Type: DILM32−XHI11
Article No.: 277376
Ordering information
Conventional thermal current I th = I e AC−1 Open Ith = IeA 10
Contacts S = Schließer, S F = Frühschließer 1 M
Contacts Ö = Öffner, Ö S = Spätöffner 1 B
Contact sequence
Auxiliary contacts
Zwangsführung der Schaltglieder innerhalb eines
Hilfsschalterbausteins (nach IEC 60947−5−1 Anhang
L) Yes
Break contact (not late−break contact) suitable as a
mirror contact (to IEC/EN 60947−4−1 Annex F) DILM7 – DILM32
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage
AC UiV AC 690
Rated operational voltage UeV AC 500
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and auxiliary contacts V AC 400
between the auxiliary contacts V AC 400
Rated operational current
AC–15
230 V IeA 6
380/415 V IeA 4
500 V IeA 1,5
DC−13 L/R f 15 ms
24 V IeA 10
60 V IeA 6
110 V IeA 3
1
220 V IeA 1
Conv. thermal current Ith A 10
Control circuit reliability (at Ue = 24 V DC, Umin = 17 V,
Imin= 5.4 mA) Failure rate » −8, < 1 one failure at 100 million
operations
Component lifespan
at Ue = 230 V, AC−15, 3 A Operations × 1061.3
Short−circuit rating without welding
max. fuse A gG/gL 10
Notes
Making and breaking conditions to DC−13,
time L/R constant as stated
See "Fuses" overlay for time/current
characteristic on request
not with DIL...−XHIV and DIL...−XHICV
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2005 by Moeller GmbH. Subject to modifications. HPL−C2005GB−INT V3.0
2