CSM_H3RN_DS_E_3_2
1
Solid-state timer
H3RN
Ultra-slim Timer for G2R Relay Socket
Pin configuration compatible with G2R Relay and mounts to the
P2R/P2RF Socket.
Standard multiple time ranges and multiple operating modes.
Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Volt-
age, and EMC Directives.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
1. Output
1: SPDT
2: DPST-NO
2. Time Range
None: Short-time range (0.1 s to 10 min)
1: Long-time range (0.1 min to 10 hrs)
Ordering Information
List of Models
Accessories (Order Separately)
Connecting Socket
H3RN-@@
1 2
Supply voltage Time-limit contact Short-time range model
(0.1 s to 10 min)
Long-time range model
(0.1 min to 10 h)
24 VAC;
12, 24 VDC
SPDT H3RN-1 H3RN-11
DPST-NO H3RN-2 H3RN-21
Note: Specify both the model number and supply voltage when ordering.
Example: H3RN-1 24 VAC
Supply voltage
Timer Track mounting/Front connecting socket Back connecting socket
H3RN-1/-11 P2RF-05-E P2R-057P
H3RN-2/-21 P2RF-08-E P2R-087P
H3RN
2
Specifications
Ratings
Note: 1. When using the H3RN in any place where the ambient temperature is more than 50°C, supply 90% to 110% of the rated voltages
(12 VDC: 95% to 110% of the rated voltage).
2. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.
Characteristics
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
Time ranges 0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max.
selectable)
0.1 min to 10 h (1 min, 10 min, 1 h, or 10 hrs max.
selectable)
Rated supply voltage (See note 2.) 24 VAC (50/60 Hz); 12, 24 VDC
Pin type Plug-in
Operating mode ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch
Operating voltage range 85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
(See note 1.)
Reset voltage 10% max. of rated supply voltage
Power consumption 24 VAC: Relay ON: approx. 0.8 VA
12 VDC: Relay ON: approx. 0.5 W
24 VDC: Relay ON: approx. 0.4 W
Control outputs 3 A at 250 VAC, resistive load (cosφ = 1) (G6B-2@14P-FD-US used (Contact materials : AgSnIn))
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
Accuracy of operating time ±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error ±15%±50 ms FS max.
Reset time Min. power-opening time: 12, 24 VDC: 0.1 s max. (including halfway reset)
24 VAC: 0.5 s max. (including halfway reset)
Influence of voltage ±2% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different
poles)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Shock resistance Destruction: 300 m/s2
Malfunction: 100 m/s2
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load at 1,800 operations/h)
Impulse withstand voltage Between power terminals: 1 kV
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Degree of protection IP40 (Terminal screw sections are excluded.)
Weight Approx. 18 g
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC51000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Approved standards UL508, CSA C22.2 No. 14
Conforms to EN61812-1, IEC60664-1 4 kV/2.
Output category according to IEC60947-5-1.
H3RN
3
Connections
Connection
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal.
Use the H3RN in interval mode as shown in the following timing charts.
OUT PW
Bottom View
H3RN-1/H3RN-11 H3RN-2/H3RN-21
DIN Indication DIN Indication
OUT PW
Bottom View
Timer
circuit Timer
circuit
H3RN-2/H3RN-21
External input
Power (3-8)
External short circuit (1-4)
External input (1-3)
Timer
circuit
50 ms
min.
Time limit contact
NO (6-5)
Run/Power indicator (PW)
Output indicator (OUT)
Note: t: Set time
Rt: Reset time
!Caution
Be careful when connecting wires.
Mode Terminals
Pulse operation Power supply between 3 and 8
Short-circuit between 4 and 1
Input signal between 3 and 1
Operating mode; interval and all other
modes
Power supply between 1 and 8
H3RN
4
Operation
Timing Chart
Note: t: Set time
Rt: Reset time
Operating mode Timing chart
H3RN-1/H3RN-11 H3RN-2/H3RN-21
ON-delay
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Interval
Power
Output
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Flicker OFF-start
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Flicker ON-start
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
H3RN
5
DIP Switch Settings
The 1-s range and ON-delay mode for H3RN-1/-2, 1-min range and ON-delay mode for H3RN-11/-21 are factory-set before shipping.
Time Ranges
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes
Note: The right two DIP switch pins are used to select the operating modes.
