SINAMICS DCM Cabinet Betriebsanleitung Operating Instructions 7/2012 SINAMICS drives SINAMICS DCM Cabinet ___________________ Preface 1 ___________________ Safety notes SINAMICS SINAMICS DCM Cabinet 2 ___________________ Device overview 3 ___________________ Mechanical installation ___________________ 4 Electrical installation ___________________ 5 Commissioning Operating Instructions ___________________ 6 Operation Functions, monitoring and ___________________ 7 protective functions Diagnostics / faults and ___________________ 8 alarms ___________________ 9 Maintenance and servicing ___________________ 10 Technical specifications ___________________ 11 Options ___________________ A Appendix 7/2012 A5E03740557 Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the relevant information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NURNBERG GERMANY Order number: 6RX1800-0SD74 07/2012 Technical data subject to change Copyright (c) Siemens AG 2012. All rights reserved Preface Scope of supply The SINAMICS DCM Cabinet is a part of a CDM (complete drive module) within the meaning of the definition in product standard EN61800-5-1 Chapter 3.1.2. The closed-loop control system and sequential control system within the meaning of this definition are not included in the scope of supply. User documentation WARNING Please read all the safety and warning notices carefully and all warning labels attached to the devices and cabinets before installation and commissioning of the electrical installation. The warning labels must always be legible. Missing or damaged labels must be replaced. Structure of this documentation The customer documentation comprises general and individual documentation. The general documentation describes the topics relevant to all versions of the SINAMICS DCM Cabinet and contains: SINAMICS DCM Cabinet Operating Instructions The Operating Instructions consist of the following sections: - Device description - Mechanical installation - Electrical installation - Commissioning guide - Description of function - Maintenance instructions - Technical specifications Overview diagrams These provide a general overview of the functionality of the SINAMICS DCM Cabinets. Basic function diagrams These provide an overview of the basic functions of the system for simple applications. SINAMICS DCM DC Converter Operating Instructions SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 3 Preface SINAMICS DCM List Manual The List Manual consists of the following sections: - Parameter list - Function diagrams - Fault / warning list Free function blocks manual Documentation for Drive Control Chart (DCC) - Programming and Operating Manual: DCC Editor description - Function Manual: Description of the standard DCC blocks The individual device documentation describes precisely one customized system and contains the following: Dimension drawing The dimension drawing documents the dimensions of the ordered system. Layout diagram The components installed in the ordered system are displayed in the layout diagram with the equipment codes and location codes. Circuit diagram The circuit diagram displays the electrical components installed in the ordered system including the equipment codes and location codes, their interconnections and the customer interfaces. Terminal diagram The terminal diagram shows all the customer terminals of the ordered system and the associated internal cabinet wiring. This diagram documents the line-side target wiring. Parts list All of the available spare parts for the ordered system are listed in the parts list with the equipment codes, the location codes and the order designation. Additional Operating Instructions The instructions for OEM components installed in the ordered system are supplied as OEM documentation. Service You can find information on our services and regional contact persons in the Internet (http://support.automation.siemens.com/WW/view/en/16604318) SINAMICS DCM Cabinet 4 Operating Instructions, 7/2012, A5E03740557 Preface Technical Support You can obtain technical assistance for products, systems, and solutions from our Technical support (www.siemens.com/automation/support-request) Central hotlines for Technical Support for the SINAMICS DCM Cabinet European and African time zone Phone: +49 (0)911 895 7222 Fax: +49 (0)911 895 7223 email (mailto:support.automation@siemens.com) America time zone 24-hour hotline: +1 800 333 7421 Asia/Australia time zone 8:00 to 17:00 CET Phone: +1 423 262 2960 Fax: +1 423 262 2200 email (mailto:support.america.automation@siemens.com) 8:00 to 17:00 Eastern Standard Time Phone: +86 1064 757575 Fax: +86 1064 747474 email (mailto:support.asia.automation@siemens.com) 7:30 to 17:30 Beijing local time Spare parts You can find information on spare parts In catalog D23.2 On the Internet from the electronic spare parts catalog Spares On Web by entering the serial number and order number of your SINAMICS DCM Cabinet (registration required) Spares On Web (http://workplace.automation.siemens.de/sparesonweb) In the supplied documentation: The parts list contains the order designations (MLFB) of the components used. Internet addresses Documents (manuals, certificates, FAQ etc. ) for the SINAMICS DCM Cabinet and the SINAMICS DCM DC Converter can be accessed on the following websites. SINAMICS DCM Cabinet (http://support.automation.siemens.com/WW/view/en/54418574/130000) SINAMICS DCM DC Converter (http://support.automation.siemens.com/WW/view/en/52233399/130000) Information about SINAMICS can be found at the following address: SINAMICS (http://www.siemens.com/sinamics) For Germany: "Noise protection" leaflet with additional links published by the DGUV (German Social Accident Insurance) (http://publikationen.dguv.de/dguv/pdf/10002/flyer-laerm.pdf) SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 5 Preface SINAMICS DCM Cabinet 6 Operating Instructions, 7/2012, A5E03740557 Table of contents Preface ...................................................................................................................................................... 3 1 2 3 4 Safety notes............................................................................................................................................. 13 1.1 Warning notices ...........................................................................................................................13 1.2 Safety and application instructions ..............................................................................................14 1.3 ESD-sensitive components..........................................................................................................15 Device overview....................................................................................................................................... 