45
SMALL DIMENSION (ELECTRONIC) FUSES
ABC
Fast-Acting
Physical Size: 1/4” x 1-1/4”
(6.3mm x 32mm)
Construction: Ceramic Tube
Voltage Rating: See Below
Interrupting Rating: See Below
Agency Approvals:
UL Listed product meets standard 248-14
UL Listed Guide & File numbers (ABC
1/4-15A): JDYX & E19180.
UL Recognition Guide & File numbers
(ABC 20-30A): JDYX2 & E19180.
CSA Certification Record No: 053787
C 000 & Class No: 1422 01 & 1422
30.
Electrical Characteristics
Current Rated AC Interrupting
Rating Voltage Rating1
AC (Max.) DC (Max.) 250V 125V
1/4 250V 125V 35A 10000A
1/2 250V 125V 35A 10000A
3/4 250V 125V 35A 10000A
1 250V 125V 35A 10000A
1-1/2 250V 125V 100A 10000A
2 250V 125V 100A 10000A
2-1/2 250V 125V 100A 10000A
3 250V 125V 100A 10000A
4 250V 125V 200A 10000A
5 250V 125V 200A 10000A
6 250V 125V 200A 10000A
7 250V 125V 200A 10000A
8 250V 125V 200A 10000A
10 250V 125V 200A 10000A
12 250V 125V 200A 10000A
15 250V 125V 750A 10000A
20 250V 125V 400A 1000A
25 125V 125V 1000A
30 125V 125V 1000A
1Interrupting ratings were measured at 70% - 80% power factor on
AC, and at a time constant described in UL 198L.
CROSS REFERENCE
NEW OLD
EDISON EDISON BUSS GOULD LF
ABC BBC ABC GAB 314
AGC
Fast-Acting
Physical Size: 1/4” x 1-1/4”
(6.3mm x 32mm)
Construction: Glass Tube, Nickel-
plated brass endcaps.
Voltage Rating: See Below
Interrupting Rating: See Below
Agency Approvals:
UL Listed product meets standard 248-14
UL Listed Card: AGC 1/500-10
UL Recognition Card: AGC 11-30
CSA Component Acceptance Card
(Class No. 1422 30)
CSA Certification Card (Class No.
1422 01)
Electrical Characteristics
Current Rated AC Interrupting
Rating Voltage Rating1
AC (Max.) 250V 125V 32V
1/20 250V 35V 10000A 1000A
1/16 250V 35V 10000A 1000A
1/10 250V 35V 10000A 1000A
1/8 250V 35V 10000A 1000A
3/16 250V 35V 10000A 1000A
2/10 250V 35V 10000A 1000A
1/4 250V 35V 10000A 1000A
3/10 250V 35V 10000A 1000A
3/8 250V 35V 10000A 1000A
45/100 250V 35V 10000A 1000A
1/2 250V 35V 10000A 1000A
3/4 250V 35V 10000A 1000A
1 250V 35V 10000A 1000A
1-1/4 250V 100A 10000A 1000A
1-1/2 250V 100A 10000A 1000A
2 250V 100A 10000A 1000A
2-1/4 125V 100A 10000A 1000A
2-1/2 125V 100A 10000A 1000A
3 125V 100A 10000A 1000A
4 125V 200A 10000A 1000A
5 125V 200A 10000A 1000A
6 125V 200A 10000A 1000A
7 125V 200A 10000A 1000A
8 125V 200A 10000A 1000A
9 125V 200A 10000A 1000A
10 125V 200A 10000A 1000A
15 32V 1000A
20 32V 1000A
25 32V 1000A
30 32V 1000A
1Interrupting ratings were measured at 70% - 80% power factor on
AC, and at a time constant described in UL 198L.
CROSS REFERENCE
NEW OLD
EDISON EDISON BUSS GOULD LF
AGC BGC AGC GGC 312
GBB
Very Fast-Acting
Physical Size: 1/4” x 1-1/4”
(6.3mm x 32mm)
Construction: Ceramic Tube
Voltage Rating: See Below
Agency Approvals:
UL recognized product meets standard 248-
14
UL Recognized Card: GBB 1-30A (JFHR2,
E56412)
CSA Component Certified Card (Class
1422-01 File 53787)
Product Code & Voltage Rating
Product Voltage
Code Rating
AC DC
GBB-1 250V 125V
GBB-1-1/4 250V 125V
GBB-2 250V 125V
GBB-3 250V 125V
GBB-4 250V 125V
GBB-5 250V 125V
GBB-6 250V 125V
GBB-7 250V 125V
GBB-8 250V 125V
GBB-9 250V 125V
GBB-10 250V 125V
GBB-12 250V 125V
GBB-15 250V 125V
GBB-20 250V 125V
GBB-25 125V 125V
GBB-30 125V 125V
CROSS REFERENCE
NEW OLD
EDISON EDISON BUSS GOULD LF
GBB GBB None 322
1/4” x 1-1/4” Fast-Acting Fuses