https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED Product Description The MACX MCR-SL-CAC-5-I(-UP) current measuring transducers convert sinusoidal alternating currents of 1 A or 5 A into standard analog signals 0...20 mA or 4...20 mA. The DIP switches, which can be accessed on the upper side of the housing, can be used to configure the input and output current. The MACX MCR-SL-CAC-5-I current transducer contains a supply voltage range of 19.2 V DC to 30 V DC. The MACX MCR-SL-CAC-5-I current transducer contains a long range version with a supply voltage range of 19.2 V AC/DC to 253 V AC/DC. Your advantages Input/output can be configured via DIP switches Key Commercial Data Packing unit 1 pc GTIN GTIN 4046356153775 Weight per Piece (excluding packing) 176.800 g Custom tariff number 85437090 Country of origin Germany Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area Dimensions Width 22.5 mm 05/03/2021Page1/7 https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Technical data Dimensions Height 104 mm Depth 114.5 mm Ambient conditions Ambient temperature (operation) -20 C ... 65 C (-4F...149F) Ambient temperature (storage/transport) -40 C ... 85 C (-40F...185F) Maximum altitude 2000 m Permissible humidity (operation) 10 % ... 95 % (non-condensing) Degree of protection IP20 Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations. Input data Configurable/programmable Via DIP switches Input current range 0 A ... 5 A Setting range for min. input current 0 A AC ... 1 A (configurable) Setting range for max. input current 0 A AC ... 5 A (configurable) Overload capacity 2 x IN (continuous) Surge strength 20 x IN (1 s) Nominal frequency fN 50 Hz Frequency measuring range 45 Hz ... 65 Hz Connection method Screw terminal block Output data Output name Current output Configurable/programmable Via DIP switches Current output signal 0 mA ... 20 mA (configurable) 4 mA ... 20 mA (configurable) Max. output current 25 mA Load/output load current output < 500 (20mA) Ripple < 10 mVPP (for 500 at 20 mA) Status display LED red (error), LED green (ready) Switching output Output name No switching output Power supply Nominal supply voltage 24 VDC (-20%...+25%) Supply voltage range 19.2 VDC ... 30 VDC Max. current consumption < 32 mA (at UB=24 V DC, IOUT=20 mA) 05/03/2021Page2/7 https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Technical data Power supply Power consumption < 0.9 W (at UB=24 V DC, IOUT=20 mA) Connection data Connection method Screw connection Stripping length 8 mm Screw thread M3 Conductor cross section solid 0.2 mm ... 2.5 mm Conductor cross section flexible 0.2 mm ... 2.5 mm Conductor cross section AWG 24 ... 14 General Maximum transmission error 0.5 % (of nominal range value under nominal conditions) Maximum temperature coefficient < 0.02 %/K Temperature coefficient, typical < 0.015 %/K Step response (10-90%) 300 ms typ. 200 ms Overvoltage category II Degree of pollution 2 Test voltage input/output 4 kV (50Hz, 1min.) Test voltage output/power supply 1.5 kV (50Hz, 1min.) Electromagnetic compatibility Conformance with EMC directive Noise emission EN 61000-6-4 Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations. Color gray Housing material Polyamide PA non-reinforced Mounting position any Standards and Regulations Electromagnetic compatibility Conformance with EMC directive Noise emission EN 61000-6-4 Connection in acc. with standard CUL Standards/regulations EN 61000-4-2 EN61000-4-3 EN61000-4-4 Comments Criterion B Standards/regulations EN61000-4-5 EN61000-4-6 Conformance/approvals 05/03/2021Page3/7 https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Technical data Conformance/approvals Designation CE Certificate CE-compliant Designation ATEX Identification II 3 G Ex nA IIC T4 Gc X Designation UL, USA/Canada Identification UL508 Recognized Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 50 years For details about hazardous substances go to tab "Downloads", Category "Manufacturer's declaration" Drawings Application drawing Dimensional drawing 104 22,5 7 0...20mA 114,5 5A 24V 00 10 A Mains voltage Current measurement Circuit diagram L(+) 1.1 OUT L(+) 1.2 3.1 N(-) 1.3 3.2 GND N(-) 1.4 3.3 GND 3.4 GND 4.1 1A OUT1 4.2 5A 4.3 NC 4.4 IN 05/03/2021Page4/7 https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Classifications eCl@ss eCl@ss 10.0.1 27210123 eCl@ss 11.0 27210123 eCl@ss 4.0 27271100 eCl@ss 4.1 27200300 eCl@ss 5.0 27200300 eCl@ss 5.1 27200300 eCl@ss 6.0 27210100 eCl@ss 7.0 27210123 eCl@ss 9.0 27210123 ETIM ETIM 3.0 EC002475 ETIM 4.0 EC002475 ETIM 6.0 EC002475 ETIM 7.0 EC002475 UNSPSC UNSPSC 6.01 30211506 UNSPSC 7.0901 39121008 UNSPSC 11 39121008 UNSPSC 12.01 39121008 UNSPSC 13.2 39121032 UNSPSC 18.0 39121032 UNSPSC 19.0 39121032 UNSPSC 20.0 39121032 UNSPSC 21.0 39121032 Approvals Approvals Approvals UL Recognized / cUL Recognized / cULus Recognized Ex Approvals ATEX / EAC Ex / ATEX 05/03/2021Page5/7 https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Approvals Approval details UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cULus Recognized Accessories Accessories DIN rail connector DIN rail bus connectors-ME 22,5 TBUS 1,5/ 5-ST-3,81 GY-2201937 DIN rail connector, color: gray, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, Number of positions per row: 5, pitch: 3.81 mm, mounting: DIN rail mounting, Locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts DIN rail bus connectors-ME 17,5 TBUS 1,5/ 5-ST-3,81 GN-2709561 DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos. Power supply 05/03/2021Page6/7 https://www.phoenixcontact.com/us/products/2810612 Current transducers-MACX MCR-SL-CAC- 5-I-2810612 Accessories Power supply unit-MINI-SYS-PS-100-240AC/24DC/1.5-2866983 Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A Power supply unit-MINI-PS-100-240AC/24DC/1.5/EX-2866653 Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the potentially explosive area Phoenix Contact 2021 (c) - all rights reserved http://www.phoenixcontact.com 05/03/2021Page7/7