UL-Series - UL489 Miniature Molded Case Circuit Breaker - 2 pole C-Trip - AC
Two Pole
Standard Pack: 6
Weight:
0.3-32A:
1.74kg (3.83lb.)
40-63A:
1.98kg (4.37lb.)
2 Pole
36.5 mm 36.8 mm
35 mm
68.4 mm
51.5 mm
30.5 mm
51.5 mm
37.5 mm
25.5 mm
14.5 mm
45 mm
105.3 mm
52.5 mm
34.5 mm
84
67
Rated Type/ Rated
Current Cat. No. Voltage
0.3A 2C03UL 480Y/277V AC
0.5A 2C05UL 480Y/277V AC
1.0A 2C1UL 480Y/277V AC
1.6A 2C1.6UL 480Y/277V AC
2.0A 2C2UL 480Y/277V AC
3.0A 2C3UL 480Y/277V AC
4.0A 2C4UL 480Y/277V AC
5.0A 2C5UL 480Y/277V AC
6.0A 2C6UL 480Y/277V AC
8.0A 2C8UL 480Y/277V AC
10A 2C10UL 480Y/277V AC
12A 2C12UL 480Y/277V AC
13A 2C13UL 480Y/277V AC
15A 2C15UL 480Y/277V AC
16A 2C16UL 480Y/277V AC
20A 2C20UL 480Y/277V AC
25A 2C25UL 480Y/277V AC
30A 2C30UL 480Y/277V AC
32A 2C32UL 480Y/277V AC
40A 2C40UL 240V AC
50A 2C50UL 240V AC
60A 2C60UL 240V AC
63A 2C63UL 240V AC
LISTED
C US
E329510
C.B.
Current/ Voltage Rating
Calibration Temperature
Ambient Temperature
Storage Temperature
Terminal Torque (min/max)
Electrical Life
Mechanical Life
Vibration Resistance
Resistance to mechanical shocks
0.3 - 63A/ 240V AC, 0.3-32A/ 480Y/277V AC*
40ºC (104ºF)
-25ºC to +55ºC (-13ºF to 131ºF )
-40ºC to +70ºC (-40ºF to 158ºF )
2 Nm (17.7 lb.in.) / 2.5Nm (22.2 lb.in)
6000 switching cycles ON/ OFF
10000 switching cycles ON/ OFF
> 15g according to DIN EN 60069-2-59 during a load
with I1= 1.05 x IN
25g @ 11ms
*One device dual voltage ratings.
10-3
4x10-3
10-2
4x10-2
10-1
0.4
1
4
10
1
4
10
40
60
123456810 20 40 100
Multiple of Rated Current
Seconds Minutes
Tripping time t
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
1.05-1.35xIN
0.3A Through 10A Rated Current
10-3
4x10-3
10-2
4x10-2
10-1
0.4
1
4
10
1
4
10
40
60
123456810 20 40 100
Multiple of Rated Current
Seconds Minutes
Tripping time t
Thermal Overload
Must Trip” < 1 hr = 135% RC
Must Not Trip” > 1 hr = 105% RC
1.05-1.35xIN
12A Through 63A Rated Current
AC
No.
Poles Type 03-32A 33-63A
2-3 AC 10kA @ 120, 240, 10kA @ 120
480Y/277V 240V
Short Circuit Interrupting Capacity
“C” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at surge of 5 times rated current.
2. Trip in under 100ms at 10 times rated current.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Altech:
2C40UL 2C8UL 2C03UL 2C4UL 2C15UL 2C30UL 2C60UL 2C3UL 2C63UL 2C32UL 2C20UL 2C1.6UL
2C10UL 2C6UL 2C50UL 2C5UL 2C1UL 2C2UL 2C25UL 2C16UL 2C05UL 2C12UL 3C60UL 2C13UL N63UL
N32UL