rrupting device in response to a simulated or
te ground-fault current, use CT-primary
circuit using a PGT-0400 Ground-Fault-Relay
9.9 A for a duration
R-5701 setting. Inject
current-transformer window for at least 2.5 seconds.
POWR-GARD®
Ground-Fault Protection
PGR-5701 SERIES
Ground-Fault Relay
PGR-5701 MANUAL
GROUND-FAULT RELAY
JUNE 8, 2009
REVISION 6
TEST
4
3
2
1
4
3
2
1
6
7
8
9
6
7
8
9
5
0
.50
.05
.40
.30
.20
.10
1.0
1.5
2.0
2.5
5
0
PWR
RESET
POWR-GARD
% CT PRIMARY
GROUND-FAULT RELAY
TIME (s)
INHB TRIP
PGR-5701
SERIES
Copyright © 2009 by Littelfuse, Inc.
All rights reserved.
Publication: PGR-5701-SM
Document: P95-C701-000SM
Printed in Canada.
Rev. 6 Page i
PGR-5701 Ground-Fault Relay
TABLE OF CONTENTS
Page
Table of Contents........................................................................................................i
List of Figures ..............................................................................................................i
List of Tables ...............................................................................................................i
1. INTRODUCTION............................................................................................1
1.1 General ...........................................................................................................1
1.2 Current-Transformer Selection.......................................................................1
2. OPERATION ..................................................................................................2
2.1 Configuration-Switch Settings ........................................................................2
2.1.1 Relay Operating Mode ........................................................................2
2.1.2 Trip Inhibit............................................................................................2
2.1.3 CT Verification.....................................................................................2
2.1.4 Filter Selection.....................................................................................2
2.1.5 Reset Mode.........................................................................................2
2.2 Front-Panel Controls ......................................................................................2
2.2.1 Ground-Fault Trip Level ......................................................................2
2.2.2 Ground-Fault Trip Time.......................................................................4
2.2.3 Reset ...................................................................................................4
2.2.4 Test......................................................................................................4
2.3 Front-Panel Indication.....................................................................................4
2.3.1 Power...................................................................................................4
2.3.2 Trip.......................................................................................................4
2.3.3 Trip Inhibit............................................................................................4
2.4 Analog Output.................................................................................................5
2.5 Self Diagnostics ..............................................................................................5
3. INSTALLATION.............................................................................................5
4. TECHNICAL SPECIFICATIONS................................................................ 10
5. ORDERING INFORMATION...................................................................... 13
6. GROUND-FAULT PERFORMANCE TEST............................................... 13
LIST OF FIGURES
Page
1. PGR-5701 Outline and Mounting Details.......................................................3
2. Typical Connection Diagram ..........................................................................5
3. PGC-3026 Earth-Fault Current Transformer .................................................6
4. PGC-3082 Earth-Fault Current Transformer .................................................7
5. PGC-3140 Earth-Fault Current Transformer .................................................8
6. PGK-0055 and PGK-0060 Panel-Mount Adapters........................................9
7. Ground-Fault-Test Circuit............................................................................ 14
LIST OF TABLES
Page
1. Trip-Features Comparison .............................................................................6
2. Ground-Fault-Test Record .......................................................................... 14
Rev. 6 Page 1
PGR-5701 Ground-Fault Relay
DISCLAIMER
Specifications are subject to change without notice. Littelfuse, Inc. is not liable for
contingent or consequential damages, or for expenses sustained as a result of
incorrect application, incorrect adjustment, or a malfunction.
1. INTRODUCTION
1.1 General
The PGR-5701 is a microprocessor-based ground-fault relay for resistance-
grounded and solidly grounded systems. It is uniquely suited for use on systems with
significant harmonic content. Its output relay can operate in the fail-safe or non-fail-
safe mode for undervoltage or shunt-trip applications. The PGR-5701 has one output
relay with isolated normally open and normally closed contacts for use in independent
control circuits. Additional features include LED trip, power, and inhibit indication,
autoreset or latching trips with front-panel and remote reset, trip memory, test switch,
self diagnostics, 0- to 5-V analog output, inputs for standard and sensitive ground-fault
current transformers, CT verification for sensitive current transformers, digital selector
switches, switch-selectable algorithms for fixed-frequency or variable-frequency
applications, and an inhibit that can be enabled to prevent the output relay from
operating during a high-current ground fault.
