160
Color-Keyed
®
Connectors Code Copper 600 Volt Applications
Hex head screws will be furnished if specified.
To order, add prefix H to catalogue number. On
all except 14-10 and 10-8 code sizes.
Pigtail Connectors
Cable Dimensions (in.)
Cat. No. Size Fig. A J
31305 10 to 8 A 121732
31307 8 to 6 B 342732
31309 6 to 4 B 781 132
31311 4 to 2 B 1116 114
31313 1 to 2/0 B 1316 112
31315 2/0 to 4/0 B 1516 12532
For torque requirements see page 162.
Stud Connectors
Type MS
Cable Dimensions (in.) Stud
Cat. No. Size G A B D E F Size
31007-T 4 to 1 38—16 1382532 78583438—16
31009-T 1 to 2/0 38—16 158781343438—16
31011-T 2/0 to 4/0 12—13 1581116 1316 78112—13
31013-T 4/0 to 300 12—13 1781316 1381116 112—13
31015-T 300 to 500 12—13 2532 1516 112114112—13
Sizes listed are standard, but studs can be furnished to the length and diameter required
for specific applications.
For torque requirements see page 162.
Each connector will accommodate a wide
range of conductor sizes. Installation is simple
and the convenient pigtail is easy to tape.
Hex head screws will be furnished if specified.
To order, add prefix H to catalogue number. On
all except 14-10 and 10-8 code sizes.
Fig. A Fig. B
161
Color-Keyed
®
INSTALLATION DIES AND TOOLS
Connectors Code Copper 600 Volt Applications
Standard tapping is shown in diagrams. Other
tapping can be furnished for specific require-
ments.
Hex head screws will be furnished if specified.
To order, add prefix H to catalogue number. On
all except 14-8 and 8-4 code sizes.
Stud Connectors (continued)
Female—Type FL
Cable Dimensions (in.) Stud
Cat. No. Size Fig. G A B Size
3126114 to 8 A 38—16 1332 5838—16
312628 to 4 A 38—16 1116 5838—16
31263 4 to 1 B 38—16 11532 3438—16
31265 4 to 1 B 12—13 11532 3412—13
31267 2/0 to 4/0 B 12—13 2316 1316 12—13
With Filister Head Screw
Fig. A Fig. B
162
Color-Keyed
®
Connectors for Code Copper Cables
Lug-It
®
connectors are designed to grip the
cable firmly between the strong body and the
serrated copper tongue. Double laps at the top
give greater thread strength and lock the screw
when it is tight. The copper tongue makes a
low resistance terminal.
Lug-It®Lugs—One Hole, Offset Tongue
Cable Dimensions (in.)
Cat. No. Size GABCDF
35301 14 to 6 #10 1316 1238.064 732
35401 8 to 2 141716 5812.081 14
*355014 to 2/0 1411316 1316 34.101 38
*356011/0 to 4/0 3821732 1332 1 .128 12
Add suffix G to above Cat. No’s for lug connector with green screw for grounding
identification.
* Aluminum body
Hex head bolt
For torque requirements, see page 162.
Cone Screw Lugs
Wire Dimensions (in.)
Cat. No. Range GABCDEF
71010-TB 4-2/0 3812132 2732 2332 316 2532 38
71014 2-4/0 381 782932 1516 316 3132 38
71015 1-250 382 132 2932 1732 138
71020-TB 2/0-500 122 341 1411132 932 11532 916
Add suffix G to lug Cat. No. 71010-TB, and 71014 for lug with green screw for
grounding identification.
For torque requirements, see page 162.
The conically shaped screw compresses the
copper conductor so that each strand is forced
to carry its own share of the load. Equal pressure
is exerted on each conductor strand and the
cone screw assures high pull-out and low
resistance.
G Bolt Size
G Bolt Size
163
Color-Keyed
®
INSTALLATION DIES AND TOOLS
Connectors for Code Copper Cables
Hinjon Junior taps are the most economical,
easiest to install, approved connector for large
to small branch taps. Jaws with all-around-
grip automatically adjust to size of main and
branch. Fast, simple installation is accom-
plished with screw driver or pliers and fitting is
easily taped.
Hinjon®Junior Tee-Parallel Taps
Cat. Cable Size Dimensions (in.)
No. Main Branch A B C
35107 8 to 4 14 to 8 1116 7858
35109 4 to 1/0 14 to 4 11411116
35111 1/0 to 4/0 14 to 4 1121382732
35112 8 to 1 1581916 2732
35115 300 to 500 14 to 4 17811316 1
T&B Recommended Tightening Torque
Size of Wrench Screwdriver
Conductor Torque Torque
Ranges in.- lb in.- lb
14 to 8 20
14 to 4 35
4 to 2/0 150
2 to 4/0 200
1 to 250 250
2/0 to 500 300