SITOP PSU100C
6EP1331-5BA00 (24 V/0,6 A)
6EP1331-5BA10 (24 V/1,3 A)
6EP1321-5BA00 (12 V/2 A)
Betriebsanleitung (kompakt)
Operating Instructions (compact)
Instrucciones de servicio (resumidas)
操作说明 (精简版)
Notice de service (compacte)
Istruzioni operative (descrizione sintetica)
Руководство по эксплуатации (компактное)
https://support.industry.siemens.com
1: Ansicht Geräte
1: View of the devices
1: Vista del aparato
1: 设备外观
1: Vue des appareils
1: Vista degli apparecchi
1: Внешний вид устройств
Die SITOP-Stromversorgungen sind Einbaugeräte,
Schutzart IP20, Schutzklasse I.
Primär getaktete Stromversorgungen zum Anschluss
an 1-phasiges Wechselstromnetz (TN-, TT- Netz nach
IEC 60364-1) mit Nennspannungen 100 - 230 V,
50 - 60 Hz bzw. 110 - 220 V DC; Ausgangsspannung
24 V DC bzw. 12 V DC, potenzialfrei, kurzschluss- und
leerlauffest.
6EP1331-5BA00, 6EP1331-5BA10: Begrenzte
Ausgangsleistung gemäß NEC Class 2 (maximal 100 VA).
Bild 1 Ansicht Geräte (Seite 1)
Der einwandfreie und sichere Betrieb dieses
Gerätes/Systems setzt sachgemäßen Transport,
sachgemäße Lagerung, Aufstellung und Montage sowie
sorgfältige Bedienung und Instandhaltung voraus.
Dieses Gerät/System darf nur unter Beachtung der
Instruktionen und Warnhinweise der zugehörigen
technischen Dokumentation eingerichtet und betrieben
werden.
Nur qualifiziertes Personal darf das Gerät/System
installieren und in Betrieb setzen.
Das Gerät erfüllt die ATEX Richtlinie 2014/34/EU;
EN 60079-0; EN 60079-15
SPANNUNGSEINSTELLUNG NUR IN NICHT-
EXPLOSIVER UMGEBUNG DURCHFÜHREN!
Montage auf Normprofilschiene TH35-15/7,5
(EN 60715).
Das Gerät ist so zu montieren, dass die
Eingangsklemmen unten und die Ausgangsklemmen
oben sind.
Unterhalb und oberhalb des Gerätes sind mindestens
die Freiräume entsprechend der Grafik einzuhalten.
Bei Installation des Gerätes in explosionsgefährdeter
Umgebung (II 3G Ex nA IIC T4 Gc) ist dieses in einen
Verteilerkasten mit Schutzart IP54 oder höher
Bild 5 Einbau (Seite 3)
Bild 2 Montage (Seite 2)
Vor Beginn der Installations- oder Instandhaltungs-
arbeiten ist der Hauptschalter der Anlage
auszuschalten und gegen Wiedereinschalten zu
sichern. Bei Nichtbeachtung kann das Berühren
spannungsführender Teile Tod oder schwere
Körperverletzung zur Folge haben.
Für die Installation der Geräte sind die einschlägigen
länderspezifischen Vorschriften zu beachten.
Wichtiger Hinweis: Eingangsseitig ist eine Sicherung
oder ein Leitungs- oder Motorschutzschalter
vorzusehen.
Verwenden sie Kupferdraht zugelassen für 65/75 °C
(nur bei UL508).
Der Anschluss der Versorgungsspannung muss gemäß
IEC 60364 und EN 50178 ausgeführt werden. Für DC-
Betrieb am Eingang ist die Gleichspannung zwischen
L1 und N anzuschließen.
Bild 4 Klemmendaten (Seite 3)
*1) Endanschlag nicht höher belasten
SITOP power supplies are built-in units, IP20 degree of
protection, protection class I.
Primary switched-mode power supplies for connection
to 1-phase AC system (TN, TT system in accordance
with VDE 0100 T 300 / IEC 364-1) with rated voltages
of 100 - 230 V, 50 - 60 Hz or 110 - 220 V DC; output
voltages of 24 V DC or 12 V DC, isolated, short-circuit-
proof and idling-proof.
6EP1331-5BA00, 6EP1331-5BA10: Limited output
power according to NEC Class 2 (maximum 100 VA).
Figure 1 View of the devices (Page 1)
Appropriate transport, proper storage, mounting, and
installation, as well as careful operation and service,
are essential for the error-free, safe and reliable
operation of the device/system.
Setup and operation of this device/system are
permitted only if the instructions and warnings of the
associated technical documentation are carefully
observed.
Only qualified personnel are allowed to install the
device/system and set it into operation.
The device complies with ATEX directive 2014/34/EU;
EN 60079-0; EN 60079-15
OPERATE VOLTAGE ADJUSTMENT IN NON-
HAZARDOUS AREAS ONLY!
Mounted on a standard mounting rail TH35-15/7,5
(EN 60715).
The device must be mounted in such a way that the
input terminals are at the bottom and the output
terminals at the top.
Above and below the device, the clearance spaces as
indicated in the chart must be maintained.
If the device is to be used in a hazardous zone
(II 3G Ex nA IIC T4 Gc) it must be installed in a
distribution box with degree of protection IP54 or
Figure 5 Installation (Page 3)
Figure 2 Mounting (Page 2)
Before starting any installation or maintenance work,
the main system switch must be opened and measures
taken to prevent it from being reclosed. If this
instruction is not observed, touching live parts can
result in death or serious injury.