Ground-fault current is sensed by a core-balance zero-sequence current transformer
(CT). The trip level of the ground-fault circuit is switch selectable in 1% increments
from 1 to 99% of the CT-primary rating.
1.2 Current-Transformer Selection
A PGR-5701 has inputs for 1-, 5-A, and sensitive 50-mA-secondary CTs. Choose a
CT that provides the required ground-fault-trip range.
For ground-fault detection, the ground-fault trip level must be substantially below the
prospective ground-fault current. In a solidly grounded system, prospective ground-
fault current is similar to phase-fault current. In a resistance-grounded system,
prospective ground-fault current is defined by the neutral-grounding-resistor let-
through-current rating.
In a solidly grounded system, protection against arcing ground faults requires a
ground-fault CT that will detect low-level fault current but not saturate up to the
operating value of the system overcurrent protection. In general, immunity to
saturation is proportional to CT mass.
To eliminate nuisance tripping, surge current must not saturate the CT.
For low-level ground-fault protection use a PGC-3026 PGC-3082, or PGC-3140,
sensitive earth-fault CT with a 5-A-primary rating. However, protection at this level
might not be possible because of high surge current or prospective ground-fault
current.
Rev. 6 Page 2
PGR-5701 Ground-Fault Relay
2. OPERATION
2.1 Configuration-Switch Settings
See Fig. 1.
2.1.1 Relay Operating Mode
Switch 1 is used to set the operating mode of the output relay. In the fail-safe mode,
the output relay energizes when the ground-fault circuit is not tripped. In the fail-safe
mode, non-volatile memory retains the trip status of the PGR-5701. If tripped, and the
supply voltage is cycled, the PGR-5701 will remain tripped, with the trip relay de-
energized and the TRIP LED on, until reset.
In the non-fail-safe mode, the output relay energizes when a ground-fault trip occurs.
In the non-fail-safe mode, trip status is not retained in non-volatile memory.
2.1.2 Trip Inhibit
Switch 2 is used to select Class I or Class II operation. In the OFF position, high-
current trip inhibit is off for Class I operation. In the ON position, high-current inhibit is
on for Class II operation. If high-current trip inhibit is on and ground-fault current
escalates above eleven times the CT-primary rating before the ground-fault circuit trips,
the output relay will not operate until ground-fault current falls below eight times the CT-
primary rating. This feature allows overcurrent protection to operate in applications
where the ground-fault current can be larger than the interrupting capacity of the device
tripped by the PGR-5701.
2.1.3 CT Verification
Switch 3 is used to enable CT verification with a PGC-3000-series CT. In the ON
position, a trip will occur if the CT is disconnected. Switch 3 must be in the OFF
position when a PGC-3000-series CT is not used.
2.1.4 Filter Selection
Switch 4 is used to select the filtering algorithm for a fixed-frequency (50/60 Hz) or
variable-frequency application. The FIXED FREQUENCY setting uses a DFT filter that
allows lower trip levels to be used by rejecting harmonics that can cause nuisance
tripping.
The VARIABLE FREQUENCY setting uses a peak-detection algorithm with a wider
band width for fault detection in variable-frequency drive applications.
2.1.5 Reset Mode
Switch 5 is used to select autoreset or latching trips. See Section 2.2.3.
2.2 Front-Panel Controls
2.2.1 Ground-Fault Trip Level
The % CT PRIMARY selector switches are used to set the ground-fault trip level as
a percentage of the CT-primary rating.
In tripping systems, a ground-fault trip level of 10 to 20% of the prospective ground-
fault current is often used. In alarm-only systems, a value of 50% of the prospective
Rev. 6 Page 3
PGR-5701 Ground-Fault Relay
NOTES:
8.7 37.5
55.0
(0.34) (1.48)
(2.17)
61.2
75.0
6.9
(2.41)
(2.95)
(0.27)
MOUNTING DETAIL
NOTE 2
110.0
6.3
118.0 (NOTE 3)
(4.33)
(0.25)
(4.65)
SIDE
55.0
(2.17)
75.0
(2.95)
FRONT
BOTTOM
9 1 0 1 1 1 2 1 3 1 4 1 5
L 2
NL 1
1 6
TOP
FIXED
FREQUENCY
LATCHING
VARIABLE
FREQUENCY
AUTORESET
OFF ON
OFF
FAIL-SAFE
ON
NON-FAIL-SAFE
3
4
5
2
1
CONFIGURATION
SWITCHES
1.
