Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-1
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Accessories and Modification Codes
Type 1 Enclosure
Electrically Held Base Contactor
Surge Suppressor
Auxiliary Contact
Side-Mounted Auxiliary Contact
15.1 Accessories
Freedom NEMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-2
A200 NEMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-18
XT IEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-23
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-28
Lighting Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-30
IT. Solid-State Soft Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-36
15.2 Modification Codes
Modification Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V10-T15-39
V10-T15-2 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Freedom NEMA
Auxiliary Contacts
NEMA Sizes 00–2
The auxiliary contacts listed
below are designed for
installation on Freedom
Series starters and
contactors. Snap-on design
facilitates quick, easy
installation.
These bifurcated design
contact blocks, featuring
silver cadmium alloy
contacts, are well suited for
use in very low energy (logic
level) circuits.
Product Selection
Notes
NCI = Normally Closed early opening designed for use in reversing applications. EC = Early Closing. LO = Late Opening.
1 For reference only—not part of catalog number. See Page V10-T15-3.
Description
Contact
Configuration
Code 1Catalog Number
Side-Mounted
1NO 10 C320KGS1
1NC 01 C320KGS2
1NO-1NC 11 C320KGS3
2NO 20 C320KGS4
2NC 02 C320KGS5
1NO-1NCI N/A C320KGS6
1NO (EC)-1NC (LO) N/A C320KGS7
1NCI N/A C320KGS8
Top-Mounted
1NO 10 C320KGT1
1NC 01 C320KGT2
1NO-1NC 11 C320KGT3
2NO 20 C320KGT4
2NC 02 C320KGT5
1NO-1NCI N/A C320KGT6
1NO (EC)-1NC (LO) N/A C320KGT7
1NCI N/A C320KGT8
3NO 30 C320KGT9
2NO-1NC 21 C320KGT10
1NO-2NC 12 C320KGT11
3NC 03 C320KGT12
4NO 40 C320KGT13
3NO-1NC 31 C320KGT14
2NO-2NC 22 C320KGT15
1NO-3NC 13 C320KGT16
4NC 04 C320KGT17
3NO-1NCI N/A C320KGT18
2NO-1NCI-1NC N/A C320KGT19
2NO-1NO (EC)-1NC (LO) N/A C320KGT20
1NO-1NC-1NO (EC)-1NC (LO) N/A C320KGT21
Side-Mounted
Top-Mounted
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-3
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Contact Configuration Code
This two-digit code is found
on the auxiliary contact to
assist in identifying the
specific contact configuration.
The first digit indicates the
quantity of NO contacts and
the second indicates the
quantity of NC contacts.
NEMA Sizes 3–8
Product Selection
Auxiliary Contact Ratings (Amperes)
Ratings—NEMA A600
Ratings—NEMA P300 Ratings—Logic Level Ratings—C320KGS20L,
C320KGS21L, C320KGS22L
Notes
1For reference only—not part of catalog number. See above.
2NO-NC occupies two positions—L2 and L3, or R2 and R3. See Page V10-T15-5.
Circuit
Contact
Configuration
Code 1
NEMA
Size Catalog Number
Base Auxiliary Contacts—NEMA Sizes 3–5
NO 10 3 C320KGS31
NO-NC 11 3 C320KGS32
NO 10 4–5 C320KGS42
NO-NC 11 4–5 C320KGS42
Auxiliary Contacts—NEMA Sizes 3–5
NO 10 3–5 C320KGS20
NC 01 3–5 C320KGS21
NO-NC 211 3–5 C320KGS22
Auxiliary Contacts—NEMA Sizes 6–8
NO-NC 11 8 C320KA5
2NO-2NC 22 6–7 C320KA6
Current
AC Volts
120V 240V 480V 600V
Make and interrupting 60 30 15 12
Break 6 3 1.5 1
Continuous 10 10 10 10
Base Auxiliary Contact
Auxiliary Contact
DC Volts
Make/Break
Amperes
Continuous Thermal Rating: 5A
125 1.10
250 0.55
Current Rating
Minimum Ratings for Logic
Level and Hostile Atmosphere
Application
Minimum amperes 20 mA
Minimum volts 24 Vac/Vdc
DC-12 AC-12
UeIeUeIe
80 0.1 250 0.1
V10-T15-4 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Auxiliary Contact Location
NEMA Sizes 00–2
The sketches below illustrate
the maximum number of
auxiliary contacts that can be
assembled to a contactor or
starter and their locations.
Auxiliary Contacts
Auxiliary Contact Location
Notes
1Available positions on contactors or starters other than what is factory installed.
2When a pneumatic timer is mounted on contactor, only side-mounted auxiliary contact positions are available.
The solid-state timer, when added, takes up side-mounted auxiliary contact position.
Size Poles
Available Mounting Positions 12
Open Type Enclosed Catalog Number
00 3 T1, L1, R1 L1 AN16
0–2 3 T1, L1 L1
00–2 3 T1, T2 AN56
00 2–4 T1, L1, R1 L1 CN15
0–2 2–3 T1, L1 L1
1, 2 4 T1, L1
1, 2 5 T1, L1
10A 2–4 T1, L1, R1 L1 CN35
20–60A 2–3 T1, L1 L1
60A 4 T1, L1
60A 5 T1, L1
00–2 3 T1, T2 CN55
L1
T1 T2
R1
L1 T1 T2 R1
L1
T1
Top View
Front View
L1 T1 R1
Front View
Reversing
Contactors and Starters
Non-Reversing
Contactors and Starters
Top View
R1
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-5
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
NEMA Sizes 3–8
The sketches below illustrate
the maximum number of
auxiliary contacts that can be
assembled to a contactor and
their locations.
Note: A base auxiliary contact
must be added in position R1
before additional auxiliary
contacts can be mounted on
NEMA Size 3 or in L1 on NEMA
Sizes 4–5.
Mounting Positions
Auxiliary Contact Location
Note
1Available positions on contactors or starters other than what is factory installed.
Size Available Mounting Positions 1
NEMA Size 3 R2, R3, L1, L2, L3
NEMA Sizes 4–5 L2, L3, R1, R2, R3
NEMA Sizes 6–7 R1
NEMA Size 8 L2, R2
NEMA Sizes 6 – 7
NEMA Sizes 3–5
NEMA Size 8
L1 R1
L1
Front
of Contactor
Left Side
of Contactor
L2
Aux.
Cont.
L3
Aux.
Cont.
R2
Aux.
Cont.
R3
Aux.
Cont.
L1
Base
Aux.
Cont.
R1
Base
Aux.
Cont.
Rear
Rear
Right Side
of Contactor
R1
L2 R2
V10-T15-6 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Heater Pack Selection
Heater packs H2001B to
H2017B and H2101B to
H2117B are to be used only
with Series B overload relays
Catalog Numbers C306DN3B
(Part No. 10-7016) and
C306GN3B (Part No. 10-7020).
The load lugs are built into the
overload relay base to allow
load wiring prior to heater
pack installation. The
previous heater design had
integral load lugs. The Series
B heater packs are electrically
equivalent to the previous
heater design. Heaters
H2018-3 to H2024-3 have not
changed.
Note: The series of a starter is
the last digit of the listed catalog
number. Example: AN16DN0AB.
Starters with Series B
Overload Relays
Fast Trip—Class 10 Heater Selection
Notes
1Heater packs are shipped three to a carton. Catalog numbers are for three heater packs.
2Sizes 5–8 use the 32A overload relay with current transformers.
Size Series
NEMA—AN Type
00–0 C
1–2 B
5B
6C
7–8 B
Overload
Relay Size
Motor Full Load Ampere Rating Catalog Number
(Includes Three
Heater Packs) 1
Dial Position
ABCD
For Use with NEMA Sizes 00–0 Series C, NEMA Sizes 1–2 Series B
32A or 75A 0.260 0.313 0.367 0.420 H2101B-3
0.384 0.464 0.543 0.623 H2102B-3
0.570 0.688 0.806 0.924 H2103B-3
0.846 1.02 1.20 1.37 H2104B-3
1.28 1.55 1.83 2.10 H2105B-3
1.92 2.33 2.74 3.15 H2106B-3
2.30 2.79 3.28 3.77 H2107B-3
3.38 4.10 4.82 5.54 H2108B-3
7.07 6.03 7.09 8.16 H2109B-3
7.07 8.58 10.1 11.6 H2110B-3
9.60 11.2 12.8 14.4 H2111B-3
14.4 17.5 20.7 23.8 H2112B-3
18.7 21.8 25.0 28.1 H2113B-3
23.5 27.3 31.0 34.8 H2114B-3
For Use with NEMA Size 2—Series B
75A 28.3 32.6 37.0 41.3 H2115B-3
36.6 42.3 48.1 53.8 H2116B-3
53.8 60.8 67.9 74.9 H2117B-3
For Use with Size 5 Starters Only—Series B
32A 251 61 72 82 H2104B-3
77 93 110 126 H2105B-3
115 140 164 189 H2106B-3
138 167 197 226 H2107B-3
203 246 289 H2108B-3
For Use with Size 6 Starters Only—Series B
32A 2154 186 220 252 H2105B-3
230 280 329 378 H2106B-3
276 335 394 452 H2107B-3
406 492 578 H2108B-3
For Use with Size 7 Starters Only—Series B
32A 2169 204 240 274 H2104B-3
256 310 366 420 H2105B-3
384 466 543 630 H2106B-3
460 558 656 754 H2107B-3
676 820 H2108B-3
For Use with Size 8 Starters Only—Series B
32A 2254 306 360 411 H2104B-3
384 465 549 630 H2105B-3
576 699 822 945 H2106B-3
690 837 984 1131 H2107B-3
1014 1230 H2108B-3
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-7
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Standard Trip—Class 20 Heater Selection
Notes
1Heater packs are shipped three to a carton. Catalog numbers are for three heater packs.
2Sizes 5–8 use the 32A overload relay with current transformers.
Overload
Relay Size
Motor Full Load Ampere Rating Catalog Number
(Includes Three
Heater Packs) 1
Dial Position
ABCD
For Use with NEMA Sizes 00–0 Series C, NEMA Sizes 1–2 Series B
32A or 75A 0.254 0.306 0.359 0.411 H2001B-3
0.375 0.452 0.530 0.607 H2002B-3
0.560 0.676 0.791 0.907 H2003B-3
0.814 0.983 1.15 1.32 H2004B-3
1.20 1.45 1.71 1.96 H2005B-3
1.79 2.16 2.53 2.90 H2006B-3
2.15 2.60 3.04 3.49 H2007B-3
3.23 3.90 4.56 5.23 H2008B-3
4.55 5.50 6.45 7.40 H2009B-3
6.75 8.17 9.58 11.0 H2010B-3
9.14 10.8 12.4 14.0 H2011B-3
14.0 16.9 19.9 22.8 H2012B-3
18.7 22.7 26.7 30.7 H2013B-3
23.5 28.5 33.5 38.5 H2014B-3
For Use with NEMA Size 2—Series B
75A 29.0 34.0 39.1 44.1 H2015B-3
39.6 45.5 51.5 57.4 H2016B-3
53.9 60.9 67.9 74.9 H2017B-3
For Use with NEMA Sizes 3–4—Series A
105A or 144A 8.0 9.2 10.3 11.5 H2025-3
11.4 12.8 14.3 15.7 H2026-3
14.3 15.7 17.4 19.0 H2027-3
18.0 20.2 22.3 24.5 H2018-3
24.6 27.6 30.5 33.4 H2019-3
33.5 37.5 41.5 45.6 H2020-3
45.7 51.2 56.7 62.1 H2021-3
62.2 69.7 77.1 84.6 H2022-3
84.7 95.0 105.0 115.0 H2023-3
106.0 118.0 131.0 144.0 H2024-3
For Use with Size 5 Starters—Series B
32A 249 59 69 79 H2004B-3
72 87 103 118 H2005B-3
107 130 152 174 H2006B-3
129 156 182 209 H2007B-3
194 234 274 H2008B-3
For Use with Size 6 Starters Only—Series B
32A 2144 174 205 235 H2005B-3
215 259 304 348 H2006B-3
258 312 365 419 H2007B-3
388 468 547 627 H2008B-3
For Use with Size 7 Starters Only—Series B
32A 2163 197 230 264 H2004B-3
240 290 342 392 H2005B-3
358 432 506 580 H2006B-3
430 520 608 698 H2007B-3
646 780 912 H2008B-3
For Use with Size 8 Starters Only—Series B
32A 2244 295 345 396 H2004B-3
360 435 513 588 H2005B-3
537 648 759 870 H2006B-3
645 780 912 1047 H2007B-3
969 1170 1368 H2008B-3
V10-T15-8 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
DC Magnet Coils
When Ordering Specify
Conversion Kit for Field
Assembly
Catalog number
Factory Installed DC Coil
For factory installed DC
magnet coil on AC
contactors or non-
combination starters (open
type only), substitute the
code suffix from table
below for the magnet coil
identifier in the device
catalog number.
Example: For Size 0 AC
contactor with a 24 Vdc
coil, change CN15BN3AC
to CN15BN3T1C
Application
Connect for separate
control
Not for use with cover
control switch operators
Use twin break, heavy-duty
pilot devices
Designed for +10%, –20%
rated voltage, continuous
duty operation
Non-Reversing Kit Consists of:
One encapsulated DC
magnet coil
One NCI or NO/NCI side-
mounted auxiliary contact
Note: These kits are supplied
with a NO/NCI side-mounted
auxiliary contact in place of the
NCI contact.
Two blue colored
connection wires
One instruction publication
Operation
These DC coil kits have
separate pickup and seal
windings. A special (side-
mounted) early-break NCI
auxiliary contact is used to
either disconnect the pickup
winding or insert the seal
winding in series with the
pickup winding, depending on
the frame size of the
contactor. DC coil kits come
in two styles, a suffix 1 and a
suffix 4. The 1 suffix contains
only the special (side-
mounted) early break NCI
auxiliary contact. The 4 suffix
contains a NO contact in the
same package as the special
(side-mounted) early-break
NCI auxiliary contact.
Note: NEMA Sizes 00 and 0
contactors may use either suffix 1
or 4 DC coil kits; starters
may use suffix 4 DC coil kits only.
For NEMA Sizes 1 and 2, both
contactors and starters may use a
suffix 4 DC coil kit only.
On the above sizes only,
when the special auxiliary
package is mounted on the
side of a contactor or starter,
no standard auxiliary contact
may be mounted on the
same side.
Note: For NEMA Sizes 3–5, the
special coil NCI clearing contact is
an add-on auxiliary (must mount
on a base mount auxiliary
contact; normally a 1NO). This
arrangement will normally account
for two of the three contact
positions on the side of each
contactor or starter.
