Product Brochure Eaton 9170+ UPS Features * N+X redundancy for both power and logic eliminates systemlevel single point-of-failure * Easily scalable to adapt to changing IT environments by simply adding power and/or battery modules * True double-conversion design * ABM(R) technology significantly increases battery service life * Universal components fit in any order without affecting UPS operation * Provides protection against all nine power problems * Complete offering of power management software included to ensure data integrity * Provides investment protection with a two-year limited warranty and a $250,000 load protection guarantee (U.S. and Canada) Product Snapshot Power Rating: 3-18 kVA Input Voltage: 200-240 Vac Output Voltage: 200-240 Vac Frequency: 50/60 Hz (auto-sensing) Configuration: Tower or rackmount The Eaton(R) 9170+ UPS is uniquely designed to meet the everchanging needs of customers with applications such as data centers, networks and call centers. Built for global deployment, the 9170+ is a scalable, modular, flexible solution that combines the highest level of reliability with the lowest cost of ownership in the 3-18 kVA range. The 9170+ enables customers to build a power solution specific to their needs, with an expandable level of redundancy and increases runtimes through plug-and-play 3 kVA UPS and battery modules. The 9170+ can be configured to fit three-, six-, nine- or twelve-slot enclosures, and is available for tower and rackmount applications. The 9170+ also features a Power Saver mode, a user-selectable feature that increases unit efficiency from 88% in normal operating mode to 97%. With its low initial investment, double-conversion technology, ABM battery management system and high-efficiency Power Saver mode, you never have to compromise reliability for efficiency. Unique to the 9170+ is its global deployment capability. By using a high-frequency design, housing both logic and power in the power module, and offering a single-cabinet design, distributors and purchasing departments around the world have fewer system components to contend with, regardless of where the system is deployed. Technical spotlight: Network level N+X redundancy As business moves from a "bricks and mortar" model to "clicks and mortar," the need for system availability at all levels of enterprise is rising exponentially. From servers to routers to telecommunication installations, the interdependence of the technological components of the wired world can make systems vulnerable to downtime. Many precautions and preventive measures are taken when designing the network, including power protection. systems with a single-module UPS. The 9170+ overcomes this potential obstacle with its modular design. Redundancy comes from the 3 kVA power modules plugged into the system. For example, if you have a 9 kVA solution, and are looking for N+2 redundancy, you only need a 15 kVA UPS (five power modules) with the 9170+, instead of 18 kVA. That's because the five UPS modules run in parallel within the system, giving you N+2 redundancy, without the additional cost and space requirements. In this shifting world, however, it's becoming more evident that simple power protection isn't enough. A new level of reliability is needed, one with redundancy, and thereby system availability. Today users can opt for an even greater degree of redundancy, with N+1, N+2, N+3, etc. However, this level of redundancy can quickly become cost prohibitive if the user is creating redundant The 9170+ eliminates a