2.
DIMENSIONS IN MILLIMETRES (INCHES).
MOUNTING SCREWS: M4 OR 8-32.
3. OVERALL DIMENSION WHEN MOUNTED ON
DIN EN50022 35 mm x 7.5 mm TOP-HAT RAIL.
4. ADJUSTMENT KNOBS ARE REMOVABLE.
5. CONFIGURATION SWITCHES SHOWN
IN DEFAULT POSITION.
1 2 3 4 5 6 7 8
S 1 S 2 R S
EFCT
A N A L O G
O U T P U T
R E S E T
1 A / 5 A C T
1A 5A C
RESET MODE
FILTER SELECTION
CT VERIFICATION
TRIP INHIBIT
RELAY OPERATING MODE
NOTE 5
TEST
4
3
2
1
4
3
2
1
6
7
8
9
6
7
8
9
5
0
.50
.05
.40
.30
.20
.10
1.0
1.5
2.0
2.5
5
0
PWR
RESET
POWR-GARD
% CT PRIMARY
GROUND-FAULT RELAY
TIME (s)
INHB TRIP
PGR-5701
SERIES
FIGURE 1. PGR-5701 Outline and Mounting Details.
Rev. 6 Page 4
PGR-5701 Ground-Fault Relay
ground-fault current is often used. To avoid sympathetic tripping, the trip level must be
above the charging current of the protected feeder.
A 0% selection provides protection at 1%.
2.2.2 Ground-Fault Trip Time
The PGR-5701 has a definite-time trip characteristic. The TIME (s) selector switch
is used to set the ground-fault trip delay time for coordination with upstream and
downstream ground-fault devices. Coordination requires the same trip level for all
ground-fault devices in a system and the trip time to progressively increase upstream.
The amount of equipment removed from the system will be a minimum if the first
ground-fault device to operate is the one immediately upstream from the fault.
2.2.3 Reset
If the Reset Mode switch is in the LATCHING position, a trip remains latched until
the RESET switch is pressed or the remote-reset terminals are momentarily
connected. In the non-fail-safe mode, cycling the supply voltage will also reset the
PGR-5701.
If the Reset Mode switch is in the AUTORESET position, a trip will reset when the
fault is removed.
The reset circuit responds only to a momentary closure so that a jammed or shorted
switch will not prevent a trip. The front-panel RESET switch is inoperative when the
remote-reset terminals (6 and 7) are connected.
2.2.4 Test
The TEST switch is used to test the ground-fault circuit, the indication, and the
output relay. When the TEST switch is pressed for one second, a test signal is applied
to the ground-fault-detection circuit, the circuit will trip, the TRIP LED will light, and the
output relay will operate. If high-current inhibit has been selected, the INHB LED will
light.
2.3 Front-Panel Indication
2.3.1 Power
The green LED labeled PWR indicates the presence of supply voltage.
2.3.2 Trip
The red LED labeled TRIP indicates a trip. A solid red LED indicates a ground-fault
trip. A regularly flashing LED indicates a trip initiated by a CT fault. Two fast flashes
indicate a diagnostic trip. See Section 2.5.
2.3.3 Trip Inhibit
The yellow LED labeled INHB indicates that output-relay operation was inhibited
during a high-current ground fault. See Section 2.1.2. When a ground-fault trip occurs
during a high-current ground fault, both the TRIP and INHB LED’s will be ON. Inhibit
indication is reset when the ground-fault trip is reset. Inhibit operation and indication
will not respond if the Trip-Inhibit switch is in the OFF position.
Rev. 6 Page 5
PGR-5701 Ground-Fault Relay
2.4 Analog Output
The non-isolated, 0- to 5-V analog output indicates ground-fault current sensed by
the ground-fault CT. The output is 5 V when ground-fault current is 100% of the CT-
primary rating.
2.5 Self Diagnostics
A diagnostic trip is indicated by two flashes of the TRIP LED. It can be caused by a
diagnostic problem detected by the watchdog timer or from an incorrect reading from
non-volatile memory. Press RESET or cycle supply voltage. If the problem persists,
contact 1-800-TEC-FUSE (1-800-832-3873).
3. INSTALLATION
A PGR-5701 can be surface or DIN-rail mounted. See Fig. 1. Panel mounting
requires a PGK-0055 or PGK-0060 Panel-Mount Adapter. See Fig. 6.