See figure on Page
V10-T15-9.
Product Selection
Note
1These kits are supplied with a NO/NCI side-mounted auxiliary contact in place of the NCI contact.
Contactor or
Starter Size
Conversion Data
Factory Installed Complete Conversion Kit
Volts
Magnet Coil NCI
Interlock
NumberNEMA
Coil
Number
Amps
P.U./Seal
Watts
P.U./Seal
Code
Suffix
Ship Wt.
Lbs (kg) Catalog Number
Non-Reversing—Kit includes NCI Side-Mounted Auxiliary Contact
00 and 0
CN35–A, B, D
D15 relays
12 9-2988-11 6.4/0.28 76.8/3.36 C320KGD1 R1 1.0 (0.5) C335KD3R1
24 9-2988-12 3.2/0.14 76.8/3.36 C320KGD1 T1 C335KD3T1
48 9-2988-13 1.6/0.07 76.8/3.36 C320KGD1 W1 C335KD3W1
120 9-2988-14 0.64/0.028 76.8/3.36 C320KGD1 A1 C335KD3A1
1
00 and 0
CN35–A, B, D
D15 relays
12 9-2988-11 6.4/0.28 76.8/3.36 C320KGD2 1R4 1.0 (0.5) C335KD3R4
24 9-2988-12 3.2/0.14 76.8/3.36 C320KGD2 1T4 C335KD3T4
48 9-2988-13 1.6/0.07 76.8/3.36 C320KGD2 1W4 C335KD3W4
120 9-2988-14 0.64/0.028 76.8/3.36 C320KGD2 1A4 C335KD3A4
1 and 2
CN35–G
12 9-2990-1 15.4/0.42 185/4.98 C320KGD5 R4 1.0 (0.5) C335KD4R4
24 9-2990-2 7.7/0.21 185/4.96 C320KGD5 T4 C335KD4T4
48 9-2990-3 3.9/0.11 185/5.04 C320KGD5 W4 C335KD4W4
120 9-2990-4 1.5/0.041 185/4.87 C320KGD5 A4 C335KD4A4
3
CN35–K
12 9-3002-1 24/0.40 293/4.84 C320KGD3 R1 2.0 (0.9) C335KD5R1
24 9-3002-2 12/0.20 288/4.75 C320KGD3 T1 C335KD5T1
48 9-3002-3 6.1/0.097 295/4.67 C320KGD3 W1 C335KD5W1
120 9-3002-4 2.5/0.038 298/4.57 C320KGD3 A1 C335KD5A1
4 and 5
CN35–N, S
24 9-2026-4 18/0.22 400/5.3 C320KGD3 T1B 2.5 (1.1) C335KA3T1
48 9-2026-3 9/0.11 400/5.2 C320KGD3 W1B C335KA3W1
120 9-2026-2 3.3/0.05 450/5.4 C320KGD3 A1B C335KA3A1
240 9-2026-1 1.7/0.02 440/4.9 C320KGD3 B1B C335KA3B1
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-9
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Product Selection, continued
Elementary Diagrams
Notes
1Factory installed DC coils on NEMA contactors and starters include a NO/NC top-mounted auxiliary contact on each contactor for electrical interlocking.
2Kit does not include mechanical interlock or crossover wiring. Two NO/NCI top-mounted auxiliary contacts are supplied for electrical interlocking.
3Available factory assembled only.
41NO available in suffix 4 kits only.
Contactor or
Starter Size
Conversion Data
Factory Installed Complete Conversion Kit
Volts
Magnet Coil NCI
Interlock
NumberNEMA
Coil
Number
Amps
P.U./Seal
Watts
P.U./Seal
Code
Suffix
Ship Wt.
Lbs (kg) Catalog Number
Reversing
00 and 0
CN35–A, B, D
D15 relays
12 9-2988-1 6.4/0.28 76.8/3.36 C320KGD1 R1 11.0 (0.9) C335KD3R1 2
24 9-2988-2 3.2/0.14 76.8/3.36 C320KGD1 T1 1C335KD3T1 2
48 9-2988-3 1.6/0.07 76.8/3.36 C320KGD1 W1 1C335KD3W1 2
120 9-2988-4 0.64/0.028 76.8/3.36 C320KGD1 A1 1C335KD3A1 2
1 and 2
CN35–G
12 9-2990-1 15.4/0.42 185/4.98 C320KGD3 R1 13
24 9-2990-2 7.7/0.21 185/4.96 C320KGD3 T1 13
48 9-2990-3 3.9/0.11 185/5.04 C320KGD3 W1 13
120 9-2990-4 1.5/0.041 185/4.87 C320KGD3 A1 13
Auxiliary
Contact
Important
Incoming DC Must
Be Connected
Between A1 and
Top A2 Terminal
A1 A2 A1 A2 Top
A2 Bottom
3
NCI
NO d
d
3
2
3
NCI
NO
2
Hold Pickup
Hold
Pickup
DC Coil Elementary Diagram
for NEMA Sizes 1–3
Contactors and Starters
DC Coil Elementary Diagram
for NEMA Sizes 00, 0, 4 and 5
Contactors and Starters
V10-T15-10 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Remote Reset Module (32A Overload Relay)
The C316RR remote reset
module for the C316F, C316S
and C316U overload relays
allows remote resetting of
tripped (32A) overload relays
by means of an electrical
solenoid attachment that
mounts on the side of the
overload relay.
Product Selection
Dimensions
Approximate Dimensions in Inches (mm)
Note: The operating coil is not suitable for a continuous duty. Recommended
impulse duration 0.2–0.35 seconds with 15 operations maximum per hour.
Remote Reset Module
Remote Reset
Module Operating
Voltage
Catalog
Number
24V 50/60 Hz C316RR1U
110V 50/60 Hz C316RR1A
3.06
(77.7)
2.62
(66.5)
1.71
(43.5)
0.96
(24.5)
0.47
(12.0)
1.97
(50.1)
2.51
(63.7)
3.08
(78.3)
3.89
(98.7)
1.48
(37.7)
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-11
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Three-Pole Top-Mounted Fuse Block Kit
NEMA Sizes 00–2
Field mount to Freedom Series
starters and contactors.
Designed to save space and
reduce installation costs.
They provide short-circuit
protection for branch circuits.
Mounted Fuse Block Kit
Fuse Block Kits
Dimensions
Approximate Dimensions in Inches (mm)
Mounted Fuse Block
Note
1Type M fuse block not approved for branch circuit protection.
Fuse Type Catalog Number Fuse Type Catalog Number
Class H 30A 250V C350KH21 Class T 60A 300V C350KT32
Class R 30A 250V C350KR21 Class J 30A 600V C350KJ61
Class G 15A 300V C350KG37 Class J 60A 600V C350KJ62
Class G 20A 300V C350KG38 Type M 30A 600V 1C350KM61
Class G 30A 300V C350KG31 Class CC 30A 600V C350KC63
Class G 60A 300V C350KG32 Class T 30A 600V C350KT61
Class T 30A 300V C350KT31 Class T 60A 600V C350KT62
Fuse Block
Class Amperes Volts Wide A High B Deep C D
G 15, 20, 30 300 2.40 (61.0) 3.00 (76.2) 2.04 (51.8)
60 300 2.62 (66.5) 4.25 (108.0) 2.08 (52.8)
H 30 250 3.00 (76.2) 3.10 (78.7) 2.23 (56.6) 3.62 (91.9)
J 30, 60 600 4.81 (122.2) 4.12 (104.6) 2.82 (71.6)
M, CC 30 600 2.40 (61.0) 3.00 (76.2) 2.04 (51.8)
R 30 250 3.00 (76.2) 3.10 (78.7) 2.23 (56.6) 3.62 (91.9)
T 30, 60 300 3.44 (87.4) 3.00 (76.2) 2.33 (59.2)
30 600 3.75 (95.3) 3.31 (84.1) 2.26 (57.4)
60 600 4.87 (123.7) 3.00 (76.2) 2.58 (65.5)
Fuse Block Kit
A C
Mounting
Plate
D
B
V10-T15-12 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Mechanical Interlock and Reversing Kits
Mechanical interlocks and
reversing kits are designed
for field assembly of
reversing contactors or
starters from Freedom Series
components. The reversing
kits include a mechanical
interlock, stabilizer bar and
a pre-cut, trimmed and
formed wire set. Auxiliary
contacts, if required, must be
ordered separately. See
Page V10-T15-2.
Mechanical Interlock Only 12
Reversing Kits (Horizontal Contactor Mounting Only)
Application
Catalog Number
NEMA
Size
Contactor
Mounting
00–2 Horizontal C321KM60B
3 Horizontal C321KM30
3 to 4 Horizontal C321KM43
4 Horizontal C321KM40
4 to 5 Horizontal C321KM45
4 to 6 Horizontal C321KM80
5 Horizontal C321KM50
5 to 6 Horizontal C321KM56
6 Horizontal C321KM70
6 to 7 Horizontal C321KM90
7 Horizontal C321KM34
4 or 5 to 6 Vertical C321KM55
5 to 6 Vertical C321KM65
6 Vertical C321KM66
6 to 7 Vertical C321KM67
Application
Catalog Number
Application
Catalog NumberNEMA Size NEMA Size
00 C321KM60K14B C321KM60K21 3
0C321KM60K13B C321KM60K18 3
1C321KM60K15B 4C321KM60K19 3
2C321KM60K16B 5C321KM60K20 3
3C321KM60K17 3C321KM60K44 3
Mechanical Interlock
Solid-State Timers
Solid-State ON DELAY Timer—Side-Mounted on Freedom Series
NEMA 00–2 and C25D, C25E and C25F Frame
This timer is designed to be
wired in series with the
load (typically a coil). When
the START button is pushed
(power applied to timer), the
ON DELAY timing function
starts. At the completion of
the set timing period, timer
and series wired load will
both be energized.
Mounted Timer Product Selection
Pneumatic Timers—Top-Mounted
Attachment mounts on top
of any NEMA Size 00–2
Freedom Series starter or
contactor (top-mounted
auxiliary contacts can not be
installed on device when timer
is used). Timer unit has 1NO-
1NC isolated timed contacts—
circuits in each pole must be
the same polarity. Units are
convertible from OFF to ON
DELAY or vice-versa.
Product Selection
Maximum Ampere Ratings
Notes
1Without cross-wiring.
2For use with latest series product.
3Kit includes two NC auxiliary contacts.
4Add operating voltage suffix to catalog number. A = 120V, B = 240V, E = 208V.
5Rated 0.5A pilot duty—not to be used on larger contactors.
6Terminal connections are quick connects only. Two per side.
Timing Range Catalog Number 456
0.1–1.0 seconds C320TDN1_
1–30 seconds C320TDN30_
30–300 seconds C320TDN300_
5–30 minutes C320TDN2000_
Solid-State Timer
Timing Range Catalog Number
0.1–30 seconds C320TP1
10–180 seconds C320TP2
Description
Volts AC
120 240 480 600
Make 30 15 7.5 6
Break 3 1.5 0.75 0.6
Pneumatic Timer
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-13
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Locking Cover for Overload Relay—C306 Only
Snap-on transparent or
opaque plastic panel for
covering access port to the
overload relay trip setting
dial—helps prevent accidental
or unauthorized changes to
trip and reset setting.
Product Selection
Control Circuit Fuse Block
These panel mounted fuse
holders, designed for control
circuit protection or other
similar low current
requirements, have extractor
type fuse caps. The Class CC
rejection type fuses (KTK-R)
used in these holders are
intended for use with
equipment designated as
being suitable for use on
systems having high available
fault currents. If branch circuit
protective device is 45A or
greater, C320FBR fuse kit
may be required for control
circuit protection per NEC
430-72.
Product Selection
Dimensions
Approximate Dimensions in Inches (mm)
Control Circuit Fuse Block
Description
Minimum
Ordering Qty.
(Std. Pkg.)
Catalog
Number
Clear cover, no accessibility 50 C320PC3
Gray cover, no accessibility,
with auto only nib
50 C320PC4
Gray cover, no accessibility,
with manual only nib
50 C320PC5
Gray cover with FLA dial
accessibility, A, B, C, D positions
and auto only nib
50 C320PC6
Gray cover with FLA dial
accessibility, A, B, C, D
positions and manual only nib
50 C320PC7
Locking Cover
Type
Maximum
Amperes Catalog Number
Fuse holder only 15 C320FB 1
30 C320FBR 2
Control Circuit Fuse
Block
0.97
(24.6)
1.25 (31.8)
1.88 (47.8)
1.19
(30.2)
0.88
(22.4)
2.06
(52.3)
Fuse
Transient Suppressor Kits
NEMA Sizes 00–2
These kits limit high voltage
transients produced in the
control circuit when power is
removed from the contactor
or starter coil. There are three
separate suppressors for use
on 24–120V, 208–240V or
277–480V coils respectively.
These devices mount directly
to the coil terminals of
Freedom Series contactors or
starters NEMA Sizes 00–2
and lighting contactors 10–
60A. Reversing devices will
require two.
Product Selection
NEMA Sizes 3–5
This device mounts on top
of any side-mounted auxiliary
contact on Freedom Series
NEMA Sizes 3–5 and lighting
contactors 100–300A. It
connects across coil
terminals on any 120V
contactor or starter magnet
coil (reversing starters or
contactors require 2).
Limits high voltage transients
produced in the circuit when
power is removed from the
coil.
Product Selection
Shorting Bar Kits
These kits provide phase-to-
phase power connections of
contactors for field assembly.
The kits include bus
connections and mounting
hardware. The shorting bars
connect all three phases of a
single contactor.
Product Selection
Notes
1A fuse is not supplied, but holder will accept a Bussman Type KTK or KTK-R
(13/32 in x 1-1/2 in) fuse, 600V maximum.
2Includes a 5A, 600V KTK-R fuse.
3Suppressor is compatible with coil voltages/ranges as shown, 50 and 60 Hz.
Description
Coil Voltage
50/60 Hz 3Catalog Number
Transient suppressor 24–120V C320TS1
208–240V C320TS2
277–480V C320TS3
Transient Suppressor
NEMA Sizes 00–2
Description Coil Voltage Catalog Number
Transient suppressor 120V C320AS1
Transient Suppressor
NEMA Sizes 3–5
Description Catalog Number Description Catalog Number
NEMA Size 3 C321SB18 NEMA Size 5 C321SB21
NEMA Size 4 C321SB19 NEMA Size 6 C321SB22
V10-T15-14 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
DC/AC Interface Module
The catalog number C320DC
Interface Module is an
optically isolated solid-state
switch which provides a
means of operating AC coils
with 5–48 Vdc control signal.
It acts as a space saving
interposing relay which can
switch a specified 50/60 Hz
AC source to the contactor or
starter coil.
