FW SERIES
PHASE CONTROL RELAY
UL cUL listed CSA recognized
•Monitors and Protects Against
Phase Loss of One or More Phases
Phase Reversal
Undervoltage
•Rugged Construction for Over Voltage
and Transient Protection
CONFORMITY:
Immunity to interference and noise (EMC)
IEC 1000.4.5 Surge immunity: Level 3
IEC 1000.4.2 Electrostatic discharges: Level 3
IEC 255.5 Damped oscillated waves: Level 3
IEC 1000.4.3 Radiated disturbance Level 3
IEC 1000.4.4 Fast transient Level 3
IEC 1000.4.6 Conducted RF: Level 3 (ENV 50141)
RF Emissions (EMC)
CENELAC EN 55022; Class A
L3L1
12 11
L1
L2
L3
L2
14 22 21 24
(23) (77)
(5)
(57)
.20”3.02”
.20”
2.24”
(95)
3.75”
(100)3.94”
(.3.5).14”
(45)
(78.5)
(99.3)
(4.2).17”
1.77”
3.07”
3.91”
(89.7)3.53”
WIRING:
DIMENSIONS: Inches (mm)
SPECIFICATIONS:
Model No. 84873010 84873011 84873015 84873016
Input Power 3 x 230VAC 3 x 380VAC 3 x 480VAC 3 x 600VAC
Threshold Adjustment 184 - 264VAC 310 - 337VAC 384 - 552VAC 460 - 661VAC
Maximum Voltage 264VAC 337VAC 552VAC 661VAC
Minimum Voltage 184VAC 304VAC 384VAC 460VAC
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
GENERAL FEATURES:
The unit has two front dial settings. The upper dial is used for the
three phase nominal voltage settings that exists in the application.
The lower dial setting is for an adjustable time delay to prevent
nuisance tripping of the unit. The FW has a space saving 45mm
wide DIN-rail mount/surface mount enclosure and LED power-on
and relay status indication.
OPERATING PRINCIPLE:
In a 3-phase network, the FW simultaneously monitors phase
sequencing, loss of phase with a maximum regeneration rate
of 70% of the displayed by a potentiometer on the front face,
and the voltage drop on the 3 phases of less than 15% of the
preset value. When the 3 phases suceed one another, the
output relay is activated and indicated via a yellow LED. The
output relay de-energizes (LED off) after a time delay T,
adjustable between 0.2 and 10 seconds on the front face,
if one of the following faults is present :
- reversed direction of phase rotation
- absence of one or more phases
- voltage drop
ORDERING INFORMATION: Voltage PartNumber
3 x 230 VAC 84873010
3 x 380 VAC 84873011
3 x 480 VAC 84873015
3 x 600 VAC 84873016
Max. Power Consumption . . . . . . . . . . . . . . 6 VA [Powered from L1 & L2]
Immunity from micro power cuts . . . . . . . . 10 ms
Delay on pick-up . . . . . . . . . . . . . . . . . . . . . 500 ms
Isolation coordination . . . . . . . . . . . . . . . . . Category III
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Degree of pollution 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . acc. to IEC 664-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VDE 0110 : 4 KV/2
Measurement input resistance . . . . . . . . . . . 1 kx input power
Regeneration rate . . . . . . . . . . . . . . . . . . . . . max 70% of present threshold
Undervoltage detection
(symmetrical drop)
. . ~15% of front dial settings
Threshold display accuracy . . . . . . . . . . . . . ±10%
Output relay . . . . . . . . . . . . . . . . . . . . . . . . . DPDT (Ag CdO)
Breaking capacity . . . . . . . . . . . . . . . . . . . . 2000 VA/AC 80 W/DC
Maximum breaking current . . . . . . . . . . . . . 8 A
Minimum breaking current . . . . . . . . . . . . . . 100 mA
Maximum breaking voltage . . . . . . . . . . . . . 250 V AC resistive
Electrical Life . . . . . . . . . . . . . . . . . . . . . . . . AC12: 2000 VA -
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 operations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AC15: cos = 0.3 -
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6000 operations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC13: L/R = 300 ms -
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6000 operations
Mechanical Life . . . . . . . . . . . . . . . . . . . . . . 5 x 105operations
Maximum rate (at full load) . . . . . . . . . . . 360 operations / hr
Time delay in the event of a fault . . . . . . 0.2 to 10 s (0 • +50 %)
Display Voltage presense . . . . . . . . . green LED
Display Relay . . . . . . . . . . . . . . . . . . . yellow LED
Casing . . . . . . . . . . . . . . . . . . . . . . . . . . . Self-extinguishing
Terminals Without ferrule . . . . . . . . . . 2 x 2.5mm2
Terminals With ferrule . . . . . . . . . . . . . 2 x 1.5mm2
Terminals Tightening . . . . . . . . . . . . . . 0.6 mN max.
Temperature Use . . . . . . . . . . . . . . . . . -20°C to +60°C
Limits Stored . . . . . . . . . . . . . . . -30°C to +70°C
Relative humidity . . . . . . . . . . . . . . . . . . 93% without condensation
Vibration Amplitude . . . . . . . . . . . . . . . 0.35mm
Vibration Frequency . . . . . . . . . . . . . . 10 - 55 Hz
Isolation resistance . . . . . . . . . . . . . . . . >100 mat 500 V
Dielectric strength . . . . . . . . . . . . . . . . . 3 kV at 1 mA for
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 minute / 50 Hz
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 g
[Only for loss of L3]