Pass the phase conductors through the CT window as shown in Fig. 2 (for 4-wire
and single-phase systems, also pass the neutral conductor through the CT window).
Do not pass ground conductors through the CT window. In applications that require
shields or drain wires to pass through the CT window, return them through the CT
window before connecting them to ground. If a ground-fault CT with a 5-A secondary is
used, connect it to terminals 2 and 3 (terminals 1 and 3 with a 1-A secondary) and
ground terminal 3. If a PGC-3000-series CT is used, connect it to terminals 4 and 5,
connect the shield to terminal 5, and ground terminal 5. Remove the connection to
terminal 9 for dielectric-strength testingall inputs and outputs have ANSI/IEEE
C37.90 surge-protection circuits that conduct above 300 Vac. See Figs. 3, 4, and 5 for
sensitive PGC-3000-series CT dimensional drawings.
XX 5X:
1 A 5 A C
STOP START
1M
1M
PGR-5701
RS
REMOTE RESET
V
LEAKAGE
ANALOG
OUTPUT
S1 S2
O/L
L N
1 2 43 5
13 14
15 16
6
7
89
L1
11 10
L2
N
ISOLATED CONTACTS
1 A 5 A C S1 S2
1 2 3 4 5
PGR-5701
PGC-3000-XX
ALTERNATE CT
CONNECTIONS
XXX:1 OR
Technical Information 11.1
provides additional
information on CT selection.
RESET
NOTE 1
NOTE:
1. USE OPTIONAL PGA-0500 ANALOG PERCENT
CURRENT METER WITH PGA-05CV CURRENT
VOLTAGE CONVERTER TO DISPLAY LEAKAGE
CURRENT AS A PERCENT OF CT RATING.
FIGURE 2. Typical Connection Diagram.
Rev. 6 Page 6
PGR-5701 Ground-Fault Relay
DETAIL A’
MOUNTING FOOT
INSTALLATION
TOOL
NOTES:
1.
2.
3.
DIMENSIONS IN MILLIMETRES (INCHES).
PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED (DETAIL A’)
MOUNTING SCREWS: M4 OR 8-32.
68.0
26.0
52.55.05.0
68.0
34.0
26.525.0
58.0
17.0
26.5
72.0
34.0
7.0
110.0 MAX
52.5
42.6
(2.68)
(1.02)
(2.07)(0.20)(0.20)
(2.68)
(1.34)
(1.04)(0.98)
(2.28)
(0.67)
(1.04)
(2.83)
(1.34)
(0.87)
(0.43)
(2.07)
(1.68)
M5 SCREWS
TOP MOUNTING DETAIL
M4 OR 8-32 TAP
FRONT SIDE
4.0 (0.16) 0
RECESSED FOR
7-mm HEX NUT
3.0 (0.12) DEEP
P
P
S S
2
2
1
1
L R 5 3 4 2 8
USC
R
POWR-GARD Products
TM
R
PGC-3026
EARTH FAULT CURRENT
TRANSFORMER
600 V Class,
Insulation Class A
FIGURE 3. PGC-3026 Earth-Fault Current Transformer.
Rev. 6 Page 7
PGR-5701 Ground-Fault Relay
NOTES:
1.
2.
3.
DIMENSIONS IN MILLIMETRES (INCHES).
MOUNTING SCREWS: M4 OR 8-32.
PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED.
121.0
25.0
110.05.5 5.5
22.0
82.0
69.8
56.0
121.0
80.0
30.0
20.5
30.0
138.0 MAX
126.0
56.0
46.0
(4.76)
(0.98)
(4.33)(0.22) (0.22)
(0.87)
(3.23)
(2.75)
(2.21)
(4.76)
(3.15)
(1.18)
(0.81)
(1.18)
(5.43)
(4.96)
(2.21)
(1.81)
M5 SCREWS
TOP MOUNTING DETAIL
NOTE 2
FRONT SIDE
5.0 (0.20) 0
EFCT-1FC
FLUX
CONDITIONER
(OPTIONAL)
RECESSED FOR
8-mm HEX NUT
1.0 (0.04) DEEP
S
1
S
2
P
1
L R 5 3 4 2 8
USC
R
POWR-GARD Products
TM
R
PGC-3082
EARTH FAULT CURRENT
TRANSFORMER
600 V Class,
Insulation Class A
FIGURE 4. PGC-3082 Earth-Fault Current Transformer.