The module may be directly
attached to the coil terminals
of any Freedom Series
contactor or starter—NEMA
Sizes 00–3 and lighting
contactors 10–100A. It also
has provisions for DIN rail
mounting.
The module will operate coils
within the voltage ranges
shown in the table below.
Design Characteristics
DC Input: 5–48 Vdc at mA
nominal
AC operating voltage:
240 Vac (360 VA) ±10% 50/
60 Hz
DC operating voltage:
30 Vdc maximum (0.5A)
AC current rating
10A make (inrush)
1A break (sealed)
Controller Coil Voltage Ranges
Typical Application
Product Selection
Controller Catalog
Number Prefix
Controller
Size or Rating
Coil Range
Volts AC
AN16, AN56, CN15, CN55 00–0 24–240
1–2 48–240
3 110–240
CN35 10–30A 24–240
60A 48–240
100A 110–240
Coil Voltage Catalog Number
5 Vdc C320DC2V5
6 Vdc C320DC2V6
9 Vdc C320DC2V9
12 Vdc C320DC2V12
48 Vdc C320DC2V48
DC/AC Interface
Module
Finger Protection Shields
Snap-on shields for both
contactors and starters
provide Type IP20 finger
protection. Prevents
accidental contact with line/
load terminals.
Product Selection
Adapter to DIN Rail Mount
NEMA 1–2 Contactors
Designed to allow DIN rail
mounting of NEMA 1–2
contactors. Includes
all hardware required to
convert contactors from
panel mounting to 35 mm
DIN rail mounting.
Product Selection
Adhesive Dust Cover
NEMA Sizes 00–2
These adhesive stickers
come 25 to a package and
provide extra protection
from
contaminants when applied to
the
sides of Freedom NEMA
Sizes 00–2.
Adhesive covers are easily
applied to side opening
where auxiliaries are not
installed and provide extra
protection from metal filings
and other debris.
Product Selection
Application Catalog Number
NEMA Size 00 C320LS1
NEMA Size 0 C320LS2
NEMA Sizes 1–2
Contactors C320LS3
Reversing contactors C320LS4
NEMA Size 1
Starters C320LS5
Reversing starters C320LS6
NEMA Size 2
Starters C320LS7
Reversing starters C320LS8
Description
Catalog
Number
Adapter to DIN rail mount C320DN65
Description Catalog Number
25 to a package C320DSTCVR
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Add-On Power Pole Kit
NEMA Sizes 00–2
This device mounts on the side of Freedom NEMA Size 00–2 contactors. One unit can be mounted
on each side and carries UL, cUL and IEC ratings. The device is rated for resistive, inductive and
lighting applications.
Product Selection—Add-On Power Pole Kit
Fuse Clips
C351—Fuse Clip Selection—Three Poles
Notes
1 These fuse clips are for Class R fuses.
2 Fuse clip “R” rejection members for use with Class R fuses are supplied loose in the fuse clip kits.
Kits do not include fuses.
UL Ampere Rating IEC 947 Ampere Rating
1NO
Power Pole
Catalog Number
Inductive
600V
Resistive
600V
hp
Single-Phase Locked
Rotor
240V
Lighting Ballast
Tungsten
480V
AC-1
600V
AC-3
600V
AC-5a
AC-5b
480V115V 230V
15 20 1/2 2 96 20 20 12 18 C320PPD10
Starter
Size
Motor
Voltage
Maximum hp
(Three-Phase)
Fuse Clip
Rating
Fuse Clip Kit
Factory Installed
Fuse Clip Kit for Field Installation in Non-Fusible Starter
For Non-Rejection
Type Fuses
For Use with
“R” Rejection Type Fuses
Dual Element
Fuses Amperes Volts
Position 10
Alpha 1Catalog Number Catalog Number
Non-Fusible—without Fuse Clips Installed A
0 200/230 3 30 250 B C351KC21 C351KC21R
460/575 5 30 600 C C351KD22-61 C351KD22-61R
1 200/230 7-1/2 30 250 B C351KC21 C351KC21R
460/575 10 30 600 C C351KD22-61 C351KD22-61R
2 200 10 60 250 D C351KD22-61 C351KD22-61R
230 15 60 250 D C351KD22-61 C351KD22-61R
460/575 25 60 600 E C351KD62 C351KD62R
3 200 25 100 250 F C351KE23-63 2C351KE23-63 2
230 30 100 250 F C351KE23-63 2C351KE23-63 2
460/575 50 100 600 G C351KE23-63 2C351KE23-63 2
4 200 40 200 250 H C351KF24-64 2C351KF24-64 2
230 50 200 250 H C351KF24-64 2C351KF24-64 2
460/575 100 200 600 J C351KF24-64 2C351KF24-64 2
5 200 75 400 250 KNot available in kit form Not available in kit form
230 100 400 250 K
460/575 200 400 600 L
C351 Fuse Clip Kit
V10-T15-16 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Control Power Transformer Kits
These control transformer
kits provide a convenient on-
the-job addition of control
transformers to the following
Type 1, 3R, 4/4X and 12
enclosed starters. Adding or
changing these kits does not
affect the UL listing in most
instances.
The transformer kit consists of:
Control transformer
Two primary and one
secondary fuse
Wires
Mounting instruction
publication
For Non-Combination Starters
These kits may be used for
transformer voltage
conversion on Freedom
NEMA starters furnished
from the factory with control
transformers installed. Non-
combination starters with
CPTs factory installed are
Class ECN07, ECA07, ECE07
and ECE11. These kits may
also be installed in oversize
enclosures that have been
designed to accept
transformers.
Combination Starters
Most combination starters
have space for standard size
(and 100 VA extra capacity)
control power transformers.
The panels are pre-drilled for
mounting.
UL/CSA
UL Listed—File Number
E10156, Guide XPTO.
When Ordering Specify
Catalog number
Standard Transformer Sizes 1
Control Transformer Kits
Note
1 Non-reversing, single contactor only.
Size
VA Capacity
Freedom Vacuum
050
1, 2 100
3 150
4 200 100
5 200 150
6 250 350
Continuous
VA
Primary 208/277V
Secondary 120V, 60 Hz
Primary 240/480V, 60 Hz
220/440V, 50 Hz
Secondary 120V, 60 Hz
110V, 50 Hz
Primary 380V
Secondary 110V, 50 Hz
Primary 600V, 60 Hz
550V, 50 Hz
Secondary 120V, 60 Hz
110V, 50 Hz
Primary 240/480V
Secondary 24V, 60 Hz
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
50 C341AE C341AC C341AL C341AD C341AS
75 C341BE C341BC C341BL C341BD C341BS
100 C341CE C341CC C341CL C341CD C341CS
150 C341DE C341DC C341DL C341DD C341DS
200 C341EE C341EC C341EL C341ED C341ES
250 C341FE C341FC C341FL C341FD C341FS
300 C341GE C341GC C341GL C341GD C341GS
350 C341HE C341HC C341HL C341HD C341HS
500 C341JE C341JC C341JL C341JD C341JS
Control Transformer Kit
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-17
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Dimensions
Approximate Dimensions in Inches (mm)
Open Type—50–500 VA with Fuse Block
Continuous
VA
Wide
A
High
B
Deep
C
Mounting Ship Wt.
Lbs (kg)D E Slots
50 3.00 (76.2) 3.00 (76.2) 2.56 (65.0) 2.00 (50.8) 2.50 (63.5) 0.203 x 0.375 (5.2 x 9.5) 3.0 (1.4)
75 3.50 (88.9) 3.00 (76.2) 2.56 (65.0) 2.50 (63.5) 2.50 (63.5) 0.203 x 0.375 (5.2 x 9.5) 4.3 (2.0)
100 3.38 (85.9) 3.38 (85.9) 2.88 (73.2) 2.38 (60.5) 2.81 (71.4) 0.203 x 0.375 (5.2 x 9.5) 4.6 (2.1)
150 4.00 (101.6) 3.75 (95.3) 3.18 (80.8) 2.88 (73.2) 3.12 (79.2) 0.203 x 0.375 (5.2 x 9.5) 7.0 (3.2)
200 4.00 (101.6) 4.50 (114.3) 3.81 (96.8) 2.50 (63.5) 3.75 (95.3) 0.203 x 0.375 (5.2 x 9.5) 7.7 (3.5)
250 4.38 (111.3) 4.50 (114.3) 3.81 (96.8) 2.88 (73.2) 3.75 (95.3) 0.203 x 0.375 (5.2 x 9.5) 10.0 (4.5)
300 4.75 (120.7) 4.50 (114.3) 3.81 (96.8) 3.25 (82.6) 3.75 (95.3) 0.203 x 0.375 (5.2 x 9.5) 13.0 (5.9)
350 5.25 (133.4) 4.50 (114.3) 3.81 (96.8) 3.75 (95.3) 3.75 (95.3) 0.203 x 0.375 (5.2 x 9.5) 14.0 (6.4)
500 5.50 (139.7) 5.25 (133.4) 4.75 (120.7) 4.25 (108.0) 4.38 (111.3) 0.312 x 0.688 (7.9 x 17.5) 18.0 (8.2)
Top View Side View
1.38
(35.1)
D A
EC
B
V10-T15-18 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
A200 NEMA
Factory Modifications
A200 Factory Modifications
Type J Auxiliary Contact
Capable of being field
mounted in a contactor or
starter (Classes A200,
A900 Sizes 00–6, V200,
V201 vacuum and definite
purpose controllers)
Provides two separate
electrical contact sets
which wire vertically and
are color coded; black
designates NC and silver
designates NO. Please
note that the vertical wiring
is contrary to the horizontal
wiring of the L-56 auxiliary
contacts
Designed to fit within
dimensions of starter; no
additional panel space is
required
Provides circuit isolation
(no polarity restrictions)
and single break bifurcated
contacts
Auxiliary Contact Ratings
Auxiliary Contact Types
Modification Description
NEMA Size Catalog
Number
Suffix00123456789
Control circuit 1 Extra auxiliary contact (1NO-1NC) J1
Non-reversing, reversing
Two-speed unwired
2 Extra auxiliary contact J2
Non-reversing
Reversing, two-speed unwired
3 Extra auxiliary contact J3
Non-reversing, unwired —————
4 Extra auxiliary contact J4
Non-reversing, unwired —————
Wired for separate control (NC) —————————C
Omit control wiring (NC) X
Overload relays
(substitutions)
Ambient compensated with auto reset (NC) —————————D
Fast trip—ambient compensated
(specify motor FLA)
———D7
Overload relay alarm contact (NO) per overload ———E
Voltage Make Break
NEMA A600
120–600 Vac 7200 VA 720 VA
72–120 Vac 60A 720 VA
28–72 Vac 60 VA 10A
NEMA R300
28–300 Vdc 28 VA 28 VA
Contact
Type Maximum Catalog Number
1NO and 1NC 4 J11
2NC 4 J02
2NO 4 J20
1 coil clearing
NC and 1NO
4J1C
Auxiliary Contact
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-19
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Heater Selection
General Information on Heater Coil Selection
For maximum motor
protection and compliance
with Article 430-32 of the
National Electrical Code,
select heater coils from the
tables in this section on the
basis of motor nameplate full
load current.
When the full load current is
unknown, selection may be
made on the basis of average
full load currents. Caution—
The average ratings could
be high or low for a specific
motor and therefore
selection on this basis
always involves risk. For
fully reliable motor
protection, select heater
coils on the basis of full
load current rating as
shown on the motor
nameplate.
Heater coils are rated to
protect 40°C rise motors, and
open and drip-proof motors
having a service factor of
1.15 where the motor and the
controller are at the same
ambient temperature.
For other conditions:
1. For 50°C, 55°C, 75°C rise
motors and enclosed
motors having a service
factor of 1.0, select one
size smaller coil.
2. Ambient temperature of
controller lower than
motor by 26°C (47°F),
use one size smaller coil.
3. Ambient temperature of
controller higher than
motor by 26°C (47°F),
use one size larger coil.
Ultimate tripping current of
heater coils is approximately
1.25 times the minimum
current rating listed in the
tables.
Heater Selection—Type A and B Overload Relays, Sizes 3 and 4
Heater Selection—Type A and B Overload Relays, Sizes 5 and 6
Note
Size 7 and larger—advise full load current.