Nomenclature
Model Time range Time setting
range
Setting Factory-set
H3RN-1,
H3RN-2
1 s 0.1 to 1 s Yes
10 s 1 to 10 s No
1 min 0.1 to 1 min No
10 min 1 to 10 min No
H3RN-11,
H3RN-21
1 min 0.1 to 1 min Yes
10 min 1 to 10 min No
1 h 0.1 to 1 h No
10 h 1 to 10 h No
Operating mode Setting Factory-set
ON-delay Yes
Interval No
Flicker OFF-start No
Flicker ON-start No
Run/Power Indicator (Green)
(Lit: Power ON)
Output Indicator (Orange)
(Lit: Output ON)
Main Dial
Set the desired time according to time
range selectable by DIP switch.
H3RN
6
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Timers
H3RN-1/H3RN-11 Front Mounting
H3RN-2/H3RN-21 Front Mounting
Mounting Height
P2RF-@-E P2R-@7P
H3RN Series H3RN Series
Use the P2RF-@-E or P2R-@7P to mount the H3RN. When ordering any one of these sockets,
replace "@" with "05" for SPDT or "08" for DPST-NO.
The P2RF-@ cannot be used because the hook is a different shape.
P2RF-@-E
Socket
79.5 (see note 1)
(83.5) (see note 2)
80.9 (see note 1)
(84.9) (see note 2)
P2R-@7P
Socket
Note: 1. The value shown indicates the dimension for the
P2RF-05-E with the PFP-@N Mounting Rail.
The value is 71.5 mm when using the PFP-N@2.
2. The value shown in parentheses indicates the
dimension for the P2RF-08-E with the PFP-@N
Mounting Rail.
The value is 75.5 mm when using the PFP-N@2.
Note: There are no restrictions to the
mounting direction.
H3RN
7
Safety Precautions
Correct Use
When using the H3RN in any place where the ambient temperature
is more than 50°C, supply 90% to 110% of the rated voltages (at
12 VDC: 95% to 110%).
Do not leave the H3RN in time-up condition (i.e., with the internal
relay in an ON state) for a long period of time (for example, more
than one month in any place where the ambient temperature is high),
otherwise the internal parts may become damaged. Therefore, the
use of the H3RN with a relay as shown in the following circuit dia-
gram is recommended.
The H3RN must be disconnected from the socket when setting the
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.
Do not connect the H3RN as shown in the following circuit diagram
on the right hand side, otherwise the H3RN’s internal contacts differ-
ent from each other in polarity may become short-circuited.
Use the following safety circuit when building a self-holding circuit
with the H3RN and an auxiliary relay, such as a G2R Relay, in combi-
nation.
In the case of the above circuit, the H3RN will be in pulse operation.
Therefore, if the circuit shown on page 3 is used, no auxiliary relay
will be required.
Do not use the SPDT contact in a circuit which may cause short-cir-
cuiting at three points (otherwise, short-circuiting of the power supply
may occur) because the SPDT contact of H3RN-1/-11 is composed
of an SPST-NC contact.
Do not set to the minimum setting in the flicker modes, otherwise the
contact may be damaged.
Do not use the H3RN in places where there is excessive dust, corro-
sive gas, or direct sunlight.
Make sure that there is a space of 3 mm or more between any H3RN
Models next to each other. (When using the P2RF-@-E Socket, a
space of 3 mm or more will be secured.) If a space of 3 mm or more
is not secured, the ambient temperature must be less than 50°C.
The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3RN.
Precautions for EN61812-1
Conformance
The H3RN as a built-in timer conforms to EN61812-1 provided that
the following conditions are satisfied.
Handling
Do not touch the DIP switch while power is supplied to the H3RN.
Before dismounting the H3RN from the socket, make sure that no
voltage is imposed on any terminal of the H3RN.
Wiring
Basic insulation is ensured between the H3RN’s operating circuit and
control output.
Basic insulation: Overvoltage category III,
pollution degree 2
(with a clearance of 3.0 mm and a creepage
distance of 3.0 mm at 240 VAC)
The clearance from the edge of the P2R-087P Socket to internal,
current-carrying metal parts is 1.3 mm. Position the H3RN to provide
the necessary clearance for the voltage used.
When using the P2RF-@-E or P2R-057P Socket, basic insulation is
ensured in the mounted condition for a voltage of 250 VAC max.
X1T X2
X
2
/bT/a X
1
/a X
1
/a
X:
Auxiliary relay such as G2R Relay
L
2
L
1
L
2
L
1
Correct Incorrect
G2R Relay
3
4
2
15
Short-circuit current
Power supply
for load
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyers request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.9
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/