17 2.1 Chapter content ...........................................................................................................................17 2.2 Description ...................................................................................................................................17 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 2.3.7 2.3.8 Design ..........................................................................................................................................20 Frame size BC .............................................................................................................................21 Frame size CC .............................................................................................................................22 Frame size DC .............................................................................................................................23 Frame size EC .............................................................................................................................24 Frame size FC..............................................................................................................................25 Terminal Module Cabinet.............................................................................................................26 Cabinet fan...................................................................................................................................26 Degrees of protection of drive cabinets .......................................................................................27 2.4 Main components - overview .......................................................................................................28 2.5 Block diagram ..............................................................................................................................30 2.6 Type plate ....................................................................................................................................31 Mechanical installation............................................................................................................................. 33 3.1 Chapter content ...........................................................................................................................33 3.2 Transportation and storage..........................................................................................................33 3.3 3.3.1 3.3.2 3.3.2.1 3.3.2.2 3.3.2.3 3.3.2.4 3.3.2.5 3.3.3 3.3.3.1 3.3.3.2 3.3.3.3 3.3.4 3.3.5 Mounting ......................................................................................................................................35 Mechanical installation: checklist .................................................................................................35 Preparation...................................................................................................................................36 On-site requirements ...................................................................................................................36 Requirements on the levelness of the floor .................................................................................38 Shipping and handling indicators .................................................................................................39 Unpacking ....................................................................................................................................41 Required tools ..............................................................................................................................41 Installation ....................................................................................................................................41 Lifting the cabinet off the transport pallet.....................................................................................41 Disassembling the crane transport assembly ..............................................................................43 Installation ....................................................................................................................................44 Mechanical connection of transport units ....................................................................................44 Fitting additional canopies (option M21) or hoods (option M23, M43, M54) ...............................45 Electrical installation ................................................................................................................................ 49 SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 7 Table of contents 4.1 Chapter content........................................................................................................................... 49 4.2 Checklist for electrical installation ............................................................................................... 49 4.3 Important safety precautions....................................................................................................... 56 4.4 Introduction to EMC .................................................................................................................... 57 4.5 EMC-compliant design ................................................................................................................ 58 4.6 4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.7 4.6.8 Cable routing............................................................................................................................... 60 Armature AC ............................................................................................................................... 60 DC armature................................................................................................................................ 62 Infeed AC auxiliary power supply................................................................................................ 64 Field DC ...................................................................................................................................... 66 Terminal Module Cabinet (TMC)................................................................................................. 68 Analog tachometer ...................................................................................................................... 70 Terminal strip X2 ......................................................................................................................... 73 Terminals XK, input and output coupling relay ........................................................................... 74 4.7 4.7.1 4.7.2 4.7.3 4.7.4 Power connections...................................................................................................................... 