drain/vent Valve Integral display housing 81 (3.19) Process connection 54 (2.13) 96 (3.78) 71 (2.80) 62 (2.44) (*) 51 (2.01), 54 (2.13) or 57 (2.24) mm (in) according to 1/2in 14 NPT adapters fitting; 54 (2.13) mm (in) on 1/4in 18 NPT process flange 54 (2.13) mm (in) with low pressure side flange without process connection and drain/vent valve Electrical connections 86 (3.39) N IO L ES C C I R IR C U S ON T S O I TS AL I V U S T E E CU T S I NS G A RD ER KE L 41.3 (1.63) ! 102 (4.02) S ON T S O I TS AL I V U S T E E CU T S I 165 (6.50) 61 (2.40) 11 (0.43) 90 (3.54) L ES C C I R IR C U E RC L E B I E UV ER T N FER V I GH M CO E P CO T E Flange N IO E RC L E B I E UV ER T N FER V I GH M CO E P CO T E 60 (2.36) with plug 72 (2.83) with d/v valve NS E T QU AN E' T H E N W G A RD ER KE L E T QU AN E' T H E N W ! Covers locking screw 78 (3.07) 82 (3.23) 102 (4.02) Adapter NOTE : Process connection, gasket groove and gaskets are in accordance with DIN 19213. Bolting threads for fixing adapter or other devices (i.e. manifold etc.) on process flange is 7/16in-20 UNF. 9 2600T Pressure Transmitters Model 264BS SS/264BS_2 Transmitter on bracket for vertical or horizontal 60 mm (2in) pipe mounting (DIN housing) 61 (2.40) External ground 41.3 (1.63) Electrical connections 86 (3.39) 55 (2.17) max Adapter L ES C C I R IR C U E T QU AN E' T H E N W 45 (1.77) E RC L E B I E UV ER T N FER V I GH M CO E P CO T E 102 (4.02) GA R Identification tag 16 (0.63) 26 (1.02) 17 (0.67) ! 36 (1.42) Integral display housing 147 (5.79) N IO Electronic side 17 (0.67) Covers locking screw Flange Certification label Harting Han connector DER KE L Adjustments S ON T S O I TS AL I V U S T E E CU T S I NS Output meter housing 7 (0.28) 142 (5.59) Terminal side DIN type housing 33 (1.30) 177 (6.97) Certification label 82 (3.23) Drain/vent Valve Transmitter with barrel AISI ss housing on bracket (flat type for box) for vertical or horizontal 60mm (2in) pipe mounting N IO L ES C C I R IR C U NS S ON T S O I TS AL I V U S T E E CU T S I G A RD ER KE L E T QU AN E' T H E N W ! 84 (3.31) 70 (2.75) 204 (8.03) E RC L E B I E UV ER T N FER V I GH M CO E P CO T E 70 (2.75) 25 (0.98) 98 (3.86) 47 (1.85) 10 2600T Pressure Transmitters Model 264BS SS/264BS_2 Transmitter on bracket for wall mounting (by four M8 screws) 25 (1) G A RD ER KE L 70 (2.75) 70 (2.75) S ON T S O I TS AL I V U S T E E CU T S I ! E T QU AN E' T H E N W N IO E RC L E B I E UV ER T N FER V I GH M CO E P CO T E NS 70 (2.75) 11 L ES C C I R IR C U 2600T Pressure Transmitters Model 264BS SS/264BS_2 Electrical connections HART Version Internal ground termination point M+ - 0 2 3 4 7 6 5 9 60 40 20 0 Remote indicator 8 10 80 10 % 0 Kent-Taylor Line load M + 3 4 2 8 1 7 5 6 Harting pin (male) identification + + 250 ohm min GND TEST COMM - 691HT External ground termination point F1 F2 + Test points 4 to 20mA F3 - F4 PV REVIEW - + Power source CONF SERIAL LINK TRIM A B C Hand-held communicator D E F 2 3 M N O P Q R 4 5 6 S T U V W X Y Z # 7 8 9 @ % & / + - 0 Optional G H I 1 J K L Receiver HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistance is 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow communications FIELDBUS Versions 7/8" connector 1 3 2 4 Internal ground termination point M12 x 1 connector 2 1 3 Fieldbus line (polarity independent) BUS CONNECTIONS 4 PIN (male) IDENTIFICATION FOUNDATION PROFIBUS Fieldbus PA 1 FFPA+ 2 FF+ GROUND 3 SHIELD PA- 4 GROUND SHIELD Mating female plug NOT SUPPLIED 12 External ground termination point 2600T Pressure Transmitters Model 264BS SS/264BS_2 BASIC ORDERING INFORMATION model 264BS Differential Pressure Transmitter (High static) Select one character or set of characters from each category and specify complete catalog number. Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required. BASE MODEL - 1st to 5th characters 2 6 4 B S X X X X X X Differential Pressure Transmitter (High static) - BASE ACCURACY 0.075% SENSOR - Span limits - 6th character 0.2 and 6kPa 2 and 60mbar 0.8 and 24inH2O 0.4 and 40kPa 4 and 400mbar 1.6 and 160inH2O 10 and 1000inH2O 2.5 and 250kPa 25 and 2500mbar 2.9 and 290psi 20 and 2000kPa 0.2 and 20bar Diaphragm material / Fill fluid (wetted parts) - 7th character C F L N AISI 316 L ss Silicone oil Hastelloy C276TM Silicone oil Monel 400TM Silicone oil AISI 316 L ss Inert fluid Hastelloy C276TM Inert fluid Tantalum Inert fluid Process flanges/adapters material and connection (wetted parts) - 8th character AISI 316 L ss (Horizontal connection) AISI 316 L ss (Horizontal connection) Hastelloy C276TM (Horizontal connection) Hastelloy C276TM (Horizontal connection) Monel 400TM (Horizontal connection) Monel 400TM (Horizontal connection) NACE NACE NACE NACE NACE NACE 1 /4in NPT-f direct (7/16in UNF U.S. drilling) /2in NPT-f through adapter (7/16in UNF U.S. drilling) 1 /4in NPT-f direct (7/16in UNF U.S. drilling) 1 /2in NPT-f through adapter (7/16in UNF U.S. drilling) 1 /4in NPT-f direct (7/16in UNF U.S. drilling) 1 /2in NPT-f through adapter (7/16in UNF U.S. drilling) NACE NACE NACE NACE NACE NACE 1 S K M A F D A B D E G H Bolts/Gasket (wetted parts) - 9th character AISI 316 ss (NACE) VitonTM AISI 316 ss (NACE) EPDM AISI 316 ss (NACE) Perbunan Housing material and electrical connection - 10th character Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) Aluminium alloy (DIN version) Aluminium alloy (DIN version) Aluminium alloy (DIN version) Aluminium alloy (DIN version) NACE NACE NACE 1 /2in NPT M20 x 1.5 (CM 20) Pg 13.5 1 /2in GK Harting Han connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM 20) Pg 13.5 1 /2in GK Harting Han connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM20) Pg 13.5 1 /2in GK Fieldbus connector M20 x 1.5 (CM 20) Pg 13.5 Harting Han connector Fieldbus connector (Note 1) (general purpose only) (Note 1) (general purpose only) (Note 1) (general purpose only) (Note 1) (general purpose only) (Note 1) (general purpose only) (general purpose only) (general purpose only) (Note 1) (general purpose only) (Note 1) (general purpose only) 3 5 6 A B D C E G H L N M P R S T V U Z J Y K W Output/Additional options - 11th character HART digital communication and 4 to 20mA HART digital communication and 4 to 20mA PROFIBUS PA PROFIBUS PA FOUNDATION Fieldbus FOUNDATION Fieldbus No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") (Notes 2, 3) (Note 2) (Notes 2, 3) (Note 3) (Notes 2, 3) (Note 3) H 1 P 2 F 3 13 2600T Pressure Transmitters Model 264BS SS/264BS_2 ADDITIONAL ORDERING INFORMATION for model 264BS Add one or more 2-digit code(s) after the basic ordering information to select all required options XX XX XX XX XX XX XX XX XX XX XX XX XX XX Drain/vent valve (material and position) (wetted parts) AISI 316 L ss on process axis (Note 4) NACE V1 AISI 316 L ss on flange side top (Note 4) NACE V2 AISI 316 L ss on flange side bottom (Note 4) NACE V3 Hastelloy C276TM on process axis (Note 5) NACE V4 Hastelloy C276TM on flange side top (Note 5) NACE V5 Hastelloy C276TM on flange side bottom (Note 5) NACE V6 Monel 400TM on process axis (Note 6) NACE V7 Monel 400TM on flange side top (Note 6) NACE V8 Monel 400TM on flange side bottom (Note 6) NACE V9 Electrical certification ATEX Group II Category 1 GD - Intrinsic Safety EEx ia ATEX Group II Category 1/2 GD - Flameproof EEx d ATEX Group II Category 3 GD - Type of protection "N" EEx nL design compliance (Note 7) Canadian Standard Association (CSA) (only 1/2in NPT, M20 and Pg 13.5 housing) Intrinsic Safety-Flameproof to Standards Australia SAA Ex ia IIC T6/T5/T4 + Ex d II C T6/T5 (Note 7) Factory Mutual (FM) approval (only with 1/2in NPT, M20 and Pg 13.5 