DRH Series
Ratings up to 18 & 20 Amps at 600VAC
Fits standard 35mm DIN Rail
Integrated over-temperature protection
Alarm output in case of over-temperature
Multicolor LED with input status and alarm indicator
AC or DC control
Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
C-UL-US Listed,
IEC Rated, CE & RoHS Compliant, Horsepower Rated
Built-in Overvoltage Protection
Fan controlled through thermistor and microprocessor to optimize fan operation
PRODUCT SELECTION
Control Voltage 18A
90-280 VAC/VDC DRH3P60A18
4-32 VDC DRH3P60D18
20A
DRH3P60A20
DRH3P60D20
AVAILABLE OPTIONS
Required for valid part number
For options only and not required for valid part number
Function
3P: Contactor
Switching Type
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
Operating Voltage
60: 48-600 VAC
Series
DRH 3P 60 R
Control Voltage
A: 90-280 VAC/VDC
D: 4-32 VDC
U
Rated Load Current
18: 18 Amps (3 Controlled legs)
20: 20 Amps (2 Controlled legs)
18
A
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [VRMS]
Transient Overvoltage [Vpk] (2)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec]
Load Current, General Use UL508/IEC62314 @ 40°C [ARMS] (3)
Minimum Load Current [ARMS]
Maximum Surge Current [Apk] 1Cycle 60Hz
Maximum Surge Current [Apk] 1Cycle 50Hz
Maximum I²t for Fusing (8.33 msec) [A²sec]
20A18A
48-600 48-600
1200 1200
3 3
500 500
18 20
Load Current, Motor Starting UL508 FLA/IEC62314 @ 40°C [ARMS] (3) 7.6 7.6
0.15 0.15
750 750
716 716
2330 2330
Maximum I²t for Fusing (10 msec) [A²sec] 2560 2560
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 per channel 1.35 per channel
Minimum Power Factor (with Maximum Load) 0.5 0.5
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :240 VAC 2/1.5 2/1.5
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :380 VAC 3/2.2 3/2.2
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :480 VAC 5/3.7 5/3.7
INPUT SPECIFICATIONS (1)
Description DRH3P60Ax
Control Voltage Range 90-280 VAC/VDC
Minimum Turn-On Voltage 90 VAC/VDC
Must Turn-Off Voltage 10 VAC
Minimum Input Current (for on-state) 1 mA
Maximum Input Current 3 mA
Nominal Input Impedance [Ohms] 100k
Maximum Turn-On Time [msec] 30
Maximum Turn-Off Time [msec] 40
DRH3P60Dx
4-32 VDC
4 VDC
1 VDC
2 mA
17 mA
2k
1/2 Cycle
1/2 Cycle
(4)
DataSheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
THERMAL DERATE INFORMATION
(7)
20
15
10
5
20 30 40 50 60 70
0
Ambient Temperature (ºC)
Load Current (Amps)
DRH3P60x20
Single unit Multiple units
(7)
18
15
12
9
6
3
20 30 40 50 60 70
0
Ambient Temperature (ºC)
Load Current (Amps)
DRH3P60x18
Single unit Multiple units
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
DataSheet
DIN Rail Mount
POWER SUPPLY SPECIFICATIONS (1)
Description
Minimum Turn-On Voltage
Must Turn-Off Voltage
Maximum Source Current [mA]
Maximun Start Up Time [msec]
8-32 VDC
8 VDC
3 VDC
125
20
DRH3P60Dx
Voltage Range
Maximun Shut Off Time [msec] 40
90-265 VAC/VDC
90 VAC/VDC
5 VAC/VDC
40
50
DRH3P60Ax
500
ALARM OUTPUT (1)
Description
Maximum Contact Switching Voltage [Volts]
Contact Rated Current [A]
Minimum Recommended Contact Load [mA]
Static Contact Resistance (max. and init.)[Ohms]
Turn-On / Off Condition
DRH3P60D18
200 VDC, 120 VAC
0.5
10
0.2
See Status Chart
GENERAL SPECIFICATIONS (1)
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) (5) 3750 Vrms
Minimum Insulation Resistance (@ 500 VDC) 109 Ohm
Maximum Capacitance, Input/Output 20 pF
Ambient Operating Temperature Range -10 to 70 °C
Ambient Storage Temperature Range -40 to 70 °C
Weight (typical) 2 Controlled Legs (7.4 oz [210 g]) / 3 Controlled Legs (8.5 oz [242 g])
Housing Material UL94 V-0
Housing Color Black and Light Gray
LED Status Indicator (color) See Status Chart
Short Circuit Current Rating (6) 100kA
Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm) 12 / 1.36
Load Terminal Screw Torque Range (in-lb/Nm) 15 / 1.7
Input Terminal Wire Capacity 18-12 AWG (IEC 1-4 mm2) (stranded /solid)
Output Terminal Wire Capacity 18-10 AWG (IEC 1-6 mm2) (stranded /solid)
Humidity 85% non-condensing
Protection Degree IP20
Pollution Degree 2
DataSheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
WIRING AND BLOCK DIAGRAM
INPUT
STATUS
+A3 13 +A1
-A4 14 -A2
L1 L2 L3
T1 T2 T3
XXXX
IND. CONT. EQ.