system-level single point-of-failure. Because both the logic and power are housed in the module and not in the enclosure, there is a redundancy for the entire UPS. This is a critical distinction when looking for multiple levels of redundancy in the UPS, as there is inherent vulnerability in a UPS that limits redundancy in any part of the system. Sample configuration With a variety cabinet sizes and a user-friendly design you can configure the scalable and redundant 9170+ with 3 kVA power modules and battery modules to grow with your requirements. 5 power modules: 15 kVA or 12 kVA N+1 or 9 kVA N+2 20 battery modules 9-slot UPS enclosure 2 EATON CORPORATION Eaton 9170+ UPS 9-slot battery enclosure Pre-configured systems with hardwire input and output POWER RATING INPUT CONNECTION OUTPUT CONNECTIONS DIMENSIONS H x W x D (IN/CM) WEIGHT (LB/KG) (1) 3-slot enclosure (1) power module (2) battery modules (1) caster kit 3 kVA expandable to 3 kVA N+1 Hardwired Hardwired 19.5 x 17.0 x 25.5/ 49.5 x 43.0 x 65.0 155.0/69.9 (1) 6-slot enclosure (1) power module (2) battery modules (1) caster kit 3 kVA expandable to 9 kVA N+X Hardwired Hardwired 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 155.0/69.9 (1) 6-slot enclosure (2) power modules (4) battery modules (1) caster kit 6 kVA expandable to 9 kVA N+X Hardwired Hardwired 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 232.0/104.8 (1) 6-slot enclosure (3) power modules (6) battery modules (1) caster kit 9 kVA expandable to 9 kVA N+X Hardwired Hardwired 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 346.0/156.7 PW9S9K (1) 9-slot enclosure (3) power modules (6) battery modules 9 kVA expandable to 18 kVA N+X Hardwired Hardwired 47.0 x 24.0 x 28.5/ 119.5 x 61.0 x 72.5 389.0/176.7 PW12S9K (1) 12-slot enclosure (3) power modules (6) battery modules 9 kVA expandable to 18 kVA N+X Hardwired Hardwired 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 427.0/193.7 PW12S12K (1) 12-slot enclosure (4) power modules (8) battery modules 12 kVA expandable to 18 kVA N+X Hardwired Hardwired 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 504.0/228.6 PW12S15K (1) 12-slot enclosure (5) power modules (10) battery modules 15 kVA expandable to 18 kVA N+X Hardwired Hardwired 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 581.0/263.5 PW12S18K (1) 12-slot enclosure (6) power modules (12) battery modules 18 kVA expandable to 18 kVA N+X Hardwired Hardwired 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 658.0/298.4 MODEL NUMBER Included Items PW3S3K PW6S3K PW6S6K PW6S9K Pre-configured systems with hardwire input and receptacles output options PW6S3K-PD (1) 6-slot enclosure (1) power module (2) battery modules (1) caster kit 3 kVA expandable to 9 kVA N+X Hardwired (2) L14-30R, (2) L6-30R, (12) 5-20R 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 192.0/86.9 (1) 6-slot enclosure (2) power modules (4) battery modules (1) caster kit 6 kVA expandable to 9 kVA N+X Hardwired (2) L14-30R, (2) L6-30R, (12) 5-20R 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 269.0/121.8 (1) 6-slot enclosure (3) power modules (6) battery modules (1) caster kit 9 kVA expandable to 9 kVA N+X Hardwired (2) L14-30R, (2) L6-30R, (12) 5-20R 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 346.0/160.7 PW9S9K-PD (1) 9-slot enclosure (3) power modules (6) battery modules 9 kVA expandable to 18 kVA N+X Hardwired (2) L14-30R, (2) L6-30R, (12) 5-20R 47.0 x 24.0 x 28.5/ 119.5 x 61.0 x 72.5 389.0/176.7 PW12S9K-PD (1) 12-slot enclosure (3) power modules (6) battery modules 9 kVA expandable to 18 kVA N+X Hardwired (3) L14-30R, (3) L6-30R, (12) 5-20R 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 427.0/193.7 PW12S12K-PD (1) 12-slot enclosure (4) power modules (8) battery modules 12 kVA expandable to 18 kVA N+X Hardwired (3) L14-30R, (3) L6-30R, (12) 5-20R 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 504.0/228.6 PW12S15K-PD (1) 12-slot enclosure (5) power modules (10) battery modules 15 kVA expandable to 18 kVA N+X Hardwired (3) L14-30R, (3) L6-30R, (12) 5-20R 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 581.0/263.5 PW12S18K-PD (1) 12-slot enclosure (6) power modules (12) battery modules 18 kVA expandable to 18 kVA N+X Hardwired (3) L14-30R, (3) L6-30R, (12) 5-20R 60.7 x 24.0 x 28.5/ 154.5 x 61.0 x 28.5 658.0/298.4 PW6S6K-PD PW6S9K-PD Pre-configured systems with line cord input and receptacles output options PW3S3K-LPD (1) 3-slot enclosure (1) power module (2) battery modules 3 kVA expandable to 3 kVA N+1 L14-30P (1) L14-30R, (1) L6-30R, (4) 5-20R 19.5 x 17.0 x 25.5/ 49.5 x 43.0 x 65.0 155.0/69.9 PW6S3K-LPD (1) 6-slot enclosure (1) power module (2) battery modules 3 kVA expandable to 6 kVA N+1 14-50P (2) L14-30R, (2) L6-30R, (12) 5-20R 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 192.0/86.9 PW6S6K-LPD (1) 6-slot enclosure (2) power modules (4) battery modules 6 kVA expandable to 6 kVA N+1 14-50P (2) L14-30R, (2) L6-30R, (12) 5-20R 33.3 x 17.0 x 25.5/ 84.5 x 43.0 x 65.0 269.0/121.8 Notes: 50/60 Hz automatic frequency selection. Input/Output voltages 208-240V or 100/200,120/208, 127/220, 110/220 and 120/240V. Split phase power module offers both high and low output voltage. Universal power module offers only high output voltage. All 3- and 6-slot enclosure dimensions include caster kit. EATON CORPORATION Eaton 9170+ UPS 3 UPS cabinet enclosures with hardwire input and output connections POWER RATING INPUT CONNECTION OUTPUT CONNECTIONS DIMENSIONS H x W x D (IN/CM) WEIGHT (LB/KG) PW9170+ 3-slot 3 kVA Hardwired Hardwired 17.8 x 17.0 x 25.5/ 45.0 x 43.0 x 65.0 66.0/30.0 PW9170+ 6-slot 3 to 9 kVA Hardwired Hardwired 31.5 x 17.0 x 25.0/ 80.0 x 43.0 x 65.0 103.0/47.0 PW9170+ 9-slot 3 to 18 kVA Hardwired Hardwired 47.0 x 24.0 x 28.5/ 119.5 x 61.0 x 72.5 158.0/72.0 Rackmount 3 to 18kVA Hardwired Hardwired 47.0 x 17.0 x 28.5/ 119.5 x 43.0 x 72.5 110.0/50.0 PW9170+ 12-slot 3 to 18 kVA Hardwired Hardwired 60.8 x 24.0 x 28.5/ 196.0/89.0 154.0 x 61.0 x 72.5 Rackmount 3 to 18 kVA Hardwired Hardwired 60.8 x 17.0 x 28.5/ 154.0 x 43.0 x 72.5 148.0/67.0 6-slot battery cabinet - DC interconnect option ASY-0525 required - 31.5 x 17.0 x 25.0/ 80.0 x 43.0 x 65.0 93.0/42.2 9-slot battery cabinet - DC interconnect option ASY-0525 required - 47.0 x 24.0 x 28.5/ 119.5 x 61.0 x 72.5 148.0/67.1 12-slot battery cabinet - DC interconnect option ASY-0525 required - 60.8 x 24.0 x 28.5/ 154.0 x 61.0 x 72.5 186.0/84.4 Split-phase power module 3 kVA/2.5 kW - - 4.2 x 14.1 x 15.3/ 10.6 x 35.8 x 38.9 17.0/7.7 Universal-phase power module 3 kVA/2.1 kW - - 4.2 x 14.1 x 15.3/ 10.6 x 35.8 x 38.9 17.0/7.7 - - - 4.2 x 7.0 x 14.8/ 10.6 x 17.8 x 37.6 30.0/13.6 3 kVA - - 4.2 x 14.1 x 15.3/ 10.6 x 35.8 x 38.9 17.0/7.7 MODEL NUMBER Battery cabinet enclosures Available modules Battery module 20-amp charger module Technical specifications 1 ELECTRICAL INPUT Voltage Voltage range Input power factor Frequency GENERAL 208-240V or 200/100, 208/120, 220/110, 240/120 Vac 176-276V .98 50/60 Hz (3 Hz) ELECTRICAL OUTPUT On utility voltage regulation On battery voltage