Size
Starter
Ambient
Compensated
Enclosed Starters
Non-Compensating
Enclosed Starters Heater
(One Heater per
Catalog Number) Size
Starter
Ambient
Compensated
Enclosed Starters
Non-Compensating
Enclosed Starters Heater
(One Heater per
Catalog Number)All Applications All Applications
Full Load Current of Motor Amps Catalog Number Full Load Current of Motor Amps Catalog Number
12.8–14.1 11.9–13.0 FH68 51–55 47–51 FH82
14.2–15.5 13.1–14.3 FH69 56–61 52–56 FH83
15.6–17.1 14.4–15.9 FH70 62–66 57–61 FH84
17.2–18.9 16.0–17.4 FH71 67–73 62–67 FH85
19.0–20.8 17.5–19.1 FH72 74–78 68–72 FH86
20.9–22.9 19.2–21.1 FH73 79–84 73–77 FH87
23.0–25.2 21.2–23.2 FH74 85–92 78–84 FH88
25.3–27.8 23.3–25.6 FH75 93–101 85–91 FH89
27.9–30.6 25.7–28.1 FH76 102–110 92–99 FH90
30.7–33.5 28.2–30.8 FH77 111–122 100–110 FH91
33.6–37.5 30.9–34.5 FH78 123–129 111–122 FH92
37.6–41.5 34.6–38.2 FH79 130–133 123–128 FH93
41.6–56.3 38.3–42.6 FH80 129–133 FH94
46.4–50 42.7–46 FH81
Compensated Overload Relay Heater (One Heater
per Catalog Number)
Compensated Overload Relay Heater (One Heater
per Catalog Number)Open Starter Enclosed Starter Open Starter Enclosed Starter
Full Load Current of Motor (Amps) Catalog Number Full Load Current of Motor (Amps) Catalog Number
Size 5 (with 300/5 Current Transformers) Size 6 (with 600/5 Current Transformers)
—— FH23 —— FH23
118–129 118–129 FH24 236–259 236–259 FH24
130–141 130–141 FH25 260–283 260–283 FH25
142–155 142–155 FH26 284–310 284–310 FH26
156–170 156–170 FH27 311–340 311–340 FH27
171–187 171–187 FH28 341–374 341–374 FH28
188–205 188–205 FH29 375–411 375–411 FH29
206–224 206–224 FH30 412–448 412–448 FH30
225–244 225–244 FH31 449–489 449–489 FH31
245–263 245–263 FH32 490–527 490–527 FH32
264–292 264–292 FH33 528–585 528–540 FH33
293–300 FH34 586–600 FH34
For Size 4 Starters
For Size 3 Starters
For Size 4 Starters
For Size 3 Starters
V10-T15-20 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Heater Selection—Type A and B Overload Relays, Sizes 0, 1 and 2
Size
Starter
Non-Compensated Open Starters and
Ambient Comp. Open and Enclosed Starters Heater
(One Heater
per Catalog Number)
Non-Compensating
Enclosed Starters
Heater
Block Type Overload
Using Three Heaters
Single-Pole
Type Overload
Block Type Overload
Using Three Heaters
Single-Pole
Type Overload
Full Load Current of Motor (Amps) Catalog Number Full Load Current of Motor (Amps) Catalog Number
0.25–0.27 0.29–0.31 FH03 0.24–0.25 0.28–0.30 FH03
0.28–0.31 0.32–0.35 FH04 0.26–0.28 0.31–0.34 FH04
0.32–0.34 0.36–0.39 FH05 0.29–0.31 0.35–0.37 FH05
0.35–0.38 0.44–0.48 FH06 0.32–0.35 0.38–0.42 FH06
0.39–0.42 0.44–0.48 FH07 0.36–0.39 0.43–0.47 FH07
0.43–0.46 0.49–0.53 FH08 0.40–0.43 0.48–0.52 FH08
0.47–0.50 0.54–0.58 FH09 0.44–0.47 0.53–0.56 FH09
0.51–0.55 0.59–0.64 FH10 0.48–0.51 0.57–0.63 FH10
0.56–0.62 0.65–0.71 FH11 0.52–0.57 0.64–0.70 FH11
0.63–0.68 0.72–0.79 FH12 0.58–0.63 0.71–0.77 FH12
0.69–0.75 0.80–0.87 FH13 0.64–0.70 0.78–0.85 FH13
0.76–0.83 0.88–0.96 FH14 0.71–0.77 0.86–0.94 FH14
0.84–0.91 0.97–1.06 FH15 0.78–0.85 0.95–1.03 FH15
0.92–1.00 1.07–1.16 FH16 0.86–0.93 1.04–1.13 FH16
1.01–1.11 1.17–1.28 FH17 0.94–1.03 1.14–1.25 FH17
1.12–1.22 1.29–1.41 FH18 1.04–1.13 1.26–1.38 FH18
1.23–1.34 1.42–1.55 FH19 1.14–1.25 1.39–1.52 FH19
1.35–1.47 1.56–1.71 FH20 1.26–1.37 1.53–1.67 FH20
1.48–1.62 1.72–1.87 FH21 1.38–1.51 1.68–1.83 FH21
1.63–1.78 1.88–2.06 FH22 1.52–1.65 1.84–2.01 FH22
1.79–1.95 2.07–2.26 FH23 1.66–1.81 2.02–2.21 FH23
1.96–2.15 2.27–2.48 FH24 1.82–1.99 2.22–2.43 FH24
2.16–2.35 2.49–2.72 FH25 2.00–2.19 2.44–2.66 FH25
2.36–2.58 2.73–2.99 FH26 2.20–2.39 2.67–2.92 FH26
2.59–2.83 3.00–3.28 FH27 2.40–2.63 2.93–3.21 FH27
2.84–3.11 3.29–3.60 FH28 2.64–2.89 3.22–3.53 FH28
3.12–3.42 3.61–3.95 FH29 2.90–3.17 3.54–3.87 FH29
3.43–3.73 3.96–4.31 FH30 3.18–3.47 3.88–4.22 FH30
3.74–4.07 4.32–4.71 FH31 3.48–3.79 4.23–4.61 FH31
4.08–4.39 4.72–5.14 FH32 3.80–4.11 4.62–4.9 FH32
4.40–4.87 5.15–5.6 FH33 4.12–4.55 5.0–5.5 FH33
4.88–5.3 5.7–6.2 FH34 4.56–5.0 5.6–6.0 FH34
5.4–5.9 6.3–6.8 FH35 5.1–5.5 6.1–6.6 FH35
6.0–6.4 6.9–7.5 FH36 5.6–5.9 6.7–7.3 FH36
6.5–7.1 7.6–8.2 FH37 6.0–6.6 7.4–8.0 FH37
7.2–.78 8.3–9.0 FH38 6.7–7.2 8.1–8.7 FH38
7.9–8.5 9.1–9.9 FH39 7.3–7.9 8.8–9.7 FH39
8.6–9.4 10.0–10.8 FH40 8.0–8.7 9.8–10.5 FH40
9.5–10.3 10.9–11.9 FH41 8.8–9.5 10.6–11.7 FH41
10.4–11.3 12.0–13.1 FH42 9.6–10.5 11.8–12.7 FH42
11.4–12.4 13.2–14.3 FH43 10.6–11.5 12.8–14.0 FH43
12.5–13.5 14.4–15.7 FH44 11.6–12.6 14.1–15.3 FH44
13.6–14.9 15.8–17.2 FH45 12.7–13.8 15.4–16.6 FH45
15.0–16.3 17.3–18.9 FH46 13.9–15.1 16.7–18.3 FH46
16.4–18.0 19.0–20.8 FH47 15.2–16.7 18.4–20.0 FH47
18.1–19.8 20.9–22.9 FH48 16.8–18.3 20.1–21.9 FH48
19.9–21.7 23.0–25.2 FH49 18.4–20.2 22.0–23.9 FH49
21.8–23.9 25.3–27.6 FH50 20.3–22.2 24.0–26.2 FH50
24.0–26.2 27.7–30.3 FH51 22.3–24.3 26.3–28.8 FH51
26.3–28.7 30.4–33.3 FH52 24.4–26.6 28.9–31.4 FH52
28.8–31.4 33.4–36.4 FH53 26.7–29.1 31.5–34.5 FH53
31.5–34.5 36.5–39.9 FH54 29.2–32.0 34.6–37.9 FH54
34.6–37.9 40.0–43.9 FH55 32.1–35.2 3.80–41.9 FH55
38.0–41.5 FH56 35.3–38.5 42.0–45.0 FH56
41.6–45.0 FH57 38.6–42.3 FH57
For Size 2 Starters
For Size 1 Starters
For Size 0 Starters
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-21
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
SS-56 Surge Suppressor
Designed to be used with
magnetic motor controllers
through Size 4 in 120V,
60 Hz control circuit
applications where
electronic equipment
is used
Steady state coil volts: 120,
60 Hz, rms
Peak input volts:
169.6, 60 Hz, maximum
amplitude
Maximum ambient
temperature: 65°C
Nominal limiting volts:
270 peak
Nominal rate of volt rise:
0.5 per ms
Surge Suppressor 1
F-56 Fuse Block
Facilitates installation of
fuses (15A, 600V max.) in
control circuits
Utilizes Bussman type KTK
fuses, or equivalent
Mounts in same cavity as
Type J auxiliary contact
No tools or mounting
hardware needed
Fuse not included
Fuse Block
R-56 Interposing Relay
The R-56AA interposing relay
is a low energy solid-state
device with a single NO solid-
state contact. It can be used
as a 120 Vac control relay,
and will operate on as little
as 40 Vac input. Is useful in
applications requiring long
control wiring runs where
excessive voltage drop would
prevent the contactor or relay
from energizing. Will operate
a Size 4 contactor from
10,000 ft using 18 AWG wire.
Interposing Relay
Type Mounting
Kit
Catalog Number
Starter SS-56
SS-56 Surge
Suppressor
Mounting
Kit
Catalog Number
Starter F56
Panel F56-P
Type
Mounting
Kit
Catalog Number
Starter or panel R56-AA
Mechanical Interlock
Prevents closing of one
member of a reversing or
multi-speed contactor until
the opposite member is
completely open
Lever type mechanism
assures positive action
Can be factory assembled
or field mounted on A200
and A900 starters and
contactors
Mechanical Interlock
B3NO Bell Alarm Contact
Isolated normally open bell
alarm contact
Mounts in Type B block-
type overload relay
Bell Alarm Contact
Control Contact Ratings (B600)
Overload Relay Reset Extension
Used to adjust overload
reset rod depth of Class
A200 Model J starters and
current design overload
relays to same dimensions
as obsolete B200 starters
and overloads identified by
suffix B, that is BA13B
When replacing obsolete B200
device with Class A200 starter
and Type B overload, order
Style 6710C11H03. No charge.
When replacing obsolete B200
device with Class A200 starter
and Type A overload, order
Style 1490C15H10. No charge.
Notes
1Can be used on Sizes 5 and 6 with 120V coil. Mounting bracket required—order separately.
Mounting bracket 177C043G04.
2For Size 3 and 4.
Contactor Arrangement
(Number of Poles,
Horizontal or Vertical)
Continuous
Size
Interlock
Catalog Number
3 x 3 horizontal 0, 1 M-33-1B
4 x 4 horizontal 0, 1 M-33-1B
5 x 3 horizontal 0, 1 M-33-1B
All pole combination, vertical 0, 1 M-34-1A
3 x 3 horizontal reversing 2 M-33-2B
3 x 3 vertical reversing 2 M-34-2A
5 x 3 horizontal 2 M-35-2A
4 x 4 horizontal 2 M-36-2A
All pole combination horizontal 3, 4 M-33-3B
All pole combination vertical 3, 4 M-34-3
Kit
Catalog Number
B3NO-2
B3NO-4 2
AC Volts
Maximum Amperes
Make Break
24–120 30 3.00
121–600 3600 VA 360 VA
Continuous current rating: 5A
V10-T15-22 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Power Pole Kit
Adds 1NO or 1NC power
pole to Size 00–1 A201
Class contactors
Factory installed or field
mountable in load side
auxiliary cavities
600 Vac
Continuous current rating
of 18A for Size 0, 27A for
Size 1
Power Pole Kit 1
Replacement Auxiliary Contacts
Replacement Auxiliary Contacts
Extra Auxiliary Contact Kits
All starters include an
auxiliary contact with 1NO
and 1NC contact. These kits
include an auxiliary contact
with contacts as shown, plus
operating arm and mounting
bracket when required.
Extra Auxiliary Contact Kits
Continuous
Current Rating
Kit
Size
Kit
Catalog Number
Normally Open
18 0 PN0-0
27 1 PN0-1
Normally Closed
18 0 PNC-0
27 1 PNC-1
Contactor
Size
Contact
Arrangement
Aux. Elect. Contact
Catalog Number Style Number
5, 6 1NO + 1NC J11 9084A17G01
2NO J20 9084A17G02
2NC J02 9084A17G03
7, 8 1NO 578D461G01
1NC 578D461G03
9 1NO + 1NC 843D943G04
2NO 843D943G05
2NC 843D943G06
Contactor
Size
Contact
Arrangement Style Number
5, 6 1NO + 1NC 3463D94G18
2NO 3463D94G04
2NC 3463D94G19
7, 8 22NO 818D498G06
1NO 818D498G04
DC Coil Conversion Kits
Kits listed below include all
necessary parts to convert
from AC to DC control
including the DC coil with
built-in diode, rectifier,
auxiliary interlock and all
mounting hardware.
DC Coil Conversion Kits
Mechanical Interlocks
Mechanical Interlocks
Overload Protection
Overload Protection Size 5 Starters
Type B overload relay is a
three-pole, block type, thermal
ambient compensated device
with manual reset mounted
integrally. Current transformers
are enclosed in a protective
case and integrally mounted
to save panel space. Standard
ratio is 300:5.
Overload Protection Size 6 Starters
Overload protection assembly
consists of three current
transformers, Type B three-
pole block overload relay and
an optional interposing relay.
These parts are mounted on a
panel which connects directly
to the load terminal of the
contactor. Current transformers
are 600:5 ratio as standard.
If automatic reset is required,
the Type A, three-pole block,
ambient compensated relay
is available upon request.
Notes
1Do not use with DC operated contactors.
2Size 7 and larger use DC coils as standard.
Size Voltage
Kit
Style Number
5110-1207864A28G01
220-240 7864A28G02
440-480 7864A28G03
6110-1207864A29G01
220-240 7864A29G02
440-480 7864A29G03
Contactor
Sizes
Style Numbers
Horizontal Vertical
3, 4 and 5 2050A11G75 2050A11G65
5 and 5 2050A11G25 2050A11G15
5 and 6 2050A11G27 2050A11G17
6 and 6 2050A11G26 2050A11G16
6 and 7, 8 2050A11G55
7, 8 and 7, 8 No (rear conn.) 567D624G01
7, 8 and 9 No (rear conn.) 9944D56G06
9 and 9 No (rear conn.) 9944D56G01
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-23
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Overload Relay Kits
Each kit includes three
current transformers
(standard ratio) and one Type
B, three-pole block overload
relay, ambient compensated
with manual reset.
Overload Relay Kits
Replacement Terminal Lugs 1
XT IEC
Auxiliary Contacts
Front mounted snap-on
auxiliary contacts for XT
contactors are available with
screw or spring cage
terminals in a variety of
contact configurations.
The 7–32A XTCE contactors
have positively driven
contacts between the
integrated auxiliary contact
and the auxiliary contact
module as well as within the
auxiliary contact modules.
The 40–65A XTCE contactors
have positively driven
contacts within the auxiliary
contact module. Six auxiliary
contacts are possible with a
combination of side-mounted
and front-mount auxiliary
contacts.
Frame B–C contactors
with 1NC built-in auxiliary
are mirror contacts
(XTCE...B01_–XTCE...C01_).
XTCE and XTCS Auxiliary Contact Overview
Notes
1All mounting hardware is included in kit.
2Frame L–R auxiliary contacts also apply to XTCS185_–XTCS500M_ contactors.
Kit Size Kit Part Number
52057A34G01
66379D80G10
Contactor
Size
Cable
Size
Terminals
Kit
Style Number
Qty.
in Kit
Qty. Req’d.
per Pole
5 1-500 kcmil 6 2 2119A76G01
6 2-500 kcmil 6 2 7858A96G01
7 4-500 kcmil 12 4 7858A96G02
8 4-500 kcmil 12 4 7858A96G03
FrameA BCDF GLR
Catalog
numbers
XTMC6A_–
XTMC9A_
XTCE007B_–
XTCE015B_
XTCE018C_–
XTCE032C_
XTCE040D00_–
XTCE065D00_
XTCE080F00_–
XTCE095F00_
XTCE115G00_–
XTCE150G00_
XTCE185L22_–
XTCEC20R22_ 2
Contactor width 45 mm 45 mm 45 mm 55 mm 90 mm 90 mm Various
Built-in auxiliary 1NO or 1NC 1NO or 1NC 1NO or 1NC ———2NO-2NC
Contact sequence
Front- (top) mount
auxiliary
Two- and four-pole
(screw or spring cage):
Standard two- and four-pole versions
(screw or spring cage):
Tall version
(screw only):
Two-pole
(screw only):
Four-pole
(screw or spring cage):
N/A
Side-mount auxiliary N/A N/A Two-pole
(screw only):
Two-pole
(screw or spring cage):
2
35
46
A1
A2
113
14
2
35
46
A1
A2
121
22
2
35
46
A1
A2
1
2
3513 21 31
46
14 22 32
43
44
A1
A2
1
V10-T15-24 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Auxiliary Contacts
Notes
1One early-make contact (1NOE), one late-break contact (1NCL).
