SITOP power supply
SITOP PSU100C
Operating Instructions
SITOP PSU100C 12 V/2 A
6EP1321-5BA00
SITOP PSU100C 12 V/6.5 A
6EP1322-5BA10
SITOP PSU100C 24 V/0.6 A
6EP1331-5BA00
SITOP PSU100C 24 V/1.3 A
6EP1331-5BA10
SITOP PSU100C 24 V/2.5 A
6EP1332-5BA00
SITOP PSU100C 24 V/3.7 A
6EP1332-5BA20
SITOP PSU100C 24 V/4 A
6EP1332-5BA10
06.2013
C98130-A7599-A1-2-7629
Overview
Safety instructions
1
Description, device design,
dimension drawing
2
Mounting/disassembly
3
Mounting position, mounting
clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Ambient conditions
8
Applications
9
Environment
10
Service & Support
11
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
C98130-A7599-A1-2-7629
Ⓟ 06/2013 Technical data subject to change
Copyright © Siemens AG 2013.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 3
Overview
The key benefits of the product include:
Power supply with wide range input for operation on 1-phase AC line supplies or a DC
voltage
Small mounting footprint as a result of the low-profile design
Low energy usage as a result of the high efficiency over the complete load range
Minimum energy losses for no-load operation (<0.75 W)
Can be snapped onto and removed from mounting rails without requiring any tools
Connection using plug-in terminals
Wide operating temperature range from -20 °C up to +70 °C (derating from
+50 °C / 55 °C)
International package of standards
Overview
SITOP PSU100C
4 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
Ordering data
The following device options are available:
SITOP PSU100C primary-clocked power supply
Type Order number
Input 100 - 230 V AC
120 - 230 V DC
Output 12 V DC / 2 A
6EP1321-5BA00
Input 100 - 230 V AC
120 - 230 V DC
Output 12 V DC / 6.5 A
6EP1322-5BA10
Input 100 - 230 V AC
120 - 230 V DC
Output 24 V DC / 0.6 A
6EP1331-5BA00
Input 100 - 230 V AC
120 - 230 V DC
Output 24 V DC / 1.3 A
6EP1331-5BA10
Input 100 - 230 V AC
120 - 230 V DC
Output 24 V DC / 2.5 A
6EP1332-5BA00
Input 100 - 230 V AC
120 - 230 V DC
Output 24 V DC / 3.7 A
6EP1332-5BA20
Input 100 - 230 V AC
120 - 230 V DC
Output 24 V DC / 4 A
6EP1332-5BA10
Accessories
Type Order number
Pluggable spring-loaded terminal 6EP1971-5BA00 (packing unit): 100 terminals, for 50 SITOP
PSU100C power supplies)
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 5
Table of contents
Overview.................................................................................................................................................... 3
1 Safety instructions ..................................................................................................................................... 7
2 Description, device design, dimension drawing ......................................................................................... 9
2.1 Device description..........................................................................................................................9
2.2 Connections and terminal designation.........................................................................................10
2.3 Potentiometer...............................................................................................................................11
2.4 Operating displays and signaling.................................................................................................12
2.5 Block diagram ..............................................................................................................................13
2.6 Dimensions and weight................................................................................................................14
3 Mounting/disassembly ............................................................................................................................. 17
4 Mounting position, mounting clearances.................................................................................................. 19
4.1 Standard mounting position .........................................................................................................19
4.2 Other mounting positions .............................................................................................................22
5 Installation ............................................................................................................................................... 23
5.1 Line-side connection ....................................................................................................................23
5.2 Output-side connection................................................................................................................25
6 Technical data ......................................................................................................................................... 27
6.1 Input .............................................................................................................................................27
6.2 Output ..........................................................................................................................................29
6.3 Efficiency and power loss ............................................................................................................32
6.4 Closed-loop control ......................................................................................................................36
6.5 Protection and monitoring............................................................................................................37
6.6 MTBF ...........................................................................................................................................37
6.7 Mechanical system ......................................................................................................................37
6.8 Accessories..................................................................................................................................39
6.9 Dimension drawing ......................................................................................................................39
7 Safety, approvals, EMC ........................................................................................................................... 41
7.1 Safety ...........................................................................................................................................41
7.2 Test voltage..................................................................................................................................42
7.3 Certifications ................................................................................................................................43
7.4 EMC .............................................................................................................................................44
Table of contents
SITOP PSU100C
6 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
8 Ambient conditions .................................................................................................................................. 45
9 Applications ............................................................................................................................................. 47
9.1 Parallel connection to increase the power rating ........................................................................ 47
9.2 Parallel connection for redundancy............................................................................................. 49
9.3 Series connection for increased voltage ..................................................................................... 51
9.4 Protection against short-time voltage dips.................................................................................. 52
10 Environment ............................................................................................................................................ 53
11 Service & Support.................................................................................................................................... 55
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 7
Safety instructions 1
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
Safety instructions
SITOP PSU100C
8 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 9
Description, device design, dimension drawing 2
2.1 Device description
SITOP PSU100C are primary clocked power supplies for connection to a 1-phase AC line
supply or to DC power systems. An electronically regulated DC voltage that can be set via a
potentiometer is available at the output of the device (not for the devices: 6EP1331-5BA00,
6EP1332-5BA20). The output of the device is isolated, no-load proof and short-circuit proof.