75 Overview ..................................................................................................................................... 75 Connection cross-sections .......................................................................................................... 75 Connecting the motor and power cables .................................................................................... 76 Main switch incl. fuses/circuit breakers....................................................................................... 77 4.8 4.8.1 4.8.2 External supply............................................................................................................................ 79 230 V AC auxiliary supply ........................................................................................................... 79 24 V DC auxiliary supply ............................................................................................................. 79 4.9 4.9.1 Signal connections ...................................................................................................................... 80 Terminal Module Cabinet (TMC) A7119 terminal strip X71 or X72 (with option G10, G11)....... 80 4.10 4.10.1 4.10.2 4.10.3 4.10.4 4.10.5 Other connections ....................................................................................................................... 85 Analog tachometer connection ................................................................................................... 86 m.c.b. trip combined alarm signal ............................................................................................... 86 External E-STOP button.............................................................................................................. 87 Input coupling relays ................................................................................................................... 87 Output coupling relays ................................................................................................................ 88 4.11 Connecting the options ............................................................................................................... 88 5 Commissioning ........................................................................................................................................ 89 6 Operation................................................................................................................................................. 95 7 Functions, monitoring and protective functions ........................................................................................ 97 7.1 Overview of the functions............................................................................................................ 97 7.2 Scope of supply........................................................................................................................... 97 7.3 Block diagrams............................................................................................................................ 99 7.4 Auxiliary supply ......................................................................................................................... 102 7.5 Power unit infeed ...................................................................................................................... 102 7.6 Armature circuit supply power circuit ........................................................................................ 103 7.7 Field supply power circuit.......................................................................................................... 104 7.8 Control functions for switch on, switch off and release............................................................. 104 SINAMICS DCM Cabinet 8 Operating Instructions, 7/2012, A5E03740557 Table of contents 8 9 10 11 7.9 E-STOP......................................................................................................................................105 7.10 Control of equipment fan, cabinet fan and motor fan ................................................................105 Diagnostics / faults and alarms .............................................................................................................. 107 8.1 Diagnostics.................................................................................................................................107 8.2 8.2.1 Operating states, alarms and faults ...........................................................................................107 General information on alarms and faults..................................................................................108 Maintenance and servicing .................................................................................................................... 111 9.1 Chapter content .........................................................................................................................111 9.2 9.2.1 Maintenance...............................................................................................................................112 Cleaning .....................................................................................................................................112 9.3 Maintenance...............................................................................................................................113 9.4 9.4.1 9.4.2 9.4.3 9.4.4 9.4.5 Replacing components ..............................................................................................................114 Replacing the filter mats ............................................................................................................115 Replacing the cabinet fan ..........................................................................................................116 Replacing fuses .........................................................................................................................117 Replacing the door-mounted operator panel .............................................................................119 Replacing the back-up battery in the AOP30 operator panel ....................................................119 9.5 Maintenance and replacing the SINAMICS DCM DC Converter...............................................121 9.6 Load the cabinet-specific parameter settings to parameter data set 20....................................122 9.7 Messages after replacement of DRIVE-CLiQ components .......................................................123 9.8 Loading new operator panel firmware from the PC ...................................................................124 Technical specifications......................................................................................................................... 