45
SMALL DIMENSION (ELECTRONIC) FUSES
ABC
Fast-Acting
Physical Size: 1/4” x 1-1/4”
(6.3mm x 32mm)
Construction: Ceramic Tube
Voltage Rating: See Below
Interrupting Rating: See Below
Agency Approvals:
UL Listed product meets standard 248-14
UL Listed Guide & File numbers (ABC
1/4-15A): JDYX & E19180.
UL Recognition Guide & File numbers
(ABC 20-30A): JDYX2 & E19180.
CSA Certification Record No: 053787
C 000 & Class No: 1422 01 & 1422
30.
Electrical Characteristics
Current Rated AC Interrupting
Rating Voltage Rating1
AC (Max.) DC (Max.) 250V 125V
1/4 250V 125V 35A 10000A
1/2 250V 125V 35A 10000A
3/4 250V 125V 35A 10000A
1 250V 125V 35A 10000A
1-1/2 250V 125V 100A 10000A
2 250V 125V 100A 10000A
2-1/2 250V 125V 100A 10000A
3 250V 125V 100A 10000A
4 250V 125V 200A 10000A
5 250V 125V 200A 10000A
6 250V 125V 200A 10000A
7 250V 125V 200A 10000A
8 250V 125V 200A 10000A
10 250V 125V 200A 10000A
12 250V 125V 200A 10000A
15 250V 125V 750A 10000A
20 250V 125V 400A 1000A
25 125V 125V – 1000A
30 125V 125V – 1000A
1Interrupting ratings were measured at 70% - 80% power factor on
AC, and at a time constant described in UL 198L.
CROSS REFERENCE
NEW OLD
EDISON EDISON BUSS GOULD LF
ABC BBC ABC GAB 314
AGC
Fast-Acting
Physical Size: 1/4” x 1-1/4”
(6.3mm x 32mm)
Construction: Glass Tube, Nickel-
plated brass endcaps.
Voltage Rating: See Below
Interrupting Rating: See Below
Agency Approvals:
UL Listed product meets standard 248-14
UL Listed Card: AGC 1/500-10
UL Recognition Card: AGC 11-30
CSA Component Acceptance Card
(Class No. 1422 30)
CSA Certification Card (Class No.
1422 01)
Electrical Characteristics
Current Rated AC Interrupting
Rating Voltage Rating1
AC (Max.) 250V 125V 32V
1/20 250V 35V 10000A 1000A
1/16 250V 35V 10000A 1000A
1/10 250V 35V 10000A 1000A
1/8 250V 35V 10000A 1000A
3/16 250V 35V 10000A 1000A
2/10 250V 35V 10000A 1000A
1/4 250V 35V 10000A 1000A
3/10 250V 35V 10000A 1000A
3/8 250V 35V 10000A 1000A
45/100 250V 35V 10000A 1000A
1/2 250V 35V 10000A 1000A
3/4 250V 35V 10000A 1000A
1 250V 35V 10000A 1000A
1-1/4 250V 100A 10000A 1000A
1-1/2 250V 100A 10000A 1000A
2 250V 100A 10000A 1000A
2-1/4 125V 100A 10000A 1000A
2-1/2 125V 100A 10000A 1000A
3 125V 100A 10000A 1000A
4 125V 200A 10000A 1000A
5 125V 200A 10000A 1000A
6 125V 200A 10000A 1000A
7 125V 200A 10000A 1000A
8 125V 200A 10000A 1000A
9 125V 200A 10000A 1000A
10 125V 200A 10000A 1000A
15 32V – – 1000A
20 32V – – 1000A
25 32V – – 1000A
30 32V – – 1000A
1Interrupting ratings were measured at 70% - 80% power factor on
AC, and at a time constant described in UL 198L.
CROSS REFERENCE
NEW OLD
EDISON EDISON BUSS GOULD LF
AGC BGC AGC GGC 312
GBB
Very Fast-Acting
Physical Size: 1/4” x 1-1/4”
(6.3mm x 32mm)
Construction: Ceramic Tube
Voltage Rating: See Below
Agency Approvals:
UL recognized product meets standard 248-
14
UL Recognized Card: GBB 1-30A (JFHR2,
E56412)
CSA Component Certified Card (Class
1422-01 File 53787)
Product Code & Voltage Rating
Product Voltage
Code Rating
AC DC
GBB-1 250V 125V
GBB-1-1/4 250V 125V
GBB-2 250V 125V
GBB-3 250V 125V
GBB-4 250V 125V
GBB-5 250V 125V
GBB-6 250V 125V
GBB-7 250V 125V
GBB-8 250V 125V
GBB-9 250V 125V
GBB-10 250V 125V
GBB-12 250V 125V
GBB-15 250V 125V
GBB-20 250V 125V
GBB-25 125V 125V
GBB-30 125V 125V
CROSS REFERENCE
NEW OLD
EDISON EDISON BUSS GOULD LF
GBB — GBB None 322
1/4” x 1-1/4” Fast-Acting Fuses