DRA4 CMX Series
• 54mm 4 Channel DIN Rail Mount SSR Assembly
• DC Ratings up to 200 VDC and 8 Amps
• 3-10 and 20-28VDC control
• Cage style screw terminals for easy connection
• Fits standard 35mm DIN rail
• Includes LED Status indicator
PRODUCT SELECTION
Description 3 A 8 A (3)
3-10 VDC Control DRA4-CMX200D3 DRA4-CMX100D10
20-28 VDC Control DRA4-CMXE200D3 DRA4-CMXE100D10
OUTPUT SPECIFICATIONS (1)
Description 3 A 8 A (3)
Operating Voltage [VDC] 1-200 1-100
Maximum Off-State Leakage Current @ Rated Voltage [µAdc] 100 100
Maximum Load Current [A] (2) (3) 3 8
Minimum Load Current [A] 0 0
Maximum On-State Resistence [Ohm] 0.2 0.01
Maximum Surge Current (10msec) [Apk] 30 100
Maximum On-State Voltage Drop @ Rated Current [VDC] 0.6 0.1
INPUT SPECIFICATIONS (1)
Description DRA4-CMX DRA4-CMXE
Control Voltage Range 3.0-10.0 VDC 20.0-2 8.0 VDC
Must Turn On Voltage 3.0 VDC 20.0 VDC
Must Turn Off Voltage 1 .0 VDC 1 .0 VDC
Typycal Input Current 15 mAdc @ 5Vdc 12 mAdc @ 20 Vdc
Nominal Input Impedance 300 Ohm 780 Ohm
Maximum Turn-On Time [msec] 1 1
Maximum Turn-Off Time [µsec] 300 300
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength (4) 2500 Vrms
Minimum Insulation Resistance (@ 500 VDC)(4) 109 Ohms
Maximum Capacitance, Input/Output 15 pF
Ambient Operating Temperature Range -30 to 80°C
Ambient Storage Temperature Range -30 to 125°C
Weight (typical) 0.23 oz. (104.6g)
Encapsulation Thermally Conductive Epoxy
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) See derating chart on page 3.
3) Steady state load Current exceeding 8 amps will damage socket.
4).Dielectric and insulation resistance is measured between input and output.