125 10.1 Chapter content .........................................................................................................................125 10.2 10.2.1 10.2.2 General data ..............................................................................................................................125 Load types..................................................................................................................................127 Derating......................................................................................................................................131 10.3 Technical specifications .............................................................................................................134 10.4 Cable types ................................................................................................................................179 Options .................................................................................................................................................. 181 11.1 11.1.1 11.1.2 11.1.3 11.1.4 11.1.5 11.1.6 11.1.7 11.1.8 11.1.9 11.1.10 11.1.11 11.1.12 SINAMICS DCM DC Converter .................................................................................................181 G00, Advanced CUD left............................................................................................................181 G10, standard CUD right ...........................................................................................................183 G11, Advanced CUD right .........................................................................................................185 G20, Communication Board CBE20 left ....................................................................................187 G21, Communication Board CBE20 right ..................................................................................190 L10, without field power unit ......................................................................................................193 L11, 2Q field power unit .............................................................................................................193 L21, unit fan for single-phase connection ..................................................................................194 L85, 85 A field power unit ..........................................................................................................194 M10, nickel-plated copper busbars............................................................................................195 S01, memory card left................................................................................................................195 S02, memory card right..............................................................................................................196 SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 9 Table of contents 11.2 11.2.1 11.2.2 11.2.3 11.2.4 11.2.5 11.2.6 11.2.7 11.2.8 11.2.9 Other voltages, frequencies ...................................................................................................... 196 L04 armature supply with extra-low voltage 10 to 50 V ............................................................ 196 L05, electronics power supply for connection to 24 V DC ........................................................ 197 L06, 24 V DC supply with SITOP.............................................................................................. 197 L07, 24 V DC power supply from an external supply................................................................ 197 L09, 24 V DC power supply using SITOP UPS ........................................................................ 199 V60, rated line frequency 60 Hz................................................................................................ 199 Y02, adaptation transformer for the field supply ....................................................................... 200 Y03, 3AC auxiliary voltage not available................................................................................... 201 Y04, 3 AC auxiliary voltage not the same as the standard voltage .......................................... 202 11.3 11.3.1 11.3.2 OFF functions............................................................................................................................ 203 B30, intervention option for the infeed circuit breaker interlocking ........................................... 203 L57, EMERGENCY OFF Category 0 for uncontrolled stopping in accordance with EN 60204-1 ..................................................................................................................................... 205 L59, EMERGENCY STOP Category 1 for controlled stopping in accordance with EN 60204-1 ..................................................................................................................................... 207 11.3.3 11.4 11.4.1 11.4.2 11.4.3 11.4.4 11.4.5 11.4.6 11.4.7 11.4.8 Display instruments................................................................................................................... 210 B60, display instrument "speed" ............................................................................................... 210 B61, display instrument "armature voltage" .............................................................................. 211 B62, display instrument "armature current" .............................................................................. 212 B63, display instrument, "line voltage excitation"...................................................................... 213 B64, display instrument "excitation current".............................................................................. 213 B65, display instrument, "line voltage armature circuit" ............................................................ 214 B66, display instrument "Line current armature circuit" ............................................................ 214 P11, display instrument for line values with PROFIBUS connection (installed in the cabinet door) ............................................................................................................................. 215 11.5 11.5.1 11.5.2 11.5.3 11.5.4 11.5.5 11.5.6 11.5.7 11.5.8 11.5.9 11.5.10 11.5.11 11.5.12 11.5.13 11.5.14 11.5.15 11.5.16 11.5.17 11.5.18 Supplementary circuits.............................................................................................................. 216 C51, 24 V coil voltage of the coupling relay at the binary inputs .............................................. 216 K85, field reversal ..................................................................................................................... 218 L00, radio interference suppression filter.................................................................................. 