Product leaflet
Three phase electricity meters C13
EQ meters in Steel version from ABB
The compact and versatile EQ meter C13 is a three
phase meter with outstanding performance. It can be
used in most of the common applications for reliable
and trustworthy metering of energy usage.
EQ meters C13 is mainly intended for stand-alone
applications.
General features
C13 is a three phase direct connected meter up to 40 A.
The C13 is measuring active energy with accuracy class B
(Cl. 1). The low rated or base currents of this product ensures
high dynamic performance with superior accuracy even at low
currents. Navigation of the meter is easily done via the push-
button below the display. The low power consumption of the
meter, less than 1.5 VA, makes it economical in the long run -
an important feature specially for large meter populations.
Instrumentation
The C13 meter supports reading of instrument values.
A large
number of electrical properties can be read.
Active power - Total and per phase
Voltage - Total and per phase
Current - Total and per phase
Power factor
Output
The C13 meter has one solid state relay output that can be
used for S0 pulses or as alarm output. C13 can generate
pulses proportionally to the measured energy and the pulses
can be used for various applications such as automatic meter
reading systems etc. When used as alarm the quantity and
levels are easily configured on the meter with the push button.
When used as alarm the output can control an external ap-
paratus like a contactor (connected via an external relay) or an
alarm indicator.
Approvals
The C13 meters are type approved according to IEC as well as
type approved and optionally verified according to MID.
MID is the Measure Instruments Directive 2004/22/EC from
European Commission. The type approval is according to stan-
dards that covers all relevant technical aspects of the meter.
These include climate conditions, electromagnetic compatibility
(EMC), electrical requirements, mechanical requirements and
accuracy.
Ordering details
40 A direct connected, 3 DIN
Voltage V Accuracy
Class
Type Order code Weight
1 pc
Steel
Active energy, pulse output
3 x 230/400 V AC Class B(Cl. 1) C13 110 - 100 *)
2CMA100191R1000
0.17
Class 1 C13 110 - 300
2CMA100192R1000
0.17
*) MID approval
levels are easily configured on the meter with the push button.
When used as alarm the output can control an external ap-
paratus like a contactor (connected via an external relay) or an
levels are easily configured on the meter with the push button.
levels are easily configured on the meter with the push button.
Product leaflet 2CMC486007L0201, rev. A, June 2014 Prod ABB AB, LP/XM
C13
Technical data
C13
Voltage/current inputs
Nominal voltage 3x230/400 V AC
Voltage range 3x220 - 240 V AC (-20% - +15%)
Power dissipation voltage circuits 1.5 VA (0.6 W) total
Power dissipation current circuits 0.04 VA (0.04 W) per phase at 230 V AC and Ib
Base current Ib5 A
Reference current Iref 5 A
Transitional current Itr 0.5 A
Maximum current Imax 40 A
Minimum current Imin 0.25 A
Starting current Ist < 20 mA
Terminal wire area 0.5 - 10 mm2
Recommended tightening torque 0.8 Nm
Pulse indicator (LED)
Pulse frequency 1000 imp/kWh
Pulse length 40 ms
General data
Frequency 50 or 60 Hz ± 5%
Accuracy Class B (Cl. 1)
Active energy 1%
Display of energy 6 digit LCD
Environmental
Operating temperature -25°C - +70°C
Storage temperature -25°C - +85°C
Humidity 75% yearly average, 95% on 30 days/year
Resistance to fire and heat Terminal 960 °C, cover 650°C (IEC 60695-2-1)
Resistance to water and dust IP20 on terminal block without protective enclosure and IP51 in protective
enclosure, according to IEC 60529.
Mechanical environment Class M1 in accordance with the Measuring Instrument Directive (MID).
(2004/22/EC).
Electromagnetic environment Class E2 in accordance with the Measuring Instrument Directive (MID),
(2004/22/EC).
Outputs
Current 2 - 100 mA
Voltage 5 - 40 V DC.
Pulse output frequency 100 (imp/kWh)
Pulse length 200 ms
Terminal wire area 0.5 - 6 mm2
Recommended tightening torque 0.8 Nm
EMC compatibility
Impulse voltage test 6 kV 1.2/50μs (IEC 60060-1)
Surge voltage test 4 kV 1.2/50μs (IEC 61000-4-5)
Fast transient burst test 4kV (IEC 61000-4-4)
Immunity to electromagnetic HF-fields
80 MHz - 2 GHz at 10 V/m (IEC 61000-4-3)
Immunity to conducted disturbance 150 kHz - 80 MHz (IEC 61000-4-6)
Immunity to disturbance with harmonics 2 kHz - 150 kHz
Radio frequency emission EN 55022, class B (CISPR22)
Electrostatic discharge 15 kV (IEC 61000-4-2)
Standards
IEC 62052-11, IEC 62053-21 class 1, GB/T 17215.211-2006, GB/T
17215.321-2008 class 1, GB 4208-2008, EN 50470-1, EN 50470-3
category B
Mechanical
Material Glass reinforced polycarbonate
Dimensions
Width 54 mm
Height 122 mm
Depth 65 mm
DIN modules 3
© Copyright 2014 ABB. All rights reserved. Specication subject to
change without notice.
This QR-code is linked to our web site
www.abb.com/lowvoltage.
You will have to download a QR-code reader
app to your phone in order to use it.
ABB AB
Meters
Box 1005
SE-611 29 NYKÖPING, Sweden
Telephone +46 155 29 50 00
www.abb.com
Wiring diagram C13
34 6 7 9
L1
L2
L3
N
110 12
94
89
58
65
54
122
94
89
58
65
54
122
Dimensions