Type: DILM32-XHI11 Article No.: 277376 Ordering information Conventional thermal current I th = I e AC-1 Open Ith = Ie A 10 Contacts S = Schlieer, S F = Fruhschlieer 1M Contacts O = Offner, O S = Spatoffner 1B Contact sequence Auxiliary contacts Zwangsfuhrung der Schaltglieder innerhalb eines Hilfsschalterbausteins (nach IEC 60947-5-1 Anhang L) Yes Break contact (not late-break contact) suitable as a mirror contact (to IEC/EN 60947-4-1 Annex F) DILM7 - DILM32 Rated impulse withstand voltage Uimp V AC Overvoltage category/pollution degree 6000 III/3 Rated insulation voltage AC Ui V AC 690 Rated operational voltage Ue V AC 500 between coil and auxiliary contacts V AC 400 between the auxiliary contacts V AC 400 Safe isolation to VDE 0106 Part 101 and Part 101/A1 Rated operational current AC-15 230 V Ie A 6 380/415 V Ie A 4 500 V Ie A 1,5 24 V Ie A 10 60 V Ie A 6 110 V Ie A 3 DC-13 L/R f 15 ms 1 220 V Ie A 1 Conv. thermal current Ith A 10 Failure rate -8, < 1 one failure at 100 million operations Operations x 106 Control circuit reliability (at Ue = 24 V DC, Umin = 17 V, I min= 5.4 mA) Component lifespan at Ue = 230 V, AC-15, 3 A 1.3 Short-circuit rating without welding max. fuse A gG/gL 10 Notes Making and breaking conditions to DC-13, time L/R constant as stated See "Fuses" overlay for time/current characteristic on request not with DIL...-XHIV and DIL...-XHICV Moeller GmbH, Hein-Moeller-Str. 7-11, D-53115 Bonn E-Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net Copyright 2005 by Moeller GmbH. Subject to modifications. HPL-C2005GB-INT V3.0 2