Catalogue Supplement
Open Circuit-Breakers
from 630 A to 6300 A
tra Combinations
SystemsIndustrial Automation
Building Automation
Think future. Switch to green.
Moeller NK1230-1045GB
Description
IZM Circuit-Breakers, IN Switch-Disconnectors
The new open IZM circuit-breaker series, offers complete coverage of the range
from 800 – 6300 A with just the frame sizes 2 and 3
The new, compact frame size 1 (which can be installed in a switchpanel which is just
400 mm wide) extends the rated current range of the series to the lower end of the
range to include 630 A. If required, this range can be extended even further by ex-
changing the rating plugs, which will extend the range to 250 A, and includes a set-
ting range of 0.4 – 1 x In.
If however, your application requires switching at the higher-end, the new IZM of-
fers the perfect solution with a maximum breaking capacity of 150 kA/415 V.
In addition, the entire range of accessories is identical for all three frame sizes.
Moreover, the entire system can be centrally operated from a PC via PROFIBUS-DP,
where it can be monitored, controlled and switched. If maintenance should prove
necessary because of a fault, the maintenance personnel can be informed by SMS.
as a feeder, distributor, coupler and outgoing circuit-breaker
for switching and protecting motors, generators, transformers, busbar systems
and cables
for use as a power disconnecting device (IEC 60 204)
3 frame sizes for 630 – 6300 A
3 and 4 pole versions with Ue = 690 V AC
(Ue = 1000 V AC on request)
4 switching capacities from 50 – 150 kA/415 V
equipped as standard with a crank handle with spring-operated stored energy
mechanism, auxiliary contact (2 M, 2 B), trip-indicating auxiliary contact (1 CO)
Fixed Installation and Withdrawable
The IZM circuit-breakers conform to:
IEC/EN 60 947
VDE 0660 (German Standard)
Climatic proofing to IEC/EN 60 068-2-30
The IZM is suitable for use in climatic conditions to IEC/EN 60 068-2-30. It can be
used in enclosed areas which are not subject to difficult operating conditions (dust,
corrosive or caustic vapours). Specialized enclosures must be considered with hu-
mid and dusty conditions.
The IZM series has a uniform height and depth. The device width varies depending
on the number of poles and the frame size.
The withdrawable versions have slightly increased depth dimensions.
The electronic microprocessor controlled control unit is independent of the auxiliary
voltage.
It offer optimum protection for each application.
All IZM are equipped as standard up to 5000 A with horizontal connections
(6300 A vertical).
The following connections are possible as options:
vertical connections
accessible from the front, single-hole fitting
accessible from the front, double-hole fitting (according to DIN 43 673)
flange connections (withdrawable)
With a communication module, a connection to the PROFIBUS-DP is very simple to
realize. The transfer of circuit-breaker data and the switching and control via a cen-
tral PC is unproblematic in this manner. Data acquisition and energy management
are enabled in conjunction with the measurement function. A significant reduction
in power costs is noticeable.
An internal circuit-breaker bus allows communication between the IZM and the typ-
ical secondary devices, e.g. for the display of measurement values or reasons which
initiated a trip, or reading further switchpanel signals.
It is possible to remotely observe, switch and define parameters for the IZM.
The connection of the auxiliary circuits depends on the respective installation type:
•withdrawable
The internal auxiliary contacts are connected with circuit-breaker side plugs. In the
connected state, they are connected with the sliding module in the socket base.
fixed mounted
Auxiliary switches are plugged directly onto the IZM.
Many accessory parts (auxiliary contacts, voltage releases, etc.) can be retrofitted
or exchanged, in order to adapt the IZM to new requirements.
The main switching contacts can be exchanged on site, in order to extend the elec-
trical lifespan of the IZM.
Areas of Application
Versions
Installation Methods
Standards
Operational Conditions
Uniform Dimensions
Control Unit
Main Current Connections
Communication Capability
Auxiliary Connections
Modularity
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
1
Moeller NK1230-1045GB
IZM Circuit-Breakers, IN Switch-Disconnectors
Contents
Circuit-breakers Switch-disconnectors
from 630 A to 6300 A
Page
Frame Size 1, 2 and 3 Overview 2
Options for Electronic Release Overview 4
IZM circuit-breakers
3-pole
Frame size 1
for the distribution circuit protection (A) 6
for selectively-opening circuit-breakers (V) 6
for universal protection (U) 6
with a digital circuit-breaker (D) 6
Frame size 2 and 3
for the distribution circuit protection (A) 8
for selectively-opening circuit-breakers (V) 8
for universal protection (U) 10
with a digital circuit-breaker (D) 10
4-pole
Frame size 1
for the distribution circuit protection (A) 12
for selectively-opening circuit-breakers (V) 12
for universal protection (U) 12
with a digital circuit-breaker (D) 12
Frame size 2 and 3
for the distribution circuit protection (A) 14
for selectively-opening circuit-breakers (V) 14
for universal protection (U) 16
with a digital circuit-breaker (D) 16
IN switch-disconnectors
3 and 4-pole
Frame size 1 18
Frame size 2 and 3 20
Page
Accessories 22
Additional functions for overcurrent release 22
Measurement converter for the neutral pole 23
Components for communication 24
Auxiliary contacts 28
Motor operators 28
Motor cut-off switch 28
Operations counter 28
Voltage release condition signal 28
Closing release 30
Shunt release 30
Undervoltage release 31
Locking facilities 32
Locking arrangement 32
Electrical ON 33
Emergency-stop button 33
Remote reset 33
Automatic reset of the re-closing lockout 33
Bracket for fixed mounted breaker 34
Door sealing frame 34
Protective covers 34
Test unit 34
Rated current rating plug 35
Withdrawable units 36
Connection technology for fixed installation 40
Connectors for withdrawable unit 42
Technical data
Selectivity table 43
IZM trip characteristics 50
IZM circuit-breakers 52
IN switch-disconnectors 56
IZM control unit 60
Permissible continuous current 61
Motor operator, voltage release, auxiliary contacts 62
Dimensions 63
Moeller NK1230-1045GB
IZM Circuit-Breakers
Technical Overview
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IN Switch-Disconnectors
Technical Overview
Circuit-breakers
with main switch and
isolating characteristics of 630 – 6300 A
Basic
switching capacity (B)
Normal
switching capacity (N)
High switching capaci-
ty (H)
Limited
switching capacity (L)
Switch-disconnectors
With main switch and isolating characteristics
from 630 6300 A
Rated ultimate short-circuit breaking capacity Icu with rated operational voltage Ue
Rated current
In
A
Icu = Ics
kA
440 V 690 V 440 V 690 V 440 V 690 V 440 V 690 V Rated current In
Rated short-circuit making capacity Icm
Rated short-time withstand current Icw t = 1 s
IZM IN
Frame size 1 INB1-...
630 – 1600 50 42 65 50 Frame size 1 In = 630 – 1600 A Icm/kA 105
Icw/kA 42
aPage 6, 12 aPage 18
Frame size 2 INN1-...
800 – 3200 55 50 80 75 100 85 150 65 Frame size 1 In = 630 – 1600 A Icm/kA 143
Icw/kA 50
aPage 8, 14 aPage 18
Frame size 3 INB2-...
4000 – 6300 100 85 150 65 Frame size 2 In = 800 – 3200 A Icm/kA 121
Icw/kA 55
aPage 8, 14 aPage 20
INN2-...
Frame size 2 In = 800 – 3200 A Icm/kA 176
Icw/kA 65
aPage 20
INH2
Frame size 2 In = 800 – 3200 A Icm/kA 220
In = 800 – 2500 A Icw/kA 65
In = 3200 A Icw/kA 80
aPage 20
INH3
Frame size 3 In = 4000 – 6300 A Icm/kA 220
In = 4000 – 5000 A Icw/kA 80
In = 6300 A Icw/kA 100
aPage 20
Electronic control options for IZM circuit-
breakers:
Standard circuit-breaker A
Selectively-operating circuit-breakers V
Universal circuit-breakers U
Digital circuit-breakers D
aPage 4
2 3
Moeller NK1230-1045GB
IZM Circuit-Breakers
Technical Overview
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IN Switch-Disconnectors
Technical Overview
Circuit-breakers
with main switch and
isolating characteristics of 630 6300 A
Basic
switching capacity (B)
Normal
switching capacity (N)
High switching capaci-
ty (H)
Limited
switching capacity (L)
Switch-disconnectors
With main switch and isolating characteristics
from 630 – 6300 A
Rated ultimate short-circuit breaking capacity Icu with rated operational voltage Ue
Rated current
In
A
Icu = Ics
kA
440 V 690 V 440 V 690 V 440 V 690 V 440 V 690 V Rated current In
Rated short-circuit making capacity Icm
Rated short-time withstand current Icw t = 1 s
IZM IN
Frame size 1 INB1-...
630 – 1600 50 42 65 50 Frame size 1 In = 630 – 1600 A Icm/kA 105
Icw/kA 42
aPage 6, 12 aPage 18
Frame size 2 INN1-...
800 – 3200 55 50 80 75 100 85 150 65 Frame size 1 In = 630 – 1600 A Icm/kA 143
Icw/kA 50
aPage 8, 14 aPage 18
Frame size 3 INB2-...
4000 – 6300 100 85 150 65 Frame size 2 In = 800 – 3200 A Icm/kA 121
Icw/kA 55
aPage 8, 14 aPage 20
INN2-...
Frame size 2 In = 800 – 3200 A Icm/kA 176
Icw/kA 65
aPage 20
INH2
Frame size 2 In = 800 – 3200 A Icm/kA 220
In = 800 – 2500 A Icw/kA 65
In = 3200 A Icw/kA 80
aPage 20
INH3
Frame size 3 In = 4000 – 6300 A Icm/kA 220
In = 4000 – 5000 A Icw/kA 80
In = 6300 A Icw/kA 100
aPage 20
Electronic control options for IZM circuit-
breakers:
Standard circuit-breaker A
Selectively-operating circuit-breakers V
Universal circuit-breakers U
Digital circuit-breakers D
aPage 4
2 3
Moeller NK1230-1045GB
IZM Circuit-Breakers
Options for Electronic Release Overview
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
Options for Electronic Release Overview
IZM ...-A...
Circuit-breakers for distribution circuit protection
630 – 6300 A
IZM ...-V...
Selectively-operating circuit-breakers
630 – 6300 A
IZM ...-U...
Universal circuit-breakers
630 6300 A
IZM ...-D...
Digital circuit-breakers
630 6300 A
Standard protective functions
Overload protection IrLK K K K
Adjustable delay time tr K K
Short-time delay
short-circuit protective device Isd
SK K K
Non-delayed
short-circuit protective device Ii
IK K K K
Optional protective functions
Neutral conductor protection Nk K K
Earth-fault protection Gk k k
Additional functions
N-conductor protection switch on / off k K K
Short-time delay short-circuit protection device
can be switched on / off K K
Non-delayed short-circuit protection device
can be switched on / off K K
Thermal memory
can be switched on / off K K
Load monitoring K K
Short-time delayed short-circuit protective device
convertible to I2t K K
Adjustable non-delayed short-circuit protective de-
vice KK K
Overload protection convertible I4t K K
Overload protection can be switched on / off k K
Adjustable N-conductor protection k K
Convertible parameter sets k K
Parameter definition and visualization
Parameter definition via rotary coding switch
(10 stage) K K K
Parameter definition via communication
(absolute values) k K
Parameter definition via menu (absolute values) K
Remote parameter definition of the basic functions k K
Remote parameter definition of the additional func-
tions k K
Alphanumeric LCD k K
Graphic LCD k
Measurement functions
“Plus” measurement functions k k
“High end” measurement functions k k
Communication
Internal system bus K K
PROFIBUS-DP communication k k
Communication via Ethernet k k
Notes Kstandard
koptional
54
Moeller NK1230-1045GB
IZM Circuit-Breakers
Options for Electronic Release Overview
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
Options for Electronic Release Overview
IZM ...-A...
Circuit-breakers for distribution circuit protection
630 6300 A
IZM ...-V...
Selectively-operating circuit-breakers
630 6300 A
IZM ...-U...
Universal circuit-breakers
630 – 6300 A
IZM ...-D...
Digital circuit-breakers
630 – 6300 A
Standard protective functions
Overload protection IrLK K K K
Adjustable delay time tr K K
Short-time delay
short-circuit protective device Isd
SK K K
Non-delayed
short-circuit protective device Ii
IK K K K
Optional protective functions
Neutral conductor protection Nk K K
Earth-fault protection Gk k k
Additional functions
N-conductor protection switch on / off k K K
Short-time delay short-circuit protection device
can be switched on / off K K
Non-delayed short-circuit protection device
can be switched on / off K K
Thermal memory
can be switched on / off K K
Load monitoring K K
Short-time delayed short-circuit protective device
convertible to I2t K K
Adjustable non-delayed short-circuit protective de-
vice KK K
Overload protection convertible I4t K K
Overload protection can be switched on / off k K
Adjustable N-conductor protection k K
Convertible parameter sets k K
Parameter definition and visualization
Parameter definition via rotary coding switch
(10 stage) K K K
Parameter definition via communication
(absolute values) k K
Parameter definition via menu (absolute values) K
Remote parameter definition of the basic functions k K
Remote parameter definition of the additional func-
tions k K
Alphanumeric LCD k K
Graphic LCD k
Measurement functions
“Plus” measurement functions k k
“High end” measurement functions k k
Communication
Internal system bus K K
PROFIBUS-DP communication k k
Communication via Ethernet k k
Notes Kstandard
koptional
54
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Basic switching capacity (B) Normal switching capacity (N)
Icu = Ics = 50 kA at 415 V 50/60 Hz Icu = Ics = 65 kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Notes
Rated current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Frame size 1
Circuit-breakers for distribution circuit protection (A)
630 315 – 630 1260 – 5040 IZMB1-A630
229889 1 off IZMN1-A630
229894 1 off Adjustable overload release Ir = 0.5 – 1 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable non-delayed short-circuit release Ii = 2 8 x In
800 400 – 800 1600 – 6400 IZMB1-A800
229890 IZMN1-A800
229895
1000 500 – 1000 2000 – 8000 IZMB1-A1000
229891 IZMN1-A1000
229896
1250 625 – 1250 2500 – 10000 IZMB1-A1250
229892 IZMN1-A1250
229898
1600 800 – 1600 3200 – 12800 IZMB1-A1600
229893 IZMN1-A1600
229899
Circuit-breaker for selective operation (V) and motor protection
630 252 – 630 788 – 7560 12600 IZMB1-V630
229900 1 off IZMN1-V630
229905 1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
•Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
Non-delayed short-circuit release Ii f 20 x In
800 320 – 800 1000 – 9600 16000 IZMB1-V800
229901 IZMN1-V800
229906
1000 400 – 1000 1250 – 12000 20000 IZMB1-V1000
229902 IZMN1-V1000
229907
1250 500 – 1250 1563 – 15000 25000 IZMB1-V1250
229903 IZMN1-V1250
229908
1600 640 – 1600 2000 – 19200 32000 IZMB1-V1600
229904 IZMN1-V1600
229909
Circuit-breaker for universal protection (U) and motor protection
630 252 – 630 788 – 7560 1.5 – 12 x In
OFF IZMB1-U630
229913 1 off IZMN1-U630
229918 1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 30 s with setting to J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
•Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release Ii = 1.5 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
800 320 – 800 1000 – 9600 IZMB1-U800
229914 IZMN1-U800
229919
1000 400 – 1000 1250 – 12000 IZMB1-U1000
229915 IZMN1-U1000
229920
1250 500 – 1250 1563 – 15000 IZMB1-U1250
229916 IZMN1-U1250
229921
1600 640 – 1600 2000 – 19200 IZMB1-U1600
229917 IZMN1-U1600
229922
Digital circuit-breaker (D)
630 252 – 630 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB1-D630
229923 please
enquire 1 off IZMN1-D630
229933 please
enquire 1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 30 s with setting to J
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
•Delay time tsd = OFF, 20, 100, 200, 300, 400, 500, 1000, 2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release Ii = 1.5 x In0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
800 320 – 800 IZMB1-D800
229927 IZMN1-D800
229934
1000 400 – 1000 IZMB1-D1000
229930 IZMN1-D1000
229935
1250 500 – 1250 IZMB1-D1250
229931 IZMN1-D1250
229936
1600 640 – 1600 IZMB1-D1600
229932 IZMN1-D1600
229937
I I
6 7
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Basic switching capacity (B) Normal switching capacity (N)
Icu = Ics = 50 kA at 415 V 50/60 Hz Icu = Ics = 65 kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Notes
Rated current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Frame size 1
Circuit-breakers for distribution circuit protection (A)
630 315 – 630 1260 – 5040 IZMB1-A630
229889 1 off IZMN1-A630
229894 1 off Adjustable overload release Ir = 0.5 – 1 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable non-delayed short-circuit release Ii = 2 – 8 x In
800 400 – 800 1600 – 6400 IZMB1-A800
229890 IZMN1-A800
229895
1000 500 – 1000 2000 – 8000 IZMB1-A1000
229891 IZMN1-A1000
229896
1250 625 – 1250 2500 – 10000 IZMB1-A1250
229892 IZMN1-A1250
229898
1600 800 – 1600 3200 – 12800 IZMB1-A1600
229893 IZMN1-A1600
229899
Circuit-breaker for selective operation (V) and motor protection
630 252 – 630 788 – 7560 12600 IZMB1-V630
229900 1 off IZMN1-V630
229905 1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
•Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
Non-delayed short-circuit release Ii f 20 x In
800 320 – 800 1000 – 9600 16000 IZMB1-V800
229901 IZMN1-V800
229906
1000 400 – 1000 1250 – 12000 20000 IZMB1-V1000
229902 IZMN1-V1000
229907
1250 500 – 1250 1563 – 15000 25000 IZMB1-V1250
229903 IZMN1-V1250
229908
1600 640 – 1600 2000 – 19200 32000 IZMB1-V1600
229904 IZMN1-V1600
229909
Circuit-breaker for universal protection (U) and motor protection
630 252 – 630 788 – 7560 1.5 – 12 x In
OFF IZMB1-U630
229913 1 off IZMN1-U630
229918 1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 – 30 s with setting to J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
•Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
800 320 – 800 1000 – 9600 IZMB1-U800
229914 IZMN1-U800
229919
1000 400 – 1000 1250 – 12000 IZMB1-U1000
229915 IZMN1-U1000
229920
1250 500 – 1250 1563 – 15000 IZMB1-U1250
229916 IZMN1-U1250
229921
1600 640 – 1600 2000 – 19200 IZMB1-U1600
229917 IZMN1-U1600
229922
Digital circuit-breaker (D)
630 252 – 630 1.25 x In 0.8 x Icw 1.5 x In 0.8 x Ics IZMB1-D630
229923 please
enquire 1 off IZMN1-D630
229933 please
enquire 1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 – 30 s with setting to J
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In – 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
•Delay time tsd = OFF, 20, 100, 200, 300, 400, 500, 1000, 2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release Ii = 1.5 x In – 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
800 320 – 800 IZMB1-D800
229927 IZMN1-D800
229934
1000 400 – 1000 IZMB1-D1000
229930 IZMN1-D1000
229935
1250 500 – 1250 IZMB1-D1250
229931 IZMN1-D1250
229936
1600 640 – 1600 IZMB1-D1600
229932 IZMN1-D1600
229937
I I
6 7
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55 kA at 415 V 50/60 Hz Icu = Ics = 80 kA at 415 V 50/60 Hz Icu = Ics = 100 kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Notes
Rated current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Circuit-breakers for distribution circuit protection (A)
Frame size 2
800 400 – 800 1600 – 6400 IZMB2-A800
225530 1 off IZMN2-A800
225534 1 off IZMH2-A800
225545 1 off Adjustable overload release Ir = 0.5 x In
Delay time tr = 10 s at 6 x Ir
Adjustable non-delayed short-circuit release
Ii = 2 8 x In
1000 500 – 1000 2000 – 8000 IZMB2-A1000
225531 IZMN2-A1000
225535 IZMH2-A1000
225546
1250 625 – 1250 2500 – 10000 IZMB2-A1250
225532 IZMN2-A1250
225536 IZMH2-A1250
225547
1600 800 – 1600 3200 – 12800 IZMB2-A1600
225533 IZMN2-A1600
225537 IZMH2-A1600
225548
2000 1000 – 2000 4000 – 16000 IZMB2-A2000
229979 IZMN2-A2000
225538 IZMH2-A2000
225549
2500 1250 – 2500 5000 – 20000 IZMB2-A2500
229980 IZMN2-A2500
225539 IZMH2-A2500
225550
3200 1600 – 3200 6400 – 25600 IZMB2-A3200
229982 IZMN2-A3200
225540 IZMH2-A3200
225551
Circuit-breaker for selective operation (V) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 16000 IZMB2-V800
229995 1 off IZMN2-V800
230004 1 off IZMH2-V800
230014 1 off Adjustable overload release Ir = 0.4 x In
Delay time tr = 10 s at 6 x Ir
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
Delay time tsd = 0, 20 (motor protection),
100, 200, 300, 400 ms
Non-delayed short-circuit release
Ii f 20 x In
max. 50 kA
1000 400 – 1000 1250 – 12000 20000 IZMB2-V1000
229996 IZMN2-V1000
230007 IZMH2-V1000
230016
1250 500 – 1250 1563 – 15000 25000 IZMB2-V1250
229997 IZMN2-V1250
230008 IZMH2-V1250
230017
1600 640 – 1600 2000 – 19200 32000 IZMB2-V1600
229998 IZMN2-V1600
230009 IZMH2-V1600
230018
2000 800 – 2000 2500 – 24000 40000 IZMB2-V2000
229999 IZMN2-V2000
230010 IZMH2-V2000
230027
2500 1000 – 2500 3125 – 30000 50000 IZMB2-V2500
230001 IZMN2-V2500
230011 IZMH2-V2500
230028
3200 1280 – 3200 4000 – 38400 50000 IZMB2-V3200
230003 IZMN2-V3200
230012 IZMH2-V3200
230029
Frame size 3
4000 1600 – 4000 5000 – 48000 50000 IZMH3-V4000
230051 please
enquire 1 off
5000 2000 – 5000 6250 – 60000 IZMH3-V5000
230053
6300 2520 – 6300 7875 – 75600 IZMH3-V6300-AV
230056
I
I
8 9
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55 kA at 415 V 50/60 Hz Icu = Ics = 80 kA at 415 V 50/60 Hz Icu = Ics = 100 kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Notes
Rated current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Circuit-breakers for distribution circuit protection (A)
Frame size 2
800 400 800 1600 6400 IZMB2-A800
225530 1 off IZMN2-A800
225534 1 off IZMH2-A800
225545 1 off Adjustable overload release Ir = 0.5 x In
Delay time tr = 10 s at 6 x Ir
Adjustable non-delayed short-circuit release
Ii = 2 – 8 x In
1000 500 1000 2000 8000 IZMB2-A1000
225531 IZMN2-A1000
225535 IZMH2-A1000
225546
1250 625 – 1250 2500 – 10000 IZMB2-A1250
225532 IZMN2-A1250
225536 IZMH2-A1250
225547
1600 800 1600 3200 12800 IZMB2-A1600
225533 IZMN2-A1600
225537 IZMH2-A1600
225548
2000 1000 – 2000 4000 – 16000 IZMB2-A2000
229979 IZMN2-A2000
225538 IZMH2-A2000
225549
2500 1250 – 2500 5000 – 20000 IZMB2-A2500
229980 IZMN2-A2500
225539 IZMH2-A2500
225550
3200 1600 – 3200 6400 – 25600 IZMB2-A3200
229982 IZMN2-A3200
225540 IZMH2-A3200
225551
Circuit-breaker for selective operation (V) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 16000 IZMB2-V800
229995 1 off IZMN2-V800
230004 1 off IZMH2-V800
230014 1 off Adjustable overload release Ir = 0.4 x In
Delay time tr = 10 s at 6 x Ir
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
Delay time tsd = 0, 20 (motor protection),
100, 200, 300, 400 ms
Non-delayed short-circuit release
Ii f 20 x In
max. 50 kA
1000 400 – 1000 1250 – 12000 20000 IZMB2-V1000
229996 IZMN2-V1000
230007 IZMH2-V1000
230016
1250 500 – 1250 1563 – 15000 25000 IZMB2-V1250
229997 IZMN2-V1250
230008 IZMH2-V1250
230017
1600 640 – 1600 2000 – 19200 32000 IZMB2-V1600
229998 IZMN2-V1600
230009 IZMH2-V1600
230018
2000 800 – 2000 2500 – 24000 40000 IZMB2-V2000
229999 IZMN2-V2000
230010 IZMH2-V2000
230027
2500 1000 – 2500 3125 – 30000 50000 IZMB2-V2500
230001 IZMN2-V2500
230011 IZMH2-V2500
230028
3200 1280 – 3200 4000 – 38400 50000 IZMB2-V3200
230003 IZMN2-V3200
230012 IZMH2-V3200
230029
Frame size 3
4000 1600 – 4000 5000 – 48000 50000 IZMH3-V4000
230051 please
enquire 1 off
5000 2000 – 5000 6250 – 60000 IZMH3-V5000
230053
6300 2520 – 6300 7875 – 75600 IZMH3-V6300-AV
230056
I
8 9
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-breaker for universal protection (U) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 1.5 – 12 x In
OFF
IZMB2-U800
225556
1 off IZMN2-U800
225560
1 off IZMH2-U800
225572
1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 30 s with setting to
J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
Delay time tsd = OFF, 20 (motor protection),
100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
1000 400 – 1000 1250 – 12000 IZMB2-U1000
225557
IZMN2-U1000
225561
IZMH2-U1000
225573
1250 500 – 1250 1563 – 15000 IZMB2-U1250
225558
IZMN2-U1250
225562
IZMH2-U1250
225574
1600 640 – 1600 2000 – 19200 IZMB2-U1600
225559
IZMN2-U1600
225564
IZMH2-U1600
225575
2000 800 – 2000 2500 – 24000 IZMB2-U2000
230069
aIZMN2-U2000
225565
IZMH2-U2000
225576
2500 1000 – 2500 3125 – 30000 IZMB2-U2500
230070
IZMN2-U2500
225566
IZMH2-U2500
225577
3200 1280 – 3200 4000 – 38400 IZMB2-U3200
230071
IZMN2-U3200
225567
IZMH2-U3200
225578
Frame size 3
4000 1600 – 4000 5000 – 48000 1.5 – 12 x In
OFF
IZMH3-U4000
225580
1 off
5000 2000 – 5000 6250 – 60000 IZMH3-U5000
225581
6300 2520 – 6300 7875 – 75600 IZMH3-U6300-AV
230072
Digital circuit-breaker (D)
Frame size 2
800 320 – 800 1.25 x In – 0.8 x Icw 1.5 x In 0.8 x Ics IZMB2-D800
230083
please
enquire
1 off IZMN2-D800
230090
please
enquire
1 off IZMH2-D800
230097
please
enquire
1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 – 30 s s with setting to J
tr = 1, 2, 3, 4, 5 ss with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
Delay time tsd = OFF, 20, 100, 200, 300, 400, 500, 1000,
2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 x In 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
1000 400 – 1000 IZMB2-D1000
230084
IZMN2-D1000
230091
IZMH2-D1000
230098
1250 500 – 1250 IZMB2-D1250
230085
IZMN2-D1250
230092
IZMH2-D1250
230099
1600 640 – 1600 IZMB2-D1600
230086
IZMN2-D1600
230093
IZMH2-D1600
230100
2000 800 – 2000 IZMB2-D2000
230087
IZMN2-D2000
230094
IZMH2-D2000
230101
2500 1000 – 2500 IZMB2-D2500
230088
IZMN2-D2500
230095
IZMH2-D2500
230102
3200 1280 – 3200 IZMB2-D3200
230089
IZMN2-D3200
230096
IZMH2-D3200
230103
Frame size 3
4000 1600 – 4000 1.25 x In 0.8 x Icw 1.5 x In – 0.8 x Ics IZMH3-D4000
230104
please
enquire
1 off
5000 2000 – 5000 IZMH3-D5000
230105
6300 2520 – 6300 IZMH3-D6300-AV
230106
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55 kA at 415 V 50/60 Hz Icu = Ics = 80 kA at 415 V 50/60 Hz Icu = Ics = 100 kA at 415 V 50/60 Hz
Rating data Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Notes
Rated current Setting range
Overload
release
Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
I I
10 11
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
3-pole
Circuit-breaker for universal protection (U) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 1.5 – 12 x In
OFF
IZMB2-U800
225556
1 off IZMN2-U800
225560
1 off IZMH2-U800
225572
1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 – 30 s with setting to
J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
Delay time tsd = OFF, 20 (motor protection),
100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 – 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
1000 400 – 1000 1250 – 12000 IZMB2-U1000
225557
IZMN2-U1000
225561
IZMH2-U1000
225573
1250 500 – 1250 1563 – 15000 IZMB2-U1250
225558
IZMN2-U1250
225562
IZMH2-U1250
225574
1600 640 – 1600 2000 – 19200 IZMB2-U1600
225559
IZMN2-U1600
225564
IZMH2-U1600
225575
2000 800 – 2000 2500 – 24000 IZMB2-U2000
230069
aIZMN2-U2000
225565
IZMH2-U2000
225576
2500 1000 – 2500 3125 – 30000 IZMB2-U2500
230070
IZMN2-U2500
225566
IZMH2-U2500
225577
3200 1280 – 3200 4000 – 38400 IZMB2-U3200
230071
IZMN2-U3200
225567
IZMH2-U3200
225578
Frame size 3
4000 1600 – 4000 5000 – 48000 1.5 – 12 x In
OFF
IZMH3-U4000
225580
1 off
5000 2000 – 5000 6250 – 60000 IZMH3-U5000
225581
6300 2520 – 6300 7875 – 75600 IZMH3-U6300-AV
230072
Digital circuit-breaker (D)
Frame size 2
800 320 – 800 1.25 x In 0.8 x Icw 1.5 x In 0.8 x Ics IZMB2-D800
230083
please
enquire
1 off IZMN2-D800
230090
please
enquire
1 off IZMH2-D800
230097
please
enquire
1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 – 30 s s with setting to J
tr = 1, 2, 3, 4, 5 ss with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In – 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
Delay time tsd = OFF, 20, 100, 200, 300, 400, 500, 1000,
2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 x In – 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
1000 400 – 1000 IZMB2-D1000
230084
IZMN2-D1000
230091
IZMH2-D1000
230098
1250 500 – 1250 IZMB2-D1250
230085
IZMN2-D1250
230092
IZMH2-D1250
230099
1600 640 – 1600 IZMB2-D1600
230086
IZMN2-D1600
230093
IZMH2-D1600
230100
2000 800 – 2000 IZMB2-D2000
230087
IZMN2-D2000
230094
IZMH2-D2000
230101
2500 1000 – 2500 IZMB2-D2500
230088
IZMN2-D2500
230095
IZMH2-D2500
230102
3200 1280 – 3200 IZMB2-D3200
230089
IZMN2-D3200
230096
IZMH2-D3200
230103
Frame size 3
4000 1600 – 4000 1.25 x In 0.8 x Icw 1.5 x In 0.8 x Ics IZMH3-D4000
230104
please
enquire
1 off
5000 2000 – 5000 IZMH3-D5000
230105
6300 2520 – 6300 IZMH3-D6300-AV
230106
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55 kA at 415 V 50/60 Hz Icu = Ics = 80 kA at 415 V 50/60 Hz Icu = Ics = 100 kA at 415 V 50/60 Hz
Rating data Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Notes
Rated current Setting range
Overload
release
Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
I I
10 11
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Basic switching capacity (B) Normal switching capacity (N)
Icu = Ics = 50kA at 415 V 50/60 Hz Icu = Ics = 65kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Notes
Rated
current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Frame size 1
Circuit-breakers for distribution circuit protection (A)
630 315 – 630 1260 – 5040 IZMB1-4-A630
229938 1 off IZMN1-4-A630
229943 1 off Adjustable overload release Ir = 0.5 – 1 x In
Delay time tr = 10s at 6 x Ir
Adjustable non-delayed short-circuit release Ii = 2 8 x In
Supplied without overload protection in the 4th pole
800 400 – 800 1600 – 6400 IZMB1-4-A800
229939 IZMN1-4-A800
229944
1000 500 – 1000 2000 – 8000 IZMB1-4-A1000
229940 IZMN1-4-A1000
229945
1250 625 – 1250 2500 – 10000 IZMB1-4-A1250
229941 IZMN1-4-A1250
229946
1600 800 – 1600 3200 – 12800 IZMB1-4-A1600
229942 IZMN1-4-A1600
229947
Circuit-breaker for selective operation (V) and motor protection
630 252 – 630 788 – 7560 12600 IZMB1-4-V630
229948 1 off IZMN1-4-V630
229953 1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 10s at 6 x Ir
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
Delay time tsd = 0,20 (motor protection), 100, 200, 300, 400 ms
Non-delayed short-circuit release Ii f 20 x In
without overload protection in 4th pole (optional with overload
protection in 4th pole: +IZM-XT additionally required)
800 320 – 800 1000 – 9600 16000 IZMB1-4-V800
229949 IZMN1-4-V800
229954
1000 400 – 1000 1250 – 12000 20000 IZMB1-4-V1000
229950 IZMN1-4-V1000
229955
1250 500 – 1250 1563 – 15000 25000 IZMB1-4-V1250
229951 IZMN1-4-V1250
229956
1600 640 – 1600 2000 – 19200 32000 IZMB1-4-V1600
229952 IZMN1-4-V1600
229957
Circuit-breaker for universal protection (U) and motor protection
630 252 – 630 788 – 7560 1.5 – 12 x In
OFF IZMB1-4-U630
229958 1 off IZMN1-4-U630
229963 1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 30 s with setting to J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release Ii = 1.5 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4
th
pole, can be set to OFF, 100 % or 50 % I
r
800 320 – 800 1000 – 9600 IZMB1-4-U800
229959 IZMN1-4-U800
229964
1000 400 – 1000 1250 – 12000 IZMB1-4-U1000
229960 IZMN1-4-U1000
229965
1250 500 – 1250 1563 – 15000 IZMB1-4-U1250
229961 IZMN1-4-U1250
229966
1600 640 – 1600 2000 – 19200 IZMB1-4-U1600
229962 IZMN1-4-U1600
229967
Digital circuit-breaker (D)
630 252 – 630 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB1-4-D630
229968 please
enquire 1 off IZMN1-4-D630
229973 please
enquire 1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 30 s with setting to J
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
Delay time
tsd = OFF, 20, 100, 200, 300, 400, 500, 1000, 2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 x In 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4
th
pole, can be set to OFF, 100 % or 50 % I
r
800 320 – 800 IZMB1-4-D800
229969 IZMN1-4-D800
229975
1000 400 – 1000 IZMB1-4-D1000
229970 IZMN1-4-D1000
229976
1250 500 – 1250 IZMB1-4-D1250
229971 IZMN1-4-D1250
229977
1600 640 – 1600 IZMB1-4-D1600
229972 IZMN1-4-D1600
229978
I
I
12 13
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Basic switching capacity (B) Normal switching capacity (N)
Icu = Ics = 50kA at 415 V 50/60 Hz Icu = Ics = 65kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std. pack Type
Article no. Price
See Price List Std. pack Notes
Rated
current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Frame size 1
Circuit-breakers for distribution circuit protection (A)
630 315 – 630 1260 – 5040 IZMB1-4-A630
229938 1 off IZMN1-4-A630
229943 1 off Adjustable overload release Ir = 0.5 – 1 x In
Delay time tr = 10s at 6 x Ir
Adjustable non-delayed short-circuit release Ii = 2 – 8 x In
Supplied without overload protection in the 4th pole
800 400 – 800 1600 – 6400 IZMB1-4-A800
229939 IZMN1-4-A800
229944
1000 500 – 1000 2000 – 8000 IZMB1-4-A1000
229940 IZMN1-4-A1000
229945
1250 625 – 1250 2500 – 10000 IZMB1-4-A1250
229941 IZMN1-4-A1250
229946
1600 800 – 1600 3200 – 12800 IZMB1-4-A1600
229942 IZMN1-4-A1600
229947
Circuit-breaker for selective operation (V) and motor protection
630 252 – 630 788 – 7560 12600 IZMB1-4-V630
229948 1 off IZMN1-4-V630
229953 1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 10s at 6 x Ir
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
Delay time tsd = 0,20 (motor protection), 100, 200, 300, 400 ms
Non-delayed short-circuit release Ii f 20 x In
without overload protection in 4th pole (optional with overload
protection in 4th pole: +IZM-XT additionally required)
800 320 – 800 1000 – 9600 16000 IZMB1-4-V800
229949 IZMN1-4-V800
229954
1000 400 – 1000 1250 – 12000 20000 IZMB1-4-V1000
229950 IZMN1-4-V1000
229955
1250 500 – 1250 1563 – 15000 25000 IZMB1-4-V1250
229951 IZMN1-4-V1250
229956
1600 640 – 1600 2000 – 19200 32000 IZMB1-4-V1600
229952 IZMN1-4-V1600
229957
Circuit-breaker for universal protection (U) and motor protection
630 252 – 630 788 – 7560 1.5 – 12 x In
OFF IZMB1-4-U630
229958 1 off IZMN1-4-U630
229963 1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 – 30 s with setting to J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4
th
pole, can be set to OFF, 100 % or 50 % I
r
800 320 – 800 1000 – 9600 IZMB1-4-U800
229959 IZMN1-4-U800
229964
1000 400 – 1000 1250 – 12000 IZMB1-4-U1000
229960 IZMN1-4-U1000
229965
1250 500 – 1250 1563 – 15000 IZMB1-4-U1250
229961 IZMN1-4-U1250
229966
1600 640 – 1600 2000 – 19200 IZMB1-4-U1600
229962 IZMN1-4-U1600
229967
Digital circuit-breaker (D)
630 252 – 630 1.25 x In 0.8 x Icw 1.5 x In 0.8 x Ics IZMB1-4-D630
229968 please
enquire 1 off IZMN1-4-D630
229973 please
enquire 1 off Adjustable overload release Ir = 0.4 – 1 x In
Delay time tr = 2 – 30 s with setting to J
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In – 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
Delay time
tsd = OFF, 20, 100, 200, 300, 400, 500, 1000, 2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 x In – 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4
th
pole, can be set to OFF, 100 % or 50 % I
r
800 320 – 800 IZMB1-4-D800
229969 IZMN1-4-D800
229975
1000 400 – 1000 IZMB1-4-D1000
229970 IZMN1-4-D1000
229976
1250 500 – 1250 IZMB1-4-D1250
229971 IZMN1-4-D1250
229977
1600 640 – 1600 IZMB1-4-D1600
229972 IZMN1-4-D1600
229978
I
I
12 13
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55kA at 415 V 50/60 Hz Icu = Ics = 80kA at 415 V 50/60 Hz Icu = Ics = 100kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std.
pack Type
Article no. Price
See Price List Std.
pack Type
Article no. Price
See Price List Std.