The LED display indicates the operating status.
Line input (pluggable screw terminal)
DC output (pluggable screw terminal)
Indicator light (output voltage OK)
Potentiometer 22.2…26.4 V/10.5…12.9 V
Slider to manually release
Lug for releasing with a screwdriver
Spring-loaded terminal MLFB 6EP1971-5BA00 (accessory)
Natural convection
Figure 2-1 Design (example: 6EP1332-5BA10)
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP PSU100C
10 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
2.2 Connections and terminal designation
The line input terminals can be used to establish the connection to supply voltage. The
output terminals are used to connect to the loads to be supplied (see also Section
Installation (Page 23)).
Connections and terminal designations
line input L, N, PE One screw terminal each for 0.5 to 2.5 mm²
Output + 1 screw terminal for 0.5...2.5 mm²
Output – 2 screw terminals for 0.5...2.5 mm²
$:*
1P
6=6[3=3+
6=6[ 6=6[3=3+
PD[ෘPP
[PP
[PP
[PP
[PP
1P

1P
PP PP
Figure 2-2 Terminal data
Description, device design, dimension drawing
2.3 Potentiometer
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 11
2.3 Potentiometer
The potentiometer on the front of the device is used to adjust the output voltage. The
output voltage is set to the rated value at the factory and can be set within certain limits; for
example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-3 Potentiometer (example 6EP1332-5BA10)
Type Factory setting Setting range
6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
12 V 10.5...12.9 V
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA10 (24 V/4 A)
24 V 22.2...26.4 V
6EP1331-5BA00 (24 V/0.6 A)
6EP1332-5BA20 (24 V/3.7 A)
24 V -
The following devices do not have a potentiometer: 6EP1331-5BA00 and 6EP1332-5BA20.
NOTICE
Thermal overload possible
When adjusting the output voltage to >24 V or >12 V, the output current must be derated by
4%/V.
Note
It is only permissible to activate the potentiometer using an insulated screwdriver.
For notes on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data
(Page 10).
Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP PSU100C
12 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
2.4 Operating displays and signaling
6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
Operating display Green LED for output voltage OK
Figure 2-4 Operating displays and signals (example of 6EP1332-5BA10)
Signaling 6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
LED lights up green Normal operation, output voltage present
LED off Output voltage not present
Description, device design, dimension drawing
2.5 Block diagram
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 13
2.5 Block diagram
7UDQVIRUPHU
3RZHU
WUDQVLVWRUV
3:0FRQWUROOHU
9ROWDJHFRQWUROOHU
8VHU,QWHUIDFH
,QSXWWHUPLQDO$&
,QUXVKFXUUHQW
OLPLWHU
5HFWLILHU
)LOWHU
6HFRQGDU\
UHFWLILHU
2XWSXWILOWHU
2XWSXWWHUPLQDO'&
$'-867
2.
Figure 2-5 Block diagram
Description, device design, dimension drawing
2.6 Dimensions and weight
SITOP PSU100C
14 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
2.6 Dimensions and weight
22,5
80
82
22,7
106,5
100
Figure 2-6 Dimension drawing 6EP1331-5BA00
30
82
22,7
106,5
100
80
Figure 2-7 Dimension drawing 6EP1331-5BA10, 6EP1321-5BA00
Description, device design, dimension drawing
2.6 Dimensions and weight
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 15
80
45
22,7
82
100
106,5
Figure 2-8 Dimension drawing 6EP1332-5BA00






Figure 2-9 Dimension drawing 6EP1332-5BA20, 6EP1332-5BA10, 6EP1322-5BA10
Description, device design, dimension drawing
2.6 Dimensions and weight
SITOP PSU100C
16 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1331-5BA00
(24 V/0.6 A)
6EP1321-5BA00
(12 V/2 A)
6EP1331-5BA10
(24 V/1.3 A)
6EP1332-5BA00
(24 V/2.5 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Dimensions
(W × H × D) in mm
22.5 × 80 × 100 30 × 80 × 100 45 × 80 × 100 52.5 × 80 × 100
Weight Approx. 0.12 kg Approx. 0.17 kg Approx. 0.22 kg Approx. 0.32 kg
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 17
Mounting/disassembly 3
WARNING
Installing the device in a housing or a control cabinet
SITOP PSU100C power supplies are built-in units. They must be installed in a casing or
control cabinet to which only qualified personnel have access.
The devices can be mounted in a control cabinet on standard mounting rails according to
EN 60715 35x7,5/15.
Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If this is too difficult, press slider
or lug at the same time, as described for "Removing".
Removing
To remove, press slider by hand downwards, or pull the lug using a screwdriver
and withdraw the device at the lower edge of the standard mounting rail. Then you can
remove the device from the upper edge of the DIN rail.