DRH3P60xxx
L1
L2
L3
L1
L2
L3
CONTROL
INPUT
/ > / > / >
Power Supply
90-265 VAC/VDC (for A Control Voltage)
8-32 VDC (for D Control Voltage)
Alarm Output (0.5 A/200 VDC, 120 VAC) Normally Open
T1 T2 T3
General Use /
AC-51 Application
T1 T2 T3
T1 T2 T3
M
3
Motor Controller /
AC-53a Application
DRHP60x18
(3 controlled legs model)
Main Circuit
L1
T1
L2
T2
L3
T3
+A1
-A2
+A3
-A4
DRHP60x20
(2 controlled legs model)
Main Circuit
L1
T1
L2
T2
L3
T3
+A1
-A2
+A3
-A4
Alarm Output
(DRHP60x18 & DRHP60x20)
13
14
48-600 VAC, 50-60Hz
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
DataSheet
DIN Rail Mount
SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES
IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and "2".
Any short-circuit that occurs is cleared safely by either type of coordination.
The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit.
Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations,
but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination,
the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used.
Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations,
and in addition the SSR will be able to operate after the fault condition is repaired.
Type of coordination 1
Protection by Thermal Magnetic Circuit Breaker or by Fuse
Nominal Motor
Current
Class gG fuses
(example from Littlefuse)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
0.40-0.63 A CY14X51G16 DRH3P60x20 DRH3P60x18
0.63-1 A CY14X51G16 DRH3P60x20 DRH3P60x18
1-1.6 A CY14X51G25 DRH3P60x20 DRH3P60x18
1.6-2.5 A CY14X51G25 DRH3P60x20 DRH3P60x18
2.5-4 A CY14X51G25 DRH3P60x20 DRH3P60x18
4-6.3 A CY14X51G40 DRH3P60x20 DRH3P60x18
DRH3P60x18 (up to 7.6A)6.3-10 A CY14X51G40 DRH3P60x20 (up to 7.6A)
GV2ME04 / GV2P04
GV2ME05 / GV2P05
GV2ME06 / GV2P06
GV2ME07 / GV2P07
GV2ME08 / GV2P08
GV2ME10 / GV2P10
GV2ME14 / GV2P14
Thermal Magnetic Circuit Breaker
(Schneider Electric)
Type of coordination 2
0.15-20 A CY14X51G25 DRH3P60x20 DRH3P60x18 (up to 18A)
Nominal
Current
Class gG fuses
(example from Littlefuse)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
Protection by Thermal Magnetic Circuit Breaker or by Fuse
Protection by Fuse
Nominal
Current
Semiconductor fuses with less than 2330 A2s
Littlefuse
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
0.15-20 A LA50QS35-4 DRH3P60x20 DRH3P60x18 (up to 18A) 50 058 06.32 Z093908
Ferraz (Cylindric)SIBA1 (Cylindric)
Protection by Fuse
Nominal Motor
Current
Semiconductor fuses with less than 2330 A2s
Littlefuse
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
0.15-7.6 A LA50QS40-4 DRH3P60x20 DRH3P60x1850 058 06.40 A093909
Ferraz (Cylindric)SIBA1 (Cylindric)
For resistive loads:
For motor loads:
For resistive loads:
For motor loads:
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
STATUS CHART
DataSheet
DIN Rail Mount
MECHANICAL SPECIFICATIONS
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
Top/Bottom view (Fig. 1)
Fig. 1
TERMINAL SCREW TYPE
INPUT
STATUS
XXXX
IND. CONT. EQ.