pping, the trip level must be
trip characteristic. The TIME (s) selector switch
time for coordination with upstream and
Coordination requires the same trip level for all
and the trip time to progressively increase upstream.
ved from the system will be a minimum if the first
remains latched until
remote-reset terminals are momentarily
ling the supply voltage will also reset the
RESET position, a trip will reset when the
a jammed or shorted
-panel RESET switch is inoperative when the
ground-fault circuit, the indication, and the
essed for one second, a test signal is applied
uit, the circuit will trip, the TRIP LED will light, and the
lected, the INHB LED will
The red LED labeled TRIP indicates a trip. A solid red LED indicates a ground-fault
initiated by a CT fault. Two fast flashes
ion was inhibited
fault trip occurs
ault, both the TRIP and INHB LEDs will be ON. Inhibit
is reset. Inhibit operation and indication
Rev. 6 Page 9
PGR-5701 Ground-Fault Relay
99.0
88.0
44.0
(3.90)
(3.46)
(1.73)
FRONT VIEW
99.0
72.0
60.0
2.0 (0.08) RAD
MAXIMUM
ALTERNATE
CONFIGURATIONS
4.5 (0.18) DIA
8.7 (0.34) DIA
4.3 (0.17) RAD
6.0 6.0
44.0
30.0
60.09.5 9.5
79.0
(3.90)
(2.83)
(2.36)
(0.24) (0.24)
(3.11)
(1.73)
(1.18)
(2.36)(0.37) (0.37)
INSTALLATION INSTRUCTIONS:
NOTE:
PANEL CUTOUT DETAIL
WITH COVER REMOVED LATCH MONITOR TO
BRACKET.
INSERT BRACKET THROUGH FRONT OF PANEL
CUTOUT AND SECURE WITH FLAT WASHERS AND
LOCKNUTS PROVIDED.
CONNECT WIRING TO TERMINALS.
ATTACH COVER USING THUMB SCREWS PROVIDED.
1.
2.
3.
4.
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MEETS NEMA 3, IP53.
116.0
75.0
(4.57)
(2.95)
PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)
SIDE VIEW
55 mm (2.2) WIDE
MONITOR
BRACKET
TRANSPARENT COVER
(NOTE 2)
85.0
72.0
60.0
2.0 (0.08) RAD
MAXIMUM
ALTERNATE
CONFIGURATIONS
4.0 (0.16) DIA
8.7 (0.34) DIA
4.3 (0.17) RAD
6.0 6.0
42.5
30.0
60.09.5 9.5
79.0
(3.35)
(2.83)
(2.36)
(0.24) (0.24)
(3.11)
(1.67)
(1.18)
(2.36)(0.37) (0.37)
INSTALLATION INSTRUCTIONS:
NOTE:
PANEL CUTOUT DETAIL
1.
2.
3.
4.
1. DIMENSIONS IN MILLIMETRES (INCHES).
REMOVE BEZEL AND LATCH MONITOR TO
BRACKET.
INSERT BRACKET THROUGH FRONT OF
PANEL CUTOUT AND SECURE WITH FLAT
WASHERS AND LOCKNUTS PROVIDED.
CONNECT WIRING TO TERMINALS.
INSTALL BEZEL USING 6-32 x 0.31 SCREWS
PROVIDED.
110.0
85.0
75.0
85.0
42.5
(4.33)
(3.35)
(2.95)
(3.35)
(1.67)
PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)
SIDE VIEW
FRONT VIEW
55 mm (2.2) WIDE
MONITOR
BRACKET
BEZEL
PGK-0055 Panel-Mount Adapter PGK-0060 Panel-Mount Adapter
M4
M4
6-32
6-32
TEST
4
3
2
1
4
3
2
1
6
7
8
9
6
7
8
9
5
0
.50
.05
.40
.30
.20
.10
1.0
1.5
2.0
2.5
5
0
PWR
RESET
POWR-GARD
% CT PRIMARY
GROUND-FAULT RELAY
TIME (s)
INHB TRIP
PGR-5701
SERIES
TEST
4
3
2
1
4
3
2
1
6
7
8
9
6
7
8
9
5
0
.50
.05
.40
.30
.20
.10
1.0
1.5
2.0
2.5
5
0
PWR
RESET
POWR-GARD
% CT PRIMARY
GROUND-FAULT RELAY
TIME (s)
INHB TRIP
PGR-5701
SERIES
FIGURE 6. PGK-0055 and PGK-0060 Panel-Mount Adapters.