Figure 3-1 Mounting (example: 6EP1331-5BA10)
Mounting/disassembly
SITOP PSU100C
18 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
WARNING
Use in hazardous zones
If the device is to be used in a hazardous zone (Ex II 3G Ex nA IIC T4 Gc) it must be
installed in a distribution box with degree of protection IP54 or higher.
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 19
Mounting position, mounting clearances 4
4.1 Standard mounting position
The device is mounted on standard mounting rails according to EN 60715 35x7,5/15. The
device must be mounted vertically in such a way that the input terminals are at the bottom
and the output terminals are at the top to ensure correct cooling.
A clearance of at least 50 mm must always be maintained above and below the device. In
the vicinity of cable ducts it is only permissible to reduce the clearance to a minimum of
25 mm (see Figure 4-1 Mounting (Page 19)).
Lateral clearances do not have to be maintained.
PLQPP
PLQPP
PLQPP
PLQ
PLQPP
PLQ
Figure 4-1 Mounting
Mounting position, mounting clearances
4.1 Standard mounting position
SITOP PSU100C
20 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
2.0
0
1.0
0.5
1.5
020 40 6010 30 50
2.5
Figure 4-2 6EP1321-5BA00: Output current in the standard mounting position
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
4
0
5
2
1
3
020 40 6010 30 50
7
6
6.5
Figure 4-3 6EP1322-5BA10: Output current in the standard mounting position
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
0.4
0
0.5
0.2
0.1
0.3
020 40 6010 30 50
0.7
0.6
Figure 4-4 6EP1331-5BA00: Output current in the standard mounting position
Mounting position, mounting clearances
4.1 Standard mounting position
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 21
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
1.0
0
1.25
1.3
0.5
0.25
0.75
020 40 6010 30 50
1.5
Figure 4-5 6EP1331-5BA10: Output current in the standard mounting position
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
2.0
0
2.5
1.0
0.5
1.5
020 40 6010 30 50
3.0
Figure 4-6 6EP1332-5BA00: Output current in the standard mounting position
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
4
3,7
0
2
1
3
020 40 6010 30 50
5
Figure 4-7 6EP1332-5BA20: Output current in the standard mounting position
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU100C
22 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
IN
OUT
SITOP PSU100C
2XWSXWFXUUHQW>$@
7HPSHUDWXUH>r&@
70
4
0
2
1
3
020 40 6010 30 50
5
Figure 4-8 6EP1332-5BA10: Output current in the standard mounting position
2XWSXWFXUUHQW>@
,QVWDOODWLRQDOWLWXGH>P@
100
60
110
80
70
90
-1000 1000 30000 2000 4000 5000 6000
Figure 4-9 Mounting height derating
For details, see Section Ambient conditions (Page 45)
4.2 Other mounting positions
Not permitted.
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 23
Installation 5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1 Line-side connection
SITOP PSU100C power supplies are designed for connection to 1-phase AC line supplies
(TN or TT system according to VDE 0100 T 300 / IEC 364-3) with a rated voltage of 1-phase
100-230 VAC, 50/60 Hz or to a power supply with 120-230 V DC.
Figure 5-1 Line connection (example 6EP1332-5BA10)
The line supply is connected using terminal L1, N and PE (see Figure 5-1 Line connection
(example 6EP1332-5BA10) (Page 23)), and must be implemented according to IEC 60364
and EN 50178. A protective device (miniature circuit-breaker or circuit-breaker) and a
disconnection unit for the power supply must be provided. A ground-fault circuit interrupter is
not permissible against indirect contact as the only protective measure. This is true for the
complete line supply protected by the ground-fault circuit interrupter.
Installation
5.1 Line-side connection
SITOP PSU100C
24 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
Protection
SITOP PSU100C Recommended line-side protection
6EP1321-5BA00 (12 V/2 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
6EP1322-5BA10
(12 V/6.5 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
6EP1331-5BA00
(24 V/0.6 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
6EP1331-5BA10
(24 V/1.3 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
6EP1332-5BA00
(24 V/2.5 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
6EP1332-5BA20
(24 V/3.7 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
6EP1332-5BA10 (24 V/4 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A and higher or characteristic
C from 10 A
The protective conductor of the line supply must be connected at the PE terminal.
Other country-specific regulations may have to be observed when installing the device.
Note
For operation on a DC power system (DC), the plus pole (+) must be connected to L1 and
the minus pole (–) to N.
Installation
5.2 Output-side connection
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 25
5.2 Output-side connection
The SITOP PSU100C power supplies provide an isolated (= non-grounded) SELV (Safety
Extra Low Voltage) output voltage. The output of the power supplies is no-load, overload and
short-circuit proof. If an overload occurs, the electronic current limiting function limits the
output current to a maximum value (refer to Chapter Technical data (Page 27)).
Figure 5-2 Connecting the output voltage (example 6EP1332-5BA10)
The output voltage is connected via the + and - terminals at the output of the power supply
(see Figure 5-2 Connecting the output voltage (example 6EP1332-5BA10) (Page 25)). Make
sure that the output cables are dimensioned correctly for the maximum output current rms
value and fused accordingly.