pack Notes
Rated
current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Circuit-breakers for distribution circuit protection (A)
Frame size 2
800 400 – 800 1600 – 6400 IZMB2-4-A800
225583 1 off IZMN2-4-A800
225587 1 off IZMH2-4-A800
225598 1 off Adjustable overload release Ir = 0.5 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable non-delayed short-circuit release
Ii = 2 8 x In
Supplied without overload protection in the 4th pole
1000 500 – 1000 2000 – 8000 IZMB2-4-A1000
225584 IZMN2-4-A1000
225588 IZMH2-4-A1000
225599
1250 625 – 1250 2500 – 10000 IZMB2-4-A1250
225585 IZMN2-4-A1250
225589 IZMH2-4-A1250
225600
1600 800 – 1600 3200 – 12800 IZMB2-4-A1600
225586 IZMN2-4-A1600
225590 IZMH2-4-A1600
225601
2000 1000 – 2000 4000 – 16000 IZMB2-4-A2000
230118 IZMN2-4-A2000
225591 IZMH2-4-A2000
225602
2500 1250 – 2500 5000 – 20000 IZMB2-4-A2500
230119 IZMN2-4-A2500
225592 IZMH2-4-A2500
225603
3200 1600 – 3200 6400 – 25600 IZMB2-4-A3200
230120 IZMN2-4-A3200
225593 IZMH2-4-A3200
225604
Circuit-breaker for selective operation (V) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 16000 IZMB2-4-V800
230147 1 off IZMN2-4-V800
230154 1 off IZMH2-4-V800
230162 1 off Adjustable overload release Ir = 0.4 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
•Delay time tsd = 0, 20 (motor protection),
100, 200, 300, 400 ms
Non-delayed short-circuit release
Ii f 20 x In
max. 50 kA
without overload protection in 4th pole (optional with over-
load protection in 4th pole: +IZM-XT additionally
required)
1000 400 – 1000 1250 – 12000 20000 IZMB2-4-V1000
230148 IZMN2-4-V1000
230156 IZMH2-4-V1000
230163
1250 500 – 1250 1563 – 15000 25000 IZMB2-4-V1250
230149 IZMN2-4-V1250
230157 IZMH2-4-V1250
230180
1600 640 – 1600 2000 – 19200 32000 IZMB2-4-V1600
230150 IZMN2-4-V1600
230158 IZMH2-4-V1600
230181
2000 800 – 2000 2500 – 24000 40000 IZMB2-4-V2000
230151 IZMN2-4-V2000
230159 IZMH2-4-V2000
230182
2500 1000 – 2500 3125 – 30000 50000 IZMB2-4-V2500
230152 IZMN2-4-V2500
230160 IZMH2-4-V2500
230183
3200 1280 – 3200 4000 – 38400 50000 IZMB2-4-V3200
230153 IZMN2-4-V3200
230161 IZMH2-4-V3200
230184
Frame size 3
4000 1600 – 4000 5000 – 48000 50000 IZMH3-4-V4000
230185 please
enquire 1 off
5000 2000 – 5000 6250 – 60000 IZMH3-4-V5000
230186
6300 2520 – 6300 7875 – 75600 IZMH3-4-V6300-AV
230187
I I
14 15
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55kA at 415 V 50/60 Hz Icu = Ics = 80kA at 415 V 50/60 Hz Icu = Ics = 100kA at 415 V 50/60 Hz
Rating data Type
Article no. Price
See Price List Std.
pack Type
Article no. Price
See Price List Std.
pack Type
Article no. Price
See Price List Std.
pack Notes
Rated
current Setting range
Overload
release Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
Circuit-breakers for distribution circuit protection (A)
Frame size 2
800 400 800 1600 6400 IZMB2-4-A800
225583 1 off IZMN2-4-A800
225587 1 off IZMH2-4-A800
225598 1 off Adjustable overload release Ir = 0.5 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable non-delayed short-circuit release
Ii = 2 – 8 x In
Supplied without overload protection in the 4th pole
1000 500 1000 2000 8000 IZMB2-4-A1000
225584 IZMN2-4-A1000
225588 IZMH2-4-A1000
225599
1250 625 – 1250 2500 – 10000 IZMB2-4-A1250
225585 IZMN2-4-A1250
225589 IZMH2-4-A1250
225600
1600 800 1600 3200 12800 IZMB2-4-A1600
225586 IZMN2-4-A1600
225590 IZMH2-4-A1600
225601
2000 1000 – 2000 4000 – 16000 IZMB2-4-A2000
230118 IZMN2-4-A2000
225591 IZMH2-4-A2000
225602
2500 1250 – 2500 5000 – 20000 IZMB2-4-A2500
230119 IZMN2-4-A2500
225592 IZMH2-4-A2500
225603
3200 1600 – 3200 6400 – 25600 IZMB2-4-A3200
230120 IZMN2-4-A3200
225593 IZMH2-4-A3200
225604
Circuit-breaker for selective operation (V) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 16000 IZMB2-4-V800
230147 1 off IZMN2-4-V800
230154 1 off IZMH2-4-V800
230162 1 off Adjustable overload release Ir = 0.4 x In
•Delay time tr = 10 s at 6 x Ir
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
•Delay time tsd = 0, 20 (motor protection),
100, 200, 300, 400 ms
Non-delayed short-circuit release
Ii f 20 x In
max. 50 kA
without overload protection in 4th pole (optional with over-
load protection in 4th pole: +IZM-XT additionally
required)
1000 400 – 1000 1250 – 12000 20000 IZMB2-4-V1000
230148 IZMN2-4-V1000
230156 IZMH2-4-V1000
230163
1250 500 – 1250 1563 – 15000 25000 IZMB2-4-V1250
230149 IZMN2-4-V1250
230157 IZMH2-4-V1250
230180
1600 640 – 1600 2000 – 19200 32000 IZMB2-4-V1600
230150 IZMN2-4-V1600
230158 IZMH2-4-V1600
230181
2000 800 – 2000 2500 – 24000 40000 IZMB2-4-V2000
230151 IZMN2-4-V2000
230159 IZMH2-4-V2000
230182
2500 1000 – 2500 3125 – 30000 50000 IZMB2-4-V2500
230152 IZMN2-4-V2500
230160 IZMH2-4-V2500
230183
3200 1280 – 3200 4000 – 38400 50000 IZMB2-4-V3200
230153 IZMN2-4-V3200
230161 IZMH2-4-V3200
230184
Frame size 3
4000 1600 – 4000 5000 – 48000 50000 IZMH3-4-V4000
230185 please
enquire 1 off
5000 2000 – 5000 6250 – 60000 IZMH3-4-V5000
230186
6300 2520 – 6300 7875 – 75600 IZMH3-4-V6300-AV
230187
I I
14 15
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-breaker for universal protection (U) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 1.5 – 12 x In
OFF
IZMB2-4-U800
225609
1 off IZMN2-4-U800
225613
1 off IZMH2-4-U800
225624
1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 30 s with setting to
J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
•Delay time tsd = OFF, 20 (motor protection),
100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4th pole, can be set to OFF,
100 % or 50 % Ir
1000 400 – 1000 1250 – 12000 IZMB2-4-U1000
225610
IZMN2-4-U1000
225614
IZMH2-4-U1000
225625
1250 500 – 1250 1563 – 15000 IZMB2-4-U1250
225611
IZMN2-4-U1250
225615
IZMH2-4-U1250
225626
1600 640 – 1600 2000 – 19200 IZMB2-4-U1600
225612
IZMN2-4-U1600
225616
IZMH2-4-U1600
225627
2000 800 – 2000 2500 – 24000 IZMB2-4-U2000
230198
IZMN2-4-U2000
225617
IZMH2-4-U2000
225628
2500 1000 – 2500 3125 – 30000 IZMB2-4-U2500
230199
IZMN2-4-U2500
225618
IZMH2-4-U2500
225629
3200 1280 – 3200 4000 – 38400 IZMB2-4-U3200
230200
IZMN2-4-U3200
225619
IZMH2-4-U3200
225630
Frame size 3
4000 1600 – 4000 5000 – 48000 1.5 – 12 x In
OFF
IZMH3-4-U4000
225632
please
enquire
5000 2000 – 5000 6250 – 60000 IZMH3-4-U5000
225633
6300 2520 – 6300 7875 – 75600 IZMH3-4-U6300-AV
230201
Digital circuit-breaker (D)
Frame size 2
800 320 – 800 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-4-D800
230212
please
enquire
1 off IZMN2-4-D800
230219
please
enquire
1 off IZMH2-4-D800
230226
please
enquire
1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 30 s s with setting to J
tr = 1, 2, 3, 4, 5 ss with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
•Delay time tsd = OFF, 20, 100, 200, 300, 400, 500, 1000,
2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 x In 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4th pole, can be set to OFF,
100 % or 50 % Ir
1000 400 – 1000 IZMB2-4-D1000
230213
IZMN2-4-D1000
230220
IZMH2-4-D1000
230227
1250 500 – 1250 IZMB2-4-D1250
230214
IZMN2-4-D1250
230221
IZMH2-4-D1250
230228
1600 640 – 1600 IZMB2-4-D1600
230215
IZMN2-4-D1600
230222
IZMH2-4-D1600
230229
2000 800 – 2000 IZMB2-4-D2000
230216
IZMN2-4-D2000
230223
IZMH2-4-D2000
230230
2500 1000 – 2500 IZMB2-4-D2500
230217
IZMN2-4-D2500
230224
IZMH2-4-D2500
230231
3200 1280 – 3200 IZMB2-4-D3200
230218
IZMN2-4-D3200
230225
IZMH2-4-D3200
230232
Frame size 3
4000 1600 – 4000 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMH3-4-D4000
230233
please
enquire
5000 2000 – 5000 IZMH3-4-D5000
230234
6300 2520 – 6300 IZMH3-4-D6300-AV
230235
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55kA at 415 V 50/60 Hz Icu = Ics = 80kA at 415 V 50/60 Hz Icu = Ics = 100kA at 415 V 50/60 Hz
Rating data Type
Article no.
Price
See Price List
Std.
pack
Type
Article no.
Price
See Price List
Std.
pack
Type
Article no.
Price
See Price List
Std.
pack
Notes
Rated
current
Setting range
Overload
release
Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
I I
16 17
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IZM Circuit-Breakers
4-pole
Circuit-breaker for universal protection (U) and motor protection
Frame size 2
800 320 – 800 1000 – 9600 1.5 – 12 x In
OFF
IZMB2-4-U800
225609
1 off IZMN2-4-U800
225613
1 off IZMH2-4-U800
225624
1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 – 30 s with setting to
J with 6 x Ir
tr = 1, 2, 3, 4, 5 s with setting to I
4
t
Adjustable delayed short-circuit release
Isd = 1.25 – 12 x In
•Delay time tsd = OFF, 20 (motor protection),
100, 200, 300, 400 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 – 12 x In
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4th pole, can be set to OFF,
100 % or 50 % Ir
1000 400 – 1000 1250 – 12000 IZMB2-4-U1000
225610
IZMN2-4-U1000
225614
IZMH2-4-U1000
225625
1250 500 – 1250 1563 – 15000 IZMB2-4-U1250
225611
IZMN2-4-U1250
225615
IZMH2-4-U1250
225626
1600 640 – 1600 2000 – 19200 IZMB2-4-U1600
225612
IZMN2-4-U1600
225616
IZMH2-4-U1600
225627
2000 800 – 2000 2500 – 24000 IZMB2-4-U2000
230198
IZMN2-4-U2000
225617
IZMH2-4-U2000
225628
2500 1000 – 2500 3125 – 30000 IZMB2-4-U2500
230199
IZMN2-4-U2500
225618
IZMH2-4-U2500
225629
3200 1280 – 3200 4000 – 38400 IZMB2-4-U3200
230200
IZMN2-4-U3200
225619
IZMH2-4-U3200
225630
Frame size 3
4000 1600 – 4000 5000 – 48000 1.5 – 12 x In
OFF
IZMH3-4-U4000
225632
please
enquire
5000 2000 – 5000 6250 – 60000 IZMH3-4-U5000
225633
6300 2520 – 6300 7875 – 75600 IZMH3-4-U6300-AV
230201
Digital circuit-breaker (D)
Frame size 2
800 320 – 800 1.25 x In 0.8 x Icw 1.5 x In 0.8 x Ics IZMB2-4-D800
230212
please
enquire
1 off IZMN2-4-D800
230219
please
enquire
1 off IZMH2-4-D800
230226
please
enquire
1 off Adjustable overload release Ir = 0.4 – 1 x In
•Delay time tr = 2 – 30 s s with setting to J
tr = 1, 2, 3, 4, 5 ss with setting to I
4
t
Adjustable non-delayed short-circuit release
Isd = 1.25 x In – 0.8 x Icw with max. permissible setting
of 0.8 x Icw is the setting of the delay time tsd only valid up
to a max. of 400 ms Icw see the technical data
•Delay time tsd = OFF, 20, 100, 200, 300, 400, 500, 1000,
2000, 3000, 4000 ms
Adjustable non-delayed short-circuit release
Ii = 1.5 x In – 0.8 x Ics
max. permissible setting value: 0.8 x Ics
OFF: Ics = Icw
with overload protection in 4th pole, can be set to OFF,
100 % or 50 % Ir
1000 400 – 1000 IZMB2-4-D1000
230213
IZMN2-4-D1000
230220
IZMH2-4-D1000
230227
1250 500 – 1250 IZMB2-4-D1250
230214
IZMN2-4-D1250
230221
IZMH2-4-D1250
230228
1600 640 – 1600 IZMB2-4-D1600
230215
IZMN2-4-D1600
230222
IZMH2-4-D1600
230229
2000 800 – 2000 IZMB2-4-D2000
230216
IZMN2-4-D2000
230223
IZMH2-4-D2000
230230
2500 1000 – 2500 IZMB2-4-D2500
230217
IZMN2-4-D2500
230224
IZMH2-4-D2500
230231
3200 1280 – 3200 IZMB2-4-D3200
230218
IZMN2-4-D3200
230225
IZMH2-4-D3200
230232
Frame size 3
4000 1600 – 4000 1.25 x In 0.8 x Icw 1.5 x In 0.8 x Ics IZMH3-4-D4000
230233
please
enquire
5000 2000 – 5000 IZMH3-4-D5000
230234
6300 2520 – 6300 IZMH3-4-D6300-AV
230235
Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
Icu = Ics = 55kA at 415 V 50/60 Hz Icu = Ics = 80kA at 415 V 50/60 Hz Icu = Ics = 100kA at 415 V 50/60 Hz
Rating data Type
Article no.
Price
See Price List
Std.
pack
Type
Article no.
Price
See Price List
Std.
pack
Type
Article no.
Price
See Price List
Std.
pack
Notes
Rated
current
Setting range
Overload
release
Short-circuit release
Delayed Non-delayed
InIrIsd Ii
AAA A
I I
16 17
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
3-pole 4-pole
Rated current Rated short-circuit
making capacity t = 1 s
Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Notes
InIcm Icw
AkAkA
Frame size 1
630 105 42 INB1-630
230261
1 off INB1-4-630
230281
1 off The INB1(-4)-... switch-disconnector has the same construction as
the IZMB1(-4)-... circuit-breaker, however, without a trip control
unit. In this manner, it is possible to equip the IN series switch-
disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
800 INB1-800
230269
INB1-4-800
230283
1000 INB1-1000
230270
INB1-4-1000
230285
1250 INB1-1250
230272
INB1-4-1250
230287
1600 INB1-1600
230273
INB1-4-1600
230288
630 143 50 INN1-630
230274
1 off INN1-4-630
230291
1 off The INN1(-4)-... switch-disconnector has the same construction
as the IZMN1(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
800 INN1-800
230276
INN1-4-800
230293
1000 INN1-1000
230277
INN1-4-1000
230294
1250 INN1-1250
230278
INN1-4-1250
230296
1600 INN1-1600
230279
INN1-4-1600
230297
18 19
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
3-pole 4-pole
Rated current Rated short-circuit
making capacity t = 1 s
Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Notes
InIcm Icw
AkAkA
Frame size 1
630 105 42 INB1-630
230261
1 off INB1-4-630
230281
1 off The INB1(-4)-... switch-disconnector has the same construction as
the IZMB1(-4)-... circuit-breaker, however, without a trip control
unit. In this manner, it is possible to equip the IN series switch-
disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
800 INB1-800
230269
INB1-4-800
230283
1000 INB1-1000
230270
INB1-4-1000
230285
1250 INB1-1250
230272
INB1-4-1250
230287
1600 INB1-1600
230273
INB1-4-1600
230288
630 143 50 INN1-630
230274
1 off INN1-4-630
230291
1 off The INN1(-4)-... switch-disconnector has the same construction
as the IZMN1(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
800 INN1-800
230276
INN1-4-800
230293
1000 INN1-1000
230277
INN1-4-1000
230294
1250 INN1-1250
230278
INN1-4-1250
230296
1600 INN1-1600
230279
INN1-4-1600
230297
18 19
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
3-pole 4-pole
Rated current Rated short-circuit
making capacity
t = 1 s
t = 1 s
Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Notes
InIcm Icw
AkA kA
Frame size 2
800 121 55 INB2-800
230300
1 off INB2-4-800
230325
1 off The INB2(-4)-... switch-disconnector has the same construction
as the IZMB2(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
1000 INB2-1000
230302
INB2-4-1000
230326
1250 INB2-1250
230303
INB2-4-1250
230327
1600 INB2-1600
230304
INB2-4-1600
230328
2000 INB2-2000
230305
INB2-4-2000
230329
2500 INB2-2500
230306
INB2-4-2500
230330
3200 INB2-3200
230307
INB2-4-3200
230331
800 176 65 INN2-800
230308
1 off INN2-4-800
230332
1 off The INN2(-4)-... switch-disconnector has the same construction
as the IZMN2(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
1000 INN2-1000
230309
INN2-4-1000
230333
1250 INN2-1250
230310
INN2-4-1250
230334
1600 INN2-1600
230311
INN2-4-1600
230335
2000 INN2-2000
230312
INN2-4-2000
230336
2500 INN2-2500
230313
INN2-4-2500
230337
3200 INN2-3200
230314
INN2-4-3200
230338
800 220 65 INH2-800
230315
1 off INH2-4-800
230339
1 off The INH2(-4)-... switch-disconnector has the same construction
as the IZMH2(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
1000 INH2-1000
230316
INH2-4-1000
230340
1250 INH2-1250
230317
INH2-4-1250
230341
1600 INH2-1600
230318
INH2-4-1600
230342
2000 INH2-2000
230319
INH2-4-2000
230343
2500 INH2-2500
230320
INH2-4-2500
230344
3200 80 INH2-3200
230321
INH2-4-3200
230345
Frame size 3
4000 220 80 INH3-4000
230322
please
enquire
1 off INH3-4-4000
230346
please
enquire
1 off The INH3(-4)-... switch-disconnector has the same construction
as the IZMH3(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch with the same accessory equipment as a comparable IZM
circuit-breaker.
5000 80 INH3-5000
230323
INH3-4-5000
230347
6300 100 INH3-6300-AV
230324
INH3-4-6300-AV
230348
20 21
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
IN Switch-Disconnectors
3- and 4-pole
3-pole 4-pole
Rated current Rated short-circuit
making capacity
t = 1 s
t = 1 s
Type
Article no.
Price
See Price List
Std. pack Type
Article no.
Price
See Price List
Std. pack Notes
InIcm Icw
AkA kA
Frame size 2
800 121 55 INB2-800
230300
1 off INB2-4-800
230325
1 off The INB2(-4)-... switch-disconnector has the same construction
as the IZMB2(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
1000 INB2-1000
230302
INB2-4-1000
230326
1250 INB2-1250
230303
INB2-4-1250
230327
1600 INB2-1600
230304
INB2-4-1600
230328
2000 INB2-2000
230305
INB2-4-2000
230329
2500 INB2-2500
230306
INB2-4-2500
230330
3200 INB2-3200
230307
INB2-4-3200
230331
800 176 65 INN2-800
230308
1 off INN2-4-800
230332
1 off The INN2(-4)-... switch-disconnector has the same construction
as the IZMN2(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
1000 INN2-1000
230309
INN2-4-1000
230333
1250 INN2-1250
230310
INN2-4-1250
230334
1600 INN2-1600
230311
INN2-4-1600
230335
2000 INN2-2000
230312
INN2-4-2000
230336
2500 INN2-2500
230313
INN2-4-2500
230337
3200 INN2-3200
230314
INN2-4-3200
230338
800 220 65 INH2-800
230315
1 off INH2-4-800
230339
1 off The INH2(-4)-... switch-disconnector has the same construction
as the IZMH2(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch-disconnector with the same accessory equipment as a
comparable IZM circuit-breaker.
1000 INH2-1000
230316
INH2-4-1000
230340
1250 INH2-1250
230317
INH2-4-1250
230341
1600 INH2-1600
230318
INH2-4-1600
230342
2000 INH2-2000
230319
INH2-4-2000
230343
2500 INH2-2500
230320
INH2-4-2500
230344
3200 80 INH2-3200
230321
INH2-4-3200
230345
Frame size 3
4000 220 80 INH3-4000
230322
please
enquire
1 off INH3-4-4000
230346
please
enquire
1 off The INH3(-4)-... switch-disconnector has the same construction
as the IZMH3(-4)-... circuit-breaker, however, without a trip
control unit. In this manner, it is possible to equip the IN series
switch with the same accessory equipment as a comparable IZM
circuit-breaker.