For installation of the devices, the relevant country-
specific regulations must be observed.
Important note: A fuse, a miniature circuit breaker or
circuit breaker must be provided at the input.
Use copper wire, approved for 65/75 °C (only for
UL508).
The supply voltage must be connected according to
IEC 60364 and EN 50178. For DC operation at the
input, the DC voltage must be connected between L1
and N.
Figure 4 Terminal data (Page 3)
ect the end stop to any higher stress
Las fuentes de alimentación SITOP son modelos
empotrables, con grado de protección IP20, clase de
protección I.
Fuentes de alimentación conmutadas en primario para
la conexión a una red de corriente alterna monofásica
(redes TN o TT conforme a IEC 60364-1) con tensión
nominal de 100 - 230 V, 50 - 60 Hz o 110 - 220 V DC;
tensión de salida de 24 V DC o bien 12 V DC, con
aislamiento galvánico, resistente a cortocircuito y
marcha en vacío.
6EP1331-5BA00, 6EP1331-5BA10: Potencia de salida
limitada conforme a NEC Class 2 (máximo 100 VA).
Figura 1 Vista del aparato (Página 1)
El funcionamiento correcto y seguro de este
aparato/sistema presupone un transporte, un
almacenamiento, una instalación y un montaje
conformes a las prácticas de la buena ingeniería, así
como un manejo y un mantenimiento rigurosos.
Este aparato/sistema debe ajustarse y utilizarse únicamente
teniendo en cuenta las instrucciones y advertencias de la
documentación técnica correspondiente.
La instalación y puesta en marcha del aparato/sistema debe
encomendarse exclusivamente a personal cualificado.
El aparato cumple la directiva ATEX 2014/34/UE;
EN 60079-0; EN 60079-15.
¡AJUSTAR LA TENSIÓN SÓLO EN ENTORNOS NO
EXPLOSIVOS!
Montaje en perfil soporte normalizado TH35-15/7,5
(EN 60715).
La fuente debe montarse de modo que los bornes de
entrada queden situados en la parte inferior y los de
salida arriba.
Por encima y abajo del aparato deben dejarse como
mínimo libres las distancias que figuran en el gráfico.
Si se va a instalar el aparato en una atmósfera
potencialmente explosiva (II 3G Ex nA IIC T4 Gc),
deberá montarse en una caja con grado de protección
Figura 5 Incorporación (Página 3)
Figura 2 Montaje (Página 2)
Antes de comenzar trabajos de instalación o
mantenimiento, se debe desconectar el interruptor
principal de la instalación y asegurarlo contra una
posible reconexión. Si no se observa esta medida, el
contacto con piezas bajo tensión puede provocar la
muerte o lesiones graves.
A la hora de instalar los aparatos, se tienen que
observar las disposiciones o normativas específicas de
cada país.
Nota importante: en el lado de entrada debe instalarse
un fusible o bien un automático magnetotérmico o un
guardamotor.
Utilice hilo de cobre homologado para 65/75 °C (solo
en UL508).
La conexión a la tensión de alimentación debe
realizarse conforme a IEC 60364 y EN 50178. Si la
alimentación es con corriente continua, la tensión debe
Figura 4 Datos de los bornes (Página 3)
*1) No aplicar una carga mayor en el tope mecánico
SITOP 电源为内置设备,防护方式为 IP20,
防护等级为 I。
本设备为主时钟电源,用于连接额定电压为
100 - 230 V,50 - 60 Hz 或 110 - 220 V DC ; 相交流供
电系统(符合 IEC 60364-1 标准的 TN、TT 电网);输
出电压 24 V DC 或 12 V DC,电位隔离,具有短路保护
和空载保护功能。
6EP1331-5BA00,6EP1331-5BA10:限制输出功率符
合 NEC Class 2(最大 100 VA)。
参见 图 1 设备外观 (页 1)
本设备/系统的安全正常运行依赖于正确规范的运输、存
放、装配、安装作业以及仔细谨慎的操作和维护。
在安装和运行本设备前请务必阅读并注意本设备/系统技
术文档中包含的规定和警示。
本设备/系统仅允许由专业技术人员安装和调试。
本设备符合 ATEX 指令 2014/34/EU、EN 60079-0、
EN 60079-15 中的规定
安装在标准型材导轨 TH35-15/7,5 (EN 60715) 上。
安装设备时,应使输入端子位于下方,输出端子位于上
方。
设备的上方和下方应和其他设备至少保持与图表中相同
的间距。
设备安装在有爆炸危险的环境 (II 3G Ex nA IIC T4 Gc)
中时 ,必须安装在防护方式符合 IP54 或满足更高要求
的配电箱中。
参见 图 5 安装 (页 3)
参见 图 2 安装 (页 2)
止设备重新合闸。违反该规定可能会导致作业人员接触
到带电零部件,从而导致严重的人身伤害甚至死亡。
设备安装同时需遵循本国相关的作业规范。
重要提示:设备输入侧必须配备熔断器、馈线断路器或
者电机断路器。
使用适用于 65/75 °C 的同芯线(仅限 UL508)。
必须按照 IEC 60364 和 EN 50178 标准连接供电电压。
在输入端上进行直流运行时须在 L1 和 N 之间接入直流
电压。
参见 图 4 端子数据 (页 3)
*1) 末端挡块勿过高负载