2To avoid duplicate terminal numbers in contact sequence, these auxiliary contacts should only be used with contactors having a built-in 1NO contact (XTCE...B10_, XTCE...C10_).
3Front- (top) mount tall version is for use with Frame B electrical wire bridges and link kits and toolless plug combination connection kits: XTCEXRLB, XTCEXSDLB, XTPAXTPCB, XTPAXTPCRB, XTPAX.
Conventional
Thermal Current,
Open at 60°C
Ith = Ie,
AC-1 in Amps Poles
Contact
Configuration Circuit Symbol
Pkg.
Qty.
Screw Terminals
Catalog Number
Spring Cage Terminals
Catalog Number
Frame B–C—Front- (Top) Mount
16 2 2NO 5 XTCEXFAC20 XTCEXFACC20
16 2 1NO-1NC 5 XTCEXFAC11 XTCEXFACC11
16 2 2NC 5 XTCEXFAC02 XTCEXFACC02
16 2 1NOE-1NCL5XTCEXFALC11 1XTCEXFALCC11 1
16 2 1NO-1NC 5 XTCEXFDC11 2XTCEXFDCC11 2
16 2 2NC 5 XTCEXFCC02 2XTCEXFCCC02 2
16 4 4NO 5 XTCEXFAC40 XTCEXFACC40
16 4 3NO-1NC 5 XTCEXFAC31 XTCEXFACC31
16 4 2NO-2NC 5 XTCEXFAC22 XTCEXFACC22
16 4 1NO-3NC 5 XTCEXFAC13 XTCEXFACC13
16 4 4NC 5 XTCEXFAC04 XTCEXFACC04
16 4 1NOE-1NCL5XTCEXFCLC22 1XTCEXFCLCC22 1
16 4 2NO-2NC 5 XTCEXFCC22 2XTCEXFCCC22 2
Frame B–C—Front- (Top) Mount—Tall Version 3
16 2 2NO 5 XTCEXFATC20
16 2 1NO-1NC 5 XTCEXFATC11
16 2 2NC 5 XTCEXFATC02
54
63
64
53
54
53 61
62
51
52
61
62
58
57 6
5
66
21
22
33
34
21 31
21
22
31
32
54
63 73
64 74
53 83
8
4
54
53 61
62
73
74
83
84
54
53 61
62
71
72
83
84
53 61 71 81
82
72
62
54
51
52
61
62
71
72 82
81
58
5765
66
71
72
83
84
21
22
31
32
43
44
53
54
54
63
64
53
54
53 61
62
51
52
61
62
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-25
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Auxiliary Contacts, continued
Notes
1Front- (top) mount tall version is for use with Frame B electrical wire bridges and link kits and toolless plug combination connection kits: XTCEXRLB, XTCEXSDLB, XTPAXTPCB, XTPAXTPCRB, XTPAX.
2Can be mounted to the left side of contactor only. Cannot be used in combination with front- (top) mount auxiliary contacts or mechanical interlocks.
3One early-make contact (1NOE), one late-break contact (1NCL).
Interlocked opposing contacts, to IEC/EN 60947-5-1 Annex L (positively driven), within the auxiliary contact modules (not NO [early make] and NC [late break] contacts) and for the built-in auxiliary
contacts of the XTCE007B_–XTCE032C_.
Auxiliary break contact can be used as mirror contact to IEC/EN 60947-4-1 Annex F (not NC [late break] contact).
No auxiliary contacts can be fitted between two contactors.
Conventional
Thermal Current,
Open at 60°C
Ith = Ie,
AC-1 in Amps Poles
Contact
Configuration Circuit Symbol
Pkg.
Qty.
Screw Terminals
Catalog Number
Spring Cage Terminals
Catalog Number
Frame B–C—Front- (Top) Mount—Tall Version, continued 1
16 4 2NO-2NC 5 XTCEXFATC22
Frame C—Side-Mount
10 2 1NO-1NC 1 XTCEXSCC11 2
Frame D–G
16 2 2NO 5 XTCEXFBG20
16 2 1NO-1NC 5 XTCEXFAG11
16 2 1NO-1NC 5 XTCEXFBG11
16 2 2NC 5 XTCEXFBG02
16 4 4NO-0NC 5 XTCEXFBG40 XTCEXFBGC40
16 4 3NO-1NC 5 XTCEXFBG31 XTCEXFBGC31
16 4 2NO-2NC 5 XTCEXFBG22 XTCEXFBGC22
16 4 2NO-2NC 5 XTCEXFAG22 XTCEXFAGC22
16 4 1NO-3NC 5 XTCEXFBG13 XTCEXFBGC13
16 4 0NO-4NC 5 XTCEXFBG04 XTCEXFBGC04
16 4 1NOE-1NCL5XTCEXFBLG22 3XTCEXFBLGC22 3
54
53 61
62
71
72
83
84
54
53 61
62
14 24
13 23
54
53 61
62
14
13 21
22
12
11 21
22
14
13 23
24
33
34
43
4
4
14
13 21
22
33
34
43
44
14
13 21
22
31
32
43
4
4
54
53 61
62
71
72
8
3
84
14
13 21
22
31
32
41
42
12
11 21
22
31
32
41
42
14
13 21
22
35
36
47
48
V10-T15-26 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Side-Mount Auxiliary Contacts for Frame D–R, 40–2000A
Auxiliary Contacts Possible Combinations
Notes
1One early-make contact (1NOE), one late-break contact (1NCL).
2To maintain proper terminal marking, XTCEXSCN_ should not be used with Frame D contactors and only used with Frame F–G contactors in combination with XTCEXSBN_.
Forced operation contact to IEC/EN 60947-5-1 Appendix L (positively driven), inside the auxiliary contact unit (not early close and late opening).
Auxiliary normally closed contact can be used as mirror contact to IEC/EN 60947-4-1 Appendix F (not late opening).
No auxiliary contacts can be fitted between two contactors.
Conventional Free Air
Thermal Current,
Ith = Ie, AC-1 in Amps Poles
Contact
Configuration Circuit Symbol
Pkg.
Qty.
Screw Terminal
Catalog Number
Spring Cage Terminal
Catalog Number
10 2 1NO-1NC 1 XTCEXSBN11 XTCEXSBNC11
10 2 1NOE-1NCL1XTCEXSBLN11 1
10 2 1NO-1NC 1 XTCEXSCN11 2XTCEXSCNC11 2
Frame
Size Contactor
Built-In
Auxiliary
Front- (Top) Mount Side-Mount Total Auxiliary
Contacts Available Catalog NumberTwo-Pole Four-Pole Two-Pole
A 1NO or 1NC1 ——3 XTMC6A_–
XTMC9A_
—1 —5
——
B 1NO or 1NC1 ——3 XTCE007B_ –
XTCE015B_
—1 —5
——
C 1NO or 1NC1 ——3 XTCE018C_ –
XTCE032C_
—1 —5
——1 3
D 1—26 XTCE040D00_ –
XTCE065D00_
116
FG 1—26 XTCE080F00_ –
XTCE150G00_
128
——4 8
L–R 2NO-2NC 2 8 XTCE185L22_ –
XTCEC20R22_
——
13
44
14
43
21
32
31
22
17
48
18
47
25
36
26
35
53
84
54
83
61
72
71
62
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-27
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Auxiliary Contact Combinations
XTMC6A_–XTMC9A_
XTCE007B_–XTCE032C_
XTMCXF...A_
XTCEXF...C_
Two-Pole or Four-Pole
XTCE007B_–XTCE032C...
XTCEXF...C_
Two-Pole or Four-Pole XTCE018C_–XTCE032C_
XTCEXSCC11
or +
XTCE040D_– XTCE065D_ XTCE040D_–XTCE065D_
XTCEXF...G_
Two-Pole
XTCEXF...G_
Four-Pole
XTCEXSBN11
or +
XTCEXSBN11
+
XTCEXSBN11
+
XTCEXSBN11
+
XTCE080F_–XTCE150G_
XTCEXF...G_
Two-Pole or Four-Pole XTCE080F_–XTCE150G_
XTCEXSBN11
XTCEXSBN11
XTCEXSCN11
or +
XTCEXSCN11
+
+
XTCEXSBN11
XTCEXSBN11
+
++
XTCE185L_–XTCEC20R_
XTCEXSBN11 (Built-in)
XTCEXSBN11 (Built-in)
XTCEXSCN11
+
XTCEXSCN11
+
++
Frame L–R
Frame F–G
Frame D
Frame C
Frame A–B
V10-T15-28 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Enclosures
Type 1 Enclosures
Type 1 Enclosures—NEMA (Freedom)
Dummy Contact Block
Notes
1 In order to install cover control kits for NEMA Sizes 00–2 and IEC Sizes A–F, the starter must be provided with a side-
mounted auxiliary contact or a separately ordered dummy contact block, C320KGSD from table above, to serve as a
mounting base. Note: NEMA Size 00 open type devices are not supplied as standard with side-mounted auxiliaries.
2 If 8 AWG wire is used with NEMA Size 1 starter, the enclosure should be changed to a Box 2 (C799B13).
3 Sub panel drilled for 50–200 VA CPTs.
4 Enclosure drilled for 150–300 VA CPTs.
Box 1 will not accept devices with top-mounted auxiliaries. Box 2 will accept NEMA Sizes 00 and 0 starters with top-mounted
auxiliaries.
Starter Type
Box
Number
NEMA Size
AN16 Catalog Number
Non-reversing starter 1 00–1 C799B11 12
1— C799B12 1
22 C799B13
434 C799B15
10 5 C799B17
Non-reversing starter with space for CPT 3 00–2 C799B14 3
434 C799B15 4
Reversing starter 2 00–0 C799B13
312 C799B14
43 C799B15
94 C799B16
10 5 C799B17
Application Catalog Number
Dummy contact block C320KGSD
Type 1 Enclosure
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-29
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Type 3R, 4X and 12 Enclosures
Type 3R, 4X and 12 Enclosures—NEMA (Freedom)
Enclosures—IEC (XT Ty p e )
Note
1 Blank cover provided.
Starter Type
Box
Number
NEMA Size
AN16
Type 3R
Catalog Number
Type 12
Catalog Number
Type 4X
Catalog Number
Non-reversing starter 5 00–1 C799B21 C799B81 C799B41
62C799B24 C799B84 C799B43
6—C799B25 C799B85 C799B44
83C799B210 C799B810 C799B47
8—C799B212 C799B812 C799B49
84C799B211 C799B811 C799B48
10 5 C799B218 C799B818 C799B413
Non-reversing starter with space for CPT 6 00–2 C799B24 C799B84 C799B43
6—C799B25 C799B85 C799B44
83C799B210 C799B810 C799B47
8—C799B212 C799B812 C799B49
84C799B211 C799B811 C799B48
10 5 C799B218 C799B818 C799B413
Reversing starter 6 00–2 C799B24 C799B84 C799B43
6—C799B25 C799B85 C799B44
83C799B210 C799B810 C799B47
8—C799B212 C799B812 C799B49
94C799B215 C799B815 C799B411
10 5 C799B218 C799B818 C799B413
Multispeed 7 10–2 C799B223 C799B823 C799B417
Starter Type
Box
Number IEC Size Catalog Number
XT starters, 15A and 25A, with reset 1 B–C C799B31
XT contactors/starters without reset 1 B–C C799B33
XT contactors/starters with reset 2 B–C–D C799B36
XT contactors/starters without reset 2 B–C–D C799B34
XT contactors/starters with resets 1 B–C C799B35
XT contactors/starters with resets 2 B–C–D C799B37
Type 3R Enclosure
V10-T15-30 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Lighting Contactors
Electrically Held Base Contactor for C30CN/ECC
The C30CNE20_0 electrically
held base contactor contains
a 2NO power pole as
standard and will allow the
addition of power poles to
build an electrically held
contactor up to 12 poles
maximum. A mechanically
held module kit can also be
added to convert the
electrically held contactor into
a mechanically held contactor
in the field.
Electrically Held Base Contactor
Coil Base Voltage (Digit 9)
Power Poles for C30CNM/ECC
The C30CNM contactor
accepts up to a maximum six
single- or two-pole (or
combinations) power poles.
These can be used to form
up to:
12 NO poles maximum
when 6 two-poles are used
in NO positions (1–6) or
8 NC poles maximum with
4 two-poles in the NC
position (1–4) and 4 NO
poles with 2 two-poles in
the 2 NO positions (5–6)
Power Poles
Power Poles Catalog Number 1
2NO C30CNE20_0
Voltage
(Digit 9)
Code
Suffix
Voltage
(Digit 9)
Code
Suffix
115–120V 60 Hz/110V 50 Hz A265–277V 60 Hz/240V 50 Hz H
230–240V 60 Hz/220V 50 Hz B24V 60 Hz/20V 50 Hz T
460–480V 60 Hz/440V 50 Hz C28V 60 Hz/24V 50 Hz V
575–600V 60 Hz/550V 50 Hz D347V 60 Hz X
200–208V 60 Hz E
Electrically Held Base
Contactor
Power Poles Catalog Number
Single-pole C320PRP1
Two-pole C320PRP2
Power Poles
Mechanically Held Module Kits for C30CN/ECC
These kits are for converting
electrically held contactors to
mechanically held units. Kits
include control module, latch,
latch cover and auxiliary
contacts plus installation
instructions. Conversion kits
are suitable for coil voltages
of 277V and below.
C30CNM Components—Exploded View
Mechanically Held Module Kits
Note
1When ordering, select required contactor by catalog number and replace the magnet coil alpha
designation in the catalog number (_) with the proper code suffix from the Coil Base Voltage
table above.
Coil Volts Control Volts Catalog Number
Tw o - W i r e
24–277 Vac 110–120 Vac C320MH2WA0
200–277 Vac C320MH2WH0
24 Vac C320MH2WT0
12–24 Vdc C320MH2WT1
Three-Wire
24–277 Vac 110–120 Vac C320MH3WA0
200–277 Vac C320MH3WH0
24 Vac C320MH3WT0
12–24 Vdc C320MH3WT1
Conversion Kit
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-31
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Auxiliary Contacts for C30CN/ECC
A mechanically held contactor
with a two-wire control
module uses 1NC auxiliary
contact as standard for the
control wiring circuit. The
mechanically held contactor
with a three-wire control
module uses 1NO-1NC
auxiliary contacts as standard
for the control wiring circuit.