5000 80 INH3-5000
230323
INH3-4-5000
230347
6300 100 INH3-6300-AV
230324
INH3-4-6300-AV
230348
20 21
Moeller NK1230-1045GB
Accessories
Additional Functions for Overcurrent Release
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
22
Type suffix
When ordered
with basic unit
Article no.
Price
See Price List
Std. pack Type
When
ordered
separately
Article no.
Price
See Price List
Std. pack Notes
Additional functions for
the release
Additional functions for IZM...-V...
selectively-operating circuit-breakers
Earth-fault protection
(and N-conductor protection with 4-pole
circuit-breakers)
+IZM-XT
230830
1 off
Additional functions for IZM...-U... universal
circuit-breakers
Earth-fault protection
(alarm and release)
+IZMU-XT
225661
1 off IZMU-XT
230426
1 off With 3-pole circuit-breakers,
an external converter for the
N-conductor is required
Earth fault alarm
(alarm only)
+IZMU-XTA
230428
1 off IZMU-XTA
230427
1 off
2-line display +IZM-XAM
230430
1 off Alphanumeric LCD-display
Additional functions for IZM...-D... digital
circuit-breakers
Earth-fault protection
(alarm and release)
+IZMD-XT
230431
1 off IZMD-XT
230432
1 off With 3-pole circuit-breakers,
an external converter for the
N-conductor is required
Earth fault alarm
(alarm only)
+IZMD-XTA
230434
1 off IZMD-XTA
230433
1 off
Fully graphic display +IZM-XAMG
230435
1 off Graphic LCD-display
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
23
Moeller NK1230-1045GB
Accessories
Measurement Converter for the Neutral Pole
Frame size For use with Type
when
ordered
separately
Article no.
Price
see Price
List
Std. pack Notes
Current transformer for N-conductor
Ring-type transformer (Rogowski convertor)
Frame size 1 Circuit-breakers
IZM...-V...
IZM...-U...
IZM...-D...
IZM1-XW
230439
1 off With 3-pole circuit-breakers, an external
converter for the N-conductor is required.
Frame size 2 IZM2-XW
230440
Frame size 3 IZM3-XW
230441
Transformer with copper connections
Frame size 1 Circuit-breakers
IZM...-V...
IZM...-U...
IZM...-D...
IZM1-XWC
230442
1 off With 3-pole circuit-breakers, an external
converter for the N-conductor is required.
Frame size 2 IZM2-XWC
230443
Frame size 3 IZM3-XWC
230444
Moeller NK1230-1045GB
Accessories
Components for Communication
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Components for Communication
Type suffix
When ordered with basic unit
Article no.
Price
See Price List Std. pack Type
When ordered
separately
Article no.
Price
See Price List Std. pack Notes
Components for the communication
only for IZM...-U(D)...
Communication module
+IZM-XCOM-DP
230751 1 off IZM-XCOM-DP
230833 1 off PROFIBUS-DP communication connection
Measurement modules
Power measurement functions +IZM-XMP
230436 1 off IZM-XMP
230834 1 off Allows measurement of I, U, P, c, W, f
Harmonic measurement function +IZM-XMH
230437 please
enquire 1 off IZM-XMH
230835 please
enquire
1 off As with Plus measurement function, with additional
measurement of the harmonic distortion and total harmonic
distortion up to the 29th harmonic component
Voltage transformer
Category 0.5
380 V/100 V +IZM-XW05U380
230872 1 off IZM-XW05U380
230445 1 off Required for the Plus and High end measurement functions
415 V/100 V +IZM-XW05U415
230873 IZM-XW05U415
230446
440 V/100 V +IZM-XW05U440
230874 IZM-XW05U440
230447
525 V/100 V +IZM-XW05U525
230875 IZM-XW05U525
230448
690 V/100 V +IZM-XW05U690
230876 IZM-XW05U690
230449
Expansion module
Digital output module relay +IZM-XEM-6DO-R
230838 1 off IZM-XEM-6DO-R
230753 1 off 6 digital outputs, adjustable delay time 0 – 2 s, outputs can be
assigned as required with signals from overload release, delayed
short-circuit release, non-delayed short-circuit release, earth
fault alarm, earth fault release or overload warning, release-
error, load shedding, load pick-up, temperature alarm, phase
unbalance
Digital output module +IZM-XEM-6DO-T
230839 IZM-XEM-6DO-T
230754 6 digital outputs, adjustable delay time 0 – 2 s, outputs can be
assigned as required with signals from overload release, delayed
short-circuit release, non-delayed short-circuit release, earth
fault alarm, earth fault release or overload warning, release-
error, load shedding, load pick-up, temperature alarm, phase
unbalance
Digital output module relay, freely programmable +IZM-XEM-6PDO-R
230841 IZM-XEM-6PDO-R
230755 6 digital outputs, freely programmable
Digital output module optocoupler, freely programmable +IZM-XEM-6PDO-T
230842 IZM-XEM-6PDO-T
230756 6 digital outputs, freely programmable
Analog output module +IZM-XEM-4AO
230843 IZM-XEM-4AO
230757 4 analog outputs, 4 20 mA or 0 10 V, outputs can be assigned
as required with phase currents, phase voltage, effective power,
power factor, frequency
Digital input module +IZM-XEM-6DI
230845 IZM-XEM-6DI
230758 6 digital inputs (24 V DC), transmission of additional information
to the PROFIBUS-DP
Zone-selective interlocking +IZM-XEM-ZSI
230837 IZM-XEM-ZSI
230752 Full selectivity with a delay time of 50 ms
Connection cable
for expansion module
0.5 m +IZM-XEM-VL05
230847 1 off IZM-XEM-VL05
230848 1 off
1 m +IZM-XEM-VL1
230849 IZM-XEM-VL1
230850
2 m +IZM-XEM-VL2
230851 IZM-XEM-VL2
230852
2524
Moeller NK1230-1045GB
Accessories
Components for Communication
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Components for Communication
Type suffix
When ordered with basic unit
Article no.
Price
See Price List Std. pack Type
When ordered
separately
Article no.
Price
See Price List Std. pack Notes
Components for the communication
only for IZM...-U(D)...
Communication module
+IZM-XCOM-DP
230751 1 off IZM-XCOM-DP
230833 1 off PROFIBUS-DP communication connection
Measurement modules
Power measurement functions +IZM-XMP
230436 1 off IZM-XMP
230834 1 off Allows measurement of I, U, P, c, W, f
Harmonic measurement function +IZM-XMH
230437 please
enquire 1 off IZM-XMH
230835 please
enquire
1 off As with Plus measurement function, with additional
measurement of the harmonic distortion and total harmonic
distortion up to the 29th harmonic component
Voltage transformer
Category 0.5
380 V/100 V +IZM-XW05U380
230872 1 off IZM-XW05U380
230445 1 off Required for the Plus and High end measurement functions
415 V/100 V +IZM-XW05U415
230873 IZM-XW05U415
230446
440 V/100 V +IZM-XW05U440
230874 IZM-XW05U440
230447
525 V/100 V +IZM-XW05U525
230875 IZM-XW05U525
230448
690 V/100 V +IZM-XW05U690
230876 IZM-XW05U690
230449
Expansion module
Digital output module relay +IZM-XEM-6DO-R
230838 1 off IZM-XEM-6DO-R
230753 1 off 6 digital outputs, adjustable delay time 0 – 2 s, outputs can be
assigned as required with signals from overload release, delayed
short-circuit release, non-delayed short-circuit release, earth
fault alarm, earth fault release or overload warning, release-
error, load shedding, load pick-up, temperature alarm, phase
unbalance
Digital output module +IZM-XEM-6DO-T
230839 IZM-XEM-6DO-T
230754 6 digital outputs, adjustable delay time 0 – 2 s, outputs can be
assigned as required with signals from overload release, delayed
short-circuit release, non-delayed short-circuit release, earth
fault alarm, earth fault release or overload warning, release-
error, load shedding, load pick-up, temperature alarm, phase
unbalance
Digital output module relay, freely programmable +IZM-XEM-6PDO-R
230841 IZM-XEM-6PDO-R
230755 6 digital outputs, freely programmable
Digital output module optocoupler, freely programmable +IZM-XEM-6PDO-T
230842 IZM-XEM-6PDO-T
230756 6 digital outputs, freely programmable
Analog output module +IZM-XEM-4AO
230843 IZM-XEM-4AO
230757 4 analog outputs, 4 20 mA or 0 10 V, outputs can be assigned
as required with phase currents, phase voltage, effective power,
power factor, frequency
Digital input module +IZM-XEM-6DI
230845 IZM-XEM-6DI
230758 6 digital inputs (24 V DC), transmission of additional information
to the PROFIBUS-DP
Zone-selective interlocking +IZM-XEM-ZSI
230837 IZM-XEM-ZSI
230752 Full selectivity with a delay time of 50 ms
Connection cable
for expansion module
0.5 m +IZM-XEM-VL05
230847 1 off IZM-XEM-VL05
230848 1 off
1 m +IZM-XEM-VL1
230849 IZM-XEM-VL1
230850
2 m +IZM-XEM-VL2
230851 IZM-XEM-VL2
230852
2524
Moeller NK1230-1045GB
Accessories
Components for Communication
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Components for Communication
Parameter definition systems
Parameter assignment module IZM-XEM-PG
230759 please
enquire
1 off Parameter definition, control, diagnosis and test of the IZM via the local interface of the control unit
Runs under Internet-Explorer or Netscape Navigator
Contains the connection cable to IZM and to the programming device (Notebook)
aPROFIBUS-DP
bInternal system bus
cExternal input and output modules
dParameter definition of the IZM
without additional software
eParameter assignment module
IZM-XEM-PG(E)
fMeasurement module IZM-XMP(H)
gCommunication module IZM-XCOM-DP
Parameter assignment module
with Ethernet interface IZM-XEM-PGE
230782 please
enquire 1 off as with the IZM-XEM-PG, additional Ethernet-interface for connection to the Ethernet/Internet, Intranet
Type suffix
When ordered with basic unit
Article no.
Price
See Price List Std. pack Type
When ordered
separately
Article no.
Price
See Price List Std. pack Notes
g
f
ab
c
ed
26 27
Moeller NK1230-1045GB
Accessories
Components for Communication
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Components for Communication
Parameter definition systems
Parameter assignment module IZM-XEM-PG
230759 please
enquire
1 off Parameter definition, control, diagnosis and test of the IZM via the local interface of the control unit
Runs under Internet-Explorer or Netscape Navigator
Contains the connection cable to IZM and to the programming device (Notebook)
aPROFIBUS-DP
bInternal system bus
cExternal input and output modules
dParameter definition of the IZM
without additional software
eParameter assignment module
IZM-XEM-PG(E)
fMeasurement module IZM-XMP(H)
gCommunication module IZM-XCOM-DP
Parameter assignment module
with Ethernet interface IZM-XEM-PGE
230782 please
enquire 1 off as with the IZM-XEM-PG, additional Ethernet-interface for connection to the Ethernet/Internet, Intranet
Type suffix
When ordered with basic unit
Article no.
Price
See Price List Std. pack Type
When ordered
separately
Article no.
Price
See Price List Std. pack Notes
g
f
ab
c
ed
26 27
Moeller NK1230-1045GB
Accessories
Auxiliary Contacts
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Auxiliary Contacts
Rated control voltage Type suffix
When ordered with basic unit
Article no.
Price
See Price List
Std. pack Type
When ordered separately
Article no.
Price
See Price List
Std. pack Notes
Us
V
Auxiliary contacts
Standard auxiliary contact
additional 2 make contacts and 2
break contacts
+IZM-XHI22
230605
1 off IZM-XHI22
230606
1 off By using jumpers on the
inputs
XHI indicates position of main contacts.
Supplied as standard with IZM and IN, do not order:
Standard auxiliary contact XNHI with 2 make contacts
and 2 break contacts.
XHIA trip signalling switch. If the communication module
is selected, the trip signalling switch cannot be used.
Control circuit plug for fixed
mounted switch
with cage clamp terminal +IZM-XKL
225657
1 off IZM-XKL
225857
1 off
Ready-to-close auxiliary
contacts ––
+IZM-XHIB
225680
1 off IZM-XHIB
225876
1 off
Motor operators
24 – 30 DC +IZM-XM24-30DC
230538
1 off IZM-XM24-30DC
230539
1 off Automatic charging of the spring-operated stored energy
mechanism
48 – 60 DC +IZM-XM48-60DC
230540
IZM-XM48-60DC
230541
110 – 125 DC
110 – 127 AC
+IZM-XM110AC/DC
230542
IZM-XM110AC/DC
230543
220 – 250 DC
208 – 240 AC
+IZM-XM230AC/220DC
230544
IZM-XM230AC/220DC
230545
Motor cut-off switch
Thumb-grip handle +IZM-XMS
230717
1 off IZM-XMS
230718
1 off Cannot be combined with
electrical ON
Operations counter
mechanical, 5-position +IZM-XSZ
230729
1 off
Voltage trip state
for the 1st voltage release
(shunt-release)
+IZM-XHIS
230713
1 off IZM-XHIS
230714
1 off Signals the state of the
voltage release
for the 2nd voltage release
(XA1..., XU..., XUV...)
+IZM-XHIS1
230715
1 off IZM-XHIS1
230716
1 off Signals the state of the
voltage release
28 29
Moeller NK1230-1045GB
Accessories
Auxiliary Contacts
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Auxiliary Contacts
Rated control voltage Type suffix
When ordered with basic unit
Article no.
Price
See Price List
Std. pack Type
When ordered separately
Article no.
Price
See Price List
Std. pack Notes
Us
V
Auxiliary contacts
Standard auxiliary contact
additional 2 make contacts and 2
break contacts
+IZM-XHI22
230605
1 off IZM-XHI22
230606
1 off By using jumpers on the
inputs
XHI indicates position of main contacts.
Supplied as standard with IZM and IN, do not order:
Standard auxiliary contact XNHI with 2 make contacts
and 2 break contacts.
XHIA trip signalling switch. If the communication module
is selected, the trip signalling switch cannot be used.
Control circuit plug for fixed
mounted switch
with cage clamp terminal +IZM-XKL
225657
1 off IZM-XKL
225857
1 off
Ready-to-close auxiliary
contacts ––
+IZM-XHIB
225680
1 off IZM-XHIB
225876
1 off
Motor operators
24 – 30 DC +IZM-XM24-30DC
230538
1 off IZM-XM24-30DC
230539
1 off Automatic charging of the spring-operated stored energy
mechanism
48 – 60 DC +IZM-XM48-60DC
230540
IZM-XM48-60DC
230541
110 – 125 DC
110 – 127 AC
+IZM-XM110AC/DC
230542
IZM-XM110AC/DC
230543
220 – 250 DC
208 – 240 AC
+IZM-XM230AC/220DC
230544
IZM-XM230AC/220DC
230545
Motor cut-off switch
Thumb-grip handle +IZM-XMS
230717
1 off IZM-XMS
230718
1 off Cannot be combined with
electrical ON
Operations counter
mechanical, 5-position +IZM-XSZ
230729
1 off
Voltage trip state
for the 1st voltage release
(shunt-release)
+IZM-XHIS
230713
1 off IZM-XHIS
230714
1 off Signals the state of the
voltage release
for the 2nd voltage release
(XA1..., XU..., XUV...)
+IZM-XHIS1
230715
1 off IZM-XHIS1
230716
1 off Signals the state of the
voltage release
28 29
Moeller NK1230-1045GB
Accessories
Closing Release, Shunt Release
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
30
Rated control voltage Type suffix
When ordered with
basic unit
Article no.
Price
see Price
List
Std. pack Type
When ordered separately
Article no.
Price
see Price
List
Std. pack
Us
V
Closing release
Closing release
100 % ED
24 DC +IZM-XE24DC
230564
1 off IZM-XE24DC
230565
1 off
30 DC +IZM-XE30DC
230566
IZM-XE30DC
230567
48 DC +IZM-XE48DC
230568
IZM-XE48DC
230569
60 DC +IZM-XE60DC
230570
IZM-XE60DC
230571
110 DC
+IZM-XE110AC/DC
230572
IZM-XE110AC/DC
230573
220 DC
230 AC 50/60 Hz
+IZM-XE230AC/220DC
230574
IZM-XE230AC/220DC
230575
Over-excited closing release
5 % ED
24 DC +IZM-XE24DC05
230576
1 off IZM-XE24DC05
230577
1 off Not suitable
for continuous
duty
48 DC +IZM-XE48DC05
230578
IZM-XE48DC05
230579
110 – 125 DC
110 – 127 AC 50/60 Hz
+IZM-XE110AC/DC05
230580
IZM-XE110AC/DC05
230581
220 – 250 DC
208 – 240 AC 50/60 Hz
+IZM-XE230AC/DC05
230582
IZM-XE230AC/DC05
230583
Shunt release
1st shunt release
100 % ED
24 DC +IZM-XA24DC
230546
1 off IZM-XA24DC
230547
1 off
30 DC +IZM-XA30DC
230548
IZM-XA30DC
230549
48 DC +IZM-XA48DC
230550
IZM-XA48DC
230551
60 DC +IZM-XA60DC
230552
IZM-XA60DC
230553
110 DC
110 AC
+IZM-XA110AC/DC
230554
IZM-XA110AC/DC
230555
220 DC
230 AC 50/60 Hz
+IZM-XA230AC/220DC
230556
IZM-XA230AC/220DC
230557
1st over-excited shunt release
5 % ED
24 DC +IZM-XA24DC05
230558
1 off IZM-XA24DC05
230559
1 off Not suitable
for continuous
duty
48 DC +IZM-XA48DC05
230560
IZM-XA48DC05
230561
110 – 125 DC
110 – 127 AC 50/60 Hz
+IZM-XA110AC/DC05
230562
IZM-XA110AC/DC05
230563
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
31
Moeller NK1230-1045GB
Accessories
Closing Release, Shunt Release
Shunt release
2nd shunt release
100 % ED
24 DC +IZM-XA1(24DC)
230760
1 off IZM-XA1(24DC)
230761
1 off
30 DC +IZM-XA1(30DC)
230762
IZM-XA1(30DC)
230763
48 DC +IZM-XA1(48DC)
230764
IZM-XA1(48DC)
230765
60 DC +IZM-XA1(60DC)
230766
IZM-XA1(60DC)
230767
110 DC
110 AC
+IZM-XA1(110AC/DC)
230768
IZM-XA1(110AC/DC)
230769
220 DC
230 AC 50/60 Hz
+IZM-XA1(230AC/220DC)
230770
IZM-XA1(230AC/220DC)
230771
2nd over-excited shunt release
5 % ED
24 DC +IZM-XA1(24DC05)
230772
1 off IZM-XA1(24DC05)
230773
1 off Not suitable
for continuous
duty
48 DC +IZM-XA1(48DC05)
230774
IZM-XA1(48DC05)
230775
110 – 125 DC
110 – 127 AC 50/60 Hz
+IZM-XA1(110AC/DC05)
230776
IZM-XA1(110AC/DC05)
230777
Undervoltage release
non-delayed
24 DC +IZM-XU24DC
230584
1 off IZM-XU24DC
230585
1 off
30 DC +IZM-XU30DC
230586
IZM-XU30DC
230587
48 DC +IZM-XU48DC
230588
IZM-XU48DC
230589
110 – 125 DC
110 – 127 AC 50/60 Hz
+IZM-XU127AC/125DC
230591
IZM-XU127AC/125DC
230592
220 – 250 DC
208 – 240 AC 50/60 Hz
+IZM-XU240AC/250DC
230593
IZM-XU240AC/250DC
230594
380 – 415 AC 50/60 Hz +IZM-XU415AC
230595
IZM-XU415AC
230596
delayed
delay time 0.2 – 3.2 s
48 DC +IZM-XUV48DC
230597
1 off IZM-XUV48DC
230598
1 off
110 – 125 DC
110 – 127 AC 50/60 Hz
+IZM-XUV127AC/125DC
230599
IZM-XUV127AC/125DC
230600
220 – 250 DC
208 – 240 AC 50/60 Hz
+IZM-XUV240AC/250DC
230601
IZM-XUV240AC/250DC
230602
380 – 415 AC 50/60 Hz +IZM-XUV415AC
230603
IZM-XUV415AC
230604
Rated control voltage Type suffix
When ordered with
basic unit
Article no.
