57
REGULATINGSTEGO - PRODUCT CATALOGUE
TECHNICAL DATA
Switch difference (temperature) 2K (±1K tolerance) at +25°C (+77°F), 50% RH
Switch difference (humidity) 4% RH (±1% tolerance) at +25°C (+77°F), 50% RH
Reaction time (humidity) approx. 5 sec.
Contact type change-over contact (relay)
Service life VDE: NO/NC > 15,000 cycles
UL: NO/NC > 30,000 cycles
Max. switching capacity (relay output) 240VAC, 10 (1.6) A
60VDC, 0.6A¹
Max. inrush current 30AAC for 10 sec.
Optical indicator LED
Connection
5-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm²
stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN 60715
Casing plastic according to UL94 V-0, light grey
Dimensions 77 x 60 x 43mm
Weight approx. 0.2kg
Fitting position vertical
Operating/Storage temperature -40 to +60°C (-40 to +140°F)
Operating/Storage humidity max. 95% RH (non-condensing)
Protection type IP20
Approvals VDE + UL File No. E164102
¹ not UL confirmed
The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/elec-
tronic components and turns on a heater (or alternatively a fan) at either set point, helping prevent the formation of
condensation in the enclosure. Due to its wide voltage range the hygrotherm can be utilised anywhere in the world.
The external sensor can be positioned freely anywhere in the enclosure for precise measurements.
> Temperature and humidity adjustable
> Wide voltage range
> Operating temperature down to -40°C
> High switching capacity
> With external sensor
Example of connection
HeaterHygrotherm
ETF 012
ELECTRONIC HYGROTHERM WITH EXTERNAL SENSOR
ETF 012
Art. No. Cable 1m Art. no. Cable 2m Operating voltage Setting range temperature Setting range humidity
01231.0-00 01231.0-01 100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC) 0 to +60°C 50 to 90% RH
01231.9-00 01231.9-01 100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC) +32 to +140°F 50 to 90% RH
01231.1-00 01231.1-01 24-48VDC (min. 20VDC, max. 60VDC) 0 to +60°C 50 to 90% RH
Connection diagram
Heater
TECHNICAL DATASHEET
20.03.2013 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se