Marshalling Solutions - Interface Modules Passive Interface Unit * CLAMSHELL style connection on module * Reduce Cabinet Space * Field wiring termination from RIGHT side * 16 channels * Feed through connections * For differential analog input signals * 48 points * Honeywell C300 IOTAs 48 pole, differential feed through interface module (Field wiring right) - CC-TAID01/TAID11 Technical data Connection data Process side Type Torque Control side Type Rated data Rated voltage Max. current per channel Operating temperature Storage temperature General Features LED status indicator per channel Disconnection per channel Voltage measuring test points Current measuring test points Fuse via channel Supply voltage LED status Power supply fuse Terminal wire size Insulation stripping length Approvals Standards Dimensions Length x width x height (inches / mm) Screw connection LP2N terminal 4.4 in-lbs (0.5Nm) Plug connection CLAMSHELL SLD 32-Pole and CLAMSHELL SLD 16-Pole 250V 5A 0C to +50C 0C to +50C No No No No No No No AWG 26 ...12 6mm cURus (E141197) 4.2 x 4.4 x 3.7 / 106.7 x 111.8 x 94.0 Note Ordering data Model Qty 48 pole, differential feed through interface module (Field wiring right); Screw connection Part No. 6720000844 Note Accessories Optional Cables Note MS - C32x - C32x - Lxx - xxx (a clamshell 32-pole to clamshell 32-pole) MS - C16x - C16x - Rxx - xxx (a clamshell 16-pole each end) Qty DWG No. 1 1101221 1 1101226