Price
see Price
List
Std. pack Type
When ordered separately
Article no.
Price
see Price
List
Std. pack
Us
V
Moeller NK1230-1045GB
Accessories
Locking Facilities, Mechanical Interlocks
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
32
Type suffix
When ordered
with basic unit
Article no.
Price
See Price
List
Std. pack Type
When ordered
separately
Article no.
Price
See Price
List
Std. pack Notes
Locking devices
Cover for setting buttons
+IZM-XHB
230638
1 off IZM-XHB
230639
1 off
Locking device,
Locking in OFF
Make: CES +IZM-XVDM
230640
1 off IZM-XVDM
230643
1 off Locking in OFF
Fulfills the isolating
requirements
Can be locked in the
OFF position
Make: Castell-
installation kit
+IZM-XVDME-C
230641
IZM-XVDME-C
230644
Locking shackle +IZM-XVDMV
230778
IZM-XVDMV
230779
Can be locked
with up to
4 padlocks
Locking device to prevent
movement of the circuit-breaker
in the withdrawable unit
Locking of the crank
handle to prevent
movement,
Make: CES
+IZM-XVK-AV
230648
1 off IZM-XVK-AV
230649
1 off Lock beside the
crank handle
Supplied as standard,
do not order:
Locking of the crank
handle to prevent
movement, can be
locked with up to
3padlocks.
Locking of the crank
handle to prevent
movement,
Make: CES
+IZM-XV-AV
230650
1 off IZM-XV-AV
230651
1 off Lock in the control
panel door
Locking arrangements
Door interlock
for fixed mounting +IZM-XVT
230652
1 off IZM-XVT
230653
1 off
for withdrawable
units
+IZM-XVT-AV
230654
1 off IZM-XVT-AV
230655
1 off
Switch on inhibit with open
control panel door
for fixed mounting +IZM-XVE
230656
1 off IZM-XVE
230657
1 off
for withdrawable
units
+IZM-XVE-AV
230658
1 off IZM-XVE-AV
230659
1 off
Locking arrangement for open
control panel utilization
prevention
+IZM-XVV
230660
1 off IZM-XVV
230661
1 off
Mutual mechanical interlock
for 2 switches (beside or under
one another with 2 m Bowden
cables)
for fixed mounting +IZM-XMV
230662
1 off
for withdrawable
switches
+IZM-XMV-AV
230663
1 off
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
33
Moeller NK1230-1045GB
Accessories
Electrical ON, Emergency-Stop Button
Rated control voltage Type suffix
When ordered with basic
unit
Article no.
Price
See Price
List
Std. pack Type
When
ordered
separately
Article no.
Price
See Price
List
Std. pack Notes
Us
V
Electrical ON
+IZM-XEE-T
230719 1 off IZM-XEE-T
230720 1 off Push-button
+IZM-XEE-TP
230721 1 off IZM-XEE-TP
230722 1 off Push-button with sealable
shroud
+IZM-XEE-C
230723 1 off IZM-XEE-C
230724 1 off Cylinder lock
Emergency-stop actuator
+IZM-XPV
230646 1 off IZM-XPV
230647 1 off Mushroom actuator instead
of the mechanical
OFF-actuator
Remote reset
24 DC +IZM-XFR24DC
230725 1 off IZM-XFR... includes the
IZM-XOW-function:
1. Automatic reset of the
mechanical reclosing lockout
2. Reset of the tripped
signalling indicator (red pin
and IZM-XHIA are reset)
48 DC +IZM-XFR48DC
230726 1 off
125 DC
120 AC +IZM-XFR120AC/125DC
230727 1 off
250 DC
220 – 240 AC +IZM-XFR230AC/250DC
230728 1 off
Automatic reset of
the mechanical reclosing
lockout
+IZM-XOW
230783 1 off
Moeller NK1230-1045GB
Accessories
Bracket for Fixed Mounted Breaker
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
34
Type suffix
When ordered
with basic unit
Article no.
Price
See Price List Std. pack Type
When ordered
separately
Article no.
Price
See Price List Std. pack Notes
Mounting brackets for
fixed mounted
circuit-breaker IZM1/2-XTW
230731 1 off 1 pair, wall mounting for frame
size 1 and 2
Door seal
IZM-XRT
230730 1 off for sealing a door cutout, degree
of protection IP40
Protective covers
IZM-XDT
230750 1 off
Test unit
+IZM-XPH
225816 please
enquire 1 off IZM-XPH
226018 please
enquire 1 off
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
35
Moeller NK1230-1045GB
Accessories
Rated Current Rating Plug
exchangeable in
the
Rated
current
Type suffix
when ordered
with basic unit
Article no.
Price
see Price List
Std. pack Type
when ordered
separately
Article no.
Price
see Price List
Std. pack Notes
In
A
Rating plug
for the reduction of the rated current In of
the circuit-breaker
Frame size 1
Frame size 2
250 +IZM-XRP250
230675
1 off IZM-XRP250
230622
1 off cannot be used for
circuit-breakers
intended for IZM...-A...
distribution circuit
protection
Frame size 1
Frame size 2
315 +IZM-XRP315
230676
IZM-XRP315
230623
Frame size 1
Frame size 2
400 +IZM-XRP400
230677
IZM-XRP400
230624
Frame size 1
Frame size 2
500 +IZM-XRP500
230678
IZM-XRP500
230625
Frame size 1
Frame size 2
630 +IZM-XRP630
230679
IZM-XRP630
230626
Frame size 1
Frame size 2
700 +IZM-XRP700
230680
IZM-XRP700
230627
Frame size 1
Frame size 2
800 +IZM-XRP800
230681
IZM-XRP800
230628
Frame size 1
Frame size 2
1000 +IZM-XRP1000
230682
IZM-XRP1000
230629
Frame size 1
Frame size 2
Frame size 3
1250 +IZM-XRP1250
230683
IZM-XRP1250
230630
Frame size 1
Frame size 2
Frame size 3
1600 +IZM-XRP1600
230684
IZM-XRP1600
230631
Frame size 2
Frame size 3
2000 +IZM-XRP2000
230685
IZM-XRP2000
230632
Frame size 2
Frame size 3
2500 +IZM-XRP2500
230686
IZM-XRP2500
230633
Frame size 2
Frame size 3
3200 +IZM-XRP3200
230687
IZM-XRP3200
230634
Frame size 3 4000 +IZM-XRP4000
230688
IZM-XRP4000
230635
Frame size 3 5000 +IZM-XRP5000
230689
IZM-XRP5000
230636
Frame size 3 6300 +IZM-XRP6300
230690
IZM-XRP6300
230637
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Pole For rated current Type suffix
when ordered with basic unit
Article no.
Pric
see Price List Std. pack Type
when ordered
separately
Article no.
Pric
see Price List Std. pack Notes
In
A
Withdrawable units
3-pole Frame size 1 1000 +IZM1-XAV10
230733 1 off IZM1-XAV10
230734 1 off When ordering the withdrawable unit
separately:
State type of mains connection
4 control circuit are supplied as standard
with the unit
Frame size 1 1600 +IZM1-XAV16
230735 IZM1-XAV16
230736
Frame size 2 2000 +IZM2-XAV20
225772 IZM2-XAV20
225978
2500 +IZM2-XAV25
225773 IZM2-XAV25
225979
3200 +IZM2-XAV32
225774 IZM2-XAV32
225980
Frame size 3 4000 +IZM3-XAV40
230737 IZM3-XAV40
230738
5000 +IZM3-XAV50
230739 IZM3-XAV50
230740
6300 +IZM3-XAV63
225776 IZM3-XAV63
225982
4-pole Frame size 1 1000 +IZM1-XAV104
230742 IZM1-XAV104
230743
Frame size 1 1600 +IZM1-XAV164
230744 IZM1-XAV164
230745
Frame size 2 2000 +IZM2-XAV204
225779 IZM2-XAV204
225985
2500 +IZM2-XAV254
225780 IZM2-XAV254
225986
3200 +IZM2-XAV324
225781 IZM2-XAV324
225987
Frame size 3 4000 +IZM3-XAV404
230746 IZM3-XAV404
230747
Frame size 3 5000 +IZM3-XAV504
230748 IZM3-XAV504
230749
Auxiliary contact modules for withdrawable unit
–Module 1+IZM-XHIAV1
230708 1 off Position indication, Modul 1:
Connected position: 1 changeover contact
Test position: 1 changeover contact
Disconnected posotion: 1 changeover contact
Module 1 with 1.5 m cable
–Module 2+IZM-XHIAV2
230709 Position indication, Modul 2:
Connected position: 3 changeover contacts
Test position: 2 changeover contacts
Disconnected posotion: 1 changeover contact
Module 2 with 1.5 m cable
36 37
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Pole For rated current Type suffix
when ordered with basic unit
Article no.
Pric
see Price List Std. pack Type
when ordered
separately
Article no.
Pric
see Price List Std. pack Notes
In
A
Withdrawable units
3-pole Frame size 1 1000 +IZM1-XAV10
230733 1 off IZM1-XAV10
230734 1 off When ordering the withdrawable unit
separately:
– State type of mains connection
– 4 control circuit are supplied as standard
with the unit
Frame size 1 1600 +IZM1-XAV16
230735 IZM1-XAV16
230736
Frame size 2 2000 +IZM2-XAV20
225772 IZM2-XAV20
225978
2500 +IZM2-XAV25
225773 IZM2-XAV25
225979
3200 +IZM2-XAV32
225774 IZM2-XAV32
225980
Frame size 3 4000 +IZM3-XAV40
230737 IZM3-XAV40
230738
5000 +IZM3-XAV50
230739 IZM3-XAV50
230740
6300 +IZM3-XAV63
225776 IZM3-XAV63
225982
4-pole Frame size 1 1000 +IZM1-XAV104
230742 IZM1-XAV104
230743
Frame size 1 1600 +IZM1-XAV164
230744 IZM1-XAV164
230745
Frame size 2 2000 +IZM2-XAV204
225779 IZM2-XAV204
225985
2500 +IZM2-XAV254
225780 IZM2-XAV254
225986
3200 +IZM2-XAV324
225781 IZM2-XAV324
225987
Frame size 3 4000 +IZM3-XAV404
230746 IZM3-XAV404
230747
Frame size 3 5000 +IZM3-XAV504
230748 IZM3-XAV504
230749
Auxiliary contact modules for withdrawable unit
–Module 1+IZM-XHIAV1
230708 1 off Position indication, Modul 1:
Connected position: 1 changeover contact
Test position: 1 changeover contact
Disconnected posotion: 1 changeover contact
Module 1 with 1.5 m cable
–Module 2+IZM-XHIAV2
230709 Position indication, Modul 2:
Connected position: 3 changeover contacts
Test position: 2 changeover contacts
Disconnected posotion: 1 changeover contact
Module 2 with 1.5 m cable
36 37
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Reserve switch for withdrawable unit
–––+IZM-XAVE
225784 1 off
Shutter
3-pole Frame size 1 +IZM1-XIKL
230664 1 off IZM1-XIKL
230665 1 off Standard: can be locked with padlocks
Frame size 2 +IZM2-XIKL
225808 IZM2-XIKL
226007
Frame size 3 +IZM3-XIKL
225810 IZM3-XIKL
226009
4-pole Frame size 1 +IZM1-XIKL4
230666 IZM1-XIKL4
230667
Frame size 2 +IZM2-XIKL4
225809 IZM2-XIKL4
226008
Frame size 3 +IZM3-XIKL4
225811 IZM3-XIKL4
226010
Covers for arcing chamber
3-pole Frame size 1 +IZM1-XLKA-AV
230696 1 off IZM1-XLKA-AV
230697 1 off
Frame size 2 +IZM2-XLKA-AV
230698 IZM2-XLKA-AV
230699
Frame size 3 +IZM3-XLKA-AV
230700 IZM3-XLKA-AV
230701
4-pole Frame size 1 +IZM1-XLKA4-AV
230702 IZM1-XLKA4-AV
230703
Frame size 2 +IZM2-XLKA4-AV
230704 IZM2-XLKA4-AV
230705
Frame size 3 +IZM3-XLKA4-AV
230706 IZM3-XLKA4-AV
230707
Coding facility
––– IZM-XCE
225999 1 off 35 Coding possibilities
Pole For rated current Type suffix
when ordered with basic unit
Article no.
Pric
see Price List Std. pack Type
when ordered
separately
Article no.
Pric
see Price List Std. pack Notes
In
A
38 39
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Accessories
Withdrawable Units
Reserve switch for withdrawable unit
–––+IZM-XAVE
225784 1 off
Shutter
3-pole Frame size 1 +IZM1-XIKL
230664 1 off IZM1-XIKL
230665 1 off Standard: can be locked with padlocks
Frame size 2 +IZM2-XIKL
225808 IZM2-XIKL
226007
Frame size 3 +IZM3-XIKL
225810 IZM3-XIKL
226009
4-pole Frame size 1 +IZM1-XIKL4
230666 IZM1-XIKL4
230667
Frame size 2 +IZM2-XIKL4
225809 IZM2-XIKL4
226008
Frame size 3 +IZM3-XIKL4
225811 IZM3-XIKL4
226010
Covers for arcing chamber
3-pole Frame size 1 +IZM1-XLKA-AV
230696 1 off IZM1-XLKA-AV
230697 1 off
Frame size 2 +IZM2-XLKA-AV
230698 IZM2-XLKA-AV
230699
Frame size 3 +IZM3-XLKA-AV
230700 IZM3-XLKA-AV
230701
4-pole Frame size 1 +IZM1-XLKA4-AV
230702 IZM1-XLKA4-AV
230703
Frame size 2 +IZM2-XLKA4-AV
230704 IZM2-XLKA4-AV
230705
Frame size 3 +IZM3-XLKA4-AV
230706 IZM3-XLKA4-AV
230707
Coding facility
––– IZM-XCE
225999 1 off 35 Coding possibilities
Pole For rated current Type suffix
when ordered with basic unit
Article no.
Pric
see Price List Std. pack Type
when ordered
separately
Article no.
Pric
see Price List Std. pack Notes
In
A
38 39
Moeller NK1230-1045GB
Accessories
Connection Technology for Fixed Installation
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
40
For rated
current Type suffix
when ordered with
basic unit
Article no.
Price
see Price
List
VPE Type
when ordered
separately
Article no.
Price
see Price
List
Std.
pack Notes
In
A
Connection technology for fixed
installation
Vertical connecting
Frame size 1 1600 +IZM1-XATV16
230450 1 off IZM1-XATV16
230451 1 off For the 3-pole circuit-breakers,
6 connections are to be ordered
and for the 4-pole circuit-
breakers, 8 connections are to
be ordered.
Frame size 2 2500 +IZM2-XATV25
230877 IZM2-XATV25
230878
Frame size 2 3200 +IZM2-XATV32
230452 IZM2-XATV32
230453
Frame size 3 5000 +IZM3-XATV50
230454 please
enquire IZM3-XATV50
230455 please
enquire
Front connecting at the top
(single-hole fittng)
Frame size 1 1000 +IZM1-XAT1F10-O
230456 1 off IZM1-XAT1F10-O
230457 1 off -O = fitted at the top
For the 3-pole circuit-breakers,
3 connections are to be ordered
and for the 4-pole circuit-
breakers, 4 connections are to
be ordered.
Frame size 1 1600 +IZM1-XAT1F16-O
230458 IZM1-XAT1F16-O
230459
Frame size 2 2000 +IZM2-XAT1F20-O
230460 IZM2-XAT1F20-O
230461
2500 +IZM2-XAT1F25-O
230462 IZM2-XAT1F25-O
230463
3200 +IZM2-XAT1F32-O
230464 IZM2-XAT1F32-O
230465
Frame size 3 4000 +IZM3-XAT1F40-O
230466 please
enquire IZM3-XAT1F40-O
230467 please
enquire
Front connecting at the bottom
(single-hole fittng)
Frame size 1 1000 +IZM1-XAT1F10-U
230468 1 off IZM1-XAT1F10-U
230469 1 off -U = fitted at the bottom
For the 3-pole circuit-breakers,
3 connections are to be ordered
and for the 4-pole circuit-
breakers, 4 connections are to
be ordered.
Frame size 1 1600 +IZM1-XAT1F16-U
230470 IZM1-XAT1F16-U
230471
Frame size 2 2000 +IZM2-XAT1F20-U
230472 IZM2-XAT1F20-U
230473
2500 +IZM2-XAT1F25-U
230474 IZM2-XAT1F25-U
230475
3200 +IZM2-XAT1F32-U
230476 IZM2-XAT1F32-U
230477
Frame size 3 4000 +IZM3-XAT1F40-U
230478 please
enquire IZM3-XAT1F40-U
230479 please
enquire
Front connecting at the top
(double-hole fittng acc. DIN 43 673)
Frame size 1 1000 +IZM1-XATF10-O
230480 1 off IZM1-XATF10-O
230481 1 off -O = fitted at the top
For the 3-pole circuit-breakers,
3 connections are to be ordered
and for the 4-pole circuit-
breakers, 4 connections are to
be ordered.
Frame size 1 1600 +IZM1-XATF16-O
230482 IZM1-XATF16-O
230483
Frame size 2 2000 +IZM2-XATF20-O
230484 IZM2-XATF20-O
230485
2500 +IZM2-XATF25-O
230486 IZM2-XATF25-O
230487
3200 +IZM2-XATF32-O
225819 IZM2-XATF32-O
226022
Frame size 3 4000 +IZM3-XAT140-O
230488 please
enquire IZM3-XATF40-O
230489 please
enquire
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
41
Moeller NK1230-1045GB
Accessories
Connection Technology for Fixed Installation
Connection technology for fixed
installation
Front connecting at the bottom
(double-hole fittng acc. DIN 43 673)
Frame size 1 1000 +IZM1-XATF10-U
230490 1 off IZM1-XATF10-U
230491 1 off -U = fitted at the bottom
For the 3-pole circuit-breakers,
3 connections are to be ordered
and for the 4-pole circuit-
breakers, 4 connections are to
be ordered.
Frame size 1 1600 +IZM1-XATF16-U
230492 IZM1-XATF16-U
230493
Frame size 2 2000 +IZM2-XATF20-U
230494 IZM2-XATF20-U
230495
2500 +IZM2-XATF25-U
230496 IZM2-XATF25-U
230497
3200 +IZM2-XATF32-U
225820 IZM2-XATF32-U
226023
Frame size 3 4000 +IZM3-XATF40-U
230498 please
enquire IZM3-XATF40-U
230499 please
enquire
For rated
current Type suffix
when ordered with
basic unit
Article no.
Price
see Price
List
VPE Type
when ordered
separately
Article no.
Price
see Price
List
Std.
pack Notes
In
A
Moeller NK1230-1045GB
Accessories
Connectors for Withdrawable Unit
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
42
For rated
current Type suffix
when ordered with
basic unit
Article no.
Price
see Price
List
VPE Type
when ordered
separately
Article no.