Note
If the safety concept of the plant or system specifies that the DC output circuit should be
grounded (PELV), then it is permissible that the output voltage of the SITOP power supply is
grounded. In this case, ideally, the grounding at the output should be directly connected from
terminal "-" of the power supply to a suitable connection point of the protective conductor
system (PE) of the plant or system using a minimum 1.5 mm2 conductor cross-section.
Installation
5.2 Output-side connection
SITOP PSU100C
26 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 27
Technical data 6
Note
For an AC input voltage, the technical data is applicable for rated input voltage, rated load
and +25° C ambient temperature (if nothing else is specified).
6.1 Input
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Input 1-phase AC or DC
Rated voltage
U
e rated / for
AC
100...230 V
Voltage range / for AC 85...264 V
Rated voltage Ue rated / for
DC
120...230 V
Voltage range / for DC 110…300 V
Wide-range input Yes
Overvoltage strength 2.3 x Ue rated, 1.3 ms
Power failure buffering
at Ia rated, min.
20 ms
Power failure buffering at Ue = 230 V
Rated line frequency 50/60 Hz
Line frequency range 47...63 Hz
Input current / at rated value
of input voltage 100 V/rated
value
0.63 A 1.6 A 0.28 A 0.63 A
Input current / at rated value
of input voltage 230 V
0.31 A 0.8 A 0.18 A 0.31 A
Inrush current limiting
(+ 25 °C), max.
33 A 31 A 28 A 34 A
I²t, max. 1.2 A²·s 3 A²·s 0.7 A²·s 1.2 A²·s
Integrated input fuse Internal
Protection in the line feeder
cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C
from 10 A
Technical data
6.1 Input
SITOP PSU100C
28 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Input 1-phase AC or DC
Rated voltage
U
e rated / for
AC
100...230 V
Voltage range / for AC 85...264 V
Rated voltage Ue rated / for
DC
120...230 V
Voltage range / for DC 110…300 V
Wide-range input Yes
Overvoltage strength 2.3 x Ue rated, 1.3 ms
Power failure buffering
at Ia rated, min.
20 ms
Power failure buffering at Ue = 230 V
Rated line frequency 50/60 Hz
Line frequency range 47...63 Hz
Input current / at rated value
of input voltage 100 V/rated
value
1.21 A 1.88 A 2.25 A
Input current / at rated value
of input voltage 230 V
0.67 A 0.95 A 1.15 A
Inrush current limiting
(+ 25 °C), max.
31 A 30 A 34 A
I²t, max. 2.4 A²·s 3 A²·s 3 A²·s
Integrated input fuse Internal
Protection in the line feeder
cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A and higher or
characteristic C from 10 A
,QSXWYROWDJH
2XWSXWYROWDJH
%XIIHUWLPH

Figure 6-1 Power failure buffering
Technical data
6.2 Output
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 29
6.2 Output
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Output Regulated, isolated DC voltage
Rated voltage value Ua rated DC 12 V 12 V 24 V 24 V
Total tolerance, static ± 3 % 3 % 3 % 3 %
Static line regulation, approx. 0.1 % 0.1 % 0.1 % 0.1 %
Static load regulation, approx. 0.2 % 0.2 % 0.2 % 0.2 %
Residual ripple peak-peak, max. 200 mV 200 mV 200 mV 200 mV
Residual ripple peak-peak, typ. 40 mV 80 mV 40 mV 25 mV
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
300 mV 300 mV 300 mV 300 mV
Spikes peak-peak, typ.
(bandwidth, approx. 20 MHz)
50 mV 80 mV 20 mV 20 mV
Setting range 10.5...12.9 V 10.5...12.9 V - 22.2…26.4 V
Product function / output voltage
can be adjusted
Yes Yes No Yes
Setting the output voltage using a
potentiometer
using a
potentiometer
- using a
potentiometer
Operating display LED green for output voltage OK
Response when switching on/off Overshoot of Ua
approx. 5 %
Overshoot of Ua
approx. 1 %
Overshoot of Ua
approx. 5 %
Overshoot of Ua
approx. 5 %
Starting delay, max. 0.6 s 1 s 1 s 0.6 s
Voltage rise, typ. 10 ms 500 ms 25 ms 90 ms
Rated current Ia rated 2 A 6.5 A 0.6 A 1.3 A
Current range
Remark
0…2 A
2 A to +55° C,
1.1 A to +70° C
0…6.5 A
6.5 A to +50° C,
1.95 A to +70° C
0…0.6 A
0.6 A to +55° C,
0.3 A to +70° C
0…1.3 A
1.3 A to +55° C,
0.7 A to +70° C
Output active power / typical 24 W 78 W 14 W 30 W
Short-time overload current / for a
short circuit in operation / typical
4.8 A 14 A 1 A 3.1 A
Can be connected in parallel to
increase the power rating
Remark
Yes
Power-up only with
single rated load
Yes
Power-up only with
single rated load
No Yes
Power-up only with
single rated load
Number of devices that can be
connected in parallel to increase
the power rating, units
2 2 - 2
Output characteristic See Figure 6-3 12 V output characteristic
(Page 31)
See Figure 6-4 24 V output characteristic
(Page 31)
Technical data
6.2 Output
SITOP PSU100C
30 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Output Regulated, isolated DC voltage
Rated voltage value Ua rated DC 24 V
Total tolerance, static ± 3 % 3 % 3 %
Static line regulation, approx. 0.1 % 0.1 % 0.1 %
Static load regulation, approx. 0.2 % 0.2 % 0.2 %
Residual ripple peak-peak, max. 200 mV 200 mV 200 mV
Residual ripple peak-peak, typ. 55 mV 90 mV 80 mV
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
300 mV 300 mV 300 mV
Spikes peak-peak, typ.
