https://www.phoenixcontact.com/us/products/2906861
04/10/2017Page1/4
Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Coarse surge protection with integrated status indicator for a signal wire with grounded reference potential.
The figure shows version TTC-6-
GDT-C-24AC-PT-I
Why buy this product
Space-saving installation due to the narrow overall width of 6.2 mm
Signaling without additional auxiliary power, thanks to the mechanical status indicator
Optional remote signaling module monitors up to 40 items, without additional wiring
Quick and tool-free installation of surge protective devices, thanks to Push-in connection technology
Safe behavior in the event of overload, thanks to the integrated disconnect device
Coarse surge protection by means of gas discharge tube
Key Commercial Data
Packing unit 1
GTIN
GTIN 4055626137162
Custom tariff number 85363010
Technical data
Dimensions
Height 92 mm
92 mm
Width 6.2 mm
https://www.phoenixcontact.com/us/products/2906861
04/10/2017Page2/4
Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Technical data
Dimensions
Depth 69.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN110 V AC
Maximum continuous voltage UC130 V AC
Rated current 2 A (60°C)
Operating effective current IC at UC≤ 1 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (core-earth) 5 kA
Pulse discharge current Iimp (10/350)µs (core-ground) 0.5 kA
Voltage protection level Up (core-ground) ≤ 800 V (C1 - 2 kV)
≤ 1 kV (C2 - 10 kV)
≤ 800 V (C3 - 25 A)
≤ 900 V (C3 - 100 A)
Response time tA (core-earth) ≤ 100 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 8 MHz / 150 Ω)
typ. 0.3 dB (≤ 30 MHz / 50 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system typ. 130 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 25 MHz
Capacity (core-earth) 5 pF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
https://www.phoenixcontact.com/us/products/2906861
04/10/2017Page3/4
Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Technical data
Protective circuit
Impulse durability (conductor-ground) C1 - 1 kA
C2 - 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (conductor-ground) ≤ 1 ms
Connection data
Connection method Push-in connection
Connection method IN Push-in connection
Connection method OUT Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Drawings
Diagram
2
1
3
8040 50 60 70
I [A]
T [°C]
90
Dimensional drawing
62
69,5
92 6,2
Circuit diagram
3
4
1
2
!
unprotected protected
Approvals
Approvals
https://www.phoenixcontact.com/us/products/2906861
04/10/2017Page4/4
Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Approvals
Approvals
UL Listed
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168
Phoenix Contact 2017 © - all rights reserved