See the table below for
possible additional auxiliary
contact configurations.
Auxiliary Contact Configurations
Auxiliary Contacts
Transient Suppressor Kits for CN35/ECL
10–60A Contactors
These kits limit high voltage
transients produced in the
control circuit when power is
removed from the contactor or
starter coil. There are three
separate suppressors for use
on 24120V, 240V or 480V
coils respectively.
These devices mount directly
to the coil terminals of
lighting contactors 10–60A.
Kits for 10–60A
100–300A Contactors
This device mounts on top of
any side-mounted auxiliary
contact on lighting contactors
100–300A. It connects across
coil terminals on any 120V
contactor magnet coil.
Limits high voltage transients
produced in the circuit when
power is removed from the
coil.
Kits for 100–300A
Two-Wire Three-Wire
None 1NC (two-pole)
1NO (single-pole) 1NO (two-pole)
2NO (two-pole) 1NO-1NC (two-pole)
1NC (two-pole)
1NO-1NC (NO single-pole, NC two-pole)
2NO-1NC (two-pole)
Auxiliary Block Catalog Number
Single-pole C320AMH1
Two-pole C320AMH2
Auxiliary Contacts
Description Coil Voltage Catalog Number
Transient suppressor 24–120V C320TS1
240V C320TS2
480V C320TS3
C320TS2
Description Coil Voltage Catalog Number
Transient suppressor 120V C320AS1
C320AS1
Auxiliary Contacts for CN35/ECL
CN35 lighting contactors
include a 1NO maintaining
auxiliary contact mounted on
right hand side (on 10A, two-
and three-pole devices,
auxiliary contact occupies
fourth power pole position—
no increase in width). The
10–60A devices will accept
additional auxiliary contacts
on the top and/or sides.
Auxiliary contact blocks are
designed for snap-on
installation—fast, easy
installation (no tools required
up to 60A). All auxiliary
contacts are of the bifurcated
design with parallel circuit
paths. This redundant path
provides very high reliability.
Auxiliary contacts can be
snapped on the side (up to
two circuits—per auxiliary
contact) and on the top (up to
four circuits). Auxiliary
contacts for larger contactors,
100–400A sizes, will accept
side-mounted auxiliaries only
and easily attach to the side
of the contactor with two
screws.
Contact Configuration Code
This two-digit code is found
on the auxiliary contact to
assist in identifying the
specific contact configuration.
The first digit indicates the
quantity of NO contacts and
the second indicates the
quantity of NC contacts.
Auxiliary Contacts—10–60A Contactors
Notes
1For reference only—not part of catalog number.
2Cannot be added to contactors or starters mounted in Box 1 (Type 1).
Description
Contact
Configuration
Code 1Catalog Number
Side-Mounted
1NO 10 C320KGS1
1NC 01 C320KGS2
1NO-1NC 11 C320KGS3
2NO 20 C320KGS4
2NC 02 C320KGS5
Top-Mounted 2
1NO 10 C320KGT1
1NC 01 C320KGT2
1NO-1NC 11 C320KGT3
2NO 20 C320KGT4
2NC 02 C320KGT5
3NO 30 C320KGT9
2NO-1NC 21 C320KGT10
1NO-2NC 12 C320KGT11
3NC 03 C320KGT12
4NO 40 C320KGT13
3NO-1NC 31 C320KGT14
2NO-2NC 22 C320KGT15
1NO-3NC 13 C320KGT16
4NC 04 C320KGT17
Side-Mounted
Top-Mounted
V10-T15-32 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Base Auxiliary Contacts—100–400A Contactors
Auxiliary Contacts—100–400A Contactors
Auxiliary Contact Ratings (Amperes)—NEMA A600
Auxiliary Contact 5A Continuous Thermal Rating—NEMA P300
Notes
1 For reference only—not part of catalog number.
2 NO-NC occupies two positions—L2 and L3 or R2 and R3. See table on Page V10-T15-33.
Circuit
Contact
Configuration
Code 1
100A Contactors
Catalog Number
200 and 300A Contactors
Catalog Number
NO 10 C320KGS31 C320KGS41
NO-NC 11 C320KGS32 C320KGS42
Circuit
Contact
Configuration
Code 1Catalog Number
NO 10 C320KGS20
NC 01 C320KGS21
NO-NC 211 C320KGS22
Current
AC Volts
120V 240V 480V 600V
Make and interrupting 60.0 30.0 15.0 12.0
Break 6.0 3.0 1.5 1.0
Continuous 10.0 10.0 10.0 10.0
DC Volts
Make/Break
Amperes
125 1.10
250 0.55
Base Auxiliary Contact
Auxiliary Contact
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-33
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Auxiliary Contact Location for CN35/ECL
Auxiliary Contacts—Mounting Positions
The sketches below illustrate
the maximum number of
auxiliary contacts that can be
assembled to a contactor and
their locations in standard
enclosures.
Auxiliary Contact Mounting Positions
Auxiliary Contact Location
Size Poles
Available Mounting Positions 123
Open Type Type 1 Type 3R, 4X, 12
10A 2–4 T1, L1, R1 L1 L1, T1
20–60A 2–3 T1, L1 L1 L1, T1
60A 4 T1, L1 L1, T1
60A 5 T1, L1 L1, T1
100A 2–3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
200A 2–3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
300A 2–3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
400A 2–3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
L1
T1
L1 T1 R1
Front View
10–60A
Contactors
Top View
R1
100–400A
Contactors
Front
of Contactor
Left Side
of Contactor
L2
Aux.
Cont.
L3
Aux.
Cont.
R2
Aux.
Cont.
R3
Aux.
Cont.
L1
Base
Aux.
Cont.
R1
Base
Aux.
Cont.
Rear
Rear
Right Side
of Contactor
Pneumatic Timers—Top-Mounted for CN35/ECL
Attachment mounts on top of
10–60A lighting contactors
(top-mounted auxiliary
contacts cannot be installed
on device when timer is
used). Timer unit has DPST
timed contacts—circuits in
each pole must be the same
polarity. Units are convertible
from OFF to ON delay or vice-
versa.
Pneumatic Timers
Maximum Ampere Ratings
Solid-State Timers for CN35/ECL
Solid-State ON DELAY Timer—Side-Mounted on CN35 Freedom Series
Lighting Contactors Through 60A
This timer is designed to be
wired in SERIES with the
load (typically a coil). When
the START button is pushed
(power applied to timer), the
ON DELAY timing function
starts. At the completion of
the set timing period, timer
and series wired load will
both be energized.
Product Selection—Mounted Timer
Notes
1Available positions on contactors or starters other than what is factory installed.
2When a pneumatic timer is mounted on contactor, only side-mounted auxiliary contact
positions are available. The solid-state timer, when added, takes up side-mounted auxiliary
contact position.
3For 100–400A contactors, a base auxiliary contact must be added in position L1 before
additional contacts can be mounted.
4Add operating voltage suffix to catalog number. A = 120V, B = 240V, E = 208V.
5Rated 0.5A pilot duty—not to be used on larger contactors.
6Terminal connections are quick connects only. Two per side.
Timing Range Catalog Number
0.1–30 seconds C320TP1
10–180 seconds C320TP2
Description
Volts AC
120 240 480 600
Make 30.0 15.0 7.5 6.0
Break 3.0 1.5 0.75 0.6
Pneumatic Timer
Timing Range Catalog Number 456
0.1–1.0 seconds C320TDN1_
1–30 seconds C320TDN30_
30–300 seconds C320TDN300_
5–30 minutes C320TDN3000_
Solid-State Timer
V10-T15-34 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Type J Auxiliary Contact for A202/ECL
Capable of being field
mounted in a contactor or
starter (Classes A200,
A900 Sizes 00–6, V200,
V201 vacuum and definite
purpose controllers)
Provides two separate
electrical contact sets
which wire vertically and
are color coded; black
designates NC and silver
designates NO. Please
note that the vertical wiring
is contrary to the horizontal
wiring of the L-56 auxiliary
contacts
Designed to fit within
dimensions of starter; no
additional panel space is
required
Provides circuit isolation
(no polarity restrictions)
and single break bifurcated
contacts
Auxiliary Contact Ratings
Auxiliary Contact Types
SS-56 Surge Suppressor for A202/ECL
Designed to be used with
magnetic motor controllers
through Size 4 in 120V,
60 Hz control circuit
applications where
electronic equipment is
used
Steady state coil volts: 120,
60 Hz, rms
Peak input volts: 169.6,
60 Hz, max. amplitude
Max. ambient temperature:
65°C
Nominal limiting volts:
270 peak
Nominal rate of volt rise:
0.5 per ms
Surge Suppressor 1
Voltage Make Break
NEMA A600
120–600 Vac 7200 VA 720 VA
72–120 Vac 60A 720 VA
28–72 Vac 60 VA 10A
NEMA R300
28–300 Vdc 28 VA 28 VA
Contact Type Max. Catalog Number
1NO and 1NC 4 J11
2NC 4 J02
2NO 4 J20
1 coil clearing
NC and 1NO
4J1C
Type J Auxiliary
Contact
Type Mounting
Kit
Catalog Number
Starter SS-56
SS-56 Surge Suppressor
F-56 Fuse Block for A202/ECL
Facilitates installation of
fuses (15A, 600V maximum)
in control circuits
Uses Bussman type KTK
fuses, or equivalent
Mounts in same cavity as
Type J auxiliary contact
No tools or mounting
hardware needed
Fuse not included
Fuse Block
R-56 Interposing Relay for A202/ECL
The R-56AA interposing relay
is a low energy solid-state
device with a single NO solid-
state contact. It can be used
as a 120 Vac control relay, and
will operate on as little as
40 Vac input. Is useful in
applications requiring long
control wiring runs where
excessive voltage drop would
prevent the contactor or relay
from energizing. Will operate
a Size 4 contactor from
10,000 ft using 18 AWG wire.
Interposing Relay
Power Pole Kit for A202/ECL
Adds 1NO or 1NC power
pole to Size 00–1 A201
Class contactors
Factory installed or field
mountable in load side
auxiliary cavities
600 Vac
Continuous current rating
of 18A for Size 0, 27A for
Size 1
Power Pole Kit 2
Notes
1Can be used on Sizes 5 and 6 with 120V coil. Mounting bracket required—order separately.
Mounting bracket 177C043G04.
2Do not use with DC operated contactors.
Mounting
Kit
Catalog Number
Starter F56
Panel F56-P
Type
Mounting
Kit
Catalog Number
Starter or panel R56-AA
Continuous
Current Rating
Kit
Size
Kit
Catalog Number
Normally Open
18 0 PNO-0
27 1 PNO-1
Normally Closed
18 0 PNC-0
27 1 PNC-1
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-35
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Replacement Auxiliary Contacts for A202/ECL
Replacement Auxiliary Contacts
Extra Auxiliary Contact Kits for A202/ECL
All starters include an
auxiliary contact with 1NO
and 1NC contact. These kits
include an auxiliary contact
with contacts as shown, plus
operating arm and mounting
bracket when required.
Extra Auxiliary Contact Kits
Contactor
Size
Contact
Arrangement
Aux. Elect. Contact
Catalog Number Style Number
5, 6 1NO + 1NC J11 9084A17G01
2NO J20 9084A17G02
2NC J02 9084A17G03
7, 8 1NO 578D461G01
1NC 578D461G03
9 1NO + 1NC 843D943G04
2NO 843D943G05
2NC 843D943G06
Contactor
Size
Contact
Arrangement Style Number
5, 6 1NO + 1NC 3463D94G18
2NO 3463D94G04
2NC 3463D94G19
7, 8 12NO 818D498G06
1NO 818D498G04
DC Coil Conversion Kits for A202/ECL
Kits listed below include all
necessary parts to convert
from AC to DC control
including the DC coil with
built-in diode, rectifier,
auxiliary interlock and all
mounting hardware.
DC Coil Conversion Kits
Note
1Size 7 and larger use DC coils as standard.
Size Voltage Kit Style Number
5110-1207864A28G01
220-240 7864A28G02
440-480 7864A28G03
6110-1207864A29G01
220-240 7864A29G02
440-480 7864A29G03
V10-T15-36 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
IT. Solid-State Soft Starters
Surge Suppressors for S801+/S811+
The surge suppressor can
mount on either the line or
load side of the IT. soft
starter. It is designed to clip
the line voltage (or load side
induced voltage).
Surge Suppressors
Lug Kits for S801+/S811+
The 200 mm and 290 mm soft
starters do not include lugs.
The 200 mm and 290 mm
soft starters each have
different lug options based on
your wiring needs. Each lug
kit contains three lugs which
can be mounted on either the
load or line side.
Lug Kits
Lug Cover Kits for S801+/S811+
Replacement covers for the T
and V Frame are available in
case of damage to the
existing covers.
Lug Cover Kits
Description Catalog Number
600V MOV for IT. soft starters EMS39
690V MOV for IT. soft starters EMS41
Surge Suppressor
Frame
Size
Frame
Designation Description
Catalog
Number
200 mm
SSRV
T, U 2 cable connections,
4 AWG to 1/0 cable
EML22
1 cable connection,
4/0 to 500 kcmil cable
EML23
2 cable connections,
4/0 to 500 kcmil cable
EML24
1 cable connection,
2/0 to 300 kcmil cable
EML25
2 cable connections,
2/0 to 300 kcmil cable
EML26
290 mm
SSRV
V 2 cable connections,
4/0 to 500 kcmil cable
EML28
4 cable connections,
4/0 to 500 kcmil cable
EML30
6 cable connections,
4/0 to 500 kcmil cable
EML32
4 cable connections,
2/0 to 300 kcmil cable
EML33 1
Lug Kits
Description Catalog Number
Lug cover T, U Frame EML27
Lug cover V Frame EML34
Digital Interface Module and Control Interface Module
The Digital Interface Module
(DIM) and control interface
module are available as
replacement parts.
DIM and CIM
Control Wire Connector
Control Wire Connector
User Manual for S811+
A comprehensive user
manual is available and can
be downloaded free of charge
from www.eaton.com by
performing a document
search for MN03902002E.
Mounting Plates for S801+/S811+
The mounting plates are
designed to help make it easy
to install or retrofit the soft
starter into enclosures and
MCCs. The soft starter can
be mounted onto the plate
prior to installation. The
mounting plate is designed
with tear drop mounting
holes for easier installation.
Mounting Plates
Note
1The EML33 does not have a CSA Listing.
