https://www.phoenixcontact.com/us/products/2906848
04/11/2017Page2/4
Surge protection device-TTC-6-TVSD-C-24DC-PT-I-2906848
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C3
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
Rated current 10 A (60°C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE ≤ 5 µA
Nominal discharge current In (8/20) µs (core-earth) 150 A
Voltage protection level Up (core-ground) ≤ 50 V (C3 - 25 A)
≤ 50 V (C3 - 30 A)
Response time tA (core-earth) ≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 520 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 1.7 MHz
Capacity (core-earth) 1.5 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-ground) C3 - 30 A
Connection data
Connection method Push-in connection
Connection method IN Push-in connection
Connection method OUT Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12