(bandwidth, approx. 20 MHz)
50 mV 60 mV 80 mV
Setting range 22.2…26.4 V - 22.2…26.4 V
Product function / output voltage
can be adjusted
Yes No Yes
Setting the output voltage using a potentiometer - using a potentiometer
Operating display LED green for output voltage OK
Response when switching on/off Overshoot of Ua approx. 1
%
Overshoot of Ua approx. 1
%
Starting delay, max. 0.7 s 1.5 s 1.5 ms
Voltage rise, typ. 100 ms 500 ms 400 ms
Rated current Ia rated 2.5 A 3.7 A 4 A
Current range
Remark
0…2.5 A
2.5 A to +50° C,
0.75 A to +70° C
0…3.7 A
3.7 A to +50° C,
1.1 A to +70° C
0…4 A
4 A to +50° C,
1.2 A to +70° C
Output active power / typical 60 W 89 W 96 W
Short-time overload current / for a
short circuit in operation / typical
5.5 A 5 A 13 A
Can be connected in parallel to
increase the power rating
Remark
Yes
Power-up only with single
rated load
No Yes
Power-up only with single
rated load
Number of devices that can be
connected in parallel to increase
the power rating, units
2 - 2
Output characteristic See Figure 6-4 24 V output characteristic (Page 31)
Technical data
6.2 Output
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 31
,QSXWYROWDJH
2XWSXWYROWDJH
6WDUWXSGHOD\ 9ROWDJHULVH
Figure 6-2 Startup delay/voltage rise
2XWSXWYROWDJH>9@
2XWSXWFXUUHQW>$@
02.0 4.0 6.01.0 3.0 5.0 7.0
10
0
12.5
5
2.5
7.5
15
8.0
12V / 6,5A12V / 2A
Figure 6-3 12 V output characteristic
2XWSXWYROWDJH>9@
2XWSXWFXUUHQW>$@
01.0 1.5 2.5 3.50.5 2.0 3.0 4.0 4.5
20
0
25
10
5
15
30
5.0
24V / 0.6A
24V / 1.3A 24V / 2.5A
24V / 4A
24V / 3.7A
Figure 6-4 24 V output characteristic
Technical data
6.3 Efficiency and power loss
SITOP PSU100C
32 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
The device supplies a constant output voltage until the current limit is reached. In the event
of an overload, the output current and the output voltage are reduced. When the output
voltage falls below approx. 9 V (12 V versions) and 15 V (24 V versions), the device switches
off, and automatically restarts. This response is repeated as long as the overload condition is
present.
6.3 Efficiency and power loss
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Efficiency at Ua rated,
Ia rated, approx.
82 % 86 % 82 % 86 %
Power loss at Ua rated,
Ia rated, approx.
5.8 W 12.5 W 2.6 W 4.5 W
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Efficiency at Ua rated,
Ia rated, approx.
87 % 87 % 88 %
Power loss at Ua rated,
Ia rated, approx.
9 W 14 W 13 W
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
70
80 100 120 140 160 180
76
78
72
71
73
79
80
81
200
82
85
220 240 260 280
74
77
75
83
84
Figure 6-5 Efficiency for AC: 6EP1321-5BA00
Technical data
6.3 Efficiency and power loss
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 33
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
75
80 100 120 140 160 180
81
83
77
76
78
84
85
86
200
87
90
220 240 260 280
79
82
80
88
89
Figure 6-6 Efficiency for AC: 6EP1322-5BA10
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
70
80 100 120 140 160 180
76
78
72
71
73
79
80
81
200
82
85
220 240 260 280
74
77
75
83
84
Figure 6-7 Efficiency for AC: 6EP1331-5BA00
Technical data
6.3 Efficiency and power loss
SITOP PSU100C
34 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
75
80 100 120 140 160 180
81
83
77
76
78
84
85
86
200
87
90
220 240 260 280
79
82
80
88
89
Figure 6-8 Efficiency for AC: 6EP1331-5BA10
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
75
80 100 120 140 160 180
81
83
77
76
78
84
85
86
200
87
90
220 240 260 280
79
82
80
88
89
Figure 6-9 Efficiency for AC: 6EP1332-5BA00
Technical data
6.3 Efficiency and power loss
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 35
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
75
80 100 120 140 160 180
81
83
77
76
78
84
85
86
200
87
90
220 240 260 280
79
82
80
88
89
Figure 6-10 Efficiency for AC: 6EP1332-5BA20
(IILFLHQF\>@
,QSXWYROWDJH>9@
ORDG
ORDG
ORDG
75
80 100 120 140 160 180
81
83
77
76
78
84
85
86
200
87
90
220 240 260 280
79
82
80
88
89
Figure 6-11 Efficiency for AC: 6EP1332-5BA10
Technical data
6.4 Closed-loop control
SITOP PSU100C
36 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6.4 Closed-loop control
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Dyn. line compensation
(Ue rated ±15%), max.
