http://www.tracopower.com Page 2 of 5
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Industrial Power Supplies
TCL Series 24–120 Watt
Input Specifications
Input voltage range 85...264 VAC / 85...375 VDC
output derating at operation between 85...93VAC/85...130VDC: 15% for TCL 060 & TCL 120 models
20% for TCL 024-112 & TCL 024-124
30% for TCL 024-105
Input frequency 47 – 63 Hz
Harmonic limits EN610000-3-2 Class A
Input current at full load (typ.) 115 VAC 230 VAC
TCL 24 models: 0.35 A 0.2 A
TCL 60 models: 1.2 A 0.6 A
TCL 120 models: 2.0 A 1.0 A
Recommended circuit breaker (characteristic C or slow blow fuse) 5.0 A
Output Specifications
Output voltage adj. range 5.1 VDC model: 5.0 – 5.25 VDC
(pot.meter on frontpanel) 12 VDC models: 12 – 15 VDC (12 - 16 VDC for TCL 024-112)
24 VDC models: 24 – 28 VDC
48 VDC models: 48 – 56 VDC
Output regulation (10 to 90% load variation) 2.5% (1% for TCL 60-112)
Ripple and Noise (20MHz Bandwidth) < 50 mV pk-pk
Electronic short circuit protection current limitation at 120 % typ
(constant current, automatic recovery
TCL 24 models: foldback, automatic recovery)
Parallel operation output current characteristic suitable for
parallel operation of max. 5 units
Overvoltage protection, triggerpoint 5.1 VDC model: < 6.5 VDC
12 / 24 VDC models: < 40 VDC
48 VDC models: < 60 VDC
Hold-up time 115 VAC 230 VAC
min. 15 ms min. 125 ms
Power good signal (TCL 60 & TCL 120 only) trigger output signal
point (reference to – Vout)
12 VDC models: >11V 11.0 V ±1.0V / 60 mA max.
24 VDC models: >22V 22.0 V ±2.0V / 30 mA max.
48 VDC models: >44V 44.0 V ±4.0V / 15 mA max.
General Specifications
Temperature ranges – Operating – 10 °C…+70 °C max.
– Storage (non operating) – 25 °C…+85 °C
Temperature derating – at 187...264 VAC or 265...375 VDC operation 1.7% /K above 50°C
– at 93...132 VAC or 130...187 VDC operation 1.1% /K above 40°C
– at 85...130 VDC operation 1.3% /K above 30°C
Humidity (non condensing) 95 % rel. H max.
Temperature coefficient 0.02 % /K
Switching frequency 55 – 180 kHz depending on load
(frequency modulation)
Efficiency 88% typ.
Isolation according to IEC/EN 60950, UL 60950,
UL 508, EN 50178, EN 60204, EN 61558-2-8
Reliability, calculated MTBF @ 25°C TCL 24 models: >2.68 Mio h
(according to IEC-1709) TCL 60 models: >2.94 Mio h
TCL 120 models: >1.62 Mio h