Rev. 6 Page 10
PGR-5701 Ground-Fault Relay
4. TECHNICAL SPECIFICATIONS
Supply:
0U Option ........................... 2.5 VA, 120 to 240 Vac (+20, -55%), 50/60 Hz,
2.0 W, 100 to 240 Vdc (+20, -25%)
0D Option ........................... 2.0 W, 12 to 30 Vdc (+20, -25%)
0T Option............................ 2.0 W, 40 to 55 Vdc (+20, -25%)
Trip-Level Range ....................... 1 to 99% CT-Primary Rating in 1% increments
(50 mA to 4.95 A with PGC-3000-series CT’s)
Trip-Time Settings ..................... 0.05, 0.10, 0.20, 0.30, 0.40, 0.50, 1.0, 1.5, 2.0,
and 2.5 s
Accuracies (1):
Trip Level (2)........................ Largest of 5% of Setting or:
1-A input:
1% setting ............ -10, +15 mA
2 – 99% setting .... 10 mA
5-A and EFCT (4) inputs:
1% setting ............ -35, +60 mA
2 – 99% setting .... 35 mA
Trip Time (3) ........................ 5% of Setting (-25, +20 ms minimum)
Trip Inhibit:
Off ...................................... Class I
On ...................................... Class II
Level .............................. 11 x CT-Primary Rating
Input:
Algorithms .......................... DFT or Peak
DFT 3 dB Frequency
Response....................... 32 to 86 Hz
Peak 3 dB Frequency
Response....................... 20 to 420 Hz
CT ...................................... 1- or 5-A Secondary Rating, or PGC-3000 series
CT Detection .................. Open-Circuit Detection with PGC-3000 series
Thermal Withstand:
Continuous..................... 5 x CT-Secondary Rating
1-Second........................ 80 x CT-Secondary Rating
Burden:
5-A input......................... < 0.01
1-A input......................... < 0.05
EFCT input..................... 2
Rev. 6 Page 11
PGR-5701 Ground-Fault Relay
Analog Output:
Range ............................... 0 to 5 Vdc, 5 V = 100% CT Rating
Output Impedance ............ 220
Reset ....................................... Front-Panel Switch and
Remote N.O. Momentary Contact
Functional Test ........................ Front-Panel Switch
Relay Contacts:
Configuration...................... Isolated N.O. and N.C.
Operating Mode.................. Fail-Safe or Non-Fail-Safe
CSA/UL Contact Rating...... 8 A resistive 250 Vac, 8 A resistive 30 Vdc
Supplemental Contact Ratings:
Make/Carry 0.2 s .......... 20 A
Break:
dc............................... 30 W resistive, 15 W inductive (L/R = 0.04)
ac............................... 2,000 VA resistive, 1,400 VA inductive
(PF = 0.4)
Subject to maximums of 8 A and 250 V (ac or dc).
Operating Mode ....................... Latching or Autoreset
Terminals ................................. Wire-clamping,
24 to 12 AWG (0.2 to 2.5 mm2) conductors
Dimensions:
Height ............................... 75 mm (3.0")
Width................................. 55 mm (2.2")
Depth ................................ 115 mm (4.5")
Shipping Weight....................... 0.45 kg (1 lb.)
Environment:
Operating Temperature..... -40 to 60°C
Storage Temperature........ -55 to 80°C
Humidity............................ 85% Non-Condensing
Surge Withstand ...................... ANSI/IEEE 37.90.1-1989
(Oscillatory and Fast Transient)
EMC Tests:
Verification tested in accordance with EN 50263:2000
Electrostatic Discharge ....... IEC 61000-4-2, EN 61000-4-2,
6 kV Contact Discharge, 8 kV Air Discharge
Rev. 6 Page 12
PGR-5701 Ground-Fault Relay
Radiated RF ...................... IEC 61000-4-3, EN 61000-4-3
10 V/m, 80-1000 MHz, 80% AM (1 kHz)
10 V/m, 900 MHz, 200 Hz Pulse Modulated
Fast Transient ................... IEC 61000-4-4, EN 61000-4-4
2 kV Common Mode, 1 kV Differential Mode
Surge Immunity ................. IEC 61000-4-5, EN 61000-4-5
2.0 kV Common Mode, 1.0 kV Differential Mode
Conducted RF ................... IEC 61000-4-6, EN 61000-4-6
10Vrms, 0.15-80 MHz, 80% AM (1 kHz)
Magnetic Field ................... IEC 61000-4-8, EN 61000-4-8
50 Hz, 30 A/m (continuous)
50 Hz, 300 A/m (1 to 3 seconds)
Voltage Interruption ........... IEC 255-22-11, EN 60255-11
100% for 2, 5, 10, 20, 50, 100 & 200 ms
MHz Burst.......................... IEC.255-22-1, EN 60255-22-1
1 kV Differential Mode, 2.5 kV Common Mode
RFI Compliance...................... FCC Part 15, Subpart B,
Class A – Unintentional Radiators
Certification............................. CSA, Canada and USA
L R 5 3 4 2 8
USC
R
Notes:
(1) Over operating temperature range of –40 to 60°C.