Description Catalog Number
Blank cover (filler) EMA68
DIM for S811+ EMA91
CIM for S801+ EMA71
CIM for S801+ pump control option EMA72
Panel mounting kit
3 ft cable EMA69A
5 ft cable EMA69B
8 ft cable EMA69C
10 ft cable EMA69D
Description Catalog Number
12-pin, 5 mm pitch connector for control wiring EMA75L
Description Catalog Number
Mounting plate N Frame EMM13N
Mounting plate R Frame EMM13R
Mounting plate T, U Frame EMM13T
Mounting plate V Frame EMM13V
Fan/hood accessory EMM18
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-37
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Adapter Plates
The adapter plate allows
customers to retrofit a
V Frame 290 mm soft starter
with the U Frame 200 mm
soft starter.
Adapter Plates
Vibration Plates for S801+/S811+
The vibration plates allow the
soft starter to be applied in
high shock and vibration
applications. The vibration
plate allows vibration up to 5g
and shock in up to 40g. The
soft starter is mounted onto
the vibration plate prior to
installation in the panel.
Vibration Plates
Power Supplies
24 Vdc power supply that
can be used with the S801+
or S811+ SSRV or as a
standalone device.
Power Supplies
DIN Rail Power Supply Mounting Kit (35 mm)
DIN Rail Mounting Kit
Description Catalog Number
Adapter Plates 1EMM13U
Description Catalog Number
Vibration plate N Frame EMM14N
Vibration plate R Frame EMM14R
Vibration plate T, U Frame EMM14T
Vibration plate V Frame EMM14V
Description SSRV Catalog Number
115 Vac input S801+/S811+ PSG240E
230 Vac input S801+/S811+ PSG240E
380–480 Vac input S801+/S811+ PSG240F
Description Catalog Number
DIN rail mounting kit (35 mm) PSSDIN
NEMA Vacuum Break Control
Lug Sizes
Size 4—12–4/0
NEMA Size 5 and 6 and
320A, 540A and 610A—
supplied without line or
load lugs
Lug Kits—Consist of 6 Lugs
Field Modification Kits
Auxiliary Electrical Contacts
Size 4—Three Type J auxiliary
contacts may be mounted on
the top of Size 4 contactors to
provide six auxiliary, isolated
600V, 10A contacts for use in
control circuits.
Sizes 5–6—Two Type J
auxiliary contacts may be
mounted on each side of
Size 5 and 6 contactors to
provide four auxiliary, isolated
600V,10A contacts for use in
control circuits.
Auxiliary Electrical Contacts
Horizontal Mechanical Interlock
Note
1For more information see Pub51719.
Size Description Catalog Number
5 and 320A 1/0–500 kcmil C325KAL8
6, 540A and 610A 1/0–500 kcmil double barrel C325KAL9
610A 1/0–600 kcmil double barrel 80-19825-2
Contact Arrangement Catalog Number
1NO, 1NC J11
2NO J20
2NC J02
Size Catalog Number
4180C113G04
5180C113G16
6180C113G17
V10-T15-38 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Heater Coils
Heater Coil Selection for Type B Overload Relay
Notes
1Three are required per overload relay.
For information on H2001 heaters, see Page V10-T15-6.
Motor Full Load Current in Amperes for Use with 3 Heaters Only Motor Full Load Current in Amperes for Use with 3 Heaters Only
Open Starter
Heater
Catalog Number 1
Open Starter
Heater
Catalog Number 1
Ambient Compensated
Overload Relay
Ambient Compensated
Overload Relay
Size 4 and 160A Size 5 and 320A with 300/5 Current Transformers
12.8–14.1 FH68 107–117 FH23
14.2–15.5 FH69 118–129 FH24
15.6–17.1 FH70 130–141 FH25
17.2–18.9 FH71 142–155 FH26
19.0–20.8 FH72 156–170 FH27
20.9–22.9 FH73 171–187 FH28
23.0–25.2 FH74 188–205 FH29
25.3–27.8 FH75 206–224 FH30
27.9–30.6 FH76 225–244 FH31
30.7–33.5 FH77 245–263 FH32
33.6–37.5 FH78 264–292 FH33
37.6–41.5 FH79 293–318 FH34
41.6–46.3 FH80 319–350 FH35
46.4–50 FH81 Size 6 and 540A with 600/5 Current Transformers
51–55 FH82 236–259 FH24
56–61 FH83 260–283 FH25
62–66 FH84 284–310 FH26
67–73 FH85 311–340 FH27
74–78 FH86 341–374 FH28
79–84 FH87 375–411 FH29
85–92 FH88 412–448 FH30
93–101 FH89 449–489 FH31
102–110 FH90 490–527 FH32
111–122 FH91 528–585 FH33
123–129 FH92 586–600 FH34
130–133 FH93
FH94
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-39
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
Modification Codes
A—Ammeters, Auxiliary Contacts, Accelerating Relays, Autotransformers
Note
1Top-mounted auxiliary contacts cannot be added to contactors in Box 1 (Type 1).
Modification Description
Catalog Number
Suffix
Ammeter Panel type wired to current transformer in Line 1, Type 1, 12 A1
Panel type wired to current transformer in Line 1, Type 3R, 4X
Panel type, selector switch and three current transformers wired to ammeter
via switch, Type 1, 12
A2
Panel type, selector switch and three current transformers wired to ammeter
via switch, Type 3R, 4X
Miniature (single-phase), Type 1, 12 A3
Miniature with selector switch, Type 1, 12 A4
Switchboard (single-phase), Type 1, 12 A5
Switchboard (single-phase), Type 3R, 4X
Switchboard with selector switch, Type 1, 12 A6
Switchboard with selector switch, Type 3R, 4X
Three-panel type (single-phase), Type 1, 12 A7
Three-panel type (single-phase), Type 3R, 4X
Three miniature (single-phase), Type 1, 3R, 4X, 12 A10
Three switchboard type (single-phase), Type 1, 12 A11
Three switchboard type (single-phase), Type 3R, 4X
Ammeter order by description, Type 1, 3R, 4X, 12 A12
Auto-transformers Hp rating selection, see Tab 5 A8
Order by description A9
Top-mounted auxiliary contacts 1
(unwired)
NEMA Sizes 00–2 only (unwired)
IEC Sizes B–L only (unwired)
XT Series
1NO A13
1NC A14
1NO-1NC A15
2NO A16
2NC A17
2NO-1NC A18
1NO-2NC A19
3NO A20
3NC A21
3NO-1NC A22
2NO-2NC A23
1NO-3NC A24
4NO A25
4NC A26
V10-T15-40 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
A—Ammeters, Auxiliary Contacts, Accelerating Relays, Autotransformers, continued
B—Breaker Modifications, Backspin Timer, Undervoltage Release, Bell Alarm, Bus Choke
Note
1Available on XT starters for 40A and greater only.
Modification Description
Catalog Number
Suffix
Side-mounted auxiliary contacts 11NO A27
1NC A28
1NO-1NC A29
2NO A30
2NC A31
2NO-1NC A32
1NO-2NC A33
3NO A34
3NC A35
3NO-1NC A36
2NO-2NC A37
1NO-3NC A38
4NO A39
4NC A40
Auxiliary contacts Contacts mounted on operating mechanism of disconnect switch, 1NO-1NC A42
Contacts mounted on operating mechanism of disconnect switch, 2NO-2NC A43
With auxiliary contact omitted A44
Accelerating relay For two-speed A46
2NO/2NC 24 Vdc auxiliary relay—IT. only A47
Modification Description
Catalog Number
Suffix
Breaker 1NO-1NC auxiliary contact on breaker B1
2NO-2NC auxiliary contacts on breaker B2
Shunt trip on circuit breaker—48–127 Vac or Vdc B3
Shunt trip on circuit breaker—9–24 Vac or Vdc B4
Shunt trip on circuit breaker—208–380 Vac B5
Shunt trip on circuit breaker—415–600 Vac or 220–250 Vdc B6
Undervoltage release for breaker B8
Current limiter mounted to breaker B9
Breaker—order by description B10
Thermal magnetic breaker B11
Backspin timer 180 seconds B12
Undervoltage release Undervoltage release for circuit breaker—208–240 Vac B13
Undervoltage release for circuit breaker—380–480 Vac B14
Undervoltage release for circuit breaker—525–600 Vac B15
Bell alarm Bell alarm for circuit breaker B16
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-41
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
C—Control Power Transformer, Power Supplies, Control Relays, Cover Control (not elsewhere
defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker,
Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC
Interface, Separate Source Disconnect, Bypass Contactors
Note
1Not available for XT starters.
Modification Description
Catalog Number
Suffix
Control power transformers
Make sure eighth character specifies
primary/secondary voltage
Standard size control transformer, 120V/60 Hz, 110V/50 Hz secondary with
two primary and one secondary fuse
C1
Standard size control transformer, 24V/60 Hz secondary with two primary
and one secondary fuse
C2
50 VA extra capacity CPT 120V/60 Hz, 110V/50 Hz with two primary and
one secondary
C42
100 VA extra capacity CPT, 120V/60 Hz, 110V/50 Hz secondary with two primary
and one secondary fuse
C3
100 VA extra capacity CPT, 24V/60 Hz secondary with two primary and one
secondary fuse
C4
200 VA extra capacity CPT, 120V/60 Hz, 110V/50 Hz secondary with two primary
and one secondary fuse
C5
200 VA extra capacity CPT, 24V/60 Hz secondary with two primary and one
secondary fuse
C6
300 VA extra capacity CPT, 120V/60 Hz, 110V/50 Hz secondary with two primary
and one secondary fuse
C7
400 VA extra capacity CPT, 120V/60 Hz, 110V/50 Hz secondary with two primary
and one secondary fuse
C8
1 kVA extra capacity CPT, 120V/60 Hz, 110V/50 Hz secondary with two primary
and one secondary fuse
C9
2 kVA extra capacity CPT, 120V/60 Hz, 110V/50 Hz secondary with two primary
and one secondary fuse
C10
Control transformer—order by description C11
CPT with power supply for XT C34
Power supplies (XT only) Separate control 120 Vac to 24 Vdc C27
Power supply with extra capacity—order by description C28
Control relays Four-pole interposing relay, 600V (2NO/2NC) C12
Four-pole, unwired, A600 rtg.—2NO-2NC C14
Eight-pole, unwired, A600 rtg.—4NO-4NC C15
Control relay—order by description C16
Three-wire control module (C30 lighting) C18 1
Two-wire control relay for mechanical/magnetic lighting contactors C20 1
Cover control Convert position seven to E30 type cover control C17
Lock-off attachment added on cover control C19
Change to M22 (22 mm) cover controls C29
Current transformer(s) In phase 1 C21
In phases 1 and 2 C22
In 3 phases C23
Compelling relay C25
Control wiring Omit control wiring C26
With separate control wiring and two 250V fuses in holder C30
With common control wiring and two 600V (Class C) fuses in holder C31
Control wiring type—order by description C33
Control circuit breaker Order by description C32
Separate control Wired for separate control (reduced voltage) C35
Customer supplied components Customer supplied components to be installed C36
Customer supplied wiring diagram to use C37
V10-T15-42 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
C—Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere
defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker,
Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC
Interface, Separate Source Disconnect, Bypass Contactors, continued
D—Device Labels, Deceleration Relay, Drain and Breather, Duplex Modifications
Note
1Not available for XT starters.
Modification Description
Catalog Number
Suffix
Contactor/starter Contactor/starter—order by description C40
Counter Operations counter C41
E-stop relay E-stop relay (DeviceNet) C43
DC/AC interface DC/AC interface module C44 1
Separate source disconnect IEC separate source disconnect for control circuitry C45
Bypass contactors for IT. RVSS Isolation contactor C46/J1
Output contactor C46/J2
Bypass contactor C46/J3
Isolation/output/bypass contactor C46/J4
Modification Description
Catalog Number
Suffix
Device labels (Each label) D1
Decel. relay 1Two-speed D2
Drain and breather
(Type 7/9 enclosure) 1
Drain and breather D5
Drain only D6
Breather only D7
Duplex modifications Alternator omitted (deduct price) D12
START/STOP pushbuttons—supplied for each motor D14
HAND/OFF/AUTO selector switch—supplied for each motor D15
No. 1 lead–No. 2 lead selector switch for manual selection of lead pump
(alternator is omitted)
D16
Red RUN pilot light—supplied for each motor D17
Push-to-test red RUN pilot light—supplied for each motor D18
TEST pushbutton for each motor D19
CPT, 120V secondary, two primary fuses and one secondary fuse—
supplied for each motor
D20
CPT with 100VA extra capacity, 120V secondary, two primary fuses and one
secondary fuse—supplied for each motor
D21
CPT with 200VA extra capacity, 120V secondary, two primary fuses and one
secondary fuse—supplied for each motor
D22
CPT for duplex—order by description D23
Add two relays to modify controller to operate with single-pole pilot devices D24
Add three relays to modify controller to operate with single-pole pilot devices D25
Green—OFF for each starter D26
Green—push-to-test OFF for each starter D27
Green—RUN light (duplex pump) D28
Red—STOP light (duplex pump) D29
P-T-T—green RUN light (duplex pump) D30
P-T-T—red STOP light (duplex pump) D31
Elapsed time meter (duplex pump) D32
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-43
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
E—Enclosure Modifications, Elapsed Time Meter, Duplex Outlet, Enclosure for Starter,
Enclosure Clear Cover, Enclosure Material
F—Fuse Clips, Fuse Blocks, Fungus Protection, Fingerproof Covers, EMI Filter
G—Ground Fault Relay, Grounding
Note
1Not available for XT starters.