219 L22, elimination of the three-phase commutating reactor......................................................... 220 L50, cabinet lighting and service socket outlet ......................................................................... 220 L55, cabinet anti-condensation heating .................................................................................... 223 V70, input isolating amplifier input: 0 mA to 20 mA .................................................................. 226 V71, input isolating amplifier input: 4 mA to 20 mA .................................................................. 228 V72, input isolating amplifiers input: 0 V to +10 V .................................................................... 229 V73, input isolating amplifier input: -20 mA to +20 mA ............................................................. 230 V74, input isolating amplifier input: -10 V to +10 V ................................................................... 231 Y51, mechanical motor brake ................................................................................................... 232 Y52, output isolating amplifier output: 0 mA to 20 mA.............................................................. 234 Y53, output isolating amplifier output: 4 mA to 20 mA.............................................................. 236 Y54, output isolating amplifier output: 0 V to 10 V.................................................................... 236 Y55, output isolating amplifier output: -20 mA to +20 mA......................................................... 237 Y56, output isolating amplifier output: -10 V to 10 V................................................................. 237 Y60, coupling relay for binary output ........................................................................................ 238 11.6 11.6.1 11.6.2 11.6.3 Motor-relevant options .............................................................................................................. 240 A06, brush wear monitoring, limit signal, isolated..................................................................... 240 A30, anti-condensation heating for motor up to maximum 2000 W, 230V ............................... 242 A97, air flow monitoring in the motor ........................................................................................ 244 SINAMICS DCM Cabinet 10 Operating Instructions, 7/2012, A5E03740557 Table of contents 11.6.4 11.6.5 11.6.6 11.6.7 11.6.8 L86, evaluation unit for the following temperature sensors: KTY84-130, PT100 2-wire and 3-wire, PT1000 2-wire and 3-wire, NTC ....................................................................................246 W15, no output to be provided for a motor fan ..........................................................................248 W20 to W41, setting range of the motor circuit breaker for the motor fan.................................249 W70 to W91, feeder for a second motor fan..............................................................................252 Y01, matching transformer for motor fan ...................................................................................254 11.7.7 11.7.8 Monitoring functions...................................................................................................................255 B83, overvoltage protection .......................................................................................................255 L52, ARC detector (arcing detector) ..........................................................................................257 L82, fault current monitoring in the grounded line supply (TN or TT supply system) ................257 L84, PTC evaluation device for alarm and fault for two sensors ...............................................260 L87, insulation monitoring in non-grounded line supplies (IT system) with insulating monitoring devices from the Bender company ..........................................................................263 L88, insulation monitoring in non-grounded line supplies (IT system) with insulating monitoring devices from the AREVA company..........................................................................265 L90, CCP (Converter Commutation Protector) ..........................................................................268 L99, monitoring the temperature inside the drive cabinet..........................................................270 11.8 11.8.1 11.8.2 11.8.3 Supplementary modules ............................................................................................................271 G60, customer terminal block extension using a Terminal Module TM31.................................271 G62, customer terminal block extension using a Terminal Module TM15.................................274 K50, Sensor Module Cabinet-Mounted SMC30.........................................................................277 11.9 11.9.1 11.9.2 11.9.3 11.9.4 11.9.5 11.9.6 11.9.7 11.9.8 Mechanical options ....................................................................................................................280 M21, degree of protection IP21..................................................................................................280 M23, IP23 degree of protection..................................................................................................281 M43, degree of protection IP43..................................................................................................282 M54, degree of protection IP54 with filter elements...................................................................283 M58, degree of protection IP54 with climate control system .....................................................284 M59, closed cabinet door, air inlet from below through floor opening .......................................284 M60, additional shock protection ...............................................................................................285 M66, marine version ..................................................................................................................285 11.10 11.10.1 11.10.2 11.10.3 Other options..............................................................................................................................286 K07, without Advanced Operator Panel AOP30 ........................................................................286 L91, commissioning interface (PROFIBUS) routed to the outside ............................................286 U09, version according to the requirements of UL ....................................................................287 11.7 11.7.1 11.7.2 11.7.3 11.7.4 11.7.5 11.7.6 Documentation ...........................................................................................................................288 11.11 11.11.1 D19, circuit diagram prepared for motor overtemperature monitoring using a limit value transmitter ..................................................................................................................................288 11.11.2 D20, circuit diagram prepared for motor temperature monitoring..............................................289 11.11.3 D21, circuit diagram prepared for speed actual value sensing (pulse encoder) .......................290 11.11.4 D22, circuit diagram prepared for speed actual value sensing (analog tachometer) ................291 A Appendix................................................................................................................................................ 