0.1 % 0.1 % 0.1 % 0.1 %
Dyn. load compensation
(Ia: 10/90/10 %), Ua ± ,typ.
3 % 3 % 3 % 3 %
Load step compensation
time
10 to 90 %, typ.
4 ms 3 ms 3 ms 5 ms
Load step compensation
time
90 to 10 %, typ.
3 ms 3 ms 3 ms 5 ms
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Dyn. line compensation
(Ue rated ±15%), max.
0.1 % 0.1 % 0.1 %
Dyn. load compensation
(Ia: 10/90/10 %), Ua ± ,typ.
3 % 3 % 3 %
Load step compensation
time
10 to 90 %, typ.
4 ms 4 ms 4 ms
Load step compensation
time
90 to 10 %, typ.
4 ms 4 ms 4 ms
Technical data
6.5 Protection and monitoring
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 37
6.5 Protection and monitoring
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Output overvoltage protection Yes, according to EN 60950-1
Current limitation, typ. 2.4 A 7.2 A 0.7 A 1.4 A
Property of the
output/short-circuit proof
Yes
Short-circuit protection Electronic trip, automatic restart
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Output overvoltage protection Yes, according to EN 60950-1
Current limitation, typ. 3 A 4 A 4.8 A
Property of the
output/short-circuit proof
Yes
Short-circuit protection Electronic trip, automatic restart
6.6 MTBF
6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
Mean Time Between Failures SN29500: >500000 h at 40 °C, rated load, 24 hour operation
6.7 Mechanical system
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Connection system Screw terminal
Connections / line supply L, N, PE: removable screw terminal, for each 1 x 0.5...2.5 mm²
Connections / output +: 1 screw terminal for 0.5...2.5 mm²; -: 2 screw terminals for 0.5...2.5 mm²
Technical data
6.7 Mechanical system
SITOP PSU100C
38 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Width of the housing 30 mm 52.5 mm 22.5 mm 30 mm
Height of the housing 80 mm 80 mm 80 mm 80 mm
Depth of the housing 100 mm 100 mm 100 mm 100 mm
Mounting width 30 mm 52.5 mm 22.5 mm 30 mm
Mounting height 180 mm 180 mm 180 mm 180 mm
Weight, approx. 0.12 kg 0.32 kg 0.12 kg 0.17 kg
Product property / of the housing /
housing that can be lined up next to one
another
Yes
Type of mounting /
panel mounting
No
Type of mounting /
rail mounting
Yes
Type of mounting /
S7-300 rail mounting
No
Mounting Can be snapped onto standard EN 60715 35x7,5/15 mounting rails
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Connection system Screw terminal
Connections / line supply L, N, PE: removable screw terminal, for each 1 x 0.5...2.5 mm²
Connections / output +: 1 screw terminal for 0.5...2.5 mm²; -: 2 screw terminals for 0.5...2.5 mm²
Width of the housing 45 mm 52.5 mm 52.5 mm
Height of the housing 80 mm 80 mm 80 mm
Depth of the housing 100 mm 100 mm 100 mm
Mounting width 45 mm 52.5 mm 52.5 mm
Mounting height 180 mm 180 mm 180 mm
Weight, approx. 0.22 kg 0.32 kg 0.32 kg
Product property / of the housing /
housing that can be lined up next to one
another
Yes
Type of mounting /
panel mounting
No
Type of mounting /
rail mounting
Yes
Type of mounting /
S7-300 rail mounting
No
Mounting Can be snapped onto standard EN 60715 35x7,5/15 mounting rails
Technical data
6.8 Accessories
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 39
6.8 Accessories
6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
Mechanical accessories Removable 6EP1971-5BA00 spring-loaded terminal
6.9 Dimension drawing
See Section Dimensions and weight (Page 14)
CAD data that can be downloaded from the Internet:
6EP1321-5BA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00411)
6EP1322-5BA10
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00468)
6EP1331-5BA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00415)
6EP1331-5BA10
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00419)
6EP1332-5BA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00462)
6EP1332-5BA20
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00717)
6EP1332-5BA10
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00465)
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 41
Safety, approvals, EMC 7
7.1 Safety
6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
Primary/secondary galvanic isolation Yes
Galvanic isolation SELV output voltage Ua according to EN 60950-1 and EN 50178
Transformer according to EN 61558-2-16
Protection class Class I
Degree of protection (EN 60529) IP20
Leakage current, typ. 0.4 mA
Leakage current, max. 3.5 mA
Test voltage See Table 7-1 Test voltage (Page 42)
Safety, approvals, EMC
7.2 Test voltage
SITOP PSU100C
42 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
7.2 Test voltage
*URXQG3(
6HFRQGDU\3ULPDU\,QSXW 2XWSXW
$
