https://www.phoenixcontact.com/us/products/2800304
09/10/2014Page2/5
Type 1 surge protection plug-FLT 100 N/PE-1.5-ST-2800304
Technical data
General
IEC power supply system TN-S
TT
Lightning protection class I
SPD design Voltage-switching type
Mode of protection N-PE
Mounting type On base element
Color black
Housing material PBT
Pollution degree 2
Inflammability class according to UL 94 V-0
Type Male
Number of positions 1
Surge protection fault message None
Protective circuit
Nominal voltage UN240 V AC (TN - only N-PE)
240 V AC (TT - only N-PE)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC260 V AC
Residual current IPE ≤ 0.01 mA
Follow current interrupt rating Ifi 100 A (260 V AC)
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures ≤ 1.5 kV (at In)
≤ 1 kV (at 10 kA)
≤ 0.9 kV (at 5 kA)
≤ 0.8 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 1.5 kV
TOV behavior at UT1200 V AC (200 ms / withstand mode)
Response time tA≤ 100 ns
NEMA/UL protective circuit
UL class Type 4 SPD for Type 2 applications
Maximum continuous operating voltage MCOV (N-G) 264 V AC
Mode of protection N-G
Power distribution system 1S
Nominal frequency 50/60 Hz
Voltage protection rating VPR (N-G) 1.5 kV
Nominal discharge current In (N-G) 20 kA