293 A.1 Connectable conductor cross-sections for screw terminals ......................................................293 A.2 Environment, resources and recycling.......................................................................................296 A.3 Standards...................................................................................................................................298 A.4 Certifications ..............................................................................................................................299 Index...................................................................................................................................................... 301 SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 11 Table of contents SINAMICS DCM Cabinet 12 Operating Instructions, 7/2012, A5E03740557 1 Safety notes 1.1 Warning notices WARNING Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. This personnel must be thoroughly familiar with all warning and maintenance procedures described in these operating instructions. The successful and safe operation of this device is dependent on correct transport, proper storage and installation, as well as careful operation and maintenance. National safety guidelines must be observed. DANGER Operation of electrical installations in accordance with EN 50110-1 This standard applies to the operation of and all work on, with or in the vicinity of electrical installations. The "five safety rules" must be observed in particular for all work: 1. Disconnect the system. 2. 3. 4. 5. Protect against reconnection. Make sure that the equipment is de-energized. Ground and short-circuit. Cover or fence off adjacent components that are still live. SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 13 Safety notes 1.2 Safety and application instructions 1.2 Safety and application instructions DANGER This electrical equipment is used in industrial high-voltage installations. During operation, this equipment contains rotating parts (fan) and live, bare parts. For this reason, it could cause severe injury or significant material damage if the required covers are removed without authorization, if the equipment is used or operated incorrectly, or if it has not been properly maintained. When the equipment is used in non-industrial areas, the installation location must be protected against unauthorized access (e.g. protective fencing). NOTICE In a residential environment this product can cause high-frequency disturbances, which may make interference suppression measures necessary. Preconditions Those responsible for protecting the plant must ensure the following: The basic planning work for the plant and the transport, assembly, installation, commissioning, maintenance, and repair work is carried out by qualified personnel and/or checked by experts responsible. The operating instructions must always be available for all of the work that is performed. The technical data and specifications regarding the permissible installation, connection, environmental and operating conditions are always consequentially observed. The country-specific and plant-specific installation and safety guidelines are observed and personal protection equipment is used. Unqualified personnel are forbidden from using this equipment and working near this equipment. These Operating Instructions are intended for qualified personnel and only contain information and notes relating to the intended purpose of the equipment. The Operating Instructions are in the languages specified in the supply contracts. Note We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. SINAMICS DCM Cabinet 14 Operating Instructions, 7/2012, A5E03740557 Safety notes 1.3 ESD-sensitive components WARNING Hearing protection Note the regional regulations for the use of hearing protection. In general, the use of hearing protection is required or recommended for a sound level of 80 dB(A). The noise emission for the ordered system is specified in Chapter Technical specifications (Page 134) in the line, fan noise. For Germany, you will find an Internet link on this topic in the preface under Internet addresses. 1.3 ESD-sensitive components CAUTION The electronic boards contain electrostatic sensitive devices. These can be easily destroyed if not handled properly. If you have to work with electronic modules, please note: You should only touch electronic modules if absolutely necessary. If you do have to touch modules, your body must be electrically discharged first. Boards must not come into contact with highly insulating materials (such as plastic parts, insulated desktops, articles of clothing manufactured from man-made fibers). Modules must only be set down on conductive surfaces. Boards and components should only be stored and transported in conductive packaging (such as metalized plastic boxes or metal containers). If the packaging material is not conductive, the modules must be wrapped with a conductive packaging material (such as conductive foam rubber or household aluminum foil). The necessary ESD protection measures are elucidated once again in the following illustration: Seated Standing Seated/standing a conductive floor b ESD Table c ESD footwear "d" ESD smock e ESD wrist strap f cubicle ground connection SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 15 Safety notes 1.3 ESD-sensitive components SINAMICS DCM Cabinet 16 Operating Instructions, 7/2012, A5E03740557 Device overview 2.1 2 Chapter content This chapter provides information on the following: Introduction to the SINAMICS DCM Cabinet The design of the systems and the main components The circuit principle Explanation of the type plate 2.2 Description The SINAMICS drive family Area of application SINAMICS is the family of drives from Siemens designed for machine and plant construction. SINAMICS offers solutions for all drive tasks: Variants Depending on the application, the SINAMICS range offers the ideal variant for any drive task. SINAMICS DCM is the DC drive belonging to the SINAMICS family. As a result of its uniform expandability, it can handle both basic and demanding requirements