%&
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another
Connect the output terminals and PE together
Test (C)
Connect the output terminals with one another and measure with respect to PE
Table 7- 1 Test voltage
Test time Prim ↔ sec (A) Prim ↔ PE (B) Sec ↔ PE (C)
60 s 4200 V DC 2200 V DC 700 V DC Type test
60 s 3000 VAC 1500 VAC 500 VAC
1 s 2200 V DC 2200 V DC 500 V DC Production test
1 s 1500 VAC 1500 VAC 350 VAC
1 s 2200 V DC 2200 V DC 500 V DC Field test
1 s 1500 VAC 1500 VAC 350 VAC
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA
Safety, approvals, EMC
7.3 Certifications
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 43
7.3 Certifications
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
CE marking Yes
UL/CSA approval Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-
1, UL 60950-1)
NEC Class 2
Remark
- - Yes
Output limited to
100 VA
Yes
Output limited to
100 VA
Explosion protection ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-
2007) Class I, Div. 2, Group ABCD, T4
CB approval Yes
Marine approval GL, ABS
Degree of protection (EN
60529)
IP20
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
CE marking Yes
UL/CSA approval Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-
1, UL 60950-1)
NEC Class 2
Remark
Yes
Output limited to 100 VA
Yes
Output limited to 100 VA
-
Explosion protection ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-
2007) Class I, Div. 2, Group ABCD, T4
CB approval Yes
Marine approval GL, ABS
Degree of protection (EN
60529)
IP20
Safety, approvals, EMC
7.4 EMC
SITOP PSU100C
44 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
7.4 EMC
6EP1321-5BA00 (12 V/2 A)
6EP1322-5BA10 (12 V/6.5 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
Electrostatic discharge EN 61000-4-2 8 kV contact, 8 kV air
Electromagnetic fields EN 61000-4-3 0.15…80 MHz 10 V/m, 80…1000 MHz 20 V/m
High-speed transient disturbance
variables (burst)
EN 61000-4-4 4 kV at line supply connections, 2 kV at the DC output
Surge voltages EN 61000-4-5 3 kV symmetrical at the line supply connections
6 kV symmetrical at the line supply connections
500 V symmetrical/asymmetrical on DC output cables
High-frequency fields EN 61000-4-6 10 V; 0.15…80 MHz
Magnetic fields EN 61000-4-8 30 A/m; 50 Hz
Voltage dips EN 61000-4-11 100% for 20 ms, 60% for 200 ms, 30% for 500 ms
Voltage interruptions EN 61000-4-11 100% for 5000 ms
Emitted interference EN 55022 Class B
Line harmonics limitation EN 61000-3-2 Class A
EN61000-6-2 Immunity for industrial environments Generic standards
EN61000-6-3 Emission for residential areas
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 45
Ambient conditions 8
6EP1322-5BA10 (12 V/6.5 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
6EP1321-5BA00 (12 V/2 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
Ambient temperature -20...+70° C with natural convection
from +50 °C: 3.5 % Ia rated/K
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat,
constant
EN 60068-2-14 temperature change
-20...+70° C with natural convection
from +55 °C: 3 % Ia rated/K
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat,
constant
EN 60068-2-14 temperature change
Transport and storage temperature -40...+85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class Climate class 3K3 according to EN 60721, without condensation
Mechanical stress in operation Tested according to:
EN 60068-2-6 vibration, test Fc:
- 7 mm deflection in the range 5...9 Hz
- 2 g acceleration in the range 9...150 Hz
EN 60068-2-27 shock, test Ea:
- Acceleration 150 m/s2, test duration 11 ms
Ambient conditions
SITOP PSU100C
46 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1322-5BA10 (12 V/6.5 A)
6EP1332-5BA00 (24 V/2.5 A)
6EP1332-5BA20 (24 V/3.7 A)
6EP1332-5BA10 (24 V/4 A)
6EP1321-5BA00 (12 V/2 A)
6EP1331-5BA00 (24 V/0.6 A)
6EP1331-5BA10 (24 V/1.3 A)
Damaging gases Tested according to:
EN 60068-2-42 Sulfur dioxide: 10cm3 / m3, 4 days
EN 60068-2-43 Hydrogen sulfide: 1cm3 / m3, 4 days
Atmospheric pressure Operation:
1080 ... 795 hPa (-1000 ... +2000 m)
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-9 Mounting height derating (Page 22)
Overvoltage category:
III up to 2000 m (EN 50178)
II from 2000 m up to 6000 m (EN 50178)
Storage:
1080 ... 660 hPa (-1000 ... +3500 m)
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 47
Applications 9
9.1 Parallel connection to increase the power rating
To increase the power rating, two identical power supplies SITOP PSU100C, with the
exception of 6EP1331-5BA00 and 6EP1332-5BA20, can be directly connected with one
another galvanically.