Price
see Price
List
Std. pack Notes
In
A
Connection system for
withdrawable unit
Vertical connection
Frame size 1 1000 +IZM1-XATV10-AV
230500 1 off IZM1-XATV10-AV
230501 1 off For the 3-pole circuit-
breakers, 6 connec-
tions are to be ordered
and for the 4-pole
circuit-breakers,
8 connections are to
be ordered
Frame size 1 1600 +IZM1-XATV16-AV
230502 IZM1-XATV16-AV
230503
Frame size 2 2000 +IZM2-XATV20-AV
230504 IZM2-XATV20-AV
230505
2500 +IZM2-XATV25-AV
230506 IZM2-XATV25-AV
230507
3200 +IZM2-XATV32-AV
230508 IZM2-XATV32-AV
230509
Frame size 3 5000 +IZM3-XATV50-AV
230510 please
enquire IZM3-XATV50-AV
230511 please
enquire
Frame size 3 6300 +IZM3-XATV63-AV
230512 please
enquire IZM3-XATV63-AV
230513 please
enquire
Front connection (single-hole fitting)
Frame size 1 1000 +IZM1-XAT1F10-AV
230514 1 off IZM1-XAT1F10-AV
230515
Frame size 1 1600 +IZM1-XAT1F16-AV
230516 IZM1-XAT1F16-AV
230517
Frame size 2 2000 +IZM2-XAT1F20-AV
230518 IZM2-XAT1F20-AV
230519
2500 +IZM2-XAT1F25-AV
230520 IZM2-XAT1F25-AV
230521
3200 +IZM2-XAT1F32-AV
230522 IZM2-XAT1F32-AV
230523
Frame size 3 4000 +IZM3-XAT1F40-AV
230524 please
enquire IZM3-XAT1F40-AV
230525 please
enquire
Front connection (double-hole
fitting according to DIN 43 673)
Frame size 1 1000 +IZM1-XATF10-AV
230526 1 off IZM1-XATF10-AV
230527
Frame size 1 1600 +IZM1-XATF16-AV
230528 IZM1-XATF16-AV
230529
Frame size 2 2000 +IZM2-XATF20-AV
230530 IZM2-XATF20-AV
230531
2500 +IZM2-XATF25-AV
230532 IZM2-XATF25-AV
230533
3200 +IZM2-XATF32-AV
230534 IZM2-XATF32-AV
230535
Frame size 3 4000 +IZM3-XATF40-AV
230536 please
enquire IZM3-XATF40-AV
230537 please
enquire
Flange connection
Frame size 1 1000 +IZM1-XATA10-AV
230817 1 off IZM1-XATA10-AV
230818
Frame size 1 1600 +IZM1-XATA16-AV
230819 IZM1-XATA16-AV
230820
Frame size 2 2000 +IZM2-XATA20-AV
230821 IZM2-XATA20-AV
230822
2500 +IZM2-XATA25-AV
230823 IZM2-XATA25-AV
230824
3200 +IZM2-XATA32-AV
230825 IZM2-XATA32-AV
230826
Frame size 3 4000 +IZM3-XATA40-AV
230827 please
enquire IZM3-XATA40-AV
230828 please
enquire
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
43
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position 2
only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
On IZM circuit breakers with V, U, D-release, the delay time
tsd must be at least 100 ms greater than the delay time of the
next downstream levels (2, 3, 4).
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 1
Type IZMB(N)1-A... Incoming circuit-breaker with standard
circuit-breaker (A)
IZMB(N)1-V... Incoming circuit-breaker with selectively-
operating circuit-breakers (V)
In [A] 630 800 1000 1250 1600 630 800 1000 1250 1600
Ii [A] 5040 6400 8000 10000 12800 50000 50000 50000 50000 50000
Icu [kA] 5065 5065 5065 5065 5065 5065 5065 5065 5065 5065
Outgoing breaker Prospective short-circuit current (kA)
Iu [A] Icu [kA] B N B N B N B N B N B N B N B N B N B N
NZM7-...N 40 35 4 4 6 6 9 9 12 12 25 25 T T T T T T T T T T
63 35 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
80 35 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
100 35 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
125 35 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
160 35 4 4 5 5 6 6 9 9 15 15 T T T T T T T T T T
200 35 4 4 5 5 6 6 8 8 11 11 T T T T T T T T T T
250 35 4 4 5 5 6 6 8 8 11 11 T T T T T T T T T T
NZM7-...S 40 65 4 4 6 6 9 9 12 12 25 25 T T T T T T T T T T
63 65 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
80 65 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
100 65 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
125 65 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
160 65 4 4 5 5 6 6 9 9 15 15 T T T T T T T T T T
200 65 4 4 5 5 6 6 8 8 11 11 T T T T T T T T T T
250 65 4 4 5 5 6 6 8 8 11 11 T T T T T T T T T T
NZM7-...H 40 100 4 4 6 6 9 9 12 12 25 25 T T T T T T T T T T
63 100 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
80 100 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
100 100 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
125 100 4 4 5 5 7 7 11 11 20 20 T T T T T T T T T T
160 100 4 4 5 5 6 6 9 9 15 15 T T T T T T T T T T
200 100 4 4 5 5 6 6 8 8 11 11 T T T T T T T T T T
250 100 4 4 5 5 6 6 8 8 11 11 T T T T T T T T T T
NZM10-...N 250 45 3 3 4.5 4.5 6 6 7 7 10 10 T60 T60 T60 T60 T60
400 45 5 5 6.5 6.5 10 10 T60 T60 T60 T60 T60
630 45 10 10 T60 T60 T60 T60 T60
NZM10-...S 250 65 3 3 4.5 4.5 6 6 7 7 10 10 T60 T60 T60 T60 T60
400 65 5 5 6.5 6.5 10 10 T60 T60 T60 T60 T60
630 65 10 10 T60 T60 T60 T60 T60
NZM10-...H 250 100 3 3 4.5 4.5 6 6 7 7 10 10 T60 T60 T60 T60 T60
400 100 5 5 6.5 6.5 10 10 T60 T60 T60 T60 T60
630 100 10 10 T60 T60 T60 T60 T60
NZM14-... 800 85 6.5 6.5 28 28 28 28 28 28 28 28 28 28
1000 85 28 28 28 28 28 28 28 28 28 28
1250 85 28 28 28 28 28 28 28 28 28 28
1600 100 28 28 28 28 28 28 28 28 28 28
Notes T: full selectivity
1
234
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
44
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position
2 only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
On IZM circuit breakers with V, U, D-release, the delay time
tsd must be at least 100 ms greater than the delay time of the
next downstream levels (2, 3, 4).
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 1
Type IZMB(N)1-U...
Incoming circuit-breaker with universal circuit-
breaker (U)
IZMB(N)1-D...
Incoming circuit-breaker with digital circuit-breaker (D)
In [A] 630 800 1000 1250 1600 630 800 1000 1250 1600
Ii [A] 50000 50000 50000 50000 50000 40000 52000 40000 52000 40000 52000 40000 52000 40000 52000
Icu [kA] 506550655065506550655065 5065 5065 5065 5065
OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON
Outgoing
breaker
Prospective short-circuit current (kA)
Iu
[A]
Icu
[kA]
B N B N B N B N B N B N B N B N B N B N
NZM7-...N 40 35 T T T T T T T T T T T T T T T T T T T T
63 35 T T T T T T T T T T T T T T T T T T T T
80 35 T T T T T T T T T T T T T T T T T T T T
100 35 T T T T T T T T T T T T T T T T T T T T
125 35 T T T T T T T T T T T T T T T T T T T T
160 35 T T T T T T T T T T T T T T T T T T T T
200 35 T T T T T T T T T T T T T T T T T T T T
250 35 T T T T T T T T T T T T T T T T T T T T
NZM7-...S 40 65 T T T T T T T T T T T T T T T T T T T T
63 65 T T T T T T T T T T T T T T T T T T T T
80 65 T T T T T T T T T T T T T T T T T T T T
100 65 T T T T T T T T T T T T T T T T T T T T
125 65 T T T T T T T T T T T T T T T T T T T T
160 65 T T T T T T T T T T T T T T T T T T T T
200 65 T T T T T T T T T T T T T T T T T T T T
250 65 T T T T T T T T T T T T T T T T T T T T
NZM7-...H 40 100 T T T T T T T T T T T T T T T T T T T T
63 100 T T T T T T T T T T T T T T T T T T T T
80 100 T T T T T T T T T T T T T T T T T T T T
100 100 T T T T T T T T T T T T T T T T T T T T
125 100 T T T T T T T T T T T T T T T T T T T T
160 100 T T T T T T T T T T T T T T T T T T T T
200 100 T T T T T T T T T T T T T T T T T T T T
250 100 T T T T T T T T T T T T T T T T T T T T
NZM10-...N 250 45 T T T T T T T T T T 43 T43 T43 T43 T43 T
400 45 T T T T T T T T T T 43 T43 T43 T43 T43 T
630 45 T T T T T T T T T T 43 T43 T43 T43 T43 T
NZM10-...S 250 65 TT/60 TT/60 TT/60 TT/60 TT/60 43 T43 T43 T43 T43 T
400 65 TT/60 TT/60 TT/60 TT/60 TT/60 43 T43 T43 T43 T43 T
630 65 TT/60 TT/60 TT/60 TT/60 TT/60 43 T43 T43 T43 T43 T
NZM10-...H 250 100 TT/60 TT/60 TT/60 TT/60 TT/60 43 T43 T43 T43 T43 T
400 100 TT/60 TT/60 TT/60 TT/60 TT/60 43 T43 T43 T43 T43 T
630 100 TT/60 TT/60 TT/60 TT/60 TT/60 43 T43 T43 T43 T43 T
NZM14-... 800 85 TT/28 TT/28 TT/28 TT/28 TT/28 18 28 18 28 18 28 18 28 18 28
1000 85 TT/28 TT/28 TT/28 TT/28 TT/28 18 28 18 28 18 28 18 28 18 28
1250 85 TT/28 TT/28 TT/28 TT/28 TT/28 18 28 18 28 18 28 18 28 18 28
1600 100 TT/28 TT/28 TT/28 TT/28 TT/28 18 28 18 28 18 28 18 28 18 28
Notes T: full selectivity
1
234
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
45
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position
2 only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 2
Type IZMB(N)(H)2-A... Incoming circuit-breaker with standard circuit-breaker (A) I
IIIi
= 8 x
xx
x I
IIIn
In [A] 800 1000 1250 1600 2000 2500 3200
Ii [A] 6400 8000 10000 12800 16000 20000 25600
Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100
Outgoing breaker Prospective short-circuit current (kA)
Iu [A] Icu [kA] B N H B N H B N H B N H B N H B N H B N H
NZM7-...N 40 35 6 6 6 9 9 9 12 12 12 25 25 25 T T T T T T T T T
63 35 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 T T T T T T
80 35 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 T T T T T T
100 35 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 T T T T T T
125 35 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 T T T T T T
160 35 5 5 5 6 6 6 9 9 9 15 15 15 22 22 22 T T T T T T
200 35 5 5 5 6 6 6 8 8 8 11 11 11 16 16 16 30 30 30 T T T
250 35 5 5 5 6 6 6 8 8 8 11 11 11 16 16 16 30 30 30 T T T
NZM7-...S 40 65 6 6 6 9 9 9 12 12 12 25 25 25 37 37 37 T T T T T T
63 65 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 T T T
80 65 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 T T T
100 65 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 T T T
125 65 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 T T T
160 65 5 5 5 6 6 6 9 9 9 15 15 15 22 22 22 40 40 40 T T T
200 65 5 5 5 6 6 6 8 8 8 11 11 11 16 16 16 30 30 30 50 50 50
250 65 5 5 5 6 6 6 8 8 8 11 11 11 16 16 16 30 30 30 50 50 50
NZM7-...H 40 100 6 6 6 9 9 9 12 12 12 25 25 25 37 37 37 72 72 72 90 90 90
63 100 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 90 90 90
80 100 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 90 90 90
100 100 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 90 90 90
125 100 5 5 5 7 7 7 11 11 11 20 20 20 26 26 26 52 52 52 90 90 90
160 100 5 5 5 6 6 6 9 9 9 15 15 15 22 22 22 40 40 40 70 70 70
200 100 5 5 5 6 6 6 8 8 8 11 11 11 16 16 16 30 30 30 50 50 50
250 100 5 5 5 6 6 6 8 8 8 11 11 11 16 16 16 30 30 30 50 50 50
NZM10-...N 250 45 4.5 4.5 4.5 6 6 6 7 7 7 10 10 10 12 12 12 16 16 16 21 21 21
400 45 5 5 5 6.5 6.5 6.5 10 10 10 12 12 12 16 16 16 21 21 21
630 45 10 10 10 12 12 12 16 16 16 21 21 21
NZM10-...S 250 65 4.5 4.5 4.5 6 6 6 7 7 7 10 10 10 12 12 12 16 16 16 21 21 21
400 65 5 5 5 6.5 6.5 6.5 10 10 10 12 12 12 16 16 16 21 21 21
630 65 10 10 10 12 12 12 16 16 16 21 21 21
NZM10-...H 250 100 4.5 4.5 4.5 6 6 6 7 7 7 10 10 10 12 12 12 16 16 16 21 21 21
400 100 5 5 5 6.5 6.5 6.5 10 10 10 12 12 12 16 16 16 21 21 21
630 100 10 10 10 12 12 12 16 16 16 21 21 21
NZM14-... 800 85 6.5 6.5 6.5 8.5 8.5 8.5 10 10 10 13.5 13.5 13.5
1000 85 8.5 8.5 8.5 10 10 10 13.5 13.5 13.5
1250 85 10 10 10 13.5 13.5 13.5
1600 100 13.5 13.5 13.5
Notes T: full selectivity
1
234
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
46
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position
2 only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
On IZM circuit breakers with V, U, D-release, the delay time
tsd must be at least 100 ms greater than the delay time of the
next downstream levels (2, 3, 4).
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 2
Type IZMB(N)(H)2-V... Incoming circuit-breaker with selectively-operating circuit-
breakers (V)
I
III
imax
= 50 kA
In [A] 800 1000 1250 1600 2000 2500 3200
Ii [A] 50000 50000 50000 50000 50000 50000 50000
Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100
Outgoing breaker Prospective short-circuit current (kA)
Iu [A] Icu [kA] B N H B N H B N H B N H B N H B N H B N H
NZM7-...N 40 35 T T T T T T T T T T T T T T T T T T T T T
63 35 T T T T T T T T T T T T T T T T T T T T T
80 35 T T T T T T T T T T T T T T T T T T T T T
100 35 T T T T T T T T T T T T T T T T T T T T T
125 35 T T T T T T T T T T T T T T T T T T T T T
160 35 T T T T T T T T T T T T T T T T T T T T T
200 35 T T T T T T T T T T T T T T T T T T T T T
250 35 T T T T T T T T T T T T T T T T T T T T T
NZM7-...S 40 65 T T T T T T T T T T T T T T T T T T T T T
63 65 T T T T T T T T T T T T T T T T T T T T T
80 65 T T T T T T T T T T T T T T T T T T T T T
100 65 T T T T T T T T T T T T T T T T T T T T T
125 65 T T T T T T T T T T T T T T T T T T T T T
160 65 T T T T T T T T T T T T T T T T T T T T T
200 65 T T T T T T T T T T T T T T T T T T T T T
250 65 T T T T T T T T T T T T T T T T T T T T T
NZM7-...H 40 100 T T T T T T T T T T T T T T T T T T T T T
63 100 T T T T T T T T T T T T T T T T T T T T T
80 100 T T T T T T T T T T T T T T T T T T T T T
100 100 T T T T T T T T T T T T T T T T T T T T T
125 100 T T T T T T T T T T T T T T T T T T T T T
160 100 T T T T T T T T T T T T T T T T T T T T T
200 100 T T T T T T T T T T T T T T T T T T T T T
250 100 T T T T T T T T T T T T T T T T T T T T T
NZM10-...N 250 45 T T T T T T T T T T T T T T T T T T T T T
400 45 T T T T T T T T T T T T T T T T T T T T T
630 45 T T T T T T T T T T T T T T T T T T T T T
NZM10-...S 250 65 T T T T T T T T T T T T T T T T T T T T T
400 65 T T T T T T T T T T T T T T T T T T T T T
630 65 T T T T T T T T T T T T T T T T T T T T T
NZM10-...H 250 100 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
400 100 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
630 100 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
NZM14-... 800 85 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
1000 85 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
1250 85 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
1600 100 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
Notes T: full selectivity
1
234
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
47
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position
2 only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
On IZM circuit breakers with V, U, D-release, the delay time
tsd must be at least 100 ms greater than the delay time of the
next downstream levels (2, 3, 4).
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 2
Type IZMB(N)(H)2-U... Incoming circuit-breaker with universal circuit-breaker (U) I
IIIi
= ON = 50 kA
In [A] 800 1000 1250 1600 2000 2500 3200
Ii [A] 50000 50000 50000 50000 50000 50000 50000
Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100
Outgoing breaker Prospective short-circuit current (kA)
Iu [A] Icu [kA] B N H B N H B N H B N H B N H B N H B N H
OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON
NZM7-...N 40 35 T T T T T T T T T T T T T T T T T T T T T
63 35 T T T T T T T T T T T T T T T T T T T T T
80 35 T T T T T T T T T T T T T T T T T T T T T
100 35 T T T T T T T T T T T T T T T T T T T T T
125 35 T T T T T T T T T T T T T T T T T T T T T
160 35 T T T T T T T T T T T T T T T T T T T T T
200 35 T T T T T T T T T T T T T T T T T T T T T
250 35 T T T T T T T T T T T T T T T T T T T T T
NZM7-...S 40 65 T T T T T T T T T T T T T T T T T T T T T
63 65 T T T T T T T T T T T T T T T T T T T T T
80 65 T T T T T T T T T T T T T T T T T T T T T
100 65 T T T T T T T T T T T T T T T T T T T T T
125 65 T T T T T T T T T T T T T T T T T T T T T
160 65 T T T T T T T T T T T T T T T T T T T T T
200 65 T T T T T T T T T T T T T T T T T T T T T
250 65 T T T T T T T T T T T T T T T T T T T T T
NZM7-...H 40 100 T T T T T T T T T T T T T T T T T T T T T
63 100 T T T T T T T T T T T T T T T T T T T T T
80 100 T T T T T T T T T T T T T T T T T T T T T
100 100 T T T T T T T T T T T T T T T T T T T T T
125 100 T T T T T T T T T T T T T T T T T T T T T
160 100 T T T T T T T T T T T T T T T T T T T T T
200 100 T T T T T T T T T T T T T T T T T T T T T
250 100 T T T T T T T T T T T T T T T T T T T T T
NZM10-...N 250 45 T T T T T T T T T T T T T T T T T T T T T
400 45 T T T T T T T T T T T T T T T T T T T T T
630 45 T T T T T T T T T T T T T T T T T T T T T
NZM10-...S 250 65 T T T T T T T T T T T T T T T T T T T T T
400 65 T T T T T T T T T T T T T T T T T T T T T
630 65 T T T T T T T T T T T T T T T T T T T T T
NZM10-...H 250 100 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
400 100 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
630 100 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
NZM14-... 800 85 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30
1000 85 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30
1250 85 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30
1600 100 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30 T/30
Notes T: full selectivity
1
234
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
48
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position
2 only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
On IZM circuit breakers with V, U, D-release, the delay time
tsd must be at least 100 ms greater than the delay time of the
next downstream levels (2, 3, 4).
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 2
Type IZMB(N)(H)2-D... Incoming circuit-breaker with digital circuit-breaker (D) I
IIIi = 0.8 x
xx
x I
IIIcu
In [A] 800 1000 1250 1600
Ii [A] 44000 68000 80000 44000 68000 80000 44000 68000 80000 44000 68000 80000
Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100
Outgoing breaker Prospective short-circuit current (kA)
Iu [A] Icu [kA] B N H B N H B N H B N H
NZM7-...N 40 35 T T T T T T T T T T T T
63 35 T T T T T T T T T T T T
80 35 T T T T T T T T T T T T
100 35 T T T T T T T T T T T T
125 35 T T T T T T T T T T T T
160 35 T T T T T T T T T T T T
200 35 T T T T T T T T T T T T
250 35 T T T T T T T T T T T T
NZM7-...S 40 65 T T T T T T T T T T T T
63 65 T T T T T T T T T T T T
80 65 T T T T T T T T T T T T
100 65 T T T T T T T T T T T T
125 65 T T T T T T T T T T T T
160 65 T T T T T T T T T T T T
200 65 T T T T T T T T T T T T
250 65 T T T T T T T T T T T T
NZM7-...H 40 100 T T T T T T T T T T T T
63 100 T T T T T T T T T T T T
80 100 T T T T T T T T T T T T
100 100 T T T T T T T T T T T T
125 100 T T T T T T T T T T T T
160 100 T T T T T T T T T T T T
200 100 T T T T T T T T T T T T
250 100 T T T T T T T T T T T T
NZM10-...N 250 45 T T T T T T T T T T T T
400 45 T T T T T T T T T T T T
630 45 T T T T T T T T T T T T
NZM10-...S 250 65 60 T T 60 T T 60 T T 60 T T
400 65 60 T T 60 T T 60 T T 60 T T
630 65 60 T T 60 T T 60 T T 60 T T
NZM10-...H 250 100 60 T T 60 T T 60 T T 60 T T
400 100 60 T T 60 T T 60 T T 60 T T
630 100 60 T T 60 T T 60 T T 60 T T
NZM14-... 800 85 25 38 50 25 38 50 25 38 50 25 38 50
1000 85 25 38 50 25 38 50 25 38 50 25 38 50
1250 85 25 38 50 25 38 50 25 38 50 25 38 50
1600 100 25 38 50 25 38 50 25 38 50 25 38 50
Notes T: full selectivity
1
234
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
49
Moeller NK1230-1045GB
Technical Data
415 V AC Selectivity Table
Selectivity
between circuit-breakers facilitates the isolation of faulty system
sections.