for drive applications and complementary markets. Platform concept and Totally Integrated Automation All SINAMICS variants are based on a platform concept. Joint hardware and software components, as well as standardized tools for dimensioning, configuration, and commissioning tasks ensure high-level integration across all components. SINAMICS handles a wide variety of drive tasks with no system gaps. The different SINAMICS variants can be easily combined with each other. SINAMICS is part of the Siemens "Totally Integrated Automation" concept. The degree of integration of SINAMICS with respect to engineering, data management, and communication with the automation level means that solutions with the SIMOTION, SINUMERIK and SIMATIC control systems can be cost-effectively implemented. Quality management to DIN EN ISO 9001 SINAMICS is able to meet the highest quality requirements. Comprehensive quality assurance measures in all development and production processes ensure a consistently high level of quality. SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 17 Device overview 2.2 Description Our quality management system is certified by an independent authority in accordance with DIN EN ISO 9001. System properties The SINAMICS range is characterized by the following system properties: Standard and seamless functionality based on a platform concept Standardized engineering High degree of flexibility and combination capability Wide range of power ratings Designed for global use Economic efficiency and effectiveness High energy efficiency Versatile interfacing facilities to higher-level controllers Totally Integrated Automation SINAMICS DC MASTER Cabinet The SINAMICS DC MASTER Cabinet is the ready-for-connection drive cabinet. The SINAMICS DC MASTER DC Converter forms the heart of the cabinet and is scalable in many areas, including computer performance, field power supply, armature power supply and interfaces. The basic version of the SINAMICS DC MASTER Cabinet itself comes with all the components required to supply power to a DC motor from the three-phase network, is ready for connection and can be put into operation immediately via the AOP30. In addition to the DC Converter options, the SINAMICS DC MASTER Cabinet has a large number of cabinet options and can therefore be adapted to a wide range of different requirements and conditions. Optionally, for example, it is possible to adapt the system to the environmental conditions or to the available auxiliary power supply. It is also possible to use the basic version of the cabinet as a starting point for order-specific adaptations, from simply rounding off a standard option to power expansion or special applications. Main applications Industrial machines and plants (steel/aluminum, plastics, printing, paper, cranes, mining, oil and gas) in the new plant and retrofit business Application examples Rolling mills Cross cutters and shears Wire-drawing machines Drilling rigs Extruders and kneaders SINAMICS DCM Cabinet 18 Operating Instructions, 7/2012, A5E03740557 Device overview 2.2 Description Presses Elevators and cranes Cableways and lifts Mine hoists Test stand drives Highlights Ready for connection and ready for switching on The SINAMICS DC MASTER Cabinet is ready for connection and ready for switching on. This can reduce planning and commissioning times and plant downtimes, and functionality is guaranteed by means of optimally coordinated components. Supply for motor fan The power supply for the external fan of the DC motor is part of the basic version, including motor circuit breakers. The set values of the circuit breaker can be tuned to the motor by selecting the corresponding option. Flexibility in the auxiliary power supply SINAMICS DC MASTER Cabinets can be used universally and flexibly for wide voltage ranges. Adaptation to the existing control voltage is particularly significant for modernization of existing installations. The auxiliary power supply of the converter cabinet is adjusted by specifying the existing mains voltage. If no separate auxiliary power supply is available, it is branched off inside the cabinet. EMC zone concept Thanks to the EMC zone concept, the SINAMICS DC MASTER Cabinet is ideally designed for industry both in terms of robustness to interference and in terms of low emitted interference. The zone concept applies to the spatial arrangement of the built-in components. These include the electrical/electronic devices, but also cables for energy and signals, which may be sources of interference or susceptible equipment. Separate cable routing and high frequency low-ohm connections are a characteristic of the concept. In order to apply this concept to the line-side as well, the easily accessible customer interfaces not only provide the appropriate terminals and shield buses, but also provide sufficient space to place cable shields as per regulations. The drive cabinet designed as per this concept provides fault-free operation in terms of electromagnetic compatibility. See also Chapter EMC-compliant design (Page 58) Monitoring the internal temperature of the drive cabinet The availability of a drive is in practice often influenced by changes in environmental conditions: - Additional external heat sources in the environment can increase the air intake temperature. - Unusually high contamination in the air clogs up the air intake filter. - Subsequent addition to the drive cabinet of devices with high heat loss places an additional load on heat dissipation in the cabinet. Monitoring the internal temperature of the drive cabinet via a PTC thermistor sensor can identify these influences early and remedial measures can be applied in good time. SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 19 Device overview 2.3 Design Good access to individual components and interfaces Despite the compact design, the individual components in the SINAMICS DC MASTER Cabinet are clearly arranged and easily accessible. The connecting terminals in particular are arranged in such a way that there is sufficient space for installation and strain relief of the lines and cables. The signal lines are grouped and routed on terminals in the lower part of the cabinet. Type-tested The SINAMICS DC MASTER Cabinets are type-tested. The comprehensive tests, e.g. for mechanical and electrical stability and heat dissipation, confirm our high quality requirements. Documentation A circuit diagram and a terminal diagram are supplied in addition to the manuals for the SINAMICS DC MASTER DC Converter. The plans are prepared individually and reflect the delivery state of the converter cabinets exactly. The plans can also be provided in digital format for integration into CAE systems by the customer. Project-specific special solutions In addition to 12-pulse series and 12-pulse parallel circuit configurations, solutions for power expansion or for use in the medium-voltage range can also be prepared (on request). Depending on requirements, the converter cabinet is mounted externally on the SINAMICS DC MASTER Converter or with the control module and separate power unit. Service Our worldwide sales and service network offers our customers consulting services tailored to their needs, provides support with planning and design, and offers a range of training courses. Contact information and the current link to our website can be found in the preface. 