Specifications
Inputs:
Sensor Types:
Pt100, 0.00385 alpha & 0.00392 alpha
Cu10
Sensor Connection: 2-wire, 3-wire or 4-wire RTD
Ranges:
Pt100 RTDs: Range
Number
°C°F alpha
-200 to 600 -328 to 1112 0.00385 1
-200 to 260 -328 to 500 0.00385 2
-200 to -100 -328 to -148 0.00385 3
-50 to 100 -58 to 212 0.00385 4
-18 to 300 0 to 572 0.00385 5
-200 to 600 -328 to 1112 0.00392 6
-200 to 260 -328 to 500 0.00392 7
-200 to -100 -328 to -148 0.00392 8
-50 to 100 -58 to 122 0.00392 9
-18 to 300 0 to 572 0.00392 10
Cu10 RTDs: Range
°C°F Number
-200 to 260 -328 to 500 11
-200 to 100 -328 to 212 12
-200 to -100 -328 to -148 13
-50 to 100 -58 to 212 14
-18 to 260 0 to 500 15
RTD Excitation:
Pt100: 0.45mA, max
Cu10: 5.0mA, max
Lead Wire Resistance: 40% of the base sensor resistance maximum
or 100 ohms (whichever is less)
Lead Wire Effect: Changing from 0 ohm lead resistance (each lead) to
maximum allowed lead resistance: Error <1% of largest span PT and Cu
ranges; -200 to 600°C for Pt and –200 to 260°C for Cu.
Pushbutton Adjustment (Inputs >10mV):
Effective zero offset: >95%
Effective span turn down: >95%
Local Range Selection: By DIP switch
Output:
Voltage: 0 to 10V
Source Impedance: <10 ohms
Drive: 10mA
Current: 0 to 20mA
Source Impedance: >100k ohms
Compliance: 20V
Output Accuracy: 0.05% of Full Scale
Response Time: 100mSec (10 to 90%)
Stability: ±100ppm of full scale/°C (±0.01%/°C)
Common Mode Rejection: 120dB @ DC, >90dB @ 60Hz, or better
Isolation: >1800VDC or peak AC between input, output & power.
ESD Susceptibility: Capable of meeting IEC 801-2 level 3 (8kV)
Humidity (non-condensing):
Operating:15 to 95% RH @45°C
Soak: 90% RH for 24hrs @60°C
Temperature:
Operating: 0 to 60°C
Storage:-25 to +85°C
Power: 9 to 30VDC; 1.0W typical, 2.0W max
Host Module Interface: IR link
Size: DIN rail case – refer to Dimensions drawing
Agency Approvals (EMC & Safety):
UL recognized per standard UL508
(File No.E99775)
CE Conformance per EMC directive 89/336/EEC and Low Voltage
73/23/EEC (Input < 75VDC, only).
RoHS Compliant
Note that detailed installation instructions are available on our website.
Ordering Information
Specify:
1. Model:
WV418-2000
2. Optional Custom Factory Calibration (specify C620, see required
settings under "Calibration, page 2).
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35 (model MD03)
DIN rail. In addition, the following accessories are available:
WVC16 Communications Interface
MD03 TS35 x 7.5 DIN Rail (2 meters)
WV905 24VDC Power Supply (0.5 Amp)
H910 24VDC Power Supply (1 Amp)
H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C650 Utility software for WVC16
Dimensions
Dimensions are in millimeters (inches)
Eurotherm, Inc
741-F Miller Drive
Leesburg, VA 20175-8993
703-443-0000
info@eurotherm.com or www.eurotherm.com/actionio
Factory Assistance
For additional information on calibration, operation and installation
contact our Technical Services Group:
703-669-1318
721-0867-00-D 02/09 Copyright© Eurotherm, Inc 2009