(2) CT accuracy not included.
(3) Trip time at 3 x trip-level setting.
(4) For maximum lead resistance of 1 !.
Rev. 6 Page 13
PGR-5701 Ground-Fault Relay
5. ORDERING INFORMATION
PGR-5701-0
U Universal 120/240-Vac/Vdc Supply
D 12/24-Vdc Supply
T 48-Vdc Supply
PGA-0500 ........Analog Percent Current Meter
PGC-3026.........Sensitive Earth-Fault CT, 5-A-primary rating, 26-mm (1) window
PGC-3082.........Sensitive Earth-Fault CT, 5-A-primary rating, 82-mm (3.2") window
PGC-31FC........Flux Conditioner for PGC-3082, 70-mm (2.7) window
PGC-3140.........Sensitive Earth-Fault CT, with Flux Conditioner,
5-A-primary rating, 139-mm (5.5) window
PGK-0055.........Panel-Mount Adapter, NEMA 1
PGK-0060.........Panel-Mount Adapter, NEMA 3, IP53
PGK-0003.........Adapter Plate, GES/MCGG
PGK-0006.........Adapter Plate, FPL-GFRM
PGT-0400...Ground-Fault Relay Tester
6. GROUND-FAULT PERFORMANCE TEST
To meet the requirements of the National Electrical Code (NEC), as applicable, the
overall ground-fault protection system requires a performance test when first installed.
A written record of the performance test is to be retained by those in charge of the
electrical installation in order to make it available to the authority having jurisdiction. A
test-record form is provided for recording the date and the final results of the
performance tests. The following ground-fault system tests are to be conducted by
qualified personnel:
a) Evaluate the interconnected system in accordance with the overall equipment
manufacturers detailed instructions.
b) Verify proper location of the ground-fault current transformer. Ensure the cables
pass through the ground-fault-current-transformer window. This check can be done
visually with knowledge of the circuit. The connection of the current-transformer
secondary to the PGR-5701 is not polarity sensitive.
c) Verify that the system is correctly grounded and that alternate ground paths do not
exist that bypass the current transformer. High-voltage testers and resistance
bridges can be used to determine the existence of alternate ground paths.
Rev. 6 Page 14
PGR-5701 Ground-Fault Relay
d) Verify proper reaction of the circuit-interrupting device in response to a simulated or
controlled ground-fault current. To simulate ground-fault current, use CT-primary
current injection. Fig. 7 shows a test circuit using a PGT-0400 Ground-Fault-Relay
Test Unit. The PGT-0400 has a programmable output of 0.5 to 9.9 A for a duration
of 0.1 to 9.9 seconds. Set the test current to 120% of the PGR-5701 setting. Inject
the test current through the current-transformer window for at least 2.5 seconds.
Verify that the circuit under test has reacted properly. Correct any problems and re-
test until the proper reaction is verified.
e) Record the date and the results of the test on the attached test-record form.
NOTE: Do not inject test current directly into CT-input terminals 1, 2, 3, 4, and 5.
FIGURE 7. Ground-Fault-Test Circuit using PGT-0400.
TABLE 2. Ground-Fault-Test Record
DATE TEST RESULTS
Retain this record for authority having jurisdiction.
PGT-0400
PGR-5701
RMT1
REMOTE
TEST 9
8
1
5
3
11 12
RMT2
L
L
N
N
L1
L1
OP1 OP2
L2
L2/N
FROM
POWER
SOURCE
LOAD
5 A C
1 A S1
1 2 3 4 5
XXX:5
S2
11
10