Modification Description
Catalog Number
Suffix
Enclosure modifications Oversize enclosure E3
Enclosure—order by description E4
Enclosure with pole mounting hardware E5
Removable end plates E6
Service entrance rating (ground/neutral banding SE labels) E7
Service entrance rating with ground bar E8
Safety door interlock E11
Elapsed time meter Wired across coil, Type 1, 12 E9
Wired across coil, Type 3R, 4X
Elapsed time meter—order by description E10
Duplex outlet Convenience duplex outlet mounted in side of enclosure E12
Enclosure for starter 1Horizontal combination starter, Size 0–2 E13
Narrow combination starter, Size 0–2 E14
Enclosure clear cover for XT Clear cover for Halyester enclosure non-metallic E19
Enclosure material Convert to 316 stainless steel E16
Convert from Type 3R to stainless steel E21
Irrigation pump panel Bottom entry E17
Modification Description
Catalog Number
Suffix
Fuse clips 1Change fuse clips in position eight to Class J F1
Change fuse clips in position eight to Class H and K (30A and 60A only) F2
Fuse blocks Power fuses included—order by description F4
30A control circuit fuseholder (KTK) mounted on panel (unwired),
fuse not supplied
F5
30A control circuit fuseholder mounted on panel (unwired), FNQR
fuse supplied
F6
Three-pole power fuseholder mounted on front contactor F7
Separate fusing of control power supply—IT. F8
Blown fuse indicator (not for PFC) F10
Class CC fuses F21
Modification Description
Catalog Number
Suffix
Ground fault relay Ground fault relay (wired) G1
Ground fault relay (unwired) G3
Grounding Special grounding—order by description G5
Ground fault protection and monitoring panel G7
V10-T15-44 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
H—Heater (Space), Heater Packs Installed
K—Keypad
Modification Description
Catalog Number
Suffix
Space heater Space heater and thermostat H1
Space heater and NC interlock H2
Install heater packs (Freedom Series) Class 20 Class 10 H5
/D1 H2001B-3 /D25 H2101B-3
/D2 H2002B-3 /D26 H2102B-3
/D3 H2003B-3 /D27 H2103B-3
/D4 H2004B-3 /D28 H2104B-3
/D5 H2005B-3 /D29 H2105B-3
/D6 H2006B-3 /D30 H2106B-3
/D7 H2007B-3 /D31 H2107B-3
/D8 H2008B-3 /D32 H2108B-3
/D9 H2009B-3 /D33 H2109B-3
/D10 H2010B-3 /D34 H2110B-3
/D11 H2011B-3 /D35 H2111B-3
/D12 H2012B-3 /D36 H2112B-3
/D13 H2013B-3 /D37 H2113B-3
/D14 H2014B-3 /D38 H2114B-3
/D15 H2015B-3 /D39 H2115-3
/D16 H2016B-3 /D40 H2116-3
/D17 H2017B-3 /D41 H2117-3
/D18 H2018-3
/D19 H2019-3
/D20 H2020-3
/D21 H2021-3
/D22 H2022-3
/D23 H2023-3
/D24 H2024-3
Modification Description
Catalog Number
Suffix
Keypad Door mounted keypad (RVSS) K5
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-45
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
L—Labels and Lighting Contactors
N—Nameplates
Modification Description
Catalog Number
Suffix
Lighting arrestor Lighting arrestor installed in enclosure on panel L3
Lugs Special lugs (order by description) L9
Carton label Customer marking—specify L10
Lighting contactors 1 NC pole L21
2 NC pole L22
3 NC pole L23
4 NC pole L24
5 NC pole L25
6 NC pole L26
7 NC pole L27
8 NC pole L28
Three-wire 120 Vac L29A
Three-wire 240 Vac L29B
Three-wire 24 Vac L29C
Three-wire 24 Vdc L29D
Two-wire 120 Vac L29E
Two-wire 240 Vac L29F
Two-wire 24 Vac L29G
Modification Description
Catalog Number
Suffix
Nameplates Enclosure nameplates N1
V10-T15-46 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
P—Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction
Capacitors, Program Timer, Percentage Timer, Photocell
Modification Description
Catalog Number
Suffix
Push-to-test pilot lights Push-to-test pilot light (red RUN) wired to coil P1
Push-to-test pilot light (green OFF) wired in series with auxiliary contact P2
Combination of P1 and P2 above P3
Push-to-test pilot light (amber RUN) wired to coil P4
Push-to-test pilot light—green RUN P49
Push-to-test pilot light—green STOP P57
Pushbuttons EMERGENCY STOP—mushroom head P5
Pushbutton omitted P6
START/STOP P7
ON/OFF P8
START P9
ON P10
OFF P11
FORWARD/REVERSE/STOP P12
FAST/SLOW/STOP P13
FAST/OFF/SLOW P14
HIGH/LOW/STOP P15
HIGH/LOW P16
SLOW/FAST P17
Pushbutton with legend plate P18
UP/STOP/DOWN P52
OPEN/STOP/CLOSE P53
Red STOP pushbutton P72
START/STOP pushbuttons (located in top two holes) P73
Green START pushbutton P74
Pilot lights With one amber pilot light marked POWER AVAILABLE wired to load side
of two fuses or circuit breaker
P19
Pilot light (amber RUN) wired to coil P20
With one red pilot light marked RUN wired thru NO auxiliary contact P21
With one push-to-test red light marked RUN Wired thru NO auxiliary contact P22
Pilot light—red RUN P23
Pilot light—red ON P24
Pilot light—green OFF P25
Pilot light—order by description P26
Pilot light—red STOP P29
Pilot light—green STOP P61
FORWARD/REVERSE red pilot lights P62
UP/DOWN red pilot lights P63
OPEN/CLOSE red pilot lights P64
HIGH/LOW red pilot lights P65
FAST/SLOW red pilot lights P66
Green RUN light P67
LED bulbs P68
Blue OVERLOAD light P69
Amber fault pilot light P71
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-47
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
P—Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction
Capacitors, Program Timer, Percentage Timer, Photocell, continued
Q—IQ Products, DN50
R—Ramp, Relays, Solid-State Electronic Overload Relays, Resets, Overload Relay Modifications,
Reversing, DeviceNet Interface
Modification Description
Catalog Number
Suffix
Illuminated pushbutton Illuminated pushbutton—order by description P27
Phase loss relay Phase loss relay P28
Phase reversal relay Phase reversal relay P30
Phase unbalance relay Phase unbalance relay P32
Phase monitoring relay Phase monitoring relay P34
Power factor correction capacitors /F1 20 kVar /F9 70 kVar /F17 200 kVar P38
/F2 25 kVar /F10 75 kVar /F18 225 kVar
/F3 30 kVar /F11 80 kVar /F19 250 kVar
/F4 35 kVar /F12 90 kVar /F20 300 kVar
/F5 40 kVar /F13 100 kVar /F21 350 kVar
/F6 45 kVar /F14 125 kVar /F22 400 kVar
/F7 50 kVar /F15 150 kVar
/F8 60 kVar /F16 175 kVar
Potential transformers Potential transformer—wired L1–L2 P39
Potential transformer—wired L1– L2 and L2–L3 P40
Potential transformer—three phases P41
Pump controller Pump controller for IT. P42
Program timers 15-minute program timer P43
24-hour program timer P44
7-day program timer with day omission feature P45
Percentage timers 15-minute percentage timer P47
60-minute percentage timer P48
Photocell Photoelectric receptacle with photocell P70
Modification Description
Catalog Number
Suffix
IQ products IQ 500 Q1
IQ100 Q2
IQ 1000 Q3
IQ 4000 Q5
IQ data metering module IQ data metering module Q12
IQ 220 with cable Q14
DN50 DeviceNet input/output module Q13
Modification Description
Catalog Number
Suffix
Ramp Extended ramp of IT.R1
Relay Overvoltage relay R2
Omit overload relay R4
V10-T15-48 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
R—Ramp, Relays, Solid-State Electronic Overload Relays, Resets, Overload Relay Modifications,
Reversing, DeviceNet Interface, continued
Notes
1Features:
Self-powered
Phase loss protection
Current adjustment knob
±1% repeat accuracy
1NO and 1NC isolated contacts
2Not UL Listed.
3NEMA Size 5 starter available with 60–300A panel mounted CTs. Starter as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).
4NEMA Size 6 starter available with 120–600A panel mounted CTs. Starter as an assembled unit with 1–5A C440 overload relay (C440A1A005SELAX or C440A2A005SELAX).
5Not available for XT starters.
Modification IEC Size NEMA Size
Full Load Current
Adjustment Range (A)
Three-Phase without
Ground Fault Auto/Manual
Reset Overload
Three-Phase with
Ground Fault Auto/Manual
Reset Overload
Selectable Class 10/20/30 Selectable Class 10/20/30
Solid-state electronic overload relay 1B and C 00 0.33–1.65 2R63/A R64/A
1–5 R63/B R64/B
4–20 R63/C R64/C
C and D 0 and 1 0.33–1.65 2R63/A R64/A
1–5 R63/B R64/B
4–20 R63/C R64/C
9–45 R63/D R64/D
D 2 9–45 R63/D R64/D
D, F and G 3 20–100 R63/E R64/E
G 4 28–140 R63/F R64/F
N/A 5 60–300 3R63/G R64/G
N/A 6 120–600 4R63/H R64/H
Modification Description
Catalog Number
Suffix
Resets 5Change external reset to internal reset—hole covered with plug R5
Internal reset—no hole plug R6
Overload reset (order by description) R7
Manual reset only on overload relay R44
Auto reset only on overload relay R45
Internal trip indicator—no external reset R47
External reset with external trip indicator R48
External reset with bell alarm R49
N3R reset boot added (Type 1/12 only) R71
Reversing 5Reversing contactor/starter R54
Overload relay mods Anti plug-in R53
DeviceNet interface DeviceNet interface R69
Standard reset for DeviceNet R65
Lighted reset for DeviceNet R66
Trip indicator for DeviceNet R67
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-49
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
S—System Voltage, Selector Switches, Suppressor, Incomplete Sequence Protection, Single-
Phase Jumper, Surge Capacitor, Speed Potentiometer
Note
1When using three-position selector switch with magnetic lighting contactor, mod C20 must also be used (ECL04, ECL13, ECL15).
Modification Description
Catalog Number
Suffix
System voltage selection System voltage selection for internal components S1
/H1 208V 60 Hz
/H2 240V 60 Hz
/H3 277V 60 Hz, single-phase
/H4 480V 60 Hz
/H5 600V 60 Hz
/H6 796V 60 Hz
/H7 220V 50 Hz
/H8 380V 50 Hz
/H9 415V 50 Hz
/H10 550V 50 Hz
/H11 660V 50 Hz
/H12 380V 60 Hz
/H13 1500V 60 Hz
System voltage selection—specify on order S2
Selector switches 1HAND/OFF/AUTO S3
HAND/AUTO S4
HAND/OFF/AUTO selector switch with one red RUN pilot light S5
RUN/OFF/AUTO S6
AUTO/OFF/TEST S7
AUTO/OFF/TEST selector switch with one red RUN pilot light S8
AUTO/OFF/TEST selector switch with one red RUN pilot light and one
green pilot light
S9
OFF/AUTO S10
START/STOP S11
OFF/ON S12
HIGH/LOW S13
FAST/OFF/SLOW S14
SLOW/FAST S15
FORWARD/REVERSE S16
HIGH/OFF/LOW S17
HIGH/LOW/OFF/AUTO S18
Selector switch omitted (pumps only) S19
HAND/OFF/AUTO spring return from left S21
OPEN/OFF/CLOSE S41
FORWARD/OFF/REVERSE S42
FAST/OFF/SLOW/AUTO S43
Selector switch omitted (pump panels only) S19
Selector switch—order by description S40
RVSS/BYPASS (soft starters only) S44
LOCAL/REMOTE selector switch S45
RUN/OFF selector switch S46
Suppressor Transient suppressor mounted on magnet coil S24
Surge suppression MOV (IT.)S20
Sequence timer Sequence timer (pump panels) S26
Sequence protection Incomplete sequence protection S27
Pump 480V BP9000 pump S28
Single-phase Convert contactor or starter from three-phase to single-phase—
install jumper
S29
Single-phase rev. 120V S30
Single-phase rev. 240V S31
Surge capacitor Surge capacitor wired to disconnect line side S37
V10-T15-50 Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
T—Timers, Time Delay Relays, Terminal Blocks, Terminal Points, Ring Lug Connections
U—Undervoltage Relay, Time Delay Undervoltage Relay
Note
1Not available for XT starters.
Modification Description
Catalog Number
Suffix
Timers Pneumatic timer installed on contactor, unwired, 30 seconds maximum T1
Pneumatic timer installed on contactor, unwired, 180 seconds maximum T2
Pneumatic timer mounted in enclosure, unwired, 180 seconds maximum T3
Solid-state ON delay timer (1–30 seconds) T4
Solid-state ON delay timer (30–300 seconds) T5
Timer—order by description T25
Time delay relays Time delay relay, 3 minutes maximum, unwired, ON DELAY T6
Time delay relay, 3 minutes maximum, unwired, OFF DELAY T7
Time delay low voltage release relay T8
Terminal blocks With one single circuit terminal block, unwired T9
With two single circuit terminal block, unwired T10
Terminal points With 6 terminal points, unwired T11
With 12 terminal points, unwired T12
With 18 terminal points, unwired T13
Terminal point per customer specification, unwired (price each) T14
Terminal point per customer specification, wired (unwired without customer diagram) T15
Three terminals mounted between contactor and overload for power factor
capacitors—Sizes 0–2
T21
Three terminals mounted between contactor and overload for power factor
capacitors—Sizes 3–4
T22
Quick-connect terminals added to DP contactor/starter T23
Ring lug connections Ring lug connections on power wires T16 1
Ring lug connections on control wires T17
Modification Description
Catalog Number
Suffix
Undervoltage relays Undervoltage relay, non-adjustable U1
Undervoltage relay, adjustable U2
Time delay undervoltage relays Time delay undervoltage relay, non-adjustable U4
Time delay undervoltage relay, adjustable U5
Under- and overvoltage relay Under- and overvoltage relay U7
Volume 10—Enclosed Control CA08100012E—August 2012 www.eaton.com V10-T15-51
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.2
Accessories and Modification Codes
Modification Codes
V Volt meter, Va rmeter, Vac uum Starter
W—Wattmeter, Watt-Hour Meter, Wiremarkers, Wiring Diagram
Notes
1Type 1/12 only.
2Not available for XT starters.
Modification Description
Catalog Number
Suffix
Voltmeters One panel type voltmeter wired L1–L2 V1
Panel type voltmeter and selector switch wired to read three-line voltages V2
Miniature voltmeter wired L1–L2 V3 1
Miniature voltmeter and selector switch wired to read three-line voltages V4 1
Switchboard type voltmeter wired L1 L2 V5
Switchboard type voltmeter and selector switch wired to read three-line voltage V6 1
Three panel type voltmeters wired in each phase V7
Three miniature voltmeters wired in each phase V8 1
Three switchboard type voltmeters wired in each phase V9 1
Voltmeter—order by description V10
Varmeter 2Varmeter V11
Varmeter—order by description V12
Vacuum starter 2Vacuum starter—1500V rating V13
Modification Description
Catalog Number
Suffix
Wattmeter 1Wattmeter W1
Watt-hour meter 1Watt-hour meter W3
Watt-hour meter with demand attachment W5
Wiremarkers Wiremarkers W7
Wiremarkers—order per customer diagram or specifications W8
Wiremarkers—order by description W9
WYE-Delta hp See Tab 5 W10 2
Windows in enclosure Enclosure windows W11
Wiring diagram Reduced copy of custom wiring diagram laminated on inside of door W12