regulation Efficiency mode Frequency regulation Language support Communication ports Communication slots SNMP capability Contact closures Emergency power off (EPO) general True double-conversion online Full system self-test on power up Automatic on overload or UPS failure See Pre-configured systems table ENVIRONMENTAL AND SAFETY 3% of nominal 3% of nominal 88% normal operation; 97% power saver (optional programmable) 3 Hz online; 0.1 Hz on battery COMMUNICATIONS LCD Topology Diagnostics UPS bypass Dimensions & weights Relative humidity REPO port 4 x 20 character backlit display, programmable English, French, Spanish and German UL, cUL FCC class A IEEE/ANSI C62.41 <50 dBA 0 to 40C (32 to 104F)/ -20 to 40C (60C without battery) -4 to 104F (140F without battery) 5% to 95%, non-condensing Meets NEC code 645-11 intent and UL requirements BATTERY RS-232 (DB-9) Two slots (standard) Web/SNMP enabled card options Relay card option Input for external EPO Safety markings EMC markings Surge suppression Audible noise Ambient operating/ storage temperature Internal battery type Battery runtime Battery replacement Recharge time Sealed, lead-acid; maintenance free See Battery Runtimes on back page Hot-swappable <4 hours standard 1. Due to continuing product improvement programs, specifications are subject to change without notice. EATON CORPORATION Eaton 9170+ UPS 4 LCD panel 9170+ 9-slot configuration 3 kVA power or charger module (one per slot) Communication cards Rackmount Battery module (two per slot) Maximum performance Maximum availability Maximum flexibility * The lowest overall cost of ownership is a direct result of the low initial investment, higher operating efficiencies and programmable high efficiency * Double-conversion online technology is universally recognized as providing the highest availability in an internet-centric global marketplace * Modular design delivers scalable, flexible solutions to constantly changing equipment requirements * A UPS solution that is as easy to install and operate as a PC --universal components fit in any order in any slot without affecting the operation of the system or its protection of the critical load * Provides protection against all nine common power problems * Easily expanded by installing additional power, charger or battery modules to support additional critical applications and devices Maximum service plans * Internal options: line cord, receptacles, communications * Featuring user-friendly LCD and two internal communication slots, which accept a wide variety of connectivity devices and the new ConnectUPS Web/ SNMP card * Lightweight, highperformance power and battery modules weigh under 30 pounds for easy service and hot-swapping Maximum reliability * N+X power and logic redundancy eliminates single point-of-failure, providing highest reliability and availability * Eaton Gold Plan Plus: Enhance and extend your standard UPS warranty with added assurance of knowing your UPS is installed and operating properly from the start * Comprehensive coverage for the entire UPS Rackmount configurations Adding yet another level of flexibility to the unique design of the 9170+ is the ability to configure it into a rackmount solution. Imagine all the standard benefits of the 9170+ installed in a standard 19-inch computer rack with return brackets. * External options: rackmount kit, casters (standard on 9- and 12-slot enclosures), extended runtime battery cabinets (housing up to 8 hours of additional runtime), wall-mounted maintenance bypass cabinets * On-site startup by authorized Eaton product representative * Replacement UPS or module delivered to your location * Original UPS or module picked up from your location * Please call for details * Redundant modularity virtually eliminates downtime and enhances serviceability * ABM technology significantly increases battery service life EATON CORPORATION Eaton 9170+ UPS 5 9170+ runtime charts IN MINUTES (FULL LOAD/HALF LOAD) SPLIT-PHASE MODULE ASY-0673 3 kVA 6 kVA 9 kVA 12 kVA 15 kVA 18 kVA 3 kVA 6 kVA 9 kVA 12 kVA 15 kVA 18 kVA Load (VA) number of strings (two battery modules per string) 1 String 2 String 3 String 4 String 5 String 6 String 7 String 8 String 9 String 10 String 11 String 12 String 6.5/16 27.5/67.5 11/27.5 6.5/16 40/98 16/40 9.5/23.5 6.5/16 53.5/132 21.5/53.5 13/31.5 9/21.5 6.5/16 67.5/167 27.5/68 16/40 11/27.5 8/20.5 6.5/16 83/204 33.5/83 20/49 13.5/33.5 10/25 8/20 98/242 40/98 23.5/58 16/40 12/30 9.5/23.5 115/283 46.5/115 27.5/67.5 19/46.5 14/35 11/27.5 132/324 53.5/132 31.5/78 21.5/53.5 16/40 12.5/30 149/365 60.5/149 35.5/88 24.5/60.5 18.5/45 14.5/35.5 167/408 67.5/167 40/98 27.5/68 20.5/50.5 16/40 13 String 14 String 15 String 16 String 17 String 18 String 19 String 20 String 21 String 22 String 23 String 24 String 185/456 75/185 44/109 30.5/75 23/56 18/44 283/692 115/285 68/167 46.5/115 35/86 27.5/68 302/750 123/302 73/179 50/123 37.5/92 29.5/73 323/790 132/324 78/191 53.5/132 40/98 31.5/78 345/850 140/345 83/204 57/140 42.5/105 33.5/83 365/900 149/365 88/210 60/149 45/111 35.5/88 387/955 157/388 93/229 64/157 48/118 38/93 408/1015 167/408 98/242 68/167 51/124 40/98 16/40 6.5/16 204/501 83/204 49/120 33.5/83 25/62 20/49 223/549 90/223 53.5/132 37/90 27.5/67.5 21.5/53.5 242/595 98/242 58/143 40/98 30/73.5 23.5/58 262/640 106/262 63/154 43/106 32.5/79.5 25.5/63 IN MINUTES (FULL LOAD/HALF LOAD) UNIVERSAL MODULE ASY-0674 3 kVA 6 kVA 9 kVA 12 kVA 15 kVA 18 kVA 3 kVA 6 kVA 9 kVA 12 kVA 15 kVA 18 kVA Load (VA) number of strings (two battery modules per string) 1 String 2 String 3 String 4 String 5 String 6 String 7 String 8 String 9 String 10 String 11 String 12 String 8/24 43/95 16/40 8/24 58/140 24/59 13/35 8/24 80/175 32/83 18/46 13/33 8/24 95/215 40/103 24/59 16/40 11.5/31 8/24 119/240 49/114 29/63 19.5/43.5 14.5/31.5 11/31.5 135/290 58/140 35/86 24/59 18/46 13/36 155/335 69/156 40/103 29/70 20.5/51 15.5/41 65/365 83/175 46/115 33/80 24/58 18/45 200/395 90/190 54/125 36/90 28/66 20.5/51 215/450 103/205 58/140 41/100 31/73 24/58 13 String 14 String 15 String 16 String 17 String 18 String 19 String 20 String 21 String 22 String 23 String 24 String 225/500 113/335 63/150 47/110 34/83 27/65 335/690 156/333 100/210 70/156 51/127 41/100 350/720 165/350 107/225 75/165 56/130 44/105 365/780 175/365 115/240 80/175 58/140 45/115 375/850 183/385 121/255 85/185 61/149 48/122 395/890 190/395 125/270 90/195 66/158 54/131 425/920 198/420 135/280 95/205 71/165 57/137 450/950 205/440 143/290 100/215 73/170 58/140 24/59 8/24 245/540 123/255 73/165 52/121 38/94 31.5/72 270/600 135/273 80/178 56/130 41.5/103 34.5/77 290/620 143/290 86/190 58/140 44.5/113 36/83 315/650 148/315 93/200 65/147 46.5/117 38/94 For additional information about the 9170+, please visit Eaton.com/9170+ or call 800.356.5794. Eaton Corporation Electrical Sector 1111 Superior Avenue Cleveland, OH 44114 USA Eaton.com (c) 2012 Eaton Corporation All Rights Reserved Printed in USA 9170PLFXA November 2012 Eaton is a registered trademark of Eaton Corporation. All other trademarks are property of their respective owners.