2.3 Design Note The detailed dimension drawing of your system can be found on the supplied DVD. The outstanding SINAMICS DCM Cabinets have a compact, modular, and service-friendly design. They contain all the required mains connection components, e.g. main switches, circuit breakers, main contactor and line fuses, and additional options such as line filter can be added. A wide range of options is therefore available, depending on the cabinet version, so that the drive system can be adapted optimally to the applicable requirements. SINAMICS DCM Cabinet 20 Operating Instructions, 7/2012, A5E03740557 Device overview 2.3 Design 2.3.1 Frame size BC View, dimensions Figure 2-1 Frame size BC SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 21 Device overview 2.3 Design 2.3.2 Frame size CC View, dimensions Figure 2-2 Frame size CC SINAMICS DCM Cabinet 22 Operating Instructions, 7/2012, A5E03740557 Device overview 2.3 Design 2.3.3 Frame size DC View, dimensions Figure 2-3 Frame size DC SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 23 Device overview 2.3 Design 2.3.4 Frame size EC View, dimensions Figure 2-4 Frame size EC SINAMICS DCM Cabinet 24 Operating Instructions, 7/2012, A5E03740557 Device overview 2.3 Design 2.3.5 Frame size FC View, dimensions Figure 2-5 Frame size FC SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 25 Device overview 2.3 Design 2.3.6 Terminal Module Cabinet The Terminal Module Cabinet (TMC) is installed in the lower part of the cabinet. This means that all digital and analog inputs/outputs can be connected quickly and easily. The installation location has been chosen to ensure physical separation from the electric power cables and so that the cable length of the existing signal-carrying cables is usually sufficient to operate the signal terminals after modernization. The digital inputs/outputs are connected by a coupling relay to ensure reliability. Figure 2-6 Terminal Module Cabinet For terminal assignment, see Chapter Terminal Module Cabinet (TMC) A7119 terminal strip X71 or X72 (with option G10, G11) (Page 80). 2.3.7 Cabinet fan In the basic version, the frame size BC converter cabinets are equipped with a cabinet fan (roof mounting). Depending on the degree of protection, cabinet fans are also used for the cabinets of the other frame sizes (roof fan and/or fan in cabinet). The information regarding air flow (rate) and fan noise can be found in Chapter Technical specifications (Page 134). SINAMICS DCM Cabinet 26 Operating Instructions, 7/2012, A5E03740557 Device overview 2.3 Design 2.3.8 Degrees of protection of drive cabinets The EN 60529 standard covers the protection of electrical equipment by means of housings, covers or equivalent, and includes: Protection of persons against accidental contact with live or moving parts within the housing and protection of the equipment against the ingress of solid foreign matter (touch protection and protection against ingress of solid foreign bodies) Protection of the equipment against the ingress of water (water protection) Abbreviations for the internationally agreed degrees of protection The degrees of protection are specified by abbreviations comprising the code letters IP and two digits. Table 2- 1 Degrees of protection of the drive cabinet: Degrees of protection of the drive cabinet First code number (touch protection and protection against ingress of foreign solid matter) Second code number (protection of equipment against the ingress of water) Version of the SINAMICS DCM Cabinet IP20 Protected against solid foreign bodies, diameter 12.5 mm. No water protection. Basic version IP21 Protected against solid foreign bodies, diameter 12.5 mm. Protected against drip water With option M21 Protected against solid foreign bodies, diameter 12.5 mm. Protected against spray water Protected against solid foreign bodies, diameter 1 mm. Protected against spray water Dust protected. Protected against splash water Ingress of dust is not totally prevented, but dust must not be allowed to enter in such quantities that the functioning or safety of the equipment is impaired. Water splashing onto the enclosure from any direction must not have a harmful effect. IP23 IP43 IP54 Vertically falling water drops shall not have a harmful effect. With option M23 Water sprayed on both sides of the vertical at an angle of up to max. 60 must not have a harmful effect. With option M43 Water sprayed on both sides of the vertical at an angle of up to max. 60 must not have a harmful effect. With option M54 (with filter mats) and with option M58 (with air conditioner) SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 27 Device overview 2.4 Main components - overview 2.4 Main components - overview Example: frame size BC 6,1$0,&6 '&0$67(5 '&&RQYHUWHU $23$GYDQFHG2SHUDWRU3DQHO $X[LOLDU\VXSSO\0DLQVZLWFK 7UDQVIRUPHU FRYHUHG )LHOGFLUFXLWUHDFWRU FRYHUHG 0RWRUFRQQHFWLRQ'&IXVH $UPDWXUHFLUFXLWPDLQVZLWFK 7HUPLQDO0RGXOH&DELQHW $UPDWXUHFLUFXLWPDLQFRQWDFWRU $UPDWXUHFRQQHFWLRQWRHTXLSPHQW DOUHDG\RQVLWH $UPDWXUHFLUFXLWUHDFWRU 3URWHFWLYHFRQGXFWRUFRQQHFWLRQ Figure 2-7 Main components - overview, frame size BC SINAMICS DCM Cabinet 28 Operating Instructions, 7/2012, A5E03740557 Device overview 2.4 Main components - overview Example: frame size EC 6,1$0,&6 '&0$67(5 '&&RQYHUWHU $23 $GYDQFHG 2SHUDWRU3DQHO $X[LOLDU\VXSSO\ 0DLQVZLWFK 7UDQVIRUPHU FRYHUHG )LHOGFLUFXLW UHDFWRU FRYHUHG 0RWRU FRQQHFWLRQ LQ WKHGHYLFH $UPDWXUH FLUFXLWPDLQ VZLWFK &XVWRPHU WHUPLQDOV FRXSOLQJUHOD\V $UPDWXUH FRQQHFWLRQWR HTXLSPHQW DOUHDG\RQVLWH 7HUPLQDO 0RGXOH &DELQHW $UPDWXUH FLUFXLWUHDFWRU 3URWHFWLYH FRQGXFWRU FRQQHFWLRQ Figure 2-8 Main components - overview, frame size EC SINAMICS DCM Cabinet Operating Instructions, 7/2012, A5E03740557 29 Device overview 2.5 Block diagram 2.5 Block diagram /LQHFRQQHFWLRQ 0DLQVZLWFKIRUWKHDUPDWXUH FLUFXLWDQGDX[LOLDU\SRZHU VXSSO\ &DEOHDQGVHPLFRQGXFWRUIXVHV /LQHFRQWDFWRUFLUFXLWEUHDNHU VHPLFRQGXFWRUIXVHV! /LQHUHDFWRUV 8. 6,1$0,&6'&0'&&RQYHUWHU LQFOXGLQJILHOGPRGXOH 0RWRUFRQQHFWLRQV <1> The main switch, fuse and main contactor functions are provided by a circuit breaker in systems with an output current of 950 A. Figure 2-9 Block diagram SINAMICS DCM Cabinet 30 Operating Instructions, 7/2012, A5E03740557 Device overview 2.6 Type plate 2.6 Type plate Type plate 'HYLFHGHVLJQDWLRQ 2UGHUQXPEHU 2SWLRQV 3ODQWQXPEHU ([DPSOH 4% 0RQWKRIPDQXIDFWXUH