DRH3
1.23
[31.3]
2.29
[58.3] 2.58
[65.5]
1.68
[42.7]
3.41
[86.7]
1.78
[45.3]
3.76
[95.6]
3.51
[89]
2.91
[73.9]
0.23
[5.8]
+A1
-A2
13+A3
14-A4
Blue
LED Color
Green Red
1, 15
2, 14
3
4, 12
5, 11
6, 10
7
8
9
13
Initial Condition
Stand by condition. LED is blinking Blue. Fan is activated at full speed for 2 seconds after power is applied to A3
A1 is On, Output is activated, temperature rises. LED is Green
Fan is activated at 50% speed. If A1 is disabled, LED changes to blinking Blue
Fan is at 75% speed
LED changes to blinking Red, fan is at full speed
Output is Off, Alarm Output is On, LED changes to solid Red
If A1 is disabled while alarm output is active, LED alternates between Blue and Red
LED is solid Red, temperature starts to fall
Fan is activated at 50% speed, temperature is steady
DescriptionStep
Fan Speed
LED Color
Alarm Output
Over Temperature
Output
Power Supply A3
Control Input A1
Alarm
Pre-alarm
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
3s 3s2s 50% 50%75% 75%100% 100%0%3s
DataSheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
ACCESSORIES
Rev. 120715
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) Relay will self trigger between 900-1200V, Not suitable for capacitive loads.
(3) Mounted in the Vertical position.
(4) Turn-on time for Instantaneous turn-on version is 4 msec.
(5) For input to alarm output the dielectric strength is 1.5kV.
(6) When protected with J Class fuses rated 600 VAC, 20 A or equivalent.
(7) Minimum spacing to obtain max. current is 22mm between adjacent units.
ID Marker
ID Marker
CNLB
CNLN
CNL2
Package of 10 plastic strip
comprising 10 individual markers
which can be placed for easy
identification during the use of
multiple units.
DRH series has Environmental Product declarations type III conforming to ISO 14025.
E116949
AGENCY APPROVALS
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
DRH series conforms to the harmonized EN standard EN/IEC 60947-4-2
Electromagnetic Compatibility:
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
Vibration Resistance:
IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75mm
Shock Resistance:
IEC 60068-2-27: Peak Acceleration 15g, Duration 11msec.
Certification in accordance with:
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
Disconnect all
power before
installing or
working with
this equipment.
Verify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
Verificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
Stellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
Spenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
apparecchiatura
Verificare tutti
i collegamenti
e sostituire
tutte le coperture
prima
dell’accensione
L'omissione di
queste istruzioni
provocherà la
morte o
lesioni serie
存在电击、
爆炸或电弧
闪烁危险
在操作此设
备之前请先
关闭电源。
若不遵守这些说明,
可能会导致严重的
人身伤害甚至死亡。
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
The product's side panels may be hot, allow
the product to cool before touching.
Follow proper mounting instructions including
torque values.
Do not allow liquids or foreign objects to enter
this product.
Failure to follow these instructions can result in
serious injury, or equipment damage.
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
Respecter les consignes de montage, et
notamment les couples de serrage.
Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
Le non-respect de cette directive peut entraîner,
des lésions corporelles graves ou des
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
Beachten Sie die Montageanweisungen,
Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
Respetar las instrucciones de montaje, y en
particular los pares de apretado.
No dejar que penetren líquidos o cuerpos
extraños en el producto.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
Seguire le istruzioni di montaggio corrette.
Non far entrare liquidi o oggetti estranei in questo
apparecchio.
如不能正确执行这些操作说明,
极有可能造成严重人体伤害或者设备的损坏。
材料损坏和高温外壳的危险性
产品的一侧面板可能很热,在其冷却前请
不要触碰。
遵照正确的安装说明,包括扭矩值。
请勿让液体及其他异物进入本产品。
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
DataSheet
DIN Rail Mount
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead Mercury Cadmium Hexavalent Polybrominated Polybrominated
(Pb) (Hg) (Cd) Chromium
(Cr (VI))
biphenyls
(PBB)
diphenyl ethers
(PBDE)
Semiconductor die
Solder
附件 - 环保信息
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
有毒有害物质或元素
名称 六价铬 多溴联苯 多溴二苯醚
(Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)
半导体芯片
焊接点
50
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Crydom Inc. Specifications subject to change without notice.
DataSheet
DIN Rail Mount