The following must be observed:
The output voltages of the power supplies to be connected in parallel may differ by a
maximum of 0.2 % under no load conditions.
When required, the output voltages must be adjusted with the potentiometer.
To do this, the "–" terminals should be connected, and under no-load conditions, the
voltage difference measured between the "+" terminals that have not been connected
together. This voltage difference must not exceed 0.2%.
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external network junction (terminal strip) if possible.
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
SITOP
+
AC
DC
-
SITOP
+
AC
DC
-
+
-
SITOP
+
AC
DC
-
SITOP
+
AC
DC
-
&255(&7
,1&255(&7
/2$' /2$'
7HUPLQDOEORFN
Figure 9-1 Parallel connection
Note
The power-up of two SITOP PSU100C (2 × Ia,rated) power supplies is only permissible with
the basic rated load (Ia, rated).
Applications
9.1 Parallel connection to increase the power rating
SITOP PSU100C
48 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
NOTICE
Protective circuit for the parallel connection of more than two power supplies
When connecting more than two power supplies in parallel, additional measures must be
taken to prevent high reverse currents in the event of a secondary device fault. For this
purpose, a suitable protective circuit (e.g. decoupling diode
or DC-compatible miniature circuit-breaker) must be installed between each "+" terminal of
the power supply and the common connection point.
Applications
9.2 Parallel connection for redundancy
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 49
9.2 Parallel connection for redundancy
Connecting several SITOP PSU100C power supplies in parallel for redundancy purposes is
required if especially high demands are placed on the availability of a reliable 24 V power
supply.
Using the SITOP PSE202U redundancy module, two 24 V power supplies of the same type
can be decoupled (Figure 9-2 Redundant configuration (Page 49)). When one of the devices
fails, then the other automatically takes over the power supply. If one of the power supplies
fails, then this is signaled using an LED on the redundancy module as well as an isolated
relay contact.
When dimensioning the system, it must be ensured that n+1 redundant connected power
supplies can handle the total power requirement of the remaining n power supplies.
Note
For a high reliability of the supply, it is recommended that the redundant switched power
supplies are protected separately on the line-side and, if possible, be connected to different
power supply networks.
Note
The SITOP PSE202U NEC Class 2 (6EP1962-2BA00) redundancy module must be used to
create a redundant circuit configuration according to NEC Class 2 (Figure 9-3 Parallel
connection with redundancy module for NEC Class 2 (Page 50)).
Figure 9-2 Redundant configuration
Applications
9.2 Parallel connection for redundancy
SITOP PSU100C
50 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
Figure 9-3 Parallel connection with redundancy module for NEC Class 2
You can find additional information at:
SITOP PSE202U manual (http://support.automation.siemens.com/WW/view/en/42248598)
Applications
9.3 Series connection for increased voltage
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 51
9.3 Series connection for increased voltage
To achieve an output voltage of 48 V DC, two SITOP PSU100C power supplies of the same
type can be connected in series. In this case, connect the "-" terminal of the first power
supply to the "+" terminal of the second power supply. The "+" terminal of the first power
supply and the "-" terminal of the second power supply are routed to the load.
Depending on the grounding point of the secondary output voltages, voltages of +48 V,
±24 V or -48 V can be realized.
In the case of an asymmetric load distribution, it is not possible to guarantee correct
functionality.
WARNING
SELV is not guaranteed in the case of a fault
When connecting two power supplies in series, the continuous, permissible SELV voltage
of a maximum of 60 V DC according to EN 60950 cannot be guaranteed in the case of a
fault.
Figure 9-4 Series connection
Applications
9.4 Protection against short-time voltage dips
SITOP PSU100C
52 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
9.4 Protection against short-time voltage dips
During a drop in the primary-side supply voltage, SITOP PSU100C power supplies still
maintain the output voltage over a short millisecond period (see section Technical data, Input
(Page 27))
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 53
Environment 10
The device is in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.
Environment
SITOP PSU100C
54 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629 55
Service & Support 11
Technical support
Technical support for all IA/DT products can be accessed through the following
communication channels:
Phone: + 49 (0) 911 895 7222
E-Mail (mailto:support.automation@siemens.com)
Internet:
Online support request form (http://www.siemens.de/automation/support-request)
Technical documentation on the Internet
Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.de/sitop/manuals)
SITOP power supply homepage
General news about our power supplies is available in the Internet at the SITOP homepage:
SITOP (http://www.siemens.de/sitop)
Information material
SITOP information can be downloaded from the Internet:
Information and download center (http://www.siemens.de/sitop-infomaterial)
CAx data
2D/3D data and circuit diagram macros can be downloaded from the Internet:
Siemens image database (http://www.siemens.de/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.de/cax)
SITOP Selection Tool
Simply and quickly select the optimum the power supply or DC-UPS:
SITOP Selection Tool (http://www.siemens.de/sitop-selection-tool)
Online catalog and ordering system
The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)
Service & Support
SITOP PSU100C
56 Operating Instructions, 06.2013, C98130-A7599-A1-2-7629