1
Power Entry Modules with Line Filter FKI
www.schurter.com/pg06
EMC Products
IEC Appliance Inlet C14 with Filter, Fuseholder 2-pole, Line Switch 2-pole
Aluminum Nickel plated steel
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount:
Screw-on mounting from front side
- 4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 2-pole, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
Approvals
- VDE Certificate Number: 40004665
- UL File Number: E72928
Characteristics
- Compact design with optimal shielding
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
If the power entry module is installed as normal, it is not possible to
touch any live parts with the test-finger according to IEC60529
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- With EMC-shield
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Medical version M80
References
Weblinks
pdf, html, General Product Information, Approvals, RoHS, CHINA-RoHS,
Mating Connectors, e-Store, SCHURTER-Stock-Check, Distributor-
Stock-Check, Accessories
Technical Data
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current standard < 0.25 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temp. -25 °C to 85 °C
Climatic Category 25/085/21 acc. to IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class 1 acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Panel Thickness s Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
Fuseholder 2-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @
Ta 23 °C
5 x 20: 1.6 W (2-pole)
Power Acceptance @ Ta >
23°C
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Line Switch Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical details
Line Filter Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
MTBF > 1'700'000 h acc. to MIL-HB-217 F
2
Power Entry Modules with Line Filter
FKI
www.schurter.com/pg06
EMC Products
Dimensions 55 mm
Case 45
40 49.5 40
R1
6.3x0.8
±0.5
±0.5
28
63
65
R3 61.5
50±0.5
50 67 28.7
±0.5
±0.5
5.5 14 29.5
3.5
ø 3.2
ø 5.8x90°
60.2
61
±0.15
M3
Case 50
40 49.5 40
R1
6.3x0.8
±0.5
±0.5
28
63
65
R3 41
50±0.5
50 55 28.7
±0.5
±0.5
5.5 15 29.5
3.5
ø 3.2
ø 5.8x90°
60.2
61
±0.15
M3
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [M]
1 Standard Version 2 x 10 68 2.2 1
2 Standard Version 2 x 4 68 2.2 1
4 Standard Version 2 x 1.5 68 2.2 1
6 Standard Version 2 x 0.8 68 2.2 1
10 Standard Version 2 x 0.3 68 2.2 1
1 Medical Version (M5) 2 x 10 68 - 1
2 Medical Version (M5) 2 x 4 68 - 1
4 Medical Version (M5) 2 x 1.5 68 - 1
6 Medical Version (M5) 2 x 0.8 68 - 1
10 Medical Version (M5) 2 x 0.3 68 - 1
3
Power Entry Modules with Line Filter FKI
www.schurter.com/pg06
EMC Products
Diagrams
Standard version
1) Line
2) only FKI
3) Load
Medical version
N
PE
L
Cx
L1
L2
N’
PE’
L’
R
Cx
F2
F1
1) 2)
1) Line
2) Load
Derating Curves
2-pole
Admissible power ac-
ceptance in Watt per pole
0 20 40 60 80 100
0.2
0.0
I = << In
I = 0.7 In
I = 1.0 In
1.6
0.6
0.4
0.8
1.2
1.0
1.4
Ambient air temperature Ta °C
Attenuation Loss - - - - differential mode _____ common mode
Standard version
1 A 2 A 4 A 6 A
10 A
Medical version (M5)
1 A 2 A 4 A 6 A
10 A
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [M]
1 Standard Version 2 x 10 68 2.2 1
2 Standard Version 2 x 4 68 2.2 1
4 Standard Version 2 x 1.5 68 2.2 1
6 Standard Version 2 x 0.8 68 2.2 1
10 Standard Version 2 x 0.3 68 2.2 1
1 Medical Version (M5) 2 x 10 68 - 1
2 Medical Version (M5) 2 x 4 68 - 1
4 Medical Version (M5) 2 x 1.5 68 - 1
6 Medical Version (M5) 2 x 0.8 68 - 1
10 Medical Version (M5) 2 x 0.3 68 - 1
4
Power Entry Modules with Line Filter
FKI
www.schurter.com/pg06
EMC Products
Variants
Socket and fuse drawer included
Type Rated Current
[A]
Filter-Type Fuseholder Line Switch Housing Material: Housing Comment Order Number
FKI 1 Standard Version 2-pole 2-pole 45 Aluminum - 4304.4061
FKI 2 Standard Version 2-pole 2-pole 45 Aluminum - 4304.4062
FKI 4 Standard Version 2-pole 2-pole 45 Aluminum - 4304.4063
FKI 6 Standard Version 2-pole 2-pole 45 Aluminum - 4304.4064
FKI 10 Standard Version 2-pole 2-pole 45 Aluminum - 4304.4065
FKI 1 Medical Version (M5) 2-pole 2-pole 45 Aluminum - 4304.4091
FKI 2 Medical Version (M5) 2-pole 2-pole 45 Aluminum - 4304.4092
FKI 4 Medical Version (M5) 2-pole 2-pole 45 Aluminum - 4304.4092
FKI 6 Medical Version (M5) 2-pole 2-pole 45 Aluminum - 4304.4094
FKI 10 Medical Version (M5) 2-pole 2-pole 45 Aluminum - 4304.4095
FKI 1 Standard Version 2-pole 2-pole 50 Nickel plated steel - 4304.4021
FKI 2 Standard Version 2-pole 2-pole 50 Nickel plated steel - 4304.4022
FKI 4 Standard Version 2-pole 2-pole 50 Nickel plated steel - 4304.4023
FKI 6 Standard Version 2-pole 2-pole 50 Nickel plated steel - 4304.4024
FKI 10 Standard Version 2-pole 2-pole 50 Nickel plated steel - 4304.4025
FKI 1 Medical Version (M5) 2-pole 2-pole 50 Nickel plated steel - 4304.4066
FKI 2 Medical Version (M5) 2-pole 2-pole 50 Nickel plated steel - 4304.4067
FKI 4 Medical Version (M5) 2-pole 2-pole 50 Nickel plated steel - 4304.4068
FKI 6 Medical Version (M5) 2-pole 2-pole 50 Nickel plated steel - 4304.4069
FKI 10 Medical Version (M5) 2-pole 2-pole 50 Nickel plated steel - 4304.4070
Packaging unit 10 Pcs
Accessories
Description
Assorted Covers
Rear Cover
0859.0074
Mating Outlets/Connectors
Category / Description
Appliance OutletOverview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal 4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal 4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal 5091
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal 5092
Appliance Outletfurther types toFKI
ConnectorOverview complete
IEC Connector C15, Rewireable, Straight 0101
IEC Connector C15A, Rewireable, Straight 0102
IEC Connector C15A, Rewireable, Straight 0102-G
IEC Connector C15A, Rewireable, Angled 0112
IEC Connector C13, Rewireable, Angled 4012
Connectorfurther types toFKI ...
5
Power Entry Modules with Line Filter FKI
www.schurter.com/pg06
EMC Products
Category / Description
Power CordOverview complete
Power Cord with IEC Connector C13, Angled 0311
Power Cord with IEC Connector C13, Angled 3011
Power Cord with IEC Connector C13, Angled 3012
Power Cord with IEC Connector C13, Angled 3013
Power Cord with IEC Connector C13 3020
Power Cordfurther types toFKI ...
The specifications, descriptions and illustrations indicated in this document are based on
current information. All content is subject to modifications and amendments.