Application Hints (Continued)
TRANSMISSION LINE TERMINATION
On a transmission line which is electrically long, it is advis-
able to terminate the line in its characteristic impedance to
prevent signal reflection and its associated noise/cross-talk.
A 180Ωtermination resistor is provided in the DS78LS120/
DS88LS120 line receiver. To use the termination resistor,
connect pins 2 and 3 together and pins 13 and 14 together.
The 180Ωresistor provides a good compromise between
line reflections, power dissipation in the driver, and IR drop in
the transmission line. If power dissipation and IR drop are
still a concern, a capacitor may be connected in series with
the resistor to minimize power loss.
The value of the capacitor is recommended to be the line
length (time) divided by 3 times the resistor value. Example:
if the transmission line is 1,000 feet long, (approximately
1000 ns), and the termination resistor value is 180Ω, the ca-
pacitor value should be 1852 pF. For additional application
details, refer to application notes AN-22 and AN-108.
FAIL-SAFE OPERATION
Communication systems require elements of a system to de-
tect the presence of signals in the transmission lines, and it
is desirable to have the system shut-down in a fail-safe
mode if the transmission line is open or shorted. To facilitate
the detection of input opens or shorts, the DS78LS120/
DS88LS120 incorporates an input threshold voltage offset.
This feature will force the line receiver to a specific logic
state if presence of either fault is a condition.
Given that the receiver input threshold is ±200 mV, an input
signal greater than ±200 mV insures the receiver will be in a
specific logic state. When the offset control input (pins 1 and
15) is connected to V
CC
=5V, the input thresholds are offset
from 200 mV to 700 mV, referred to the non-inverting input,
or −200 mV to −700 mV, referred to the inverting input.
Therefore, if the input is open or shorted, the input will be
greater than the input threshold and the receiver will remain
in a specified logic state.
The input circuit of the receiver consists of a 5k resistor ter-
minated to ground through 120Ωon both inputs. This net-
work acts as an attenuator, and permits operation with
common-mode input voltages greater than ±15V. The offset
control input is actually another input to the attenuator, but its
resistor value is 56k. The offset control input is connected to
the inverting input side of the attenuator, and the input volt-
age to the amplifier is the sum of the inverting input plus 0.09
times the voltage on the offset control input. When the offset
control input is connected to 5V the input amplifier will see
V
IN(INVERTING)
+0.45V or V
IN(INVERTING)
+0.9V when the con-
trol input is connected to 10V. The offset control input will not
significantly affect the differential performance of the re-
ceiver over its common-mode operating range, and will not
change the input impedance balance of the receiver.
It is recommended that the receiver be terminated (500Ωor
less) to insure it will detect an open circuit in the presence of
noise.
The offset control can be used to insure fail-safe operation
for unbalanced interface (RS-423) or for balanced interface
(RS-422) operation.
For unbalanced operation, the receiver would be in an inde-
terminate logic state if the offset control input was open.
Connecting the fail-safe offset pin to 5V, offsets the receiver
threshold to 0.45V. The output is forced to a logic zero state
if the input is open or shorted.
DS007499-10
FIGURE 2.
Unbalanced RS-423 and RS-232 Fail-Safe
DS007499-11
www.national.com5