Incoming breaker 1 and outgoing breaker 2
operate selectively if, in the event of a short circuit at position
2 only, outgoing breaker 2 trips out.
System sections 3 and 4 remain operational.
Selection:
Provided the short-circuit current does not exceed those
values (Icc rms in kA) specified in the table below, the
outgoing breakers and incoming breakers will operate
selectively in relation to one another.
The details represent the limit of selectivity.
Both breakers switch off with larger short-circuit currents.
On IZM circuit breakers with V, U, D-release, the delay time
tsd must be at least 100 ms greater than the delay time of the
next downstream levels (2, 3, 4).
In:
Iu:
Ii:
Rated current
Rated uninterrupted current
Setting of non-delayed
short-circuit release
Frame size 2
Type IZMB(N)(H)2-D... Incoming circuit-breaker with digital circuit-breaker (D) I
IIIi = 0.8 x
xx
x I
IIIcu
In [A] 2000 2500 3200
Ii [A] 44000 68000 80000 44000 68000 80000 44000 68000 80000
Icu [kA] 55 80 100 55 80 100 55 80 100
Outgoing breaker Prospective short-circuit current (kA)
Iu
[A]
Icu [kA] B N H B N H B N H
NZM7-...N
40 35 T T T T T T T T T
63 35 T T T T T T T T T
80 35 T T T T T T T T T
100 35 T T T T T T T T T
125 35 T T T T T T T T T
160 35 T T T T T T T T T
200 35 T T T T T T T T T
250 35 T T T T T T T T T
NZM7-...S
40 65 T T T T T T T T T
63 65 T T T T T T T T T
80 65 T T T T T T T T T
100 65 T T T T T T T T T
125 65 T T T T T T T T T
160 65 T T T T T T T T T
200 65 T T T T T T T T T
250 65 T T T T T T T T T
NZM7-...H
40 100 T T T T T T T T T
63 100 T T T T T T T T T
80 100 T T T T T T T T T
100 100 T T T T T T T T T
125 100 T T T T T T T T T
160 100 T T T T T T T T T
200 100 T T T T T T T T T
250 100 T T T T T T T T T
NZM10-...N
250 45 T T T T T T T T T
400 45 T T T T T T T T T
630 45 T T T T T T T T T
NZM10-...S
250 65 60 T T 60 T T 60 T T
400 65 60 T T 60 T T 60 T T
630 65 60 T T 60 T T 60 T T
NZM10-...H
250 100 60 T T 60 T T 60 T T
400 100 60 T T 60 T T 60 T T
630 100 60 T T 60 T T 60 T T
NZM14-...
800 85 25 38 50 25 38 50 25 38 50
1000 85 25 38 50 25 38 50 25 38 50
1250 85 25 38 50 25 38 50 25 38 50
1600 100 25 38 50 25 38 50 25 38 50
Notes T: full selectivity
1
234
Moeller NK1230-1045GB
Technical Data
IZM Tripping Characteristic
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
50
IZM...-A... Distribution Circuit Protection IZM...-V... Selectively Opening Circuit-Breakers
IZM...-V... selectively-opening circuit-breakers
Earth-fault protection
current dependent delayed overload range J = constant
short-time delay short-circuit range Isd
non-delayed short-circuit range Isd
earth-fault protection range
10000
1000
100
10
0.1
1
0.01
12 8100.1
t
[s]
x In
t
[s]
10000
1000
100
10
1
0.1
0.01
1 1.25 10 12
0.1
x In
[A]
10000
1000
10
100
1
0.01
0.1
0.5
1000001000 1200 10000100
t
[s]
I
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IZM Tripping Characteristic
51
IZM...-U... universal circuit-breaker, IZM...-D... digital circuit-breaker
overload range I
IIIr
IZM...-U... universal circuit-breaker, IZM...-D... digital circuit-breaker
non-delayed short-circuit range I
IIIsd
IZM...-U... universal circuit-breaker, IZM...-D... digital circuit-breaker
short-time delay short-circuit range I
IIIsd
IZM...-U... universal circuit-breaker, IZM...-D... digital circuit-breaker
Earth-fault protection
current dependent delayed overload range J = constant
Overlap of the current-dependant delayed overload range
of J and I
4
t
current dependent delayed overload range I
4
t = constant
short-time delay short-circuit range Isd
non-delayed short-circuit range Isd
earth-fault protection range
10000
1000
100
10
0.1
1
0.01
1100.1
t
[s]
x In
10000
1000
100
10
0.01
0.1
1
11.5 100.1
t
[s]
x In
10000
1000
100
10
0.01
0.1
1
1 1.25 100.1
t
[s]
x In
0.8 x Ics (Icw)
I2t OFF
I2t ON
I [A]
10000
1000
100
10
0.1
0.5
0.01
1
1000 1200 10000 100000100
t
[s]
I2t OFF
I2t ON
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 1
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 1
Frame size 1
IZM...1(-4)-...630 IZM...1(-4)-...800 IZM...1(-4)-...1000 IZM...1(-4)-...1250 IZM...1(-4)-...1600
B N B N B N B N B N
General
Standards and specifications IEC/EN 60 947, VDE 0660 IEC/EN 60 947, VDE 0660
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C -25 – 70 (device with LCD-display up to 55 °C) -25 – 70 (device with LCD-display up to 55 °C)
open °C -25 – 55 -25 – 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA630 630 800 800 1000 1000 1250 1250 1600 1600
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 105 143 105 143 105 143 105 143 105 143
up to 690 V 50/60 Hz Icm kA 88 105 88 105 88 105 88 105 88 105
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 42 65 42 65 42 65 42 65 42 65
t = 1 s Icw kA 42 50 42 50 42 50 42 50 42 50
t = 2 s Icw kA 29.5 35 29.5 35 29.5 35 29.5 35 29.5 35
t = 3 s Icw kA 24 29 24 29 24 29 24 29 24 29
t = 4 s Icw kA 21 25 21 25 21 25 21 25 21 25
Rated short-circuit breaking capacity Icn
IEC/EN 60 947 test cycle Icu 0-t-C0
up to 440 V 50/60 Hz Icu kA 50 65 50 65 50 65 50 65 50 65
up to 690 V 50/60 Hz Icu kA 42 50 42 50 42 50 42 50 42 50
IEC/EN 60 947 test cycle Ics 0-t-C0-t-C0
up to 440 V 50/60 Hz Ics kA 50 65 50 65 50 65 50 65 50 65
up to 690 V 50/60 Hz Ics kA 42 50 42 50 42 50 42 50 42 50
Operating delays
Total opening delay ms 38 38 38 38 38 38 38 38 38 38
Closing delay ms 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Lifespan, electrical at 415 V Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Maximum operating frequency Switching operations/h 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 65 65 100 100 100 100 95 95 150 150
Withdrawable units W 80 80 135 135 195 195 205 205 350 350
Weight
Fixed mounting
3-pole kg 43 43 43 43 43 43 43 43 43 43
4-pole kg 50 50 50 50 50 50 50 50 50 50
Withdrawable units
3-pole kg 70 70 70 70 70 70 70 70 70 70
4-pole kg 84 84 84 84 84 84 84 84 84 84
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
Withdrawable units
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚
52 53
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 1
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 1
Frame size 1
IZM...1(-4)-...630 IZM...1(-4)-...800 IZM...1(-4)-...1000 IZM...1(-4)-...1250 IZM...1(-4)-...1600
B N B N B N B N B N
General
Standards and specifications IEC/EN 60 947, VDE 0660 IEC/EN 60 947, VDE 0660
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C -25 – 70 (device with LCD-display up to 55 °C) -25 – 70 (device with LCD-display up to 55 °C)
open °C -25 – 55 -25 – 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA630 630 800 800 1000 1000 1250 1250 1600 1600
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 105 143 105 143 105 143 105 143 105 143
up to 690 V 50/60 Hz Icm kA 88 105 88 105 88 105 88 105 88 105
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 42 65 42 65 42 65 42 65 42 65
t = 1 s Icw kA 42 50 42 50 42 50 42 50 42 50
t = 2 s Icw kA 29.5 35 29.5 35 29.5 35 29.5 35 29.5 35
t = 3 s Icw kA 24 29 24 29 24 29 24 29 24 29
t = 4 s Icw kA 21 25 21 25 21 25 21 25 21 25
Rated short-circuit breaking capacity Icn
IEC/EN 60 947 test cycle Icu 0-t-C0
up to 440 V 50/60 Hz Icu kA 50 65 50 65 50 65 50 65 50 65
up to 690 V 50/60 Hz Icu kA 42 50 42 50 42 50 42 50 42 50
IEC/EN 60 947 test cycle Ics 0-t-C0-t-C0
up to 440 V 50/60 Hz Ics kA 50 65 50 65 50 65 50 65 50 65
up to 690 V 50/60 Hz Ics kA 42 50 42 50 42 50 42 50 42 50
Operating delays
Total opening delay ms 38 38 38 38 38 38 38 38 38 38
Closing delay ms 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Lifespan, electrical at 415 V Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Maximum operating frequency Switching operations/h 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 65 65 100 100 100 100 95 95 150 150
Withdrawable units W 80 80 135 135 195 195 205 205 350 350
Weight
Fixed mounting
3-pole kg 43 43 43 43 43 43 43 43 43 43
4-pole kg 50 50 50 50 50 50 50 50 50 50
Withdrawable units
3-pole kg 70 70 70 70 70 70 70 70 70 70
4-pole kg 84 84 84 84 84 84 84 84 84 84
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
Withdrawable units
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚
52 53
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 2 and 3
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 2 and 3
Frame size 2 Baugröße 3
IZM...2(-4)-...800 IZM...2(-4)-...1000 IZM...2(-4)-...1250 IZM...2(-4)-...1600 IZM...2(-4)-...2000 IZM...2(-4)-...2500 IZM...2(-4)-...3200 IZM...3(-4)-
...4000
IZM...3(-4)-
...5000
IZM...3(-4)-
...6300-AV
B N H B N H B N H B N H B N H B N H B N H H H H
General
Standards and specifications IEC/EN 60 947, VDE 0660 IEC/EN 60 947, VDE 0660
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C -25 – 70 (device with LCD-display up to 55 °C) -25 – 70 (device with LCD-display up to 55 °C)
open °C -25 – 55 -25 – 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 8000 8000 8000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 220 220 220
up to 690 V 50/60 Hz Icm kA 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 187 187 187
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 85 85 100
t = 1 s Icw kA 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 80 80 80 100
t = 2 s Icw kA 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 56.5 56.5 56.5 70.5
t = 3 s Icw kA 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 46 46 46 57.5
t = 4 s Icw kA 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 40 40 40 50
Rated short-circuit breaking capacity Icn
IEC/EN 60 947 test cycle Icu 0-t-C0
up to 440 V 50/60 Hz Icu kA 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
up to 690 V 50/60 Hz Icu kA 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 85 85 85
IEC/EN 60 947 test cycle Ics 0-t-C0-t-C0
up to 440 V 50/60 Hz Ics kA 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
up to 690 V 50/60 Hz Ics kA 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 85 85 85
Operating delays
Total opening delay ms 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34
Closing delay ms 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
Lifespan, electrical at 415 V Switching operations 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 4000 4000 4000 4000 4000 4000 2000 2000 2000
Maximum operating frequency Switching operations/h 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 40 40 40 80 80 80 175 175 175 260 260 260 410 410 410
Withdrawable units W 95 95 95 165 165 165 320 320 320 520 520 520 710 710 710 1600
Weight
Fixed mounting
3-pole kg 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 59 59 59 64 64 64 82 82 90
4-pole kg 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 71 71 71 77 77 77 99 99 108
Withdrawable units
3-pole kg 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91 102 102 102 113 113 113 148 148 166
4-pole kg 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 123 123 123 136 136 136 190 190 227
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
Withdrawable units
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚
30˚ 30˚
54 55
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 2 and 3
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IZM Circuit-Breakers, Frame size 2 and 3
Frame size 2 Baugröße 3
IZM...2(-4)-...800 IZM...2(-4)-...1000 IZM...2(-4)-...1250 IZM...2(-4)-...1600 IZM...2(-4)-...2000 IZM...2(-4)-...2500 IZM...2(-4)-...3200 IZM...3(-4)-
...4000
IZM...3(-4)-
...5000
IZM...3(-4)-
...6300-AV
B N H B N H B N H B N H B N H B N H B N H H H H
General
Standards and specifications IEC/EN 60 947, VDE 0660 IEC/EN 60 947, VDE 0660
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C -25 – 70 (device with LCD-display up to 55 °C) -25 – 70 (device with LCD-display up to 55 °C)
open °C -25 – 55 -25 – 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 8000 8000 8000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 220 220 220
up to 690 V 50/60 Hz Icm kA 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 187 187 187
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 85 85 100
t = 1 s Icw kA 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 80 80 80 100
t = 2 s Icw kA 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 56.5 56.5 56.5 70.5
t = 3 s Icw kA 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 46 46 46 57.5
t = 4 s Icw kA 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 40 40 40 50
Rated short-circuit breaking capacity Icn
IEC/EN 60 947 test cycle Icu 0-t-C0
up to 440 V 50/60 Hz Icu kA 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
up to 690 V 50/60 Hz Icu kA 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 85 85 85
IEC/EN 60 947 test cycle Ics 0-t-C0-t-C0
up to 440 V 50/60 Hz Ics kA 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
up to 690 V 50/60 Hz Ics kA 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 85 85 85
Operating delays
Total opening delay ms 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34
Closing delay ms 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
Lifespan, electrical at 415 V Switching operations 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 4000 4000 4000 4000 4000 4000 2000 2000 2000
Maximum operating frequency Switching operations/h 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 40 40 40 80 80 80 175 175 175 260 260 260 410 410 410
Withdrawable units W 95 95 95 165 165 165 320 320 320 520 520 520 710 710 710 1600
Weight
Fixed mounting
3-pole kg 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 59 59 59 64 64 64 82 82 90
4-pole kg 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 71 71 71 77 77 77 99 99 108
Withdrawable units
3-pole kg 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91 102 102 102 113 113 113 148 148 166
4-pole kg 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 123 123 123 136 136 136 190 190 227
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
Withdrawable units
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚
30˚ 30˚
54 55
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 1
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 1
Frame size 1
IN...1(-4)-630 IN...1(-4)-800 IN...1(-4)-1000 IN...1(-4)-1250 IN...1(-4)-1600
B N B N B N B N B N
General
Standards and specifications IEC/EN 60 947, VDE 0660 IEC/EN 60 947, VDE 0660
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C -25 – 70 -25 – 70
open °C -25 – 55 -25 – 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA630 630 800 800 1000 1000 1250 1250 1600 1600
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 105 143 105 143 105 143 105 143 105 143
up to 690 V 50/60 Hz Icm kA 88 105 88 105 88 105 88 105 88 105
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 42 65 42 65 42 65 42 65 42 65
t = 1 s Icw kA 42 50 42 50 42 50 42 50 42 50
t = 2 s Icw kA 29.5 35 29.5 35 29.5 35 29.5 35 29.5 35
t = 3 s Icw kA 24 29 24 29 24 29 24 29 24 29
t = 4 s Icw kA 21 25 21 25 21 25 21 25 21 25
Operating delays
Total opening delay ms 38 38 38 38 38 38 38 38 38 38
Closing delay ms 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Lifespan, electrical at 415 V Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Maximum operating frequency Switching operations/h 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 65 65 70 70 100 100 95 95 150 150
Withdrawable units W 80 80 135 135 195 195 205 205 350 350
Weight
Fixed mounting
3-pole kg 43 43 43 43 43 43 43 43 43 43
4-pole kg 50 50 50 50 50 50 50 50 50 50
Withdrawable units
3-pole kg 70 70 70 70 70 70 70 70 70 70
4-pole kg 84 84 84 84 84 84 84 84 84 84
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
Withdrawable units
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚
56 57
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 1
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 1
Frame size 1
IN...1(-4)-630 IN...1(-4)-800 IN...1(-4)-1000 IN...1(-4)-1250 IN...1(-4)-1600
B N B N B N B N B N
General
Standards and specifications IEC/EN 60 947, VDE 0660 IEC/EN 60 947, VDE 0660
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C -25 – 70 -25 – 70
open °C -25 – 55 -25 – 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA630 630 800 800 1000 1000 1250 1250 1600 1600
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 105 143 105 143 105 143 105 143 105 143
up to 690 V 50/60 Hz Icm kA 88 105 88 105 88 105 88 105 88 105
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 42 65 42 65 42 65 42 65 42 65
t = 1 s Icw kA 42 50 42 50 42 50 42 50 42 50
t = 2 s Icw kA 29.5 35 29.5 35 29.5 35 29.5 35 29.5 35
t = 3 s Icw kA 24 29 24 29 24 29 24 29 24 29
t = 4 s Icw kA 21 25 21 25 21 25 21 25 21 25
Operating delays
Total opening delay ms 38 38 38 38 38 38 38 38 38 38
Closing delay ms 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Lifespan, electrical at 415 V Switching operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Maximum operating frequency Switching operations/h 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 65 65 70 70 100 100 95 95 150 150
Withdrawable units W 80 80 135 135 195 195 205 205 350 350
Weight
Fixed mounting
3-pole kg 43 43 43 43 43 43 43 43 43 43
4-pole kg 50 50 50 50 50 50 50 50 50 50
Withdrawable units
3-pole kg 70 70 70 70 70 70 70 70 70 70
4-pole kg 84 84 84 84 84 84 84 84 84 84
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
Withdrawable units
blank mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
black mm 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 60 x 10 2 x 60 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚
56 57
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 2 and 3
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 2 and 3
Frame size 2 Frame size 3
IN...2(-4)-800 IN...2(-4)-1000 IN...2(-4)-1250 IN...2(-4)-1600 IN...2(-4)-2000 IN...2(-4)-2500 IN...2(-4)-3200 IN...3(-4)-
4000
IN...3(-4)-
5000
IN...3(-4)-6300-
AV
B N H B N H B N H B N H B N H B N H B N H H H H
General
Standards and specifications IEC/EN 60 947 IEC/EN 60 947
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C –25 ... 70 –25 ... 70
Open °C –25 ... 55 –25 ... 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 8000 8000 8000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 415 V 50/60 Hz Icm kA 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 220 220 220
up to 690 V 50/60 Hz Icm kA 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 187 187 187
Rated short-time withstand current
t = 0.5 s Icw kA 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 85 85 100
t = 1 s Icw kA 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 80 80 80 100
t = 2 s Icw kA 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 56.5 56.5 56.5 70.5
t = 3 s Icw kA 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 46 46 46 57.5
t = 4 s Icw kA 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 40 40 40 50
Operating delays
Total opening delay ms 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34
Closing delay ms 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
Lifespan, electrical at 415 V Operations 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 4000 4000 4000 4000 4000 4000 2000 2000 2000
Maximum operating frequency Operations/h 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 40 40 40 80 80 80 175 175 175 260 260 260 410 410 410
Withdrawable units W 95 95 95 165 165 165 320 320 320 520 520 520 710 710 710 1600
Weight
Fixed mounting
3-pole kg 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 59 59 59 64 64 64 82 82 90
4-pole kg 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 71 71 71 77 77 77 99 99 108
Withdrawable units
3-pole kg 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91 102 102 102 113 113 113 148 148 166
4-pole kg 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 123 123 123 136 136 136 190 190 227
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
Withdrawable units
blank mm 1x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚
30˚ 30˚
58 59
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 2 and 3
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
Moeller NK1230-1045GB
Technical Data
IN Switch-Disconnectors, Frame size 2 and 3
Frame size 2 Frame size 3
IN...2(-4)-800 IN...2(-4)-1000 IN...2(-4)-1250 IN...2(-4)-1600 IN...2(-4)-2000 IN...2(-4)-2500 IN...2(-4)-3200 IN...3(-4)-
4000
IN...3(-4)-
5000
IN...3(-4)-6300-
AV
B N H B N H B N H B N H B N H B N H B N H H H H
General
Standards and specifications IEC/EN 60 947 IEC/EN 60 947
Climatic proofing IEC/EN 60 068-2-30 IEC/EN 60 068-2-30
Ambient temperature
Storage °C –25 ... 70 –25 ... 70
Open °C –25 ... 55 –25 ... 55
Mounting position
Direction of incoming supply as required as required
Main circuits
Rated current InA800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 8000 8000 8000
Rated operational voltage UeV AC 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage UiV 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 415 V 50/60 Hz Icm kA 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 220 220 220
up to 690 V 50/60 Hz Icm kA 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 187 187 187
Rated short-time withstand current
t = 0.5 s Icw kA 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 85 85 100
t = 1 s Icw kA 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 65 55 65 80 80 80 100
t = 2 s Icw kA 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 46 39 46 56.5 56.5 56.5 70.5
t = 3 s Icw kA 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 37.5 32 37.5 46 46 46 57.5
t = 4 s Icw kA 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 32.5 27.5 32.5 40 40 40 50
Operating delays
Total opening delay ms 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34
Closing delay ms 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Lifespan, mechanical Operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
Lifespan, electrical at 415 V Operations 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 4000 4000 4000 4000 4000 4000 2000 2000 2000
Maximum operating frequency Operations/h 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current
Fixed mounting W 40 40 40 80 80 80 175 175 175 260 260 260 410 410 410
Withdrawable units W 95 95 95 165 165 165 320 320 320 520 520 520 710 710 710 1600
Weight
Fixed mounting
3-pole kg 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 59 59 59 64 64 64 82 82 90
4-pole kg 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 71 71 71 77 77 77 99 99 108
Withdrawable units
3-pole kg 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91 102 102 102 113 113 113 148 148 166
4-pole kg 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 123 123 123 136 136 136 190 190 227
Copper busbar connection cross-section
Fixed mounting
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
Withdrawable units
blank mm 1x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 3 x 120 x 10 4 x 120 x 10 6 x 120 x 10
30˚ 30˚ 30˚ 30˚ 30˚ 30˚
30˚ 30˚
58 59
Moeller NK1230-1045GB
Technical Data
IZM Control Unit
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
60
IZM...-A... IZM...-V... IZM...-U... IZM...-D...