electrical connection) Output meter ProMeter, Standard calibration ProMeter, Special calibration Analog output indicator linear 0-100% scale Analog output indicator square root 0-10 scale Analog output indicator, special graduation (to be specified for linear scale) Analog output indicator, special graduation (to be specified for square root scale) Programmable signal meter and HART configurator (CoMeter) Programmable signal meter and HART configurator (CoMeter - customer configuration) (Note 7) (Note 7) (Note 7) (Note 7) (Note 7) (Note 7) (Note 7) (Note 7) E1 E2 E3 E4 E5 E6 D1 D2 D3 D4 D5 D6 D7 D8 Integral LCD Digital LCD integral display L1 Mounting bracket (shape and material) For pipe mounting For pipe mounting For wall mounting For wall mounting Flat type for box (Not suitable for AISI housing) (Not suitable for AISI housing) (Not suitable for AISI housing) (Not suitable for AISI housing) Carbon steel AISI 316 L ss Carbon steel AISI 316 L ss AISI 316 L ss B1 B2 B3 B4 B5 Surge Surge/Transient Protector (Note 7) S1 Operating manual German Italian French M1 M2 M4 Labels & tag language German Italian French T1 T2 T4 Additional tag plate Laser printing of tag on stainless steel plate I2 Configuration Standard - Pressure = inH2O/psi at 20 C; Temperature = deg. F Standard - Pressure = inH2O/psi at 4 C; Temperature = deg. F Standard - Pressure = inH2O/psi at 20 C; Temperature = deg.C Standard - Pressure = inH2O/psi at 4 C; Temperature = deg. C Custom N2 N3 N4 N5 N6 Preparation procedure Hydrogen service preparation Special services preparation P2 P4 Certificates Inspection certificate EN 10204-3.1.B of calibration (9-point) Certificate of compliance with the order EN 10204-2.1 of instrument design C1 C6 Material traceability Certificate of compliance with the order EN 10204-2.1 of process wetted parts Inspection certificate EN 10204-3.1.B of process wetted parts H1 H3 Connector Fieldbus 7/8 Fieldbus M12x1 Harting Han - straight entry Harting Han - angle entry 14 (RECOMMENDED for FOUNDATION Fieldbus) (RECOMMENDED for PROFIBUS PA) (Notes 3, 8) (Notes 3, 8) (Notes 2, 8) (Notes 2, 8) U1 U2 U3 U4 2600T Pressure Transmitters Model 264BS Note 1: Select type in additional ordering code Note 2: Not available with Electronic Housing code Z, R, G and W Note 3: Not available with Electronic Housing code P, E and K Note 4: Not available with Process flanges/adapters code D,E,G,H Note 5: Not available with Process flanges/adapters code A, B, G, H Note 6: Not available with Process flanges/adapters code A, B, D, E Note 7: Not available with PROFIBUS PA and FF output code 2 or 3 Note 8: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y TM Hastelloy is a Cabot Corporation trademark TM Monel is an International Nickel Co. trademark TM Viton is a Dupont de Nemour trademark SS/264BS_2 Standard delivery items (can be differently specified by additional ordering code) - Adapters supplied loose - Plug on axis (no drain/vent valves) - General purpose (no electrical certification) - No meter/display, no mounting bracket, no surge protection - English manual and labels - Configuration with kPa and deg. C units - No test, inspection or material traceability certificates THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING. 15 2600T Pressure Transmitters Model 264BS SS/264BS_2 The Company's policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. ABB has Sales & Customer Support expertise in over 100 countries worldwide Printed in Italy (01.04) www.abb.com/instrumentation SS/264BS_2 (c) ABB 2004 ABB Ltd Howard Road, St. Neots Cambridgeshire, PE19 3EU UK Tel: +44(0)1480 475321 Fax: +44(0)1480 217948 ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB SACE spa Business Unit Instrumentation Via Statale 113 22016 Lenno (CO) Italy Tel: +39 0344 58111 Fax: +39 0344 56278