System protection Selective and motor
protection
Universal and motor
protection
Digital release
Control units
Overload protection L
Setting range IrA 0.5 – 1.0 x In0.4 – 1.0 x In0.4 – 1.0 x In0.4 – 1.0 x In
Delay time with
6 x Irtrs10 10
6 x Ir with setting
to Jtrs 2 – 30 2 – 30
Setting to I
4
tt
rs 1 – 5 1 – 5
Single-phasing sensitivity only with tsd = 20 (motor
protection) ms only with tsd = 20 (motor
protection) ms ON/OFF via internal
system bus
Thermal memory can be switched on/off can be switched on/off
Short-time delayed short-circuit
protection S
Setting range Isd A 1.25 – 12 x In1.25 – 12 x In1.25 x In – 0.8 x Icw
(max. 0.8 x Icw)
Delay time tsd ms 0, 20 (motor protection),
100, 200, 300, 400 20 (motor protection),
100, 200, 300, 400, OFF 20, 100, 200, 300, 400,
500, 1000, 2000, 3000,
4000, OFF
Jsd bei 12 x Intsd s 1, 2, 3, 4, 5
Non-delayed short-circuit protection I
Can be de-activated OFF OFF
Setting range IiA2 – 8 x Inf 20 x In
(max. 50 kA) 1.5 x In – 0.8 x Ics
(max. 0.8 x Ics)
OFF: Ics = Icw
1.5 x In – 0.8 x Ics
(max. 0.8 x Ics)
OFF: Ics = Icw
Eart-fault protection G
Option for fixed
mounting Module can be
retrofitted Module can be
retrofitted
Adjustable IgA max. 1200, OFF max. 1200 max. 1200
Delay time tgms 100, 200, 300, 400, 500 100, 200, 300, 400, 500 100, 200, 300, 400, 500
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
61
Moeller NK1230-1045GB
Technical Data
Permissible Continuous Current
Admissible continuous current (A)
dependent on the ambient temperature
Type Version Ambient temperature
up to 55 °C 60 °C 70 °C
Frame size 1
IZM...1(-4)-...630
IN...1(-4)-630
Fixed mounting 630 630 630
Withdrawable units 630 630 630
IZM...1(-4)-...800
IN...1(-4)-800
Fixed mounting 800 800 800
Withdrawable units 800 800 800
IZM...1(-4)-...1000
IN...1(-4)-1000
Fixed mounting 1000 1000 1000
Withdrawable units 1000 1000 1000
IZM...1(-4)-...1250
IN...1(-4)-1250
Fixed mounting 1250 1250
Withdrawable units 1250 1250
IZM...1(-4)-...1600
IN...1(-4)-1600
Fixed mounting 1600 1600 1500
Withdrawable units 1600 1600 1500
Frame size 2
IZM...2(-4)-...800
IN...2(-4)-800
Fixed mounting 800 800 800
Withdrawable units 800 800 800
IZM...2(-4)-...1000
IN...2(-4)-1000
Fixed mounting 1000 1000 1000
Withdrawable units 1000 1000 1000
IZM...2(-4)-...1250
IN...2(-4)-1250
Fixed mounting 1250 1250 1250
Withdrawable units 1250 1250 1250
IZM...2(-4)-...1600
IN...2(-4)-1600
Fixed mounting 1600 1600 1600
Withdrawable units 1600 1600 1600
IZM...2(-4)-...2000
IN...2(-4)-2000
Fixed mounting 2000 2000 2000
Withdrawable units 2000 2000 2000
IZM...2(-4)-...2500
IN...2(-4)-2500
Fixed mounting 2500 2500 2350
Withdrawable units 2500 2500 2350
IZM...2(-4)-...3200
IN...2(-4)-3200
Fixed mounting 3200 3150 2950
Withdrawable units 3200 3150 2950
Frame size 3
IZM...3(-4)-...4000
IN...3(-4)-4000
Fixed mounting 4000 4000 3900
Withdrawable units 4000 4000 3900
IZM...3(-4)-...5000
IN...3(-4)-5000
Fixed mounting 5000 5000 4800
Withdrawable units 5000 5000 4800
IZM...3(-4)-...6300-AV
IN...3(-4)-6300-AV
Withdrawable (40 °C) 6100 5900 5500
Moeller NK1230-1045GB
Technical Data
Motor Operator, Voltage Release, Auxiliary Contacts
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
62
Motor operators
IZM-XM24-30DC IZM-XM48-60DC IZM-XM110AC/DC IZM-XM230AC/220DC
Motor operators
Rated control voltage
AC 50/60 Hz UsV 230
DC UsV 24 – 30 48 – 60 110 – 127 220 – 225
Starting current A 19.3 (24 V DC)
24.5 (30 V DC) 7.6 (48 V DC)
11.6 (60 V DC) 8.8 (110 V AC)
7 (110 V DC) 3.9 (220 V AC)
2.6 (220 V DC)
AC-3 rating
VA 110 110 110 110
W110 110 110 110
Maximum operating
frequency switching
operations/h 60 60 60 60
Duration of charging
process sF 10 F 10 F 10 F 10
Voltage releases
Closing release Shunt release Undervoltage release
Voltage releases
Rated control voltage
AC 50/60 Hz UsV 110 230
DC UsV24, 30, 48, 60 110 220
AC-3 rating
VA 15 15 5
W15 15 5
Circuit-breaker response time ms 80 80 80 non-delayed, otherwise according to
delay time
Effective range
Drop-out voltage % 35 – 70
Pick-up voltage % 70 – 110 70 – 110 85 – 110
Auxiliary contacts
IZM-XHI...
auxiliary contacts
IZM-XHIAV...
position indication
Auxiliary contacts
Rated insulation voltage UiV AC/DC 500 250
Rated operational voltage UeV AC/DC 500 250
Rated impulse withstand voltage Uimp kV 4 4
Short-circuit protection
max. fuxe A gL 10 8
fuseless Typ FAZ-C10 FAZ-C6
Rated breaking capacity
AC-12
24 – 230 V A 10
110/127 V A 5
220/230 V A 4
400 V A 10
AC-15
24 – 230 V A 6
220/230 V A 4
400 V A 4 3
DC-12
24 V A 10
48 V A 8
100 V A 3.5
220 V A 1
DC-13
24 V A 3
220/240 V A 0.1
DC-15
24 V A 10
48 V A 4
100 V A 1.2
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
63
Moeller NK1230-1045GB
Dimensions
IZM and IN, External Dimensions, Door Cut-Out, Current Transformer
Overall dimensions
Door cut-out for control panel when a door sealing frame is used
aInstallation surface
bIZM/IN control panel centre
c8 mounting holes for door sealing frame
d3 mounting holes for door interlock
Measurement converter for the neutral pole
Frame size 1
IZM1-XWC
Frame size 2
IZM2-XWC
Frame size 3
IZM3-XWC
b
t
h
3-pole Fixed mounting Withdrawable units
BHTBHT
Frame size 1
Frame size 2
Frame size 3
320
460
704
434
434
434
357
357
357
320
460
704
460
460
460
471
471
471
4-pole Fixed mounting Withdrawable units
BHTBHT
Frame size 1
Frame size 2
Frame size 3
410
590
914
434
434
434
357
357
357
410
590
914
460
460
460
471
471
471
40
120
300
314
40 120
R5 R5
da
b
c
65
o 5.5
140
175
350
o 5.5
140
185
180
o 5.5
22
1
7
34
83
55
15
97
41
170
o 13.5
51 44
68
130
131
50.5
90
3 x 10
170
30 30
51 44
68
130
o 13.5
30
160
170
30 30
51 44
68
130
o 13.5
123
52
3 x 10
Moeller NK1230-1045GB
Dimensions
IZM and IN Frame Size 1, Fixed Mounted
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
64
Terminations
Frame size 1, fixed mounting, 3 and 4 pole
Standard version horizontal connection
Optional connection terminals
Front connection (single hole fitting): IZM1-XAT1F...
Front connection (double hole fitting) according to DIN 43 673: IZM1-XATF...
Vertical connection: IZM1-XATV...
aMounting space for removal of arcing chamber
covers
bArcing space, space for electrical auxiliary
connections
cGrooves (4 mm wide, 5 mm depth) for support of
phase barriers in the unit
dControl circuit plug with screw terminals
eControl circuit plugs with tension clamp terminals
fDimensions for internal area of closed control panel
door
gAttachment points for circuit-breaker mounting
in the control panel
hLocking in OFF position (optional accessories)
iKey operation (optional accessories)
15
270
300 10
390
434
123.5
439.5
275
ed
c
11 435
82
c47
c
28 421
o 13.5
90 90 9060
55 55 55 55
230
45
127
5.5
150
103
a
b
c
f
60.5
33.5
h
i
210
76 327.5
150
a
a
275
461.5
541.5
82
c47
34
541
90 90 9060
55 55 55 55
c
14
40 421 40
o 13.5
410
320
58
139
60
55
90 90 90
c
gg
o 13.5
o M8
113.5
128.5
127.5 30
287.5
60
o 13.5
60 90 90 90
b
c
c
90 90 90
60
Rated current InaBc
up to 1000 A 10 10 10
1250 – 1600 A 15 15 15
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
65
Moeller NK1230-1045GB
Dimensions
IZM and IN Frame Size 1, Withdrawable
Terminations
Frame size 1, withdrawable, 3 and 4 pole
Standard version horizontal connection
Optional terminals
Front connection (single hole fitting): IZM1-XAT1F...-AV
Front connection (double hole fitting) according to DIN 43 673: IZM1-XATF...-AV
Vertical connection: IZM1-XATV...-
AV
Flange connection: IZM1-XATA...-
AV
cGrooves (4 mm wide, 5 mm depth) for support of
phase barriers in the unit
dControl circuit plug with screw terminals
eControl circuit plugs with tension clamp terminals
fDimensions for internal area of closed control
panel door
gIZM in connected position
hIZM in test position
iIZM in disconnected position
jAttachment holes, o 10 mm
55
270
30
13
210
300
320
de
123.5 275
465.5
jj
169.5
c62.5
11 403
90 90 90
55 55 55 55
15
26 373
o 13.5
c
45
88.5
121.5
140.5
220
367.5
382.5
c
gh
i
j
52 f
76
150
aa
275
460
327.5
62.5
169.5
c
34
493
90 90 90
55 55 55 55
15
14
40 40
373
o 13.5
55 55 55 55
68
139
25
270
320
410
o 13.5
150
165
34
127.5
30
267.5
60
o 13.5
15 90 90 90
b
c
55
15
90 90 90
c
jj
121
14
90 90
15 90
55 55 55 55
c
o M12
142.5
59 59
26 33
282.5
Rated current InaBc
up to 1000 A 10 10 10
1250 – 1600 A 15 15 15
Moeller NK1230-1045GB
Dimensions
IZM and IN Frame Size 2, Fixed Mounted
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
66
Terminations
Frame size 2, fixed mounting, 3 and 4 pole
Standard version horizontal connection
Optional terminals
Front connection (single hole fitting): IZM2-XAT1F...
Front connection (double hole fitting) according to DIN 43 673: IZM2-XATF...
Vertical connection: IZM2-XATV...
aMounting space for removal of arcing chamber
covers
bArcing space, space for electrical auxiliary
connections
cGrooves (4 mm wide, 5 mm depth) for support of
phase barriers in the unit
dControl circuit plug with screw terminals
eControl circuit plugs with tension clamp terminals
fDimensions for internal area of closed control panel
door
gAttachment points for circuit-breaker mounting in
the control panel
10
270 85
440
570
d
e
123.5 275
435.5
434
82
c
47
11 435
90 130 130 130
30
90 90 90 90
c
30
26 421
o 13.5
150
45
5.5
a
b
f
c
210
230
103
127
76 327.5
a
150 a
275
461.5
541.5
82
c47
541
34
c
14
40 40
421
90 130 130 130
30 30
90 90 90 90
o 13.5
460
128
130
90
130 130 90
30
30
139
590
o 13.5
gg
o M10
113
128
134.5
98
290
30
30
o 13.5
90 130 130 130
b
c
130
13090 130
c
Rated current InaBc
up to 2000 A 10 10 10
2500 A 15 15 15
3200 A 30 30 30
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
67
Moeller NK1230-1045GB
Dimensions
IZM and IN Frame Size 2, Withdrawable
Terminations
Frame size 2, withdrawable, 3 and 4 pole
Standard version horizontal connection
Optional terminals
Front connection (single hole fitting): IZM2-XAT1F...-AV
Front connection (double hole fitting) according to DIN 43 673: IZM2-XATF...-AV
Vertical connection: IZM2-XATV...-
AV
Flange connection: IZM2-XATA...-
AV
cGrooves (4 mm wide, 5 mm depth) for support of phase barriers in the unit
dControl circuit plug with screw terminals
eControl circuit plugs with tension clamp terminals
fDimensions for internal area of closed control panel door
gIZM in connected position
hIZM in test position
iIZM in disconnected position
jAttachment holes, o 10 mm
55350
270 40
480
j
ed
j
461
123.5 275
465.5
c
62.5
169.5
11 403
55 130 130 130
30 30
90 90 90 90
c
45
26
373
o 13.5
88.5
121.5
140.5
45
52
220
367.5
382.5
40.5
j
h
g
f
i
150
a
275
a
460
76 327.5
34
493
c62.5
169.5
c
14
40 40
373
55 130 130 130
30 30
90 90 90 90
45
o 13.5
30
138
139
95270
460
590
30
o 13.5
157
172
135
100
290
30
30
55 45 130 130 130
b
c
55
90 90 90 90
45 130 130 130
jj
121
45 130 130 130
90 40
c
59
59
26 33
282.5
142.5
o M12
Rated current InaBc
up to 2000 A 10 10 10
2500 A 15 15 15
3200 A 30 30 30
Moeller NK1230-1045GB
Dimensions
IZM and IN Frame Size 3, Fixed Mounted
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
68
Terminations
Frame size 3, fixed mounting, 3 and 4 pole
Standard version horizontal connection F 5000 A
Optional terminals
Front connection (single hole fitting): IZM3-XAT1F... F 4000 A
Front connection (double hole fitting) according to DIN 43 673: IZM3-XATF... F 4000 A
Vertical connection: IZM3-XATV... F 5000 A
aMounting space for removal of arc chamber covers
bArcing space, space for electrical auxiliary connections
cGrooves (4 mm wide, 5 mm depth) for support of phase barriers in the unit
dControl circuit plug with screw terminals
eControl circuit plugs with tension clamp terminals
fDimensions for internal area of closed control panel door
gAttachment points for circuit-breaker installation in the control panel
12
205
270
680
890
ed
434
123.5 275
439
11 435
82
20
47
130 210 210 210
15 30
160 160 160
c
26
421
160
o 13.5
230
150 45
103
127
5.5
a
b
f
c
210
35
76 327.5
150
30
275
30
461.5
541.5
82
20
47
34
541
c
40
421
40
14
130 210 210 210
15 30
160 160 160160
o 13.5
160
210
914
704
130
210
15
210
248
139
gg
30
o M10
o 13.5
142
162
40
107
94.5
120
330.5
30
15
o 13.5
c
85 210 210 210
10
20
c
130 210 210 210 130
Circuit-Breakers, Switch-Disconnectors
from 630 A to 6300 A
69
Moeller NK1230-1045GB
Dimensions
IZM and IN Frame Size 3, Withdrawable
Terminations
Frame size 3, withdrawable, 3 and 4 pole
Standard version horizontal connection F 5000 A
Optional terminals
Front connection (single hole fitting): IZM3-XAT1F...-AV F 4000 A
Front connection (double hole fitting) according to DIN 43 673: IZM3-XATF...-AV F 4000 A
Vertical connection: IZM3-XATV...-AV F 6300 A
cGrooves (4 mm wide, 5 mm depth) for support of phase
barriers in the unit
dControl circuit plug with screw terminals
eControl circuit plugs with tension clamp terminals
fDimensions for internal area of closed control panel door
gIZM in connected position
hIZM in test position
iIZM in disconnected position
jAttachment holes, o 10 mm
Flange connection: IZM3-XATA...-AV F 4000 A
57
590
800
160
270
jj
ed
123.5 275
466.5
461
20 62.5
169.5
11 403
57
85 210 210
15 30
160 160 160 160
590
800
210
26 373 o 13.5
220 45
88.5
40.5
367.5
382.5
121.5
140.5
gh
i
f
c
j
52
76 327.5
150
30 30
275
460
34
493
20 62.5
169.5
57
85 210 210
15 30
160 160 160 160
590
800
210
40 40
14
373
o 13.5
704
914
217
270
260
139
3030
o 13.5
177
197
24
94.5
124.5 30
330.5
o 13.5
57
a
590
914
800
bb210
10
20
704
57
160
85 210 210 210
160 160 160
121
Rated current InaB
4000 A 40 210
5000 A 40 210
6300 A 5 245
85 210 210 210
30
57
590
800
914
160 160 160 160
704
5
142.5
282.5
59 59
26
33 o M12
Moeller GmbH
Industrial Automation
Hein-Moeller-Str. 7 –11
D-53115 Bonn
E-Mail: info@moeller.net
Internet: www.moeller.net
© 2001 by Moeller GmbH
Subject to alterations
NK1230-1045GB MDS/DMD/Mei (03/01)
Printed in the Federal Republic of Germany (04/01)
Article No.: 231175
Think future. Switch to green.
tra Combinations
Xtra Combinations is the new world
of automation from Moeller. This means
that one company can now serve all
your automation requirements. Moeller
is your competent partner for building
automation, industrial automation
and power distribution. We provide
a complete package or individual
combinations, depending on your
application. And everything fits together
perfectly: core products, PLCs, data and
process display units, communication
products, SIMATIC®software standards,
accessibility via the Internet, design and
solution competence, and professional
services. All backed up by Moeller's
experience and expertise, spanning
more than 100 years, with switchgear,
controlgear and PLC technology in
the fields of automation and power
distribution. What other company offers
you so much from a single source?
Contact us, we'd like to talk to you